MODBUS Server COM Ethernet
MODBUS Server COM Ethernet
HMI Setting:
Parameters Recommended Options Notes
PLC type MODBUS Server (COM/Ethernet)
PLC I/F RS232 RS232, RS485
9600~115200 Ethernet supports UDP or TCP/IP
Baud rate 9600
Ethernet protocol
Data bits 8 8
Parity Even Even, Odd,
Stop bits 1 None
1
PLC sta. no. 1 1-31 HMI Modbus Station No.
Port no. 502
If HMI is Modbus Server, connecting two or more Modbus Servers with one Modbus RTU
via RS485 4W is not supported. To do so, use RS485 2W instead.
PLC Connection Guide
PLC Setting:
Communication mode Modbus RTU protocol
Modbus Server Port No. can not be set identically to HMI Port No. When doing so, the
warning message below will be shown requesting users to change setting.
PLC Connection Guide
Note:
A maximum of 64 Clients can be connected simultaneously.
Modbus Server Port No. can’t be identical to HMI Port No.
By adding MODBUS Server with [Ethernet] interface, the [MODBUS TCP/IP Gateway] feature
Note the following two points when enabling the [MODBUS TCP/IP Gateway]:
a. The original mapping between the MODBUS Server and the HMI address will be
canceled.
b. The SCADA cannot read from or write in the addresses defined in different Address
Mapping Table at one time.
For more information about this, see “Chapter37 MODBUS TCPIP Gateway”.
PLC Connection Guide
Device Address:
Bit/Word Device type Format Range Memo
B LB dddd 0 ~ 9998 Mapping to 0x/1x 1 ~ 9999
W LW dddd 0 ~ 9998 Mapping to 3x/4x 1 ~ 9999
W RW ddddd 0 ~ 55536 Mapping to 3x/4x 10000 ~ 65536
Wiring Diagram:
RS232 (Diagram 1 ~ Diagram 3)
Diagram 1
RS-232
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS232
Rx TXD
Tx RXD
GND GND
RTS
CTS
PLC Connection Guide
Diagram 2
RS-485 4W
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS485 4W
Rx- Tx-
RX+ Tx+
Tx- Rx-
Tx+ Rx+
GND GND
Diagram 3
RS-485 2W
The serial port pin assignments may vary between HMI models, please click the following
link for more information.
HMI PLC
Link RS485 2W
Data- D-
Data+ D+
GND GND
Note: Setting more than one Modbus Server in HMI Device List is of no effect.
PLC Connection Guide
Diagram 4
Ethernet cable: