Setting Device HT21-001 (Operation Manual) Teresaki

The document describes the setting value display functions of a plant management system. It details the operation parts of the setting device, standard setting values and addresses, and lists setting values for generators and bus monitoring with their ranges and default settings.

Uploaded by

ergul neroglu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 11

GENERATING PLANT MANAGEMENT SYSTEM

GAC21

INSTRUCTION MANUAL

PART 3

Setting Value Display Functions

 TERASAKI ELECTRIC CO., LTD.


Table of Contents

1. Introduction -------------------------------------------------------------------- 3-1

2. Operation Part of Setting Device ----------------------------------------- 3-1

3. Standard Setting Values and Addresses for Setting Value -------- 3-2

4. Function of Key switch and Slid switch ----------------------------------- 3-5

5. Procedure for Changing a Setting Value ------------------------------- 3-6

 TERASAKI ELECTRIC CO., LTD.


3-1

1. Introduction
As the display function for entering and modifying various parameter values and for displaying the
measured values, the handy type Setting device with an LED display (red) (hereafter referred to as
“Setting device”) is provided for the GAC21 System.
The communication between the GAC21 System and the Setting device is performed via the digital I/O
module for the Setting device, which is included in the GAC21 Controller.
However, this communication is only possible when the control-related modules and the digital I/O
module for the Setting device are normal.
In addition to the parameter values, the voltage and power for generators, and the measured value for the
frequency of the bus can be displayed.
The Setting device is normally removed and put in the accommodation pocket (near GAC21 Controller)
on the rear of the door for the common section at the lower part of the generator panel, etc.
2. Operation Part of Setting Device
Fig.3-1 illustrates the operation part of the Setting device.
For using and handling the keys and slide switches, refer to the subsequent items.
The Setting device has two connectors with 1meter connector cable, the one for the power source of 24V
DC for the Setting device and the other for the digital I/O module for the Setting device.
The power source for the Setting device is located near the GAC21 Controller.

1:LED Display (Red ) 4 character 5:Add. No. ⇔ Value Change over Slid switch
2:TEN Key (0∼9) 6:Now ⇔ New Change over slide switch

3:CANCEL Key (C) 7:I/O Module connector(40P)

4:ENTER Key (ENTER) 8:Power source connector(2P)

Fig.3-1 Appearance of Setting device


3. Standard setting values and addresses for setting values
The setting values and measured values can be viewed by entering a 4-digit number for each of them on

 TERASAKI ELECTRIC CO., LTD.


3-2

the Setting device.


Once a 4-digit number is entered, the corresponding setting value or measured value is searched for.
The format of numbers available for this search is predefined according to each group of setting values.
The meaning of each 4-digit number for a setting value is, in principle, is predetermined according to the
following standard.
The standard setting values and the numbers for setting values (hereafter referred to as “addresses”) are
shown in the list of the Table 3-1 below.
:SETTING ADDRESS−□ □ □ □

Serial number (01∼99)


Group of setting item
(0: Constant setting, 1: Timer setting, 2: Measured value)
Generator number or other
(0:Common, 1:G1, 2:G2, 3:G3 …)

 CAUTION Reading the 4-Digit Number Indicated with LEDs

The LED indication for SETTING VALUE shows no decimal point.


Therefore, take care not to misread the unit for the 4-digit number.
Tables 3-1, 3-2, and 3-3 show“LED INDICATE”for the number in“SETTING RANGE”.
The number indicated with LEDs conforms to the following standard.
STANDARD SETTING/LCD INDICATION
SETTING VALUE LED INDICATION

1 0001
1.0 0010
10 0010
10.0 0100
100 0100
100.0 1000

MEASURE VALUE/LCD INDICATION


ACTUAL VALUE LED INDICATION
500kW 0500
450V 0450
60.0Hz 0600

Table 3-1 List of Standard Setting Value for generator


STANDARD SETTING ADDRESS
SETTING ITEM SETTING
RANGE SETTING LED G1 G2 G3
INDICATE

 TERASAKI ELECTRIC CO., LTD.


