CMPAPPK Distance Piece-Packer Venting For H2S
CMPAPPK Distance Piece-Packer Venting For H2S
Contents Page
K1.0 Introduction
Environmental protection and maintaining safety require close attention to contain-
ment of gas contaminated with hydrogen sulfide. Reciprocating compressors will
always have some gas leakage from the cylinders. The leakage occurs along the
piston rod and through the rod packer. This appendix outlines requirements for
preventing the escape of toxic, corrosive gas into the atmosphere or the compressor
crankcase. Leakage into the crankcase not only will result in atmospheric contami-
nation but, also, can result in crankcase explosions. The principles described herein
may also be applied to other compression services where controlled disposition of
leakage is required.
K1.1 Summary
Six designs for preventing the escape of gas from a compressor cylinder packer into
the atmosphere are discussed in Section I.
Designs 1 and 2 are conventional, non-purged arrangements which provide limited
protection. Designs 3 and 4 use purge gas to block the entry of gas into the distance
piece. Using a purge will prevent any leakage of H2S containing gas into the atmo-
sphere except when poor compressor rod or packer condition results in excessive
packer leakage. Designs 5 and 6, using expensive and space consuming double-
compartment distance pieces, will provide some additional protection in the event
of excessive packer leakage. However, the probability of needing this extra protec-
tion is low.
All designs require venting to a gas disposal system operating at a pressure less
than 10 psig and preferably, near atmospheric pressure.
Basic considerations and mechanical design features are discussed in Section II. It
must be emphasized that packer and wiper designs discussed in the following
require careful consideration of pressures to be encountered and of other applica-
tion details. Design must be a coordinated effort between the user, the compressor
manufacturer, and the packing manufacturer.
Fig. K-1 Guide to the Selection of Packer & Distance Piece Venting Systems for H2S Service (1 of 2)
Design No.
1 2 3 4 5 6
Governing Selection Factor
Allowable Atmospheric Contamination
(a) Continuous, Non-Toxic (odor ok) x
(b) None During Normal Operating x
(c) None, With Exceptions(1) x x
(d) None(2) x
B. Compressor Housing
(a) Open - 3 Side Minimum x x x x x x
(b) Closed (3) (3) x x
C. Environment
(a) Unpopulated Areas x
(b) In-Plant, Populated Areas x x x x x
Fig. K-1 Guide to the Selection of Packer & Distance Piece Venting Systems for H2S Service (2 of 2)
Design No.
1 2 3 4 5 6
Relative Ranking (A=Preferred, B=Acceptable, C=Undesirable)
D. Other Considerations
(a) Operator Safety C B A- A- A A
(b) Minimum Crankcase Contamination A B+ B+ B+ A- A
(c) Installed Cost A A- B B- C C
(d) Maintenance Effort A A- B B C C
(e) Equipment Space Required A A A A B B
(f) Purge Gas Use Rate - B- B C C C-
(g) Adaptability to Existing Compressors A B B B C C
(1) Some H2S escape permitted for short periods in the event of unforeseeable failures
(2) Least H2S escape possible under any circumstance
(3) Design not recommended unless safety devices recommended in Figure K-2 are used
Fig. K-2 Design Details, Packer & Distance Piece Venting Systems for H2S Service (1 of 2)
Design No.
1 2 3 4 5 6
(1) (1) (1) (2)
IB OB IB OB(1)
Distance Piece
No. of Compartments 1 1 1 1 2 2
Solid Access Covers R x x x x x x x
Cover Gaskets x x x x x x
Vent to Disposal System x x x
Vent to Atmosphere x x
Nitrogen Purge x x x
Rod Packer
Vent to Disposal System x x x x x x
Nitrogen Purge x x x
(2) (2)
Sweet Gas Purge
Preloaded Outer Rings R x x
Rod Wiper
Oil Control Rings x x x x x x
Preloaded Seal Rings x x x x
Code: x=required; R=recommended option. Superscripted numbers refer to footnotes.
Fig. K-2 Design Details, Packer & Distance Piece Venting Systems for H2S Service (2 of 2)
Design No.
1 2 3 4 5 6
(1) (1) (1) (2)
IB OB IB OB(1)
Rod-Diaphragm Packer x x
Safety Devices
Dist. Piece Safety Valve (4) x (4) x x (4)
Indicators
Purge Gas Flow Rate R R R R R
Distance Piece Pressure (5) R (5) (5)
The appendices in API 618 include figures that show the locations of vents and
purges for the designs discussed below.
are in good condition, providing the purge gas pressure is always greater than the
packer vent system pressure. However, poor mechanical condition will probably
result in gas blowing through the distance piece and into the atmosphere. Failure of
the purge gas system will have the same result. Therefore, Design 2 should not be
used for compressors handling highly toxic concentrations of H2S, particularly if
the compressor is housed. It should not be used for any H2S service when odor
from escaping gas is highly objectionable.
Fig. K-4 Two Cup Wiper Assembly with One Set of Seal Rings
Double-compartment distance pieces are generally used only for very hazardous
services, such as near 100% concentration of highly toxic or corrosive gases, or
oxygen. These distance pieces have a partition containing an auxiliary rod packer to
isolate the two compartments. Either or both compartments may have solid covers
and vent connections. Both compartments should have drain connections.
• Distance piece and packer vents may be piped separately to different gas
disposal systems. They also can be connected to a single disposal system
through common piping outside of the compressor. In either case, it is essential
that the piping does not restrict the flow of vented gas. Any unnecessary restric-
tion will increase the gas pressure in the packer vent cup or in the distance
piece. Increased pressure in either will increase the possibility of leaking unde-
sirable gas to the atmosphere.