1) The document discusses psychrometrics and air conditioning processes including psychrometric charts, simple heating and cooling where humidity is constant, humidification, cooling and humidification, and cooling and dehumidification. 2) Key psychrometric properties discussed include dry bulb temperature, humidity ratio, relative humidity, specific enthalpy, wet bulb temperature, and dew point temperature. 3) Air conditioning processes explained include heating, cooling, humidification, bypass factor, contact factor, sensible heat factor.

Uploaded by

mondyelgabry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views

Section10-Psychrometry Introduction

1) The document discusses psychrometrics and air conditioning processes including psychrometric charts, simple heating and cooling where humidity is constant, humidification, cooling and humidification, and cooling and dehumidification. 2) Key psychrometric properties discussed include dry bulb temperature, humidity ratio, relative humidity, specific enthalpy, wet bulb temperature, and dew point temperature. 3) Air conditioning processes explained include heating, cooling, humidification, bypass factor, contact factor, sensible heat factor.

Uploaded by

mondyelgabry
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

Thermodynamics II (ME333)

Section 10 – Psychrometry Introduction


ENG. ZIAD ASHRAF ABOULSEOUD

College of Engineering & Technology


Mechanical Engineering Department (Mechatronics Program)
Content
• Psychrometric chart
• Air conditioning processes
• Solving questions

5/18/2023 2
5/18/2023 3
1. Dry-bulb temperature - 𝒕𝒅𝒃 𝒐𝒓 𝑫𝑩𝑻 (°𝑪)
2. Humidity ratio (absolute humidity) - 𝝎 (𝒈 𝒐𝒇 𝒘𝒂𝒕𝒆𝒓 𝒗𝒂𝒑𝒐𝒓 𝒑𝒆𝒓 𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓, 𝒈/𝒌𝒈)
3. Relative humidity - 𝐑𝐇 𝐨𝐫 ∅ (%)
4. Specific enthalpy -h (𝒌𝑱/𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓)
5. Wet-bulb temperature -𝒕𝒘𝒃 𝒐𝒓 𝑾𝑩𝑻 (°𝑪)
6. Dew-point temperature -𝒕𝒅𝒑 𝒐𝒓 𝑫𝑷𝑻 (°𝑪)
7. Specific volume - 𝑣 (𝒎3 /𝒌𝒈 𝒐𝒇 𝒅𝒓𝒚 𝒂𝒊𝒓)
8. Density of air - 𝜌 (𝒌𝒈/𝒎3 )

5/18/2023 4
5/18/2023 5
5/18/2023 6
5/18/2023 7
5/18/2023 8
𝟏
𝝆(𝒂𝒊𝒓 𝒅𝒆𝒏𝒔𝒊𝒕𝒚) =
𝒗

5/18/2023 9
Air conditioning processes

5/18/2023 10
Simple (sensible) Heating and Cooling (𝝎 = constant)
𝒕𝑨𝑫𝑷 > 𝒕𝒅𝒑𝟏
(𝒕𝒐 𝒂𝒗𝒐𝒊𝒅 𝒄𝒐𝒏𝒅𝒆𝒏𝒔𝒂𝒕𝒊𝒐𝒏)

Heating Capacity Cooling Capacity

𝟏𝐓𝐑 = 𝟑. 𝟓𝐤𝐖

5/18/2023 11
Humidification
Steam humidifier 𝒕𝒅𝒃 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝝎𝟐 > 𝝎𝟏
Humdifier Capacity
(amount of humidification/moisture content)

𝐦ሶ 𝐬𝐭𝐞𝐚𝐦 = 𝐦ሶ 𝐚 𝛚𝟐 − 𝛚𝟏 (𝐤𝐠 𝐰 /𝐬)


Heating capacity (Amount of heat added)

(kW)
Heating & Humidification
= 𝐦ሶ 𝐬𝐭𝐞𝐚𝐦 𝒉𝒔𝒕𝒆𝒂𝒎
Steam injection 𝒕𝒅𝒃 ≠ 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝝎𝟐 > 𝝎𝟏
𝐱≠𝟏 𝐱=𝟏
𝒉𝒔𝒕𝒆𝒂𝒎 = 𝒉𝒇𝒈 𝒉𝒔𝒕𝒆𝒂𝒎 = 𝒉𝒈

5/18/2023 12
Cooling & Humidification
WBT & h lines are almost
Air washer/Adiabatic saturation/Adiabatic humidification [h=constant] parallel to each other
Evaporative cooling/Desert conditioner [WBT=constant] therefore error is not
significant in the answer
• Process across air washer is (h=constant) unless extra information given such as: Air washed with
recirculated spray water (WBT=constant)
• Process across evaporative cooling is (WBT=constant) unless told otherwise in problem
(amount of humidification/moisture content/make up water)

𝐦ሶ 𝐰 = 𝐦ሶ 𝐚 𝛚𝟐 − 𝛚𝟏 (𝐤𝐠 𝐰 /𝐬)