3-3

SHARING RATIO 1.0∼5.0 1.0 0010 1001 2001 3001

GOV CHARACT 2.0∼16.0sec/Hz 8.0 0080 1002 2002 3002

LOAD LIMIT 50∼100 % 95 0095 1003 2003 3003

ENG IDLING TIME 0∼2400 sec 600 0600 1105 2105 3105

VOLT ESTABLISH 60∼100 % 95 0095 1004 2004 3004

VOLT ESTABLISH TIME 0∼30 sec 7 0007 1101 2101 3101

VOLT NON EST TIME 0∼30 sec 20 0020 1102 2102 3102

ACB NON CLOSE TIME 0∼10 sec 3 0003 1103 2103 3103

AUTO SY FAIL TIME 0∼240 sec 60 0060 1104 2104 3104

GEN LIGHT LOAD 0∼100 % 20 0020 1005 2005 3005

GEN LIGHT LOAD TIME 0∼240 sec 0 0000 1106 2106 3106

STANDARD SETTING ADDRESS


SETTING ITEM SETTING
RANGE SETTING LED G4 G5
INDICATE

SHARING RATIO 1.0∼5.0 1.0 0010 4001 5001

GOV CHARACT 2.0∼16.0sec/Hz 8.0 0080 4002 5002

LOAD LIMIT 50∼100 % 95 0095 4003 5003

ENG IDLING TIME 0∼2400 sec 600 0600 4105 5105

VOLT ESTABLISH 60∼100 % 95 0095 4004 5004

VOLT ESTABLISH TIME 0∼30 sec 7 0007 4101 5101

VOLT NON EST TIME 0∼30 sec 20 0020 4102 5102

ACB NON CLOSE TIME 0∼10 sec 3 0003 4103 5103

AUTO SY FAIL TIME 0∼240 sec 60 0060 4104 5104

GEN LIGHT LOAD 0∼100 % 20 0020 4005 5005

GEN LIGHT LOAD TIME 0∼240 sec 0 0000 4106 5106

 TERASAKI ELECTRIC CO., LTD.


3-4

Table 3-2 List of Standard Setting Value for Bus Monitoring


STANDARD
SETTING ITEM SETTING RANGE SETTING
SETTING LED ADDRESS
INDICATE

BUS VOLT LIGHT LOW 75∼100 % 97 0097 0001

BUS VOLT LIGHT LOW TIME 0∼30 sec 10 0010 0101

BUS VOLT LIGHT HIGH 100∼125 % 103 0103 0003

BUS VOLT LIGHT HIGH TIME 0∼30 sec 10 0010 0103

BUS FREQ LIGHT LOW 80.0∼100.0 % 97.5 0975 0005

BUS FREQ LIGHT LOW TIME 0∼30 sec 10 0010 0105

BUS FREQ LIGHT HIGH 100.0∼120.0 % 102.5 1025 0007

BUS FREQ LIGHT HIGH TIME 0∼30 sec 10 0010 0107

BUS VOLT LOW 75∼100 % 90 0090 0002

BUS VOLT LOW TIME 0∼30 sec 5 0005 0102

BUS VOLT HIGH 100∼125 % 106 0106 0004

BUS VOLT HIGH TIME 0∼30 sec 5 0005 0104

BUS FREQ LOW 80.0∼100.0 % 95.0 0950 0006

BUS FREQ LOW TIME 0∼30 sec 5 0005 0106

BUS FREQ HIGH 100.0∼120.0 % 105.0 1050 0008

BUS FREQ HIGH TIME 0∼30 sec 5 0005 0108

START REQUEST 50∼100 % 90 0090 0011

START REQUEST TIME 0∼30 sec 10 0010 0109

STOP REQUEST 50∼100 % 70 0070 0012

STOP REQUEST TIME 0∼2400 sec 600 0600 0110

Table 3-3 List of Measuring Value


SETTING EXAMPLE LED SETTING ADDRESS
SETTING ITEM RANGE RATED INDICATE
G1 G2 G3

GEN POWER MEASURED --- 500 0500 1201 2201 3201


VALUE (kW)
GEN VOLT MEASURED --- 450 0450 1202 2202 3202
VALUE (V)
BUS FREQ MEASURED --- 60.0 0600 0201
VALUE (Hz)

 TERASAKI ELECTRIC CO., LTD.


