Vdoc - Pub Active and Passive Beam Application Design Guide
Vdoc - Pub Active and Passive Beam Application Design Guide
Editors
John Woollett
Julian Rimmer
Reviewers
This book underwent an independent review process before publishing. The following
persons have reviewed the book and made valuable suggestions for improvements:
Birgit Mueller, Germany
Jorma Railio, Finland
Jarek Kurnitski, Estonia
Livio Mazzarella, Italy
PREFACE
This design guide is a revision of the REHVA Chilled Beam Application Guidebook, which was pub-
lished in 2004. ASHRAE and REHVA decided to collaborate on a revision of the guidebook and
enlisted experts from both organizations to revise the document.
This new guide is aimed at consulting engineers, architects, owners, and contractors who are
involved in the design, operation, and installation of active and passive beam systems.
This book provides tools and guidance to design, commission, and operate active and passive beam
systems to achieve a determined indoor climate. It also presents examples of active and passive beam
calculations and selections. Online tools can be found at ashrae.org/beamcalc.
ACKNOWLEDGMENTS
There are many ASHRAE and REHVA members who should be recognised for their expertise in
realizing this design guide.
The following ASHRAE and REHVA experts should be recognised for their diligent help, guidance
and collaboration in producing this design guide.
ASHRAE REHVA
1
Active and Passive Beam Application Design Guide
The following terms and definitions are based on the CEN and ASHRAE standards for testing
and rating of chilled beams. Additional definitions are mainly from the ISSO publication Climatic
Ceilings and Beams: Applications of Low Temperature Heating and High Temperature Cooling (2001).
active beam: a terminal device with an integrated, ducted air supply that induces ambient air through a
hydronic coil for the purpose of transferring sensible heat to/from the space.
dew point: the temperature at which water vapour present in the air begins to condense.
draught: unwanted cooling of the body caused by local air movement.
draught rating (DR-value): the percentage of people predicted to be dissatisfied due to draught.
induced airflow: the secondary airflow from the room induced by the primary air in an active beam.
induction ratio (IR): the volume or mass flow rate of induced air (sum of the primary and secondary
air) divided by that of the primary air. IR equals Qp + Q s Qp .
infiltration: the transport of unconditioned air through leakage paths in the envelope of a building,
resulting from pressure (e.g., wind) and temperature differences.
mixed airflow rate: the total airflow rate (primary plus induced) of the mixture supplied from the beam
to the space.
mean radiant temperature: the theoretical uniform temperature of a room in which the radiant
exchange between the human body and its environment is the same as the radiant exchange in the actual
location.
passive beam (static beam): the cooled element or cooling coil fixed in, above, or under a ceiling fitted
with a cooling coil, that cools mainly convectively, using natural airflows. The cooling medium is usu-
ally water.
primary airflow rate: conditioned air supplied to an active beam through a duct from the air-handling
unit.
room air temperature: the average of air temperatures measured at 3.61 ft (1.1 m) high, positioned out
of the main air current from the beam.
turbulence intensity: the ratio of the standard deviation of the air velocity to the mean air velocity. Used
to measure variations in air velocity.
2
3 Symbols and Units
3
Active and Passive Beam Application Design Guide
4 ABBREVIATIONS
A floor area
ACH, ach air changes per hour
ACHINF infiltration air changes per hour
AHU air-handling unit
Cair cooling by air (primary airflow)
CAPEX capital expenditure
CHWR chilled-water return
CHWS chilled-water supply
CW cooling by water (water coil)
CWTin Beam chilled-water temperature in
DB, db dry-bulb temperature,
°F (°C)
DBIDA IDA design condition cooling
DBODA1 ODA design condition cooling
DBODA3 ODA design condition heating
DBSUP primary air temperature
DCV demand-controlled ventilation
DP dew-point temperature, °F (°C)
DPIDA IDA design condition cooling
DPODA2 ODA design condition dehumidification
DPSUP primary air dew point
DR draught rating
dT temperature difference
Enth enthalpy, Btu/lb (kJ/kg)
h ceiling height
HR humidity ratio, lb moisture/lb dry air (g moisture/kg dry air)
HRIDA IDA design condition cooling
HRODA1 ODA design condition cooling
HRODA2 ODA design condition dehumidification
HRSUP primary air humidity ratio
4
4 Abbreviations
5
Active and Passive Beam Application Design Guide
5 INTRODUCTION
Active and passive beam systems are an energy-efficient solution for spaces that require indi-
vidual zone control and where the internal moisture loads are moderate. Active and passive beam
systems provide good thermal comfort and energy and space saving advantages. The operation of
the system is simple, with low maintenance requirements. Although they are often referred to as
“chilled” beams, in many cases active beams can be used for both heating and cooling the space. In
this guide, we will refer to them as active or passive beams.
Active and passive beams are room air recirculation devices that transfer sensible heat to and
from the space using water. In addition, conditioned primary air is ducted to active beams. This
primary air must satisfy the ventilation and latent requirements of the space and drive the induction
of room air through the beam’s coil. In the case of passive beams, this primary air is delivered to
the space through a decoupled ventilation system. Active and passive beams may be integrated
with acoustic ceilings or independently mounted.
6
5 Introduction
7
8
TABLE 5-1 Typical Ventilation Rate for Difference Spaces According to ASHRAE/EN Standards
2010 ASHRAE
Default Default
2007 and 2010 Default Occupant Density, LEED v2 EQc2—
ASHRAE 62.1 Ventilation Ventilation, Ventilation,
ASHRAE ft2/Occupant Increase Ventilation
cfm/person cfm/ft2
Standard 62.1 Requirements
Occupancy ASHRAE
Category ASHRAE Rp, Ra, Default, Default, ASHRAE ASHRAE Rate, Governing
Standard 62.1,
Standard 62.1 cfm/person cfm/ft2 cfm/person cfm/ft2 Standard 62.1 Standard 62.1 cfm/ft2 Standard
Number/1000 ft2
Daycare ASHRAE
25 40 10 0.18 17 0.43 17 0.43 0.56
(through age 4) Standard 62.1
Classrooms ASHRAE
35 29 10 0.12 13 0.46 13 0.45 0.59
(age 9+) Standard 62.1
Lecture ASHRAE
65 15 7.5 0.06 8 0.52 8 0.52 0.68
classroom Standard 62.1
ASHRAE
Multiuse assembly 100 10 7.5 0.06 8 0.80 8 0.8 1.04
Standard 62.1
Active and Passive Beam Application Design Guide
Restaurant ASHRAE
70 14 7.5 0.18 10 0.70 10 0.7 0.91
dining rooms Standard 62.1
Cafeteria/ ASHRAE
100 10 7.5 0.18 9 0.90 9 0.9 1.17
fast-food dining Standard 62.1
ASHRAE
Conference/meeting 50 20 5 0.06 6 0.30 6 0.3 0.39
Standard 62.1
ASHRAE
Office space 5 200 5 0.06 17 0.09 17 0.09 0.12
Standard 62.1
ASHRAE
Retail 15 67 7.5 0.12 16 0.24 16 0.24 0.31
Standard 62.1
ASHRAE
Mall common areas 40 25 7.5 0.60 9 0.36 9 0.36 0.47
Standard 62.1
5 Introduction
5.1.2 Schools
Schools are another application that can benefit from active and passive beam systems. Similar to
office buildings, the benefits of a reduced supply air volume to the space are decreased fan power, lower
plenum height, reduced reheat requirements, and lower noise levels (often a critical design parameter of
schools).