Since (h=constant) heating capacity equals zero


∅ 𝒔 = 𝟏𝟎𝟎%
Humidification efficiency (𝜼𝑯𝒖𝒎𝒊𝒅𝒊𝒇𝒊𝒆𝒓 )
length 𝝎𝟐 > 𝝎𝟏
𝑨𝒄𝒕𝒖𝒂𝒍 𝒕𝒅𝒃𝟏 − 𝒕𝒅𝒃𝟐 𝛚𝟐 − 𝛚𝟏 𝟏𝟐
𝜼𝑯𝒖𝒎𝒊𝒅𝒊𝒇𝒊𝒆𝒓 = = = =
𝑰𝒅𝒆𝒂𝒍 𝒕𝒅𝒃𝟏 − 𝒕𝒅𝒃𝒔 𝛚𝐬 − 𝛚𝟏 𝟏𝒔

5/18/2023 13
Cooling & Dehumidification
Coil surface temperature/Apparatus dew point (ADP)
is less than air dew point

𝒕𝑨𝑫𝑷 < 𝒕𝒅𝒑𝟏


(𝒇𝒐𝒓 𝒄𝒐𝒏𝒅𝒆𝒏𝒔𝒂𝒕𝒊𝒐𝒏)

(𝑹𝑯𝟐 = 𝟗𝟎 − 𝟗𝟓%) Chilled water spray (𝑹𝑯𝟐 = 𝟏𝟎𝟎%)


Doesn’t reach saturation Reach saturation

Chilled water cooling coil DX (direct expansion) coil


𝒉𝟏
𝒉𝒙 Cooling Capacity
𝒉𝟐 𝝎𝟏
𝟏𝐓𝐑 = 𝟑. 𝟓𝐤𝐖
𝝎𝟐
Amount (rate) of condensation/moisture content
𝑹𝑯𝟐 = 𝟗𝟎%

𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏 𝐦ሶ 𝐜𝐨𝐧𝐝 = 𝐦ሶ 𝐚 𝛚𝟏 − 𝛚𝟐 (𝐤𝐠 𝐰 /𝐬)

5/18/2023 14
Cooling & Dehumidification
Bypass factor (BPF)
𝒉𝟏
𝑨𝒊𝒓 𝒕𝒉𝒂𝒕 𝒃𝒚𝒑𝒂𝒔𝒔𝒆𝒅 𝒄𝒐𝒊𝒍 𝒕𝒅𝒃𝟐 − 𝒕𝑨𝑫𝑷
𝑩𝑷𝑭 = =
𝑨𝒍𝒍 𝒂𝒊𝒓 𝒕𝒅𝒃𝟏 − 𝒕𝑨𝑫𝑷 𝒉𝒙
𝝎𝟐 − 𝝎𝑨𝑫𝑷
= 𝒉𝟐 𝝎𝟏
𝝎𝟏 − 𝝎𝑨𝑫𝑷
𝒉𝟐 − 𝒉𝑨𝑫𝑷
= 𝝎𝟐
𝒉𝟏 − 𝒉𝑨𝑫𝑷
𝟐𝑨𝑫𝑷 𝑹𝑯𝟐 = 𝟗𝟎%
=
𝟏𝑨𝑫𝑷
Contact factor (CF)/[efficiency of coil] 𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏

𝑪𝑭 = 𝟏 − 𝑩𝑷𝑭
For chilled water spray BPF = 0 (CF = 1)
Mass of bypassed air (𝒎ሶ 𝒃𝒚𝒑𝒂𝒔𝒔)
(𝒕𝒅𝒃𝟐 = 𝒕𝑨𝑫𝑷 )
𝒎ሶ 𝒃𝒚𝒑𝒂𝒔𝒔 = 𝒎ሶ 𝒂 𝑩𝑷𝑭

5/18/2023 15
Cooling & Dehumidification
Recall sensible change (heating/cooling)
𝒉𝟏
𝝎 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝒕𝒅𝒃 ≠ 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕 𝒉𝒙

Recall latent change (moisture added/removed) 𝝎𝟏


𝒉𝟐
𝝎 ≠ 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝝎𝟐
𝒕𝒅𝒃 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕
𝑹𝑯𝟐 = 𝟗𝟎%
𝒉𝟏 𝒕𝒐 𝒉𝒙 ∶ 𝒍𝒂𝒕𝒆𝒏𝒕 𝒄𝒉𝒂𝒏𝒈𝒆
𝒉𝒙 𝒕𝒐 𝒉𝟐 ∶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒄𝒉𝒂𝒏𝒈𝒆 𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏
𝒉𝟏 𝒕𝒐 𝒉𝟐 ∶ 𝒕𝒐𝒕𝒂𝒍 𝒄𝒉𝒂𝒏𝒈𝒆
𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 = 𝟎 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 = 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆
𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒄𝒉𝒂𝒏𝒈𝒆 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒙 − 𝒉𝟐
𝑺𝑯𝑭 𝑺𝑯𝑹 = = = 𝑸ሶ 𝒍𝒂𝒕𝒆𝒏𝒕 = 𝟎
𝒕𝒐𝒕𝒂𝒍 𝒄𝒉𝒂𝒏𝒈𝒆 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 𝒉𝟏 − 𝒉𝟐