3-5

SETTING EXAMPLE LED SETTING ADDRESS


SETTING ITEM RANGE RATED INDICATE
G4 G5
GEN POWER MEASURED --- 500 0500 4201 5201
VALUE (kW)
GEN VOLT MEASURED --- 450 0450 4202 5202
VALUE (V)
BUS FREQ MEASURED --- 60.0 0600 0201
VALUE (Hz)

 CAUTION Search for Various Setting Values for Functions of GAC21 System

The standard setting values may be changed to the optical values depending on the
applicable ship. Some groups of setting values may be added.
To search for setting values, use address numbers for the following items included in “VOL. 3
GENERATOR AUTOMATIC CONTROL DEVICE --- GA” in the completed view of the main
switchboard.
・GENERATOR
・BUS MONITOR
・NUMBER OF DIESEL GENERATOR ON LINE CONTROL (GAC-PMS-G)
・OPTIMUM LOAD SHARING CONTROL (GAC-PMS-TG/SG)
・LARGE MOTOR START BLOCKING CONTROL (GAC-PMS-M)

4. Function of Key switch and Slid switch


This section describes the functions of the keys and slide switches shown in Fig.3-1, based on data
transmission and reception.

(1) 2 TEN numeric key (0∼9):


The numeric keys 0~9 are used to enter a 4-digit value or address.
After checking the position, Add. No. (data number indication position) of the slide switch 5 on
the Setting device, enter the data number (ADDRESS) for the setting value with numeric keys and
then transmit it to the Digital I/O module for the Setting device (hereafter referred to as“module
for the setting device”).

(2) 1 LED indication:


The data number (ADDRESS) that has been entered with numeric keys and then transmitted will be
sent back to the Setting device and indicated on it.

(3) 4 ENTER Key:


Check the data number (ADDRESS) and press the ENTER key.
If the established data number is transmitted from the Setting device to the module for the setting
device, the module for the setting device searches for the appropriate setting value and then stores
that data.

 TERASAKI ELECTRIC CO., LTD.


3-6

(4) 5 6 Slid switches:


If the slide switch 6 on the Setting device is in the Now (current value display position) when it is
changed slide switch 5 from Add to the Value (setting value data display position), the module for
the setting device transmits the stored current value to Setting device, which is then displayed on
the Setting device.
If the slide switch 6 is in the New (changed value display position), enter the changed value on the
Setting device using numeric keys and then transmit it to the module for the setting device.

(5) The module for the setting device returns the transmitted changed value to the Setting device,
which is then displayed on the LED.
Establish the changed value by pressing the ENTER key on the Setting device.
After the changed value has been transmitted to the module for the setting device, the setting
range and the changed value are checked.
If the changed value falls in that range, that changed value is accepted.

(6) 3 C Key(CANCEL)

If the entered value falls outside the setting range, an error is generated with“9999”displayed on the
LED of the Setting device.
To enter another value, press the CANCEL key. The displayed“9999”will be cleared.
Enter another changed setting value using numeric keys.
The CANCEL key is used to reset the specified data number (address) or the entered value to be
changed. When this data is reset, the LED on the Setting device simultaneously displays“0000”.

5. Procedure for changing a setting value


Before entering the ADDRESS for a setting value, check the following points:

Handling and Checking the Setting Device


 CAUTION Before Changing the Settings --- (1/2)

1. Check the setting positions of the slide switches:


Add. No. ←→ Value : Add. No. position
Now ←→ New: : Now position
2. Connecting the connectors to the setter
Firmly connect the connector (2P) for the power source of 24V DC and the connector
(40P) for the I/O module for the setting , which come with the Setting device, to the power
receptacle of 24 VDC and the I/O module in the following order.
The power receptacle of 24 V DC is located near the GAC21 Controller.
1) First connect the connector for the I/O module.
2) Then connect the connector for the power source of 24V DC.
-To remove the connectors, reverse this order.
If you should connect the connectors in the reverse order, the setter and the module
would not be damaged.

