Ppfa CPVC Installation Handb
Ppfa CPVC Installation Handb
2
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
3
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
4
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Installation
Wheel cutters: Wheel–type plastic tubing cut-
With Primer or One-step Sol- ters2 with blades made for cutting plastic pipe may
vent Cementing Method be used if blades are regularly sharpened. However,
these type cutters will create raised ridges that are
CPVC piping and fittings are joined with CPVC ce- caused by material displacement from the downward
ments. The solvent cement process can be a one- or force of the cutting wheel and the ridges must then be
a two-step process. The one-step cement does not removed.
require the use of a primer and the cement will be
yellow in color. The two-step process does require
the use of a primer and the cement will be orange in
color. Both types of cements are manufactured under
ASTM F493 for use with CPVC hot- and cold-water
piping. The label on the can will indicate the cement
color and whether a primer is required. Before using
one-step cement, check to determine if the local code
permits its use or if a two-step cement with primer is
required. Primer is manufactured under ASTM F656
and can be clear or purple in color (also verify local Image 2. Tubing Style Cutter with a Reaming Tool
code requirements for required primer color).
Fine tooth saw: When saw cutting, a miter box
Joining CTS CPVC Tube and should be used to ensure a square cut. Cutting tubing
Fittings as squarely as possible provides optimal bonding area
within a joint.
Note: Scissor-style cutters are not recommended
Step 1: Cutting because of the extreme forces that may be applied to
the pipe.
A variety of cutting tools are available and recom-
mended for use with CPVC pipe. CTS CPVC can
be easily cut with a wheel type plastic tubing cutter, Cutting previously installed CPVC: Pip-
ratchet cutter, or fine tooth saw, depending on the tool ing that has been in service for long periods of time
size available. should be cut with a fine tooth saw or a wheel-type
cutter. In such instances, ratchet cutters may cause
end cracking on the aged pipe and are not recom-
Ratchet cutters: The use of ratchet cutters 1 is
mended.
permitted under certain condition, but blades must be
regularly sharpened and should not be used when am-
If any indication of damage or cracking is evident at
bient temperature is below 50oF due to the increased
the tubing end, cut off 3 at least 2” beyond any visible
risk of overstressing the pipe.
damage.
5
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Step 5: Assembly
6
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
around the joint. If this bead is not continuous around minimize chances of pushing solvent cement to the
the socket edge, it may indicate that insufficient ce- bottom of the joint.
ment was applied. In this case, remake the joint to
avoid potential leaks. Wipe excess cement from the
tubing and fittings surfaces for an attractive, profes-
sional appearance
Image 8. Assembly
Image 10. Deburring
Joining IPS CPVC Pipe and
Step 3: Fitting Preparation
Fittings
Using a clean dry rag, wipe dirt and moisture from
Step 1: Cutting the fitting socket and pipe end11. Moisture can slow
the curing, and dirt can prevent adhesion. Check the
IPS CPVC pipe can be easily cut with a mechanical dry fit of the pipe and fitting12. For a proper interfer-
saw9 or fine-toothed saw. To ensure a square cut, a ence fit, the pipe should enter the fitting socket 1/3 to
miter box should be used. Cutting the pipe as square- 2/3 of the depth.
ly as possible provides maximum bonding area in the
most effective part of the joint.
Image 11 and 12. Fitting preparation
7
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Once the fitting socket has been primed, aggressively Image 16. Cement application
work the primer14 around the end of the pipe to a
depth of about ½” beyond the socket depth. Step 8: Fitting Solvent Cement Applica-
tion
8
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Step 10: Assembly inches with every 100°F degree temperature increase.
Expansion does not vary with pipe diameter. Mea-
While the cement is still wet, immediately assemble sured expansion of installed piping is typically well
the pipe and fitting, rotating the pipe ¼ to ½ turn (if below the theoretical values. Although some expan-
possible) until the fitting stop is reached. Hold the sion joints are available, they are rarely used in water
assembly together for approximately 30 seconds to distribution systems.
avoid push out19. A continuous bead of cement should
be evident around the pipe and fitting juncture. If the Generally, thermal expansion can be accommodated
bead is not continuous, sufficient cement was not ap- with changes in direction; however, a long straight
plied and the joint may be defective. In this case, the run may require an offset or loop. Only one expan-
fitting should be discarded and the joint reassembled. sion loop, properly sized, is required in any single
Wipe excess cement from the pipe and fittings sur- straight run, regardless of its total length. If more
faces for an attractive, professional appearance20. convenient, two or more smaller expansion loops,
properly sized, can be utilized in a single run of pipe
to accommodate the thermal movement. In addition,
there are many ways to compensate for expansion
and contraction in vertical piping, always consult the
pipe manufacturer for specific recommendations.