5/18/2023 16
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)

𝒉𝟏

𝒉𝒙

𝒉𝟐 𝝎𝟏

𝝎𝟐

𝑹𝑯𝟐 = 𝟗𝟎%

𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏

𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏

𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 = 𝟎 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 = 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆


𝑸ሶ 𝒍𝒂𝒕𝒆𝒏𝒕 = 𝟎

5/18/2023 17
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)

𝒉𝟏

𝒉𝒙

𝒉𝟐 𝝎𝟏

𝝎𝟐

𝑹𝑯𝟐 = 𝟗𝟎%

𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏

𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏

𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 = 𝟎 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 = 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆


𝑸ሶ 𝒍𝒂𝒕𝒆𝒏𝒕 = 𝟎

5/18/2023 18
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)

𝒉𝟏

𝒉𝒙

𝒉𝟐 𝝎𝟏
summer winter
𝝎𝟐

𝑹𝑯𝟐 = 𝟗𝟎%

𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏

𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏

𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 = 𝟎 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 = 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆


𝑸ሶ 𝒍𝒂𝒕𝒆𝒏𝒕 = 𝟎

5/18/2023 19
Cooling & Dehumidification
𝑺𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒇𝒂𝒄𝒕𝒐𝒓 (𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 𝒉𝒆𝒂𝒕 𝒓𝒂𝒕𝒊𝒐)
𝐜𝐨𝐦𝐟𝐨𝐫𝐭 (𝐫𝐞𝐟𝐞𝐫𝐞𝐧𝐜𝐞) 𝐩𝐨𝐢𝐧𝐭/𝐳𝐨𝐧𝐞
𝒉𝟏
𝑫𝑩𝑻 = 𝟐𝟒℃
𝑹𝑯 = 𝟓𝟎% 𝒉𝒙

𝒉𝟐 𝝎𝟏

𝝎𝟐

𝑹𝑯𝟐 = 𝟗𝟎%

𝒕𝒅𝒃𝟐 𝒕𝒅𝒃𝟏

𝟎 ≤ 𝑺𝑯𝑭 ≤ 𝟏

𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆 = 𝟎 𝑸ሶ 𝒕𝒐𝒕𝒂𝒍 = 𝑸ሶ 𝒔𝒆𝒏𝒔𝒊𝒃𝒍𝒆


𝑸ሶ 𝒍𝒂𝒕𝒆𝒏𝒕 = 𝟎

5/18/2023 20
Dehumidification
𝒕𝒅𝒃 = 𝒄𝒐𝒏𝒔𝒕𝒂𝒏𝒕

Heat rejection (latent change)

Moisture content removed


𝐦ሶ 𝐰 = 𝐦ሶ 𝐚 𝛚𝟏 − 𝛚𝟐 (𝐤𝐠 𝐰 /𝐬)

5/18/2023 21
Heating & Dehumidification
Adiabatic chemical dehumidification/Adiabatic drier [h=constant]

(amount of dehumidification/moisture removal)

𝐦ሶ 𝐰 = 𝐦ሶ 𝐚 𝛚𝟏 − 𝛚𝟐 (𝐤𝐠 𝐰 /𝐬)

Dehumidification efficiency [dehumidifier effectiveness ] (𝜼𝑫𝒆𝒉𝒖𝒎𝒊𝒅𝒊𝒇𝒊𝒆𝒓 )

𝑨𝒄𝒕𝒖𝒂𝒍 𝒕𝒅𝒃𝟐 − 𝒕𝒅𝒃𝟏 𝛚𝟏 − 𝛚𝟐 𝟏𝟐


𝜼𝑫𝒆𝒉𝒖𝒎𝒊𝒅𝒊𝒇𝒊𝒆𝒓 = = = = 𝑹𝑯𝒔
𝑰𝒅𝒆𝒂𝒍 𝒕𝒅𝒃𝒔 − 𝒕𝒅𝒃𝟏 𝛚𝟏 − 𝛚𝐬 𝟏𝒔

5/18/2023 22
Adiabatic mixing of two air streams

𝒎ሶ 𝟏

𝒎ሶ 𝟐

𝒎ሶ 𝒘𝟏
𝝎𝟏 =
𝒎ሶ 𝒂𝟏

5/18/2023 23
Adiabatic mixing of two air streams

𝒎ሶ 𝟏

𝒕𝒅𝒃𝟑 − 𝒕𝒅𝒃𝟐 32
= = 𝒎ሶ 𝟐
𝒕𝒅𝒃𝟏 − 𝒕𝒅𝒃𝟑 13

𝑚ሶ 1 23
= Distance 23 can be calculated
𝑚ሶ 3 21
𝑚ሶ 1 𝑚ሶ 2
+ =1
𝑚ሶ 3 𝑚ሶ 3

5/18/2023 24
5/18/2023 25
5/18/2023 26