SBC 2018 801 Chapter32
SBC 2018 801 Chapter32
be adequately protected by the automatic sprinkler 3205.7 Arrays. Arrays shall comply with Section
system provided. The engineering analysis shall 3207.4.
consider the ability of the sprinkler system to
3205.8 Flue spaces. Flue spaces shall comply with
deliver the higher density required by the higher
Section 3208.3.
hazard commodity. The higher density shall be
based on the actual storage height of the pile or rack
and the minimum allowable design area for SECTION 3206 GENERAL FIRE
sprinkler operation as set forth in the density/area
PROTECTION AND LIFE SAFETY
figures provided in NFPA 13. The contiguous area
occupied by the higher hazard commodity shall not FEATURES
exceed 11 m2 and additional areas of higher hazard 3206.1 General. Fire protection and life safety
commodity shall be separated from other such areas features for high-piled storage areas shall be in
by 7.5 m or more. The sprinkler system shall be accordance with Sections 3206.2 through 3206.10.
capable of delivering the higher density over a
3206.2 Extent and type of protection. Where
minimum area of 81 m2 for wet pipe systems and
required by Table 3206.2, fire detection systems,
111 m2 for dry pipe systems. The shape of the
smoke and heat removal and automatic sprinkler
design area shall be in accordance with Section 903.
design densities shall extend the lesser of 4.5 m
beyond the high-piled storage area or to a
permanent partition. Where portions of high-
SECTION 3205 HOUSEKEEPING AND
piled storage areas have different fire protection
MAINTENANCE requirements because of commodity, method of
3205.1 Rack structures. The structural integrity storage or storage height, the fire protection features
of racks shall be maintained. required by Table 3206.2 within this area shall be
based on the most restrictive design requirements.
3205.2 Ignition sources. Clearance from ignition
sources shall be provided in accordance with 3206.3 Separation of high-piled storage areas.
Section 305. High-piled storage areas shall be separated from
other portions of the building where required by
3205.3 Smoking. Smoking shall be prohibited.
Sections 3206.3.1 through 3206.3.2.2.
Approved “No Smoking” signs shall be
conspicuously posted in accordance with Section 3206.3.1 Separ ation from other uses.
310. Mixed occupancies shall be separated in accordance
with the SBC 201.
3205.4 Aisle maintenance. When restocking is not
being conducted, aisles shall be kept clear of 3206.3.2 Multiple high-piled stor age
storage, waste material and debris. Fire department ar eas. Multiple high piled storage areas shall be in
(Civil Defense) access doors, aisles and exit doors accordance with Section 3206.3.2.1 or 3206.3.2.2.
shall not be obstructed. During restocking
3206.3.2.1 Aggregate area. The aggregate of
operations using manual stocking methods, a
all high-piled storage areas within a building shall
minimum unobstructed aisle width of 600 mm shall
be used for the application of Table 3206.2 unless
be maintained in 1200 mm or smaller aisles, and a
such areas are separated from each other by 1-hour
minimum unobstructed aisle width of one-half of
fire barriers constructed in accordance with Section
the required aisle width shall be maintained in aisles
707 the SBC 201. Openings in such fire barriers
greater than 1200 mm. During mechanical stocking
shall be protected by opening protectives having a
operations, a minimum unobstructed aisle width of
1-hour fire protection rating.
1100 mm shall be maintained in accordance with
Section 3206.9. 3206.3.2.2 Multiclass high-piled storage
areas. High-piled storage areas classified as Class
3205.5 Pile dimension and height limitations.
I through IV not separated from high-piled storage
Pile dimensions and height limitations shall comply
areas classified as high hazard shall utilize the
with Section 3207.3.
aggregate of all high-piled storage areas as high
3205.6 Designation of storage heights. Where hazard for the purposes of the application of Table
required by the fire code official, a visual method of 3206.2. To be considered as separated, 1-hour fire
indicating the maximum allowable storage height barriers shall be constructed in accordance with
shall be provided. Section 707 of the SBC 201. Openings in such fire
barriers shall be protected by opening protectives 3206.6.1.3 Locking devices. Only approved
having a 1-hour fire protection rating. locking devices shall be used.
Exception: As provided for in Section 3204.2. 3206.7 Smoke and heat removal. Where smoke
and heat removal is required by Table 3206.2 it
3206.4 Automatic sprinklers. Automatic
shall be provided in accordance with Section 910.
sprinkler systems shall be provided in accordance
with Sections 3207, 3208 and 3209. 3206.8 Fire department (Civil Defense) hose
connections. Where exit passageways are required
3206.4.1 Pallets. Automatic sprinkler
by the SBC 201 for egress, a Class I standpipe
system requirements based upon the presence of
system shall be provided in accordance with
pallets shall be in accordance with NFPA 13.
Section 905.
3206.4.1.1 Plastic pallets. Plastic pallets
3206.9 Aisles. Aisles providing access to exits and
listed and labeled in accordance with UL 2335 or
fire department (Civil Defense) access doors shall
FM 4996 shall be treated as wood pallets for
be provided in high-piled storage areas exceeding
determining required sprinkler protection.
46 m2, in accordance with Sections 3206.9.1
3206.5 Fire detection. Where fire detection is through 3206.9.3. Aisles separating storage piles or
required by Table 3206.2, an approved automatic racks shall comply with NFPA 13. Aisles shall also
fire detection system shall be installed throughout comply with Chapter 8 of SBC 201.
the high-piled storage area. The system shall be
Exception: Where aisles are precluded by rack
monitored and be in accordance with Section 907.
storage systems, alternate methods of access and
3206.6 Building access. Where building access is protection are allowed when approved.
required by Table 3206.2, fire apparatus access
3206.9.1 Width. Aisle width shall be in
roads in accordance with Section 503 shall be
accordance with Sections 3206.9.1.1 and
provided within 45 m of all portions of the exterior
3206.9.1.2.
walls of buildings used for high-piled storage.