5.1.4 Laboratories
Active and passive beam systems can be suitable in sensible-load-driven laboratories where the
supply airflow rate is driven by the internal gains (such as refrigerators, testing equipment, etc.) as
opposed to the exhaust requirements. In these environments, it is not unusual to require a large air-
change rate in order to satisfy the load, although significantly fewer air changes may be required by
code.
TABLE 5-2 Typical Load Fractions for Several Spaces from Europe
Ventilation Requirement,
Total Air Volume,
EN 15251—Cat II / Air-Side
Application All-Air System,
Low-Pollution Building, Load Fraction
cfm/ft2 (L/s·m²)
cfm/ft2 (L/s·m²)
9
Active and Passive Beam Application Design Guide
In these applications, the difference between the supply air volume required to manage the sensible
loads and that required to meet the fume hood airflow requirements provides opportunity for energy
savings through the application of active and passive beams. These savings are typically due to the
reduction in fan power as well as the energy associated with treating the outdoor air, which, in the case
of a sensible-load-driven lab, may be significant.
5.1.6 Limitations
There are several possible applications where humidity can be difficult to control, such as lobby
areas, kitchens, natatoriums, and spaces where there is a large and/or variable latent load from occu-
pants.
Entrance areas may see a significant short-term humidity load if they are not isolated in some way
(revolving doors or vestibules). In these areas, if outdoor conditions are very humid, a choice of a com-
plementary technology is ideal. This is also more likely if the building envelope has a high infiltration
rate and the outdoor conditions are very humid.
10
5 Introduction
vices, such as lighting, power, network cabling, PA, smoke detection, and fire suppression. This consol-
idation is typically investigated in order to minimize the disparate elements in the ceiling. These are
referred to as multiservice beams and are available with both active and passive beam types.
5.3.1 Energy
The heat transfer capacity of water allows for a reduction in the energy used to transport an equiva-
lent amount of heat as compared to an all-air system. These reductions can be achieved primarily
through reduced fan energy. The higher chilled-water supply (CHWS) temperatures used with active
and passive beam systems, typically around 58°F(14.5°C), provide many opportunities for reducing in
energy use.
11
Active and Passive Beam Application Design Guide
12
5 Introduction
FIGURE 5-6 Approximate comparison between water and air transporting equivalent energy.
13
Active and Passive Beam Application Design Guide
6 COMFORT
14
6 Comfort
15
Active and Passive Beam Application Design Guide
7 PASSIVE BEAMS
• Capacity
- Locating the passive beams in consideration of natural movement of room air can optimize beam
output.
- Avoid strong heat sources located directly below a passive beam.
- Care should be taken to not locate a passive beam too far above the finished floor, as the cool
convective air may not penetrate the occupied zone because of heat gain from room air or sur-
faces. Typical height above the finished floor is 15 ft (<4,5m). More detailed analysis is required
to verify performance.
• Comfort
- The higher the capacity per unit length, the more important the positioning becomes to maintain
acceptable comfort (because of the potential of draught sensation).
- Use areas outside the occupied zone to allow the cooled air to mix with the room air before it
reaches the occupants.
7.2 FUNCTION
A passive beam consists of a coil and a casing (Figure 7-1). In some cases, it can include an
architectural cover plate such as a perforated face or grille. The coil includes a circuit of copper
16
7 Passive Beams
pipe expanded into aluminium fins to maximize the heat exchange between the water and the fins.
The fins are spaced closely enough to maximize the cooling capacity but widely enough to avoid
restriction of natural convection. When cold water circulates through the coil, the fins are cooled
down. The air in contact with the fins is cooled and, because cold air is heavier (denser) than warm
air, it will descend into the room, in turn drawing warmer air into the top of the coil. There are two
basic types of passive beams, exposed (see Figure 7-2) and recessed versions (see Figure 7-8).
17
Active and Passive Beam Application Design Guide
7.4 CAPACITY
Passive beams typically provide sensible cooling capacities ranging between approximately 50–
260 Btu/h·ft (50–250 W/m). The capacity is influenced by the difference between the mean water
temperature tw and the entering air temperature troom as shown from generic test data (Figure 7-5).
Capacity reduces as the t (typically 14°F to 16°F [8 to 9 K]) decreases. Capacity can also be influ-
enced by the height of the shroud, beam configuration, and size. In a laboratory test, doubling the
height of the shroud from 6 in. to 12 in. (150 mm to 300 mm) gave an increase of approximately 25%
capacity at a t of 9 K as shown in Figure 7-6.
t a ± t w K
The design of the face material may restrict air falling through the face. If the beam is installed
behind a perforated ceiling, the air falling below the beam will hit the ceiling, spread out, and fall
into the zone below over a larger area. As long as there is enough free area in the ceiling (i.e., if
there is a gap relative to 25% of the beam width, there will be no effect on the capacity) to allow
the air to fall through as well as rise through to feed the beam with warm air (see Figure 7-7), there
should not be a reduction in the capacity of the unit, as shown in Figure 7-8. Use of a perforated ceil-
ing is also a good way to reduce velocities below the beam, if required. Because airflow through
the beam is driven by buoyancy forces, any restriction in the air paths will affect the passive beam’s
performance.
18
7 Passive Beams
FIGURE 7-4 Performance correction for passive beams located near a wall (less than B) in rela-
tion to gap and beam width ratio Z/B.
19
Active and Passive Beam Application Design Guide
FIGURE 7-5 Typical capacity of passive beams increases with increasing temperature differen-
tial (w = temperature water, a = temperature room air).
20
7 Passive Beams
FIGURE 7-7 Capacity of passive beams as function of ratio of return path free area (gap) to
beam width.
significant disturbances to the air entering the beam exist, the performance may be compromised. Venti-
lation systems that promote thermal stratification, such as underfloor air distribution or displacement
ventilation, may offer improved performance and energy savings because of the higher air temperatures
entering the beam.
7.6 HEATING
Passive beams are not used for heating; instead, a separate heating system is typically used, where
required.
21
Active and Passive Beam Application Design Guide
5. Determine the sensible cooling capacity of the primary air, S,p, Btu/h (kW)
V × 1.1 × (DBIDA – DBSUP) I-P
V × 1.2 × (DBIDA – DBSUP) SI
6. Determine the required sensible cooling capacity from the beam(s), S,b (Btu/h [kW]), which
corresponds to the beam capacity, where P is defined as space.
Space sensible cooling load-cooling capacity of supply air volume
7. Determine the beam quantity, size, and water flow rate based on the sensible cooling require-
ment.
8. Check that the beam(s) satisfy the acoustical and comfort requirements of the space where
NP = number of occupants in the space
OCPL = latent heat produced by the occupants
INF = outdoor air infiltration
HRODA2 = humidity ratio of space air
HRIDA = humidity ratio of space operating design condition
V = volumetric flow rate of the supply air
DBIDA = dry-bulb temperature of space operating design condition
DBSUP = dry-bulb temperature of supply air
22
7 Passive Beams
7.8 LAYOUT
FIGURE 7-9 Perimeter beam installation using a ceiling opening and plenum cavity created
with a partition.
