Ieee Modified 30 Bus System Documentation
Ieee Modified 30 Bus System Documentation
Abstract:
Modelica implementation of the IEEE modified 30 bus system using the OpenIPSL library is
shown in Figure 1. The power system model consists of 4 generators, 2 Synchronous
Condensers, 4 transformers, 20 loads, 37 transmission lines. A three winding transformers are
replaced by their equivalent connections by a two winding transformers. A single line diagram
(SLD) is shown in figure 2. A three-phase balanced fault is simulated at 18th Bus for the
duration of 0.4 seconds (4.6 seconds to 5 seconds). The purpose of this power system
simulation is to study the voltage stability at multiple buses.
The IEEE modified 30 bus model implemented in Modelica language using OpenIPSL
package, is used to study the voltage stability at different buses. The system base is 100 MVA
base. For all analysis on this system, the lower voltage magnitude limits at all buses are 0.9
p.u and upper limits are 1.1 p.u. A three winding transformers are replaced by their equivalent
connections by a single two winding transformer. The generator models in the implemented
network use Automatic Voltage Regulators (AVR) type 1. The purpose of using the AVR is to
control the generator field voltage to stabilize this oscillation of the bus voltage after the fault
clearing time. Type of generator used is round rotor machine (GENROU). A fault is simulated
for the duration of 4.6 to 5 seconds at the 18th bus. During the fault, we can observe from the
bus voltage profiles, that the voltage dip is more for 18th bus as it is the fault bus and the
severity of the fault is decreased as we move away from the fault bus. Simulation obtained
shows profiles at various buses and wave forms obtained are observed
Conclusion:
The implemented IEEE modified 30 bus model in Modelica represents the system behaviour
before and after the fault occurs at the 18th bus. Bus voltage magnitude (p.u.) of all modified 30
buses obtained are found to be between 0.9 p.u and 1.1 p.u. The relation between line
impedance and fault severity is also observed.