9
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Support Spacing
Supports
Where pipes go through wood studs, provide oversize Although such incremental variations are technically
holes to allow pipe to move. When installed through correct, most codes use the simplified version shown
metal studs, provide some form of plastic insulators, in Table 6.
pipe insulation or similar devices to protect the pipe
from abrasion and to prevent noise. Verify the insu-
lating device is chemically compatible with CPVC.
See Appendix A for further details.
10
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
11
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Water Heater
Connections
Some plumbing codes contain detailed requirements
for connections to gas or electric storage type water
heaters. Determine whether your jurisdiction has
such code requirements and satisfy them.
Image 22. Sample compression fittings
If no detailed requirements exist, use the following
Thread Sealants information. On electric water heaters CPVC can
be piped directly to the heater with special metal-to-
Threaded CPVC fittings with tapered pipe threads CPVC transition fittings. On high-efficiency, gas wa-
(e.g. male thread adapters) must be used with a suit- ter heaters that use plastic vent piping, CPVC can be
able thread sealant to insure leak-proof joints. Over connected directly to the heater just like the electric
the years, PTFE tape has been the preferred thread water heater connections 23. On all other gas water
sealant and it is still the most widely accepted and heaters there should be at least 6 inches of clearance
approved sealant. between the exhaust flue and any CPVC piping 24.
Six-inch long metal nipples or appliance connectors
Some paste sealants may negatively affect CPVC should be connected directly to the heater so that the
fittings; therefore only sealants recommended for CPVC tubing cannot be damaged by the build-up of
use with CPVC by the thread sealant manufacturer excessive radiant heat from the flue.
should be used.
An approved temperature/pressure (T/P) relief valve
should be installed so that the probe or sensing ele-
Chemical Resistance ment is in the water at the top of the heater. CPVC
is approved by all the model codes for use as relief
CPVC piping products can be susceptible to stress valve drain line piping. Although CPVC is rated for
cracking agents that may be found in certain ancillary 100 psi at 180 ºF, it is suitable for the higher tempera-
products. The information in Appendix A, “Analy- ture of 210 ºF, because the pressure is nearly zero psi
sis of Improper Use or Installation Issues”, has been for a discharge pipe that is open to the atmosphere.
generated to create awareness that the potential for Water heater temperature relief valves are generally
damage exists. Contact the CPVC manufacturer for set to open at 210 ºF.
additional detailed information.
Use a metal-to-CPVC transition fitting to connect to
When choosing ancillary products that are intended the relief valve and continue the pipe full size to the
to be in direct contact with the piping system, such as outlet. For horizontal runs, slope the pipe toward the
thread sealants, fire stopping materials, pipe insula- outlet and support it at three-foot centers or closer.
tion, etc., the installer should choose products that The pipe must discharge to the atmosphere at an ap-
have demonstrated little or no effect on the piping proved location.
material. ALWAYS CHECK with the pipe and fittings
manufacturer if you have questions regarding chemi- While CPVC piping systems are suitable for use with
cal compatibility. If chemical compatibility with the properly controlled residential tank less water heat-
plastic remains in question, it is recommended to ers, do not use CPVC pipe and fittings with commer-
isolate the suspect product from direct contact with cial-type, non-storage water heaters. Many residential
the CPVC pipe or fittings. tank less water heaters in North America are limited
12
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
to the temperature range of 122ºF to 140ºF. This also a factor in the joint setting and curing process.
temperature is within the specific range of CPVC Joint setting time refers to the time required for the
materials used in plumbing applications. solvent-cement joint to reach handling strength.
Do not use CPVC pipe and fittings where operat- Joint set and cure times are a function of pipe size,
ing temperatures can exceed 180°F. Exceeding the temperature, humidity, degree of interference, and
temperature/pressure ratings of the pipe is not recom- even length of the pipes being handled. Curing time
mended and may result in system failure. is shorter for drier environments, smaller sizes, and
higher temperatures. Follow the solvent cement
manufacturer’s recommended set and cure times.
Thermal Conductiv-
Pressure Testing ity, Condensation, &
(Joint Cure Time) Sweating
When pressure testing CPVC piping, the focus is on In general, plastic materials have low coefficients of
time required for the solvent-cemented joints to gain thermal conductivity when compared with metallic
sufficient strength to permit pressure testing without materials (see table below). Because of this, some
affecting the long-term strength and durability of the users ask whether insulation is necessary to prevent
system. ASTM D2846 contains pipe OD and socket heat loss from hot water piping or sweating of cold-
ID tolerance requirements that are more restrictive water piping. Generally, it is not necessary to insulate
than those in most other pressure piping standards. CPVC piping within heated buildings unless it is
Because of this, the solvent-cemented joints gain required by local codes. Following are some factors
strength very quickly after assembly. to support this:
Furthermore, it is widely recognized that pipe size is 2” Schedule 80 CPVC pipe (2.375” OD - 0.230”
13
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
wall) would lose about 140 BTU/h/LF while convey- this condition immediately stops the flow of water at
ing 170° F water in a 70° F air environment. the fixture, it may or may not have progressed to the
point of rupturing the pipe. Therefore, immediate
2” Type M copper tube (2.125” OD - 0.060” wall) steps should be taken to eliminate the source of air
would lose about 5,000 BTU/h/LF under the same causing the freeze condition, locate the frozen section
conditions. and thaw the water line, if possible.