23
Active and Passive Beam Application Design Guide
• Roller blinds are more effective at guiding the thermal plumes from solar gains to perimeter
beams than slatted horizontal blinds. Separation distance of the roller blind to the glazing surface
is critical as well as a relief at the top to allow the warm air to rise; otherwise, there is a risk that
the blind surface temperature may rise, and asymmetric radiant thermal occupant discomfort may
increase.
• A larger pathway for the plume to be drawn into the plenum space offers lower resistance and
increases beam cooling performance.
FIGURE 7-10 A typical installation where passive beams are perpendicular to façade (note
spacing for return air path).
Courtesy of Swegon
24
8 Active Beams
8 ACTIVE BEAMS
8.2 INTRODUCTION
Active beams are connected to both the primary air as well as the chilled- and heated-water sys-
tems. Primary air is supplied through nozzles to provide ventilation and dehumidification to the space,
while inducing room air through the coil to control the balance of the heating or sensible cooling load.
To ensure that there is no condensation, the chilled-water supply temperature must be maintained at or
above the room dew point, while the heating-water temperature is typically supplied at temperatures
that do not cause beam exit air temperatures more than 15°F (9 K) higher than the room temperature
during occupied hours, to prevent stratification from occurring.
An overhead active beam produces mixed-flow room air-distribution conditions in the space. Room
temperature may be controlled by varying the water flow rate through the heat exchanger, the volume
flow rate of primary air, or both.
The primary air is delivered from the air-handling unit to pressurize a small cavity in the beam
to between 0.2 and 1.0 in. w.c. (50 and 250 Pa). This pressurized air is then injected near the heat
25
Active and Passive Beam Application Design Guide
exchanger at relatively high velocity, creating a region where the static pressure is reduced, relative
to the room. Figure 8-2 shows an active beam in operation. The area above the coil is the pressur-
ized plenum with integral nozzles injecting primary air into the mixing cavity. The raised velocity
of the primary air reduces the static pressure behind the coil, inducing room air through the face
and coil. This room air, now conditioned, mixes with the primary air and is discharged back into
the room through integral diffusers.
One of the performance determinants of an active beam is its induction ratio. This is defined as the
total air volume flow rate discharged from the beam divided by the primary air volume flow rate deliv-
ered from the system:
Q primary Q sec ondary
IR = -------------------------------------------------
-
Q primary
26
8 Active Beams
27
Active and Passive Beam Application Design Guide
In some models, there is space within the beam for valve and damper installation (Figure 8-8). This
can minimize the number of access doors into ceiling void, but will also reduce the coil length within
the casing (Figure 8-9).
28
8 Active Beams
The flow rate of the primary air is determined by the following three criteria:
• Required ventilation rate
• Flow required to maintain space design humidity levels.
• Any additional flow required to increase the overall beam sensible cooling capacity
The required ventilation rates are dictated by codes and vary with application. To keep humidity
levels within the design parameters, the primary air is supplied at a sufficient flow rate and dew point to
offset the latent gains in the zone.
FIGURE 8-8 Active beam with integrated water and air volume control.
Courtesy of Swegon
29
Active and Passive Beam Application Design Guide
As in cooling mode, the heating capacity of active beams is dependent on the primary airflow
rate and induction of room air. As a result, the ventilation system must be operating when heating
is required.
FIGURE 8-10 Infrared measurements of beam during heating mode with two different inlet
water temperatures provided by KTH, Sweden.
30
8 Active Beams
31
Active and Passive Beam Application Design Guide
8.7 LAYOUT
To suit architectural requirements, the length of the beam casing can be selected longer than
the actual capacity requires (e.g., as long as the room). In this case, the coil is sized according to
the required cooling load. In practice, it is always beneficial to select as few distinct beam types,
configuration, and sizes as possible in order to simplify the design, tendering process, and the
logistics on the building site. A caution: beams can be manufactured in lengths longer than can eas-
ily be moved on the construction site (e.g., longer than will fit in an elevator).
One of the first considerations is architectural requirements (aesthetics, owner’s wishes for
flexibility, etc.), including coordination with the rest of the reflected ceiling plan (lights, sprin-
klers, smoke detectors, etc.). The optimal placement of active beams is dependent on the occupied
zone conditions. The active beams are typically placed above the work stations, because the veloc-
ity is low directly underneath the beam (when the throw pattern of the beam is horizontal). If the
beam is positioned near a wall, the unidirectional throw pattern is recommended. The designer
should understand these velocities and air temperature differences in order to properly locate the
beams. Manufacturers’ performance data, software, CFD models, and mock-ups can be used to
assist with this.
Whether active beams can be arranged parallel or perpendicular to the façade primarily
depends on the application, and arrangement may affect ceiling coordination. The layout has con-
siderable influence on the horizontal air discharge in the space and should thus be taken into
account at the design stage, considering the room or module dimensions, intended use, and flexibil-
ity required.
32
8 Active Beams
FIGURE 8-12 Active beams installed parallel to façade (façade at top, wall at bottom).
33
Active and Passive Beam Application Design Guide
FIGURE 8-13 Active beams installed perpendicular to façade (façade at top, wall at bottom).
34
Active and Passive Beam Application Design Guide
For the same room, the required airflow for ventilation according to ANSI/ASHRAE 62.1 is calcu-
lated in the following table.
Note the significant difference between the two standards in ventilation airflow requirements.
There can be an addition to the indoor air humidity level which results from infiltration of outdoor air
through the building envelope. Whenever indoor pressure is lower than outdoor pressure, outdoor air
will enter the building through the envelope. Infiltration air entering the building will leave the building,
through the envelope or through the HVAC system, at the indoor humidity ratio.
36
9 Primary Airflow Calculation Methodology
TABLE 9-1 Sensible and Latent Heat Loads per Person for Various Activities
(ASHRAE Handbook—Fundamentals 2013, Chapter 18, Table 1)
Seated in theater 245 (70) 105 (35) 0.216 (0.014) 0.11 (50)
Moderate office work 250 (75) 200 (55) 0.339 (0.022) 0.17 (79)
Light bench work 275 (80) 475 (140) 0.864 (0.056) 0.45 (202)
Moderate dancing 305 (90) 545 (160) 0.988 (0.064) 0.51 (230)
Light machine work 375 (110) 625 (185) 1.142 (0.074) 0.59 (266)
Heavy work 580 (170) 870 (255) 1.574 (0.102) 0.81 (367)
The mass flow of water vapour entering the space due to the infiltration airflow, in pounds per
hour (grams per second), is calculated by determining the difference between the mass flow of water
vapour entering the space with the infiltration airflow and the mass flow of water vapour displaced
from the room with the room air that is forced out of the space because of the infiltration airflow:
·
m inf (lb/h) = 60Qvinf · · HRODA – 60Qvinf · · HRIDA = 60Qvinf · ·(HRODA – HRIDA) (I-P)
·
m inf (g/s) = Qvinf · · HRODA – Qvinf · · HRIDA = Qvinf · ·(HRODA – HRIDA) (SI)
where
·
m inf = mass flow of water vapour entering the space due to the infiltration airflow, lb/h (g/s)
37
Active and Passive Beam Application Design Guide
The mass of water vapour generated in or entering the space is given by the following formula:
· · ·
m w = m ocp + m inf
where
·
mw = mass flow of water vapour generated in or entering the space, lb/h (g/s)
·
m ocp = mass flow of water vapour generated by the occupants, lb/h (g/s)
·
m inf = mass flow of water vapour entering the space with the infiltration airflow, lb/h (g/s)
An approximation of the capacity of the water vapour sources can be calculated from the space
latent load:
·
m w = LLAT/1.075 (I-P)
·
m w = LLAT/2.500 (SI)
where
·
mw = mass flow of water vapour generated in or entering the room, lb/h (g/s)
LLAT = calculated room latent load, Btu/h (W)
1.075 (2.500) = approximate heat content of 50% rh water vapour at 75°F (24ºC) less the heat content of
water at 50°F, Btu/lb (10ºC, kJ/kg)
Note: A common design condition for the space is 50% rh at 75°F (24°C), and 50°F (10°C) is a normal
condensate temperature from cooling and dehumidifying coils.