Exceptions:
Exception: Where fire apparatus access roads
cannot be installed because of topography, 1. Aisles crossing rack structures or storage
railways, waterways, nonnegotiable grades or other piles, that are used only for employee access,
similar conditions, the fire code official is shall be not less than 600 mm wide.
authorized to require additional fire protection.
2. Aisles separating shelves classified as shelf
3206.6.1 Access doors. Where building storage shall be not less than 750 mm wide.
access is required by Table 3206.2, fire department
3206.9.1.1 Sprinklered buildings. Aisles in
(Civil Defense) access doors shall be provided in
sprinklered buildings shall be not less than 1100
accordance with this section. Access doors shall be
mm wide. Aisles shall be not less than 2400 mm
accessible without the use of a ladder.
wide in high-piled storage areas exceeding 232 m2
3206.6.1.1 Number of doors required. Not in area, that are accessible to the public and
less than one access door shall be provided in each designated to contain high-hazard commodities.
30 m, or fraction thereof, of the exterior walls
Exception: Aisles in high-piled storage areas
that face required fire apparatus access roads. The
exceeding 232 m2 in area, that are accessible to the
required access doors shall be distributed such that
public and designated to contain high-hazard
the lineal distance between adjacent access doors
commodities, are protected by a sprinkler system
does not exceed 30 m.
designed for multiple-row racks of high-hazard
Exception: The linear distance between adjacent commodities shall be not less than 1100 mm wide.
access doors is allowed to exceed 30 m in existing
Aisles shall be not less than 2400 mm wide in areas
buildings where no change in occupancy is
accessible to the public where mechanical stocking
proposed. The number and distribution of access
methods are used.
doors in existing buildings shall be approved.
3206.9.1.2 Non-sprinklered buildings.
3206.6.1.2 Door size and type. Access doors
Aisles in non-sprinklered buildings shall be not less
shall be not less than 900 mm in width and 2000 mm
than 2400 mm wide.
in height. Roll-up doors shall not be used unless
approved. 3206.9.2 Clear height. The required aisle
width shall extend from floor to ceiling. Rack
3208.4 Column protection. Steel building provide for observation of the carousel
columns shall be protected in accordance with system.
NFPA 13.
3209.4 Automated rack storage. High-piled
3208.5 Extra-high-rack storage systems. storage areas with automated rack storage shall be
Approval of the fire code official shall be obtained provided with a manually activated emergency
prior to installing extra high-rack combustible shutdown switch for use by emergency personnel.
storage. The switch shall be clearly identified and shall be in
a location approved by the fire chief.
3208.5.1 Fire pr otection. Buildings with
extra-high-rack combustible storage shall be SECTION 3210 SPECIALTY
protected with a specially engineered automatic STORAGE
sprinkler system. Extra-high-rack combustible
storage shall be provided with additional special 3210.1 General. Records storage facilities used for
fire protection, such as separation from other the rack or shelf storage of combustible paper
buildings and additional built-in fire protection records greater than 3.6 m in height shall be in
features and fire department (Civil Defense) accordance with Sections 3206 and 3208 and NFPA
access, where required by the fire code official. 13. Palletized storage of records shall be in
accordance with Section 3207.
TABLE 3208.3
REQUIRED FLUE SPACES FOR RACK STORAGE
SPRINKLER AT THE CEILING
IN-RACK NON
AUTOMATIC WITH OR WITHOUT
SPRINKLERS
RACK SPRINKLER MINIMUM IN-RACK SPRINKLERED
AT EVERY TIER
PROTECTION SPRINKLERS
CONFIGURATION
7.5 m
> 7.5 m Any height Any height
Storage height Option 1 Option 2
Not
Sizeb 75 mm 75 mm Not Required Not Required
Transverse Applicable
flue space Vertically Not Not
Single-row rack Yes Not Applicable Not Required
aligned Required Applicable
Longitudinal flue Not Not Not
Not Required Not Required
space Required Applicable Required
Sizeb 150 mma 75 mm 75 mm Not Required Not Required
Transverse
flue space Vertically Not Not
Yes Not Applicable Not Required
Double-row rack aligned Required Required
Longitudinal flue Not
150 mm 150 mm Not Required Not Required
space Required
Not
Sizeb 150 mm 150 mm Not Required Not Required
Transverse Applicable
flue space Vertically Not Not
Multirow rack Yes Not Applicable Not Required
aligned Required Applicable
Longitudinal flue Not Not Not
Not Required Not Required
space Required Applicable Required
a. 75 mm transverse flue spaces shall be provided not less than every 3 m where ESFR sprinkler protection
is provided.
b. Random variations are allowed, provided that the configuration does not obstruct water penetration
FIGURE 3203.7.4
MIXED COMMODITIESa, b
a. This figure is intended to determine the commodity classification of a mixed commodity in a package, carton
or on a pallet where plastics are involved.
b. The following is an example of how to apply the figure: A package containing a Class III commodity has 12-
percent Group A expanded plastic by volume. The weight of the unexpanded Group A plastic is 10 percent.
This commodity is classified as a Class IV commodity. If the weight of the unexpanded plastic is increased
to 14 percent, the classification changes to a high-hazard commodity.
Volume of plastic in pallet load
c. Percent by volume =
Total volume of pallet load,including pallet
Weight of plastic in pallet load
d. Percent by weight =
Total weight of pallet load,including pallet