However, both the CPVC and the copper pipe will As soon as the frozen section is located, close any
cool to ambient temperature in a short time when outside openings with insulation, circulate warm
there is no flow. air into the area, or direct heated air onto the piping
using a low wattage heater/blower. A second op-
CPVC piping carrying 180° F water will have an tion is to apply electrical heat tapes to the problem
outside surface temperature of about 150° F in an air- area. Limit the heat source to 180° F or less. If the
conditioned building. frozen section is substantially inaccessible, it may be
possible to cut open the line at an accessible point
Under most use conditions that cause copper tube to and insert a small flexible tube and pump hot water
sweat and drip, CPVC will remain free of condensa- directly to the ice plug. As the hot water is pumped
tion. in and the ice is melted, the excess flows back out
around the flexible tube.
Thermal conduction is defined as “transfer of heat
from one part of a body to another part of the same Once the ice plug has melted, check to see if any pipe
body, or from one body to another in physical con- or fitting is ruptured, make repairs if necessary, and
tact with it, without appreciable displacement of the insulate the area or pipe to prevent future freezing.
particles of the body.” This definition leads us to the Do not use an open flame to heat the frozen pipe.
commonly used “K” factor Table 7, which refers to
thermal conductivity.
14
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
taken to provide a suitable ground whenever CPVC slab must be pressure-tested3 before pouring the slab.
piping is installed to replace metal piping that has The tube should be sleeved where it penetrates the
been used as a ground. Because plastic water service slab and at construction joints in the slab.
lines are being used extensively, and because of gal-
vanic corrosion to metal piping systems from ground CPVC water piping, manufactured in accordance
faults, many codes prohibit grounding to any type of with ASTM D2846, is available in coils for underslab
hot and cold water pipe. Check your local code. installations. When turning the end up through the
slab, into walls, etc., be careful not to kink the pipe.
Fire Rated Construc- Should a kink result, it must be cut out to avoid pos-
sible failure. Follow the pipe manufacturer’s installa-
tion tion instructions for minimum bend radius permitted
to be imposed on the coiled pipe.
CPVC water piping can be used within fire rated
buildings provided all penetrations of fire barriers
(e.g. walls or floor slabs) are made in such a way that
CPVC in Plenums
the fire rating of the barrier will not be compromised. CPVC plumbing pipe is safe for installation in return
Most codes and code officials accept penetration air plenums; however, the installation must be ap-
sealing systems or devices that have qualified for UL proved by the local jurisdiction. Even though CPVC
Certification and Listing or have passed appropriate is considered a combustible material, it will not burn
ASTM E119 or E814 tests. The PPFA manual Plastic without a significant external flame source. CPVC
Pipe in Fire Resistive Construction provides more requires an environment with at least 60% oxygen
detailed information on this subject and lists available to sustain a flame, Earth’s atmosphere contains only
test reports. (Or see the current issue of the Under- 21% oxygen, meaning that once a flame source is
writers Laboratories, Inc. Directories of Fire Resis- removed, CPVC will not sustain combustion.
tance - Vol. II or WHI Certification Listings.). Some
fire stop sealants contain solvents or other chemical Testing indicates that water filled CPVC in diameters
additives that can cause damage to CPVC. Only use 6 inches or less will pass the 25/50 flame smoke
compatible fire stop materials, systems or devices developed requirements for non-metallic material in
which are recommended for use with CPVC. return air plenums. Refer to piping manufacturer for
specific test reports and approvals.
Underslab Installa- CPVC fire sprinkler pipe tested and listed in accor-
tions dance with UL 1887, “Fire Test of Plastic Sprinkler
Pipe for Flame and Smoke Characteristics,” meets
CPVC is approved for underslab installations, with
model code requirements for installation in return air
joints, in all model plumbing codes. Some local
plenums.
codes contain restrictions on joints underslab and
other installation practices; always verify local code
requirements. Revision Policy
The PPFA CPVC Product Line Committee has initial
When performing underslab installations, it is im- responsibility for assuring that the data and other in-
portant that the tube is evenly supported on a smooth
bottom. The bedding and backfill should be sand or
clean soil free of sharp rocks and other debris that 3
The IAPMO IS 20 (Installation Standard for CPVC SOL-
could damage the tube. Systems with joints under VENT CEMENTED HOT AND COLD WATER DISTRIBU-
TION SYSTEMS) requires a pressure test for 2 hours. This
requirement applies only to pipe installed under a slab.