38
9 Primary Airflow Calculation Methodology
Knowing the capacity of the sources, the required indoor air humidity ratio, and the primary air
humidity ratio, the primary airflow required for dehumidification can be determined by a water mass
balance for the space.
Qv · · HRIDA = m· w + Qv · ·HRSUP
Solving for Qv ,
Qv = m· w/[ · (HRIDA – HRSUP)]
where
Qv = primary airflow, cfm (m3/s)
·
mw = mass flow of water vapour generated in or entering the space, lb/h (g/s)
= air density, lb/ft3 (kg/m3)
HRIDA = indoor air humidity ratio, lb/lb (g/kg)
HRSUP = primary air humidity ratio, lb/lb (g/kg)
The values of the following design temperatures greatly influence the quantity and quality of the
primary airflow:
DPIDA = indoor air dew point temperature, °F (°C)
DPSUP = primary air dew point temperature, °F (°C)
dT = temperature difference, °F (°C)
The primary airflow required for dehumidification decreases one of the following happens:
• DPIDA increases,
• DPSUP decreases
• dT decreases
FIGURE 9-2 Overview of airflow and mass flow balance in the occupied space.
39
Active and Passive Beam Application Design Guide
The indoor air dew-point temperature must be such that the indoor air relative humidity falls inside
the comfort range specified in the OPR. For example, if the OPR requires that the indoor air relative
humidity lies between 30% and 60%, for an indoor air dry-bulb temperature of 77°F (25°C), the maxi-
mum indoor air dew-point temperature is 62.1°F (16,7°C).
To prevent condensation, the indoor air dew-point temperature must be equal to or lower than
the chilled-water temperature supplied to the beams. The following equation expresses this state-
ment:
DPIDA = CWTin – dT
where
DPIDA = indoor air dew-point temperature, °F (°C)
CWTin = chilled-water temperature supplied to the beams, °F (°C)
dT = temperature difference, °F (°C)
The safety temperature difference dT is typically 1°F to 3°F (1°C to 2°C). Its value has a big
influence on the dimensioning of the primary airflow and should be kept as small as possible.
·
m ocp (lb/h) = N · 0.17 (lb/h) (I-P)
·
m ocp (g/s) = N · 0,022 (g/s) (SI)
·
m inf (lb/h) = Qvinf · (HRODA – HRIDA) (I-P)
·
m inf (g/s) = Qvinf · (HRODA – HRIDA) (SI)
40
9 Primary Airflow Calculation Methodology
The use of the spreadsheet facilitates the exercise of investigating different base conditions and
optimizing the following key design parameters:
• CWTin, chilled-water temperature supplied to the beams
• dT, safety temperature difference
• DPIDA, indoor air dew-point temperature
• DPSUP , primary air dew point
• DBSUP , primary air dry-bulb temperature
43
Active and Passive Beam Application Design Guide
10 CONTROLS
• Zone control
• Beam water temperature control
• Primary air-conditioning control
• Condensation prevention
44
10 Controls
FIGURE 10-1 Beam zone temperature control using constant-volume primary airflow.
45
Active and Passive Beam Application Design Guide
FIGURE 10-2 Beam zone temperature control with variable-volume primary airflow.
(such as classrooms and meeting rooms) where significant variations in occupancy are expected.
When whole-building DCV solutions are applied, the ventilation rate to each individual zone is
modulated between its design value and a minimum value, according to occupancy sensors.
Figure 10-3 shows demand-controlled ventilation with active beams. Upon an increase in
occupancy, a proportional volume of additional primary air is provided to compensate for the
added space ventilation and cooling loads. This additional primary air can be introduced via the
beams, through a separate supply air diffuser, or both. In this case, the water flow rate through the
beam will continue to be modulated in accordance with the zone temperature demand. When DCV
is applied with passive-beam systems, temperature and humidity are controlled, but the analysis is
less complex, because of the decoupling of the airflow rate and beam capacity.
46
10 Controls
47
Active and Passive Beam Application Design Guide
Figure 10-7 illustrates the use of a heat exchanger and separate, closed water loop. The primary
water flow in the heat exchanger is modulated to maintain the beam chilled-water supply temperature;
this is used when there are several uses of the primary chilled-water circuit.
Beam chilled-water temperature control is a closed-loop control system in which the supply water
temperature is controlled via adjustment of the water flow through a two- or three-way control valve or
heat exchanger installed on the suction side of the pump. In this application, the use of modulating
FIGURE 10-5 Open-loop beam chilled-water system supply temperature maintained by mixing
primary and secondary chilled water (three-way valve and bypass).
FIGURE 10-6 Open-loop beam chilled-water system supply water temperature maintained by
mixing primary and secondary chilled water (two-way valve and bypass).
48
10 Controls
valves (valve controlled) with proportional integral response is preferred. During the commissioning
process, the performance of the control system must be tested to verify that a stable supply water tem-
perature is achieved (i.e., that the temperature setpoint is met without significant error).
49
Active and Passive Beam Application Design Guide
In response to the sensor feedback, chilled-water supply temperature setpoint can be reset above the
room dew point or the supply water to the zone can be halted.
Figure 10-9 presents a control strategy in which the chilled-water supply temperature is varied
in accordance with the space dew-point temperature. In this case, the beam chilled-water tempera-
ture control system maintains a minimum differential between the space dew-point temperature
and its chilled-water supply. To maintain this differential, the dew-point temperature must be mon-
itored or calculated. This can be done by monitoring the humidity either in the return air duct or
directly in the zone. This strategy allows the coil within the beam to continue to contribute to the
space sensible cooling even during periods of elevated space moisture levels.
Figure 10-10 diagrams a strategy in which the beam chilled-water flow is interrupted when the
measured space dew-point temperature rises above the beam chilled-water supply temperature.
FIGURE 10-9 Condensation prevention strategy involving reset of beam chilled-water supply
temperature.
50
10 Controls
FIGURE 10-10 Condensation prevention strategy in which water flow is discontinued when
chilled-water temperature is below space dew-point temperature because of increased humidity
or decreased temperature in the zone.
51
Active and Passive Beam Application Design Guide
Window contact switches can detect if a window is open. Alternatively, moisture sensors, such as
that shown in Figure 10-8, may be used to discontinue the chilled-water flow during periods of conden-
sation risk. When these sensors are applied, one sensor should be installed on the chilled-water supply
pipe in each room (with operable windows or doors) the system serves. It must be remembered that the
chilled-water flow will not be restored until the sensor determines that all moisture has been evaporated
from the surface of the pipe.
Figure 10-12 illustrates a proactive sequence in which a sensor detects the opening of a window and
interrupts the chilled-water flow to the space. A surface moisture sensor is also used to ensure that the
space dew-point temperature is acceptable for restoring the chilled-water flow once the window is
closed. Now the control system can boost the airflow to the space to reduce the time to restore the
chilled water.
FIGURE 10-11 Control strategy in which chilled-water supply is halted when moisture is
detected on CHWS pipe.
52
10 Controls
FIGURE 10-12 Condensation prevention strategy involving interruption of water flow after
window is opened.
53
Active and Passive Beam Application Design Guide
11.1 INSTALLATION
Beams can be installed fully exposed, recessed, integrated within a suspended ceiling, or positioned
above a perforated or an open grid ceiling. When beams are installed within or above a ceiling, suitable
access must be provided for service and maintenance. It is recommended that a preinstallation meeting
be held between affected contractors to coordinate installation.
In all cases, active and passive beams should be independently supported with hangers from the
slab or structure above. Attention should be paid so that the beams are mounted in their specified verti-
cal positions to ensure adequate clearance from the structure when the upper surface serves as the return
air path. Beam weights are typically 7 to 15 lb/ft (10 to 20 kg/m) dry.
If beams are to be integrated into a suspended ceiling grid, the beams should be hung prior to the
grid installation. The beam should be initially mounted 2 ½ to 3 in. (60 to 75 mm) above the plane of the
finished ceiling. After installation of the ceiling grid, the beam is positioned horizontally, then carefully
lowered into the ceiling module. A mounting method that allows roughly 3 in. (75 mm) of movement in
all horizontal and vertical directions should be used to facilitate the final positioning in the ceiling sys-
tem. To allow beam movement and alignment, connections for the hydronic and air systems must be
properly selected. A typical installation can be seen in Figure 11-1.
Support location and installation should be done in accordance with manufacturer’s documentation.
Upon final positioning of the beam, all support connections should be adequately tightened and secured.
FIGURE 11-1 Installation of active beam using flexible hoses in water pipes and flexible duct in
air side.
54
11 Installation and Commissioning
When beams are connected to the pipe with threaded connections, caution should be used when
tightening the joint with a wrench to avoid coil damage because of the pipe’s relatively thin wall. Hard
pipe with solder, compression, or crimp connections can also be used.
11.3 BALANCING
Airflow-balancing dampers are often installed upstream of the active beam. It is recommended that
the primary airflow rate be determined by using a static pressure measurement in the beam plenum,
because it gives the most accurate reading at the relatively high pressure level (0.2 to 0.8 in. w.c. [50 to
200 Pa]). Pitot-tube traverse of the beam supply duct is difficult because of the low velocity pressure
levels and may prevent accurate measurement of the duct airflow rate. When balancing projects at sig-
nificant altitude, it is important to correct the pressure/airflow correlation for density.
FIGURE 11-2 Careful tightening of threaded pipe connections to avoid damage to beam coil.
55
Active and Passive Beam Application Design Guide
11.5 COMMISSIONING
When commissioning a beam system, several initial steps should be considered:
• Ensure that the coil is free of dust and debris by visual inspection.
• Ensure that the beam is free of all transportation packaging.
• Ensure that the primary air supply rate and temperature is within tolerance.
• Ensure that the supply water flow rate(s) and temperature(s) are within tolerance.
During commissioning, the commissioning agent should verify the operation of the control
sequence, including sensors used for condensation avoidance and any other project specifications.
• Breathing on dew-point or humidity sensors. This local increase of humidity from breath should be
sufficient to develop moisture on the device.
• Dripping water on condensation sensors.
• Opening the window to trip the contact.
These methods should trigger a signal and associated controller response, which can then be veri-
fied against the specified control sequence.
56
12 System Operation
12 SYSTEM OPERATION
12.1.1 Draught
Firstly, check that the room air temperature is not too low. Secondly, check that the airflow rate is
not too high or too low. Too high an airflow rate may create draught near the floor. Conversely, if the air-
flow rate is too low or too cold, the air jet may fall unintentionally downwards, which may create
draught at the neck level.
If the heat loads in the space are significantly higher than the capacity of the beam, the water flow
rate might be increased.
FIGURE 12-1 Cleaning of chilled beam. FIGURE 12-2 Cleaning of chilled beam.
57
Active and Passive Beam Application Design Guide
13.1 INTRODUCTION
When selecting HVAC systems, a life-cycle cost (LCC) analysis, or total cost of ownership (TCO)
calculation, is often performed for each different HVAC system. Important information for the LCC or
TCO analysis can be found in the 2011 ASHRAE Handbook—HVAC Applications, Chapter 37, Owning
and Operating Costs.
Compared to alternative HVAC systems, beam systems may offer significant savings in operat-
ing costs, namely in energy and maintenance. Replacement costs are also lower. When beam sys-
tems are used, mechanical rooms may be smaller, and suspended ceiling height may be reduced.
This offers the opportunity for a reduction in the floor-to-floor height and a potential increase in
the building usable floor area because of potentially smaller riser requirements. The increase in the
value of the building associated with the increase in the building usable area should be taken into
account in the TCO analysis.
Properly sized mechanical systems and energy-efficient building envelopes are fundamental for
energy-efficient operation. It is assumed that this condition exists and that the construction team is
fully committed to this goal. Careful attention must be given to renovation or retrofit projects,
because the envelope may require remediation to avoid moisture infiltration, thus assisting with suit-
able indoor humidity control for the beam system. Refer to ECS EN 13829, Thermal Performance of
Buildings—Determination of Air Permeability of Buildings—Fan Pressurization Method (ISO 2001),
ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Buildings Except Low-Rise Residen-
tial Buildings, and ANSI/ASHRAE/USGBC/IES Standard 189.1-2011, Standard for the Design of
High-Performance Green Buildings Except Low-Rise Residential Buildings.
58
13 Energy and Total Cost of Ownership
13.3.1 Energy
To calculate the energy costs, energy analysis should be performed using a dynamic energy simulation
program, preferably with a validated and widely used beam system model. In the absence of a beam model
that fulfills these conditions, the limitations of the model used should be fully understood, and a more
detailed analysis of the calculation’s output must be performed to validate the results.
To accurately simulate beam systems (as with any other system), it is necessary to fully know and
understand the technology to be simulated and the calculation method used in the simulation software.
Special attention should be taken of to ensure that the simulation correctly accounts for the latent load
(dehumidification) taken care at the air-handling unit and that only sensible cooling is performed at the
zones. Most energy simulation software provides models for HVAC systems that can be used to simu-
late beam systems, namely, beam system models, induction unit models, or fan coil models (in this case,
the fan energy must be subtracted from the final result).