15
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
16
Installation Handbook:
CPVC Hot & Cold Water Piping
Appendix A: Analysis of Improper
Use or Installation Issues
18
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
system is not being used to support wire or cable, and the product (i.e. product identification, listing marks,
that runs of wire and cable have not been pulled over etc.) and to change color of the pipe and fittings from
the installed CPVC system. its identifiable color prior to painting.
Rubber and Flexible Materials: CPVC is Cooking Oils and Grease: When CPVC pipe
not compatible with many rubber and flexible plastic is installed in kitchen areas the pipe must be protect-
materials as these materials may contain certain types ed from contact with grease or cooking oils. Certain
of plasticizers, which when placed in contact with cooking oils can cause the CPVC piping to crack,
CPVC can cause the piping system to crack, leak leak, or break when applied to the piping system.
or break 2. (Incompatible plasticizers include, but
are not limited to, phthalates, adipates, trimellitates, Spray On Coatings: Certain types of spray-on
dibenzoates, etc.) Incompatible rubber and flexible coatings that form a peelable film to protect fixtures
plastic materials can be found in plastic hangers or during construction may be incompatible with CPVC.
plastic coated hangers, hoses and tank linings and in Care should be used to protect exposed piping from
the fluids that come in contact with them. over-spray when this type of protective coating is
applied.
19
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
20
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Section Two
Thermal / Thermal
Expansion Damage
Excessive stress and restriction of movement from
thermal expansion can damage any piping material. Image 5 & 6. Thermal expansion / contraction dam-
age to fitting
CPVC, like all other materials, undergoes changes in
length as a result of temperature variations above and
below the installation temperature. When designing
or installing a CPVC system, you must compensate
for the expansion and/or contraction of the system
due to the temperature fluctuations.
Image 7. Pipe under excessive flexural stress
There are three primary methods for controlling or
compensating for expansion and contraction:offsets, Improperly designed expansion loops:
loops and changes of direction. Below are examples 4 Properly designing expansion loops, offsets and
of each. changes in direction will ensure that excessive flex-
ural stresses do not contribute to the system failure
or property damage. In the image 8 you can see that
there was no area for movement in the loop.In the
second photo9 you can see that room for expansion
was incorporated and the system was allowed to
move, relieving flexural stresses.
21
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Hangers restricting movement: Proper sizing Non-uniform support: Piping systems should
of offsets, loops and changes of direction are critical also be uniformly supported, and installed away
to the overall effectiveness of the compensation for from sources of high heat, such as a combustion flue.
expansion and contraction, as are the accurate place- Failure to properly locate or support pipe can damage
ment of guides and anchors. If movement occurs and or place stress on the piping system, as seen in the
the system is constrained either by a stationary object photo examples 12, 13 below.
or anchor, therefore restricting movement, stresses
and forces may cause damage to the pipe system. In
the example below 10 you can see that restraints are
improperly placed on the vertical arms of the expan-
sion loop, thereby obstructing expansion.
22
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
Image 14. CPVC in UV protective cover Dull cutting blades: Tools used to cut pipe
must be in good condition. Cutting blades should
Prior to installation, CPVC pipe and fittings should be sharpened regularly to prevent overly stressing
be inspected for physical damage that can occur dur- the pipe that can create minute breaks in the pipe 18
ing shipping or from improper handling such as from that can grow to create leaks. A longitudinal crack,
being dropped or struck by another object. Improper which caused a leak located several inches back from
handling of CPVC pipe and fittings 15, 16 can create the end of the joint, is an indication that the pipe was
minute cracks at or near the area of impact. These possibly overly stressed due to improper cutting such
cracks often occur near the ends of the pipe. While as from dull cutting blades.
these cracks may not be immediately visible, in ser-
vice they can grow to eventually permeate the pipe Cold weather use of cutters: The use of
wall and cause leaks. Longitudinal cracks may occur ratchet cutters is permitted under certain condition,
along an extrusion line on the inside wall of the pipe. but should not be used when ambient temperature is
These extrusion lines are not the cause of the crack or below 50oF due to the increased risk of overstressing
leak, but rather concentration points for the stresses the pipe.
that result from improper cutting or improper han-
dling.
Image 15 and 16. Pipe or fitting damaged before Image 18. End crack shown in cutaway
installation
23
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
24
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
25
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
26
CPVC Piping Systems - Installation Handbook: CPVC Hot & Cold Water Piping
27