As discussed in Chapters 7 and 8, beam systems have the following characteristics that may reduce
HVAC system energy consumption:
• Higher chilled-water temperatures (57°F–64°F [14°C–18°C]), which may increase chiller efficien-
cies
• Lower hot-water temperatures (90°F–113°F [32°C–45°C]), which creates an opportunity for the use
of low-temperature heat sources
• Use of water for zone-sensible cooling reduces transport energy costs
• Sufficient latent cooling produced at the AHU to ensure adequate humidity control, preventing con-
densation on the beam cooling coil
• Energy-efficient room air supply:
- Active beams: Air distribution in the room is powered by the air pressure in the beam plenum.
The pressure is produced by central, high-efficiency fans (in fan coil systems, air distribution is
powered by small, low-efficiency fans and motors).
- Passive beams: Ventilation and dehumidification air is typically supplied via a low-energy air dis-
tribution system, such as displacement ventilation or DCV.
On the other hand, compared to conventional water-based systems, beam systems consume more
pump energy because of the low water temperature differential (4°F to 6°F [2°C to 3°C]) when com-
pared to the conventional water temperature differential of 9°F (5°C).
The beams require chilled water at 57°F to 64°F (14°C to 18°C), but the AHU, for dehumidification
purposes, typically requires chilled water at around 42°F (6°C). The chiller plant may produce water at
42°F (6°C) and the required 57°F to 64°F (14°C to 18°C) water is produced by mixing with return
water. This is not an ideal solution with respect to energy efficiency, but the solution has an important
effect on energy consumption when compared to a conventional 42°F/54°F (6°C/12°C) chilled-water
system, due to the higher temperature of water returned to the chiller plant.
Energy consumption is minimized if there are dedicated chilled-water production systems for the
two different chilled-water temperatures required. This separation enhances energy efficiency for the
following reasons:
59
Active and Passive Beam Application Design Guide
• Dedicated chillers for the beams can work with a 57°F (14°C) chilled-water temperature setpoint,
highly increasing their energy efficiency rating (EER).
• Free cooling can be implemented with some of the following solutions/technologies:
- Cooling tower (for warmer/drier climates)
- Dry cooler (for colder climates)
- Geothermal sources (water or ground)
The energy analysis should take into consideration all of these aspects.
60
14 References and Bibliography
Alexander, D., and M. O’Rourke. 2008. Design considerations for active chilled beams. ASHRAE Jour-
nal 50(9): 50–8.
ASHRAE. n.d. ASHRAE Standard 200P, Methods of Testing Chilled Beams. Atlanta: ASHRAE.
ASHRAE. 2008. ASHRAE/ANSI/ASHRAE Standard 170-2008, Ventilation of Health Care Facilities.
Atlanta: ASHRAE.
ASHRAE. 2009. ASHRAE Handbook—Fundamentals. Atlanta: ASHRAE.
ASHRAE. 2011a. ANSI/ASHRAE/USGBC/IES Standard 189.1, Standard for the Design of High-Per-
formance Green Buildings Except Low-Rise Residential Buildings. Atlanta: ASHRAE.
ASHRAE. 2011b. ASHRAE Handbook—HVAC Applications. Atlanta: ASHRAE.
ASHRAE. 2013a. ANSI/ASHRAE Standard 55-2013, Thermal Environmental Conditions for Human
Occupancy. Atlanta: ASHRAE.
ASHRAE. 2013b. ANSI/ASHRAE 62.1-2013, Ventilation for Acceptable Indoor Air Quality. Atlanta:
ASHRAE.
ASHRAE. 2013c. ANSI/ASHRAE/IES Standard 90.1-2013, Energy Standard for Buildings Except
Low-Rise Residential Buildings. Atlanta: ASHRAE.
Barista, D. 2005. Chill the ceilings and achieve cool energy savings. Building Design and Construction
56(11).
Barnet, Barry M. 2008. Chilled beams for labs: Using dual energy recovery. ASHRAE Journal 50(12):28–37.
BSI. 2010. BS 8550, Guide for the Auditing of Water Quality Sampling. London: British Standards
Institution.
BSRIA. 2002. Flexible hoses—Code of practice for service installers. BSRIA Code of Practice COP 11/
2002. Bracknell, UK: Building Services Research and Information Association.
BSRIA. 2004. Flexible hose standard–A standard for manufacturers. BSRIA Guide BG 4/2004. Brack-
nell, UK: Building Services Research and Information Association.
BSRIA. 2010. Commissioning water systems. BSRIA Guide BG 2/2010. Bracknell, UK: Building Ser-
vices Research and Information Association.
BSRIA. 2011. Pre-commission Cleaning of Pipework Systems. BSRIA Guide BG 29/2011. Bracknell,
UK: Building Services Research and Information Association.
B&ES. 1998. HVCA DW 144:1998, Specification for Sheet Metal Ductwork, Low, Medium and High
Pressure/Velocity Air Systems. London: Building and Engineering Services Association.
B&ES. 2000. HVCA DW143: 2000, Practical Guide to Ductwork Leakage Testing. London: Building
and Engineering Services Association.
CIBSE. 2004. CIBSE Commissioning Code A: 1996/2004 Air Distribution Systems. London: Char-
tered Institution of Building Services Engineers.
CIBSE. 2010. CIBSE Commissioning Code W: 2010 Water Distribution Systems. London: Chartered
Institution of Building Services Engineers.
CBCA. 2013. Summary findings. CBCA Technical Fact Sheet 2, EDSL Tas Energy Study, June 2013.
Chilled Beams and Ceilings Association.
DOE. 2010a. Engineering reference. EnergyPlus Manual. April. Washington: U.S. Department of
Energy.
DOE. 2010b. Input-output Reference. EnergyPlus Manual, April. Washington: U.S. Department of
Energy.
61
Active and Passive Beam Application Design Guide
62
14 References and Bibliography
Rumsey, P., and J. Weale. 2007. Chilled beam in labs: eliminating reheat & saving energy on a budget.
ASHRAE Journal 49(1):18–25.
Ruponen, Streblow, Mustakallio. Room velocity control for room ventilation device. Presented at the
8th REHVA world congress CLIMA 2005, Lausanne, Switzerland.
Schultz, C.C. 2007. Next-generation cooling is looking up. Engineered Systems, 24(5):64.
Simmonds, P. 1993a. Designing comfortable office climates. Presented at the ASHRAE Building
Design Technology and Occupant Well-being in Temperate Climates International Conference,
Brussels, Belgium.
Simmonds, P. 1993b. Dynamic comfort control. Presented at the CIBSE National Conference, Man-
chester, England.
Simmonds, P. 1993c. Thermal comfort and optimal energy use. ASHRAE Transactions 99(1):1037–48.
Simmonds, P. 2010. Controlling and operating active chilled beam systems. Presented at the ASHRAE
Annual Conference, Albuquerque, NM.
Simmonds, P. 2011. Do active beams save energy and provide occupant comfort? Presented at the
ASHRAE Winter Conference, Las Vegas, NV.
Simmonds, P. 2013. To beam or not to beam. Engineered Systems, January.
TIAX. 2002. Energy consumption characteristics of commercial building HVAC systems—Volume III:
Energy savings potential. Final Report to U.S. Department of Energy, Office of Building Technolo-
gies.
University of Wisconsin–Madison. 2007. TRNSYS 16 Input Output Parameter Reference. March. Mad-
ison: University of Wisconsin–Madison.
Virta (ed.), Butler, Gräslund, Hogeling, Kristiansen, Reinikainen, and Svensson. 2004. Chilled Beam
Application Guidebook, Rehva Guidebook No. 5. Brussels: REHVA, Federation of European Heat-
ing, Ventilation, and Air Conditioning Associations.
Virta, M., Takki, T., and Oy, I. 2005. WS 07—Air Distribution Systems. Presented at the Rehva Work-
shops at Clima, Rehva Europe, October.
Weidner, Steve, Jerome Doerger, and Michael Walsh. 2009. Cooling with less air using underfloor air
distribution and chilled beams. ASHRAE Journal 51(12).
Woollett, Åkesson. 2014. Chilled beam technology overview. Presented at the TTMD IX International
HVAC+R Technology Symposium, Istanbul, May.
63
Active and Passive Beam Application Design Guide
TABLE A-2 Beam Selection Data and Layout for Cellular Office
Parameter Value Units Notes
Number of beams 1 —
66
Appendix A: Examples for I-P Applications
Discussion Points
Given the high level of flexibility required for office buildings and also the very variable effective
occupancy that often occurs, the system must be conceived and dimensioned so that it is easily adapted to
different floor plan layouts and occupant densities. The following provisions should be made in design:
• Adequate air distribution must be verified with and without room partitions while checking ade-
quate air distribution in critical points, namely where colliding airstreams occur.
• Design the primary air distribution system for variable airflow.
In the branch primary air duct for the beam, a motorized damper is installed. This motorized
damper is actuated to control the pressure in the beam plenum. The beam plenum pressure has two set-
points, one corresponding to occupied room, design conditions, and the other to unoccupied room. The
room occupancy is detected by a simple occupancy detector integrated into the beam.
In the unoccupied mode, adequate air distribution is not required. The beam selection only needs to
ensure adequate air distribution at design conditions.
The primary airflow required for dehumidification exceeds that required for ventilation and is propor-
tional to the humidity ratio difference between indoor air and primary air; slightly increasing the allowable
indoor air dew point or slightly decreasing the primary air dew point can significantly reduce the primary air-
flow required for dehumidification. On the other hand, the chilled-water temperature supplied to the beam
must be at or above the indoor air dew point, thus increasing the indoor air dew point reduces the beam water
coil cooling capacity. The designer must balance these aspects when choosing these parameters.
One key parameter is the safety temperature difference between the temperature of the chilled water
supplied to the beam and the indoor air dew point. The temperature’s value is a designer’s choice and must
be equal to or greater than zero. In this example, a value of 0.5 was chosen. Typical values are 0 to 1 K.
TABLE A-3 Beam Selection Data and Layout (Passive Beam Example)
Parameter Value Units Notes
Number of beam 1 —
Beam width 24 in.
Beam length 96 in.
Water temperature in 60 °F From “beam calculation”
Water temperature out 64.6 °F Manufacturer’s performance data
Water flow rate 1 gpm Manufacturer’s performance data
Water pressure drop 3.6 ft Manufacturer’s performance data
Cooling capacity, air 521 Btu/h From “beam calculation”
Cooling capacity, water 2227 Btu/h Manufacturer’s performance data
Transfer effectiveness 115 Btu/h·ft3 Cooling capacity/primary airflow
Height of occupied zone 3.5 ft Owner’s project requirement
Maximum velocity in occupied zone 54–62 fpm Owner’s project requirement
67
Active and Passive Beam Application Design Guide
Discussion
Passive beams provide sensible cooling to the space, without any ventilation. In this example,
it is assumed that the airflow supplied to the space will add to the sensible cooling. Based on the
beam calculation table, 24 cfm are required to meet the latent load requirements. Supplied at 55°F,
the airflow supplied to the space complements the passive beam sensible cooling to meet the design
conditions.
A variety of air distribution methods may be used with a passive beam. In this example, over-
head air distribution was chosen. This method of air distribution allows the designer to supply
colder air in the space without causing discomfort to the occupants.
Displacement ventilation or underfloor air distribution could also be used with passive beams.
Because the passive beam creates a gentle plume of cold air in the room, it shares many attributes
with stratified air systems. That being said, it is important to consider that this cold plume will cre-
ate some mixing in the occupied space and may induce some contaminants in the occupied space.
Heating is supplied by a separate system.
Considering the plume created by the passive beam, its placement in the room is particularly
important. The velocity below the beam chosen for this example will vary between 54 and 62 fpm.
To avoid creating discomfort for the occupants, the passive beam should be installed away from the
occupant’s workstation. Ideally, the beam should be installed above a transient zone in that space or
along a wall.
68
Appendix A: Examples for I-P Applications
TABLE A-5 Beam Selection Data and Layout for Open-Plan Office
Number of beams 3 —
71
Active and Passive Beam Application Design Guide
TABLE A-7 Beam Selection Data and Layout (Conference Room Example)
Quantity of beams 2 2 2
Sound power, NC 33 — —
Occupancy, persons 10 0 2
74
Appendix A: Examples for I-P Applications
Discussion Points
Conference rooms often have high primary airflows because of ventilation and dehumidification
requirements and, therefore, in design conditions, the percentage of cooling performed by air is greater
than in rooms that require less primary airflow. This situation can only be avoided through the supply of
primary air close to the indoor air temperature, not the best solution in terms of energy consumption in a
hot and humid climate like New Orleans.
In this example, a primary air temperature of 57°F was chosen and, at design conditions, the per-
centage of cooling by air reaches 43%. More than half of the sensible cooling load of the room is asso-
ciated with occupancy and electronic equipment, so a demand-controlled ventilation (DCV) system was
adopted that modulates the primary airflow according to the space CO2 concentration.
Early condensation detection overrides the DCV control and forces maximum primary airflow to
stop condensate formation. With this control strategy, when the conference room is unoccupied or at
less than design occupancy, the primary airflow is kept to a minimum, and most of the cooling is per-
formed by the water coil. The primary airflow will automatically rise with the rise in the number of
occupants, delivering the cooling by air only when required, avoiding reheat energy consumption.
Because the room can be occupied in times when the primary airflow is significantly reduced from
the design airflow, the beams selected must be able to promote adequate air distribution in the pre-
viewed range of primary airflows.
75
Active and Passive Beam Application Design Guide
CFMALL AIR = LSENS / [1.085 × (DBIDA – DBSA)] = 34,800/(1.085 × 20) = 1603 cfm
Number of beams 6 —
78
Appendix A: Examples for I-P Applications
79
Active and Passive Beam Application Design Guide
Discussion Points
When all-air VAV systems are used in patient rooms, a minimum of 6 ach must be delivered by
the air-handling unit at all times. When a supply air temperature of 60°F is used, this results a deliv-
ery of 378 cfm (8 ach) at design cooling conditions, but the supply air volume flow rate can never
be reduced below 6 ach. The reduced delivery results in a sensible cooling rate that remains 75% of
the design value. During periods where the space cooling demand is below 75% of the design
value, reheat of the supply air must be accomplished to offset the overcooling it provides.
The ventilation (primary) airflow rate (2 ach) of the beams provides only 25% of the space design
cooling; the remainder is provided by the beams’ coils. As such, the beam system can react to a 75%
reduction in space-cooling demand by simple modulation of the zone chilled-water flow rate (without
reheat).
82
Appendix A: Examples for I-P Applications
TABLE A-11 Beam Selection Data and Layout (Patient Room Example)
Number of beams 1 —
83
Appendix A: Examples for I-P Applications
TABLE A-13 Beam Selection Data and Layout (Hotel Room Example)
Number of beams 1 —
Maximum air velocity in the occupied zone 50 fpm Owner’s project requirements
87
Active and Passive Beam Application Design Guide
Discussion Points
In some applications, a fast temperature response may be required (e.g., to get the room to comfort
conditions after a room reservation is made in the front office system). In this situation, a larger beam
would be a solution.
Condensation detection is imperative, because of moisture transfer from the bathroom and the exis-
tence of operable windows.
To minimize reheating in nonoccupied hours, consider the following:
Dust content from linen creates the requirement for regular vacuum cleaning of the water coil.
88
Appendix B: Examples for SI Applications
TABLE B-2 Beam Selection Data and Layout for Cellular Office
Number of beams 1 —
Pressure drop 58 Pa
Maximum predicted velocity in occupied zone 0.20 m/s Owners project requirements
91
Active and Passive Beam Application Design Guide
Discussion Points
Given the high level of flexibility required for office buildings and also the very variable effective
occupancy that often occurs, the system must be conceived and dimensioned so that it is easily adapted
to different floor plan layouts and occupant densities. The following provisions should be made in
design:
• Adequate air distribution must be verified with and without room partitions, checking adequate air
distribution in critical points, namely where colliding airstreams occur.
• Design the primary air distribution system for variable airflow.
In the branch primary air duct for the beam, a motorized damper is installed. This motorized
damper is actuated to control the pressure in the beam plenum. The beam plenum pressure has two set-
points, one corresponding to occupied room, design conditions, and the other to unoccupied room. The
room occupancy is detected by a simple occupancy detector integrated in the beam.
In the unoccupied mode, adequate air distribution is not required; the beam selection only needs to
ensure adequate air distribution at design conditions.
The primary airflow required for dehumidification is proportional to the humidity ratio differ-
ence between indoor air and primary air; slightly increasing the allowable indoor air dew point or
slightly decreasing the primary air dew point can significantly reduce the primary airflow required
for dehumidification. On the other hand, because the chilled-water temperature supplied to the
beam must be at or above the indoor air dew point, increasing the indoor air dew point reduces the
beam water coil cooling capacity. The designer must balance these aspects when choosing these
parameters.
92
Active and Passive Beam Application Design Guide
TABLE B-4 Beam Selection Data and Layout for Open-Office Plan
Number of beams 3 —
Pressure drop 72 Pa
96
Active and Passive Beam Application Design Guide
TABLE B-6 Beam Selection Data and Layout for Conference Room
Minimum Medium Maximum
Parameter Units Notes
Airflow Airflow Airflow
Number of beams 3 3 3 —
Cooling capacity/
Transfer effectiveness 90 91 87 W/L·s
primary airflow
100
Appendix B: Examples for SI Applications
Discussion Points
Conference rooms have high primary airflows because of ventilation and dehumidification require-
ments, and, therefore, in design conditions, the percentage of cooling performed by air is bigger than in
other kind of rooms that require less primary airflow. This situation can only be avoided through the
supply of primary air close to the indoor air temperature, not be the best solution in terms of energy con-
sumption in a hot and humid climate like Hong Kong.
In this example, a primary air temperature of 14°C was chosen and, in design conditions, the per-
centage of cooling by air reaches 60%. Slightly over half of the sensible cooling load of the room is
associated with occupancy (persons and personal electronic equipment) and a demand-controlled venti-
lation (DCV) system was adopted, modulating the primary airflow according to CO2 measurement in
the indoor air. Thus, this additional cooling by air occurs only when required.
Early condensation detection overrides the DCV control and forces maximum primary airflow,
stopping condensate formation.
With this design and control strategy, most of the working hours in which the conference room is
unoccupied or has less than design occupancy, the primary airflow is kept to a minimum, and almost all
of the cooling is performed by the water coil. The primary airflow will automatically rise with the rise in
the number of occupants, delivering the cooling by air only when required and avoiding reheat energy
consumption.
Because the room can be occupied in times when the primary airflow is significantly reduced from
the design airflow, the beams selected must be able to promote adequate air distribution in the pre-
viewed range of primary airflows.
101
Active and Passive Beam Application Design Guide
Number of beams 6 —
104
Appendix B: Examples for SI Applications
Beams with a T0.25 of 4.8 m or less may be selected and located above the two outdoor lab
benches, as illustrated below. Manufacturer’s data indicates a T0.25 value of 3.7 m; thus, the selection
is appropriate.
Note that an all-air variable-air-volume (VAV) system supplying air at 13°C would have required
757 L/s to meet the design sensible cooling load of the space, according to the following equation:
L/s ALL AIR = LSENS/[1.2 × (DBIDA – DBSA)] = 10200/(1.2 × 20) = 757 L/s
105
Active and Passive Beam Application Design Guide
TABLE B-10 Beam Selection Data and Layout (Patient Room Example)
Maximum air velocity in occupied zone 0.15 m/s Owners project requirements
108
Appendix B: Examples for SI Applications
Beams capable of satisfying the design sensible cooling and heating loads with a primary airflow
rate of 69 L/s each are desired.
Manufacturer’s data indicates that two 1.5 m long beams, supplied with, in total, 69 L/s of primary
air and 0.1222 L/s of 16°C chilled water, will provide the required sensible cooling. The same beams
with 35°C hot water supplied at 0.061 L/s can deliver the required heating.
Discussion Points
The ventilation (primary) airflow rate (1.8 ach) of the beams provides only 31% of the space
design cooling; the remainder is provided by the beam’s coil. As such, the beam system can react to
a 69% reduction in space cooling demand by simple modulation of the zone chilled-water flow rate
(without reheat).
109
Active and Passive Beam Application Design Guide
Maximum air velocity in occupied zone 0.15 m/s Owner’s project requirements
110
Active and Passive Beam Application Design Guide
TABLE B-13 Beam Selection Data and Layout (Hotel Room Example)
Number of beams 1 —
Pressure drop 75 Pa
114
Appendix B: Examples for SI Applications
The same beams with 45°C hot water supplied at 0,022 L/s, 1.9 kPa, can deliver the required heating.
TABLE B-14 Beam Selection Data and Layout (Hotel Room Example)
Discussion Points
In some applications, a fast temperature response may be required (e.g., to get the room to comfort
conditions after a room reservation is made in the front office system). In this situation, a larger beam
would be a solution. Another solution is to have VAV primary air and supply maximum primary boosted
airflow for a short period of time before occupancy.
Condensation detection is imperative, because of moisture transfer from the bathroom and the exis-
tence of operable windows.
To minimize reheating in nonoccupied hours, consider the following:
Dust content from linen creates the requirement for regular vacuum cleaning of the water coil.
During selection, adopting a larger cooling water temperature T (e.g., 3 K) would result in lower
pressure drop and lower water flow.
115