 TERASAKI ELECTRIC CO., LTD.


3-7

Handling and Checking the Setting Device


 CAUTION Before Changing the Settings --- (2/2)

3. After connecting the connector for the power source of 24V DC, check that the LED
indicator shows“0000”.

4. Check that the shaded part on the top of the module, shown in Fig. 3-2, does not
indicate any illuminated LED error message like “ERR” or “ALM”.
For the “ERR” indication, refer to “Part 4“Inspection・Maintenance and Self-Diagnostic
Functions.”

ERR/ALM LED indicate part


24V DC source Setting device
RECEPTACLE

Connector cables

Fig.3-2 Between GAC21 Module and Setting device Connection

An example of changing a setting value is given below:


This example assumes that the sharing ratio for No.1 generator is to be changed from the standard
setting value“1.0”to“2.0”.

Step ①:Check that two slide switches are in the Add No.
(Setting address) and Now (Current value) positions.
Also check that the LED on the Setting device
Indicates“0000”.
0000
Add No Value Now

Step ②:Enter a address number (Address) using numeric


keys address: 1 0 0 1 .
Every time each digit is entered, the LED on the
Setting device indicates the entered number.
I 00I
Add No Value Now

 TERASAKI ELECTRIC CO., LTD.


3-8

Step ③:Check with the LED display that the entered


address is correct, and then press the ENTER key.
If the entered address is wrong.
Press the C key and clear the LED display on
1001
I00I
Add No
Add No Value
Value Now New
the Setting device to“0000”and then enter a
correct address.
Step ④:Change the slide switch from the Add No.(setting
address) position to the Value (setting value) position.
1001
I00I
Add No
Add No Value
Value Now New

Step ⑤:Since the slide switch is in the Now (Current value)


position, the LED on the Setting device indicates
thecurrent setting value.
In this example,“0010”is displayed.
1001
00I0
Add No
Add No Value
Value Now New
Note:No decimal point is displayed.

Step ⑥:Change the slide switch in the Now (Current value)


position to the New (Changed value) position.
This operation will clear the LED on the Setting
device to“0000”.
1001
0000
Add No
Add No Value Now
Value Now New

Step ⑦:Enter the changed value using numeric keys,


in this example, 0 0 2 0.
The entered value will be indicated on the LED
on the Setting device.
1001
0020
Add No
Add No Value
Value Now New

Step ⑧:Check with the LED that the changed value is


correct, and then press the ENTER key.
If the entered value is wrong, press the C key
and clear the LED display on the Setting device to
1001
0020
Add No
Add No Value
Value Now New
“0000”and then enter a correct value.

Step ⑨:Change the slide switch in the New (Change value)


position to the Now (current value) position.
This operation will display“0020”on the LED
on the Setting device. Check that the data has
1001
0020
Add No Value Now
Now New
been changed to the entered value (0.2).

 TERASAKI ELECTRIC CO., LTD.


3-9

Step ⑩:Return the Value position of the slide switch to


the Add. No.(Setting address) position, which is
the initial position of that slide switch for the
Setting device.
0000
Add No Value Now New
.
Now the setting value has been changed

The“measured value”is displayed only and can be viewed by performing the steps ① through ⑤.

Handling and Disposing the Setting Device


 CAUTION After Changing the Setting

1. Check the setting positions of the slide switches:


Add. No. ←→ Value : Add. No. position
Now ←→ New: : Now position

2. Removing the setting device connectors


Remove the connector (2P) for the power source of 24V DC and the connector (40P) for
the I/O module, which come with the setting device, from the power receptacle of 24V
DC and the I/O module in the following order:
1) First remove the connector for the power source of 24V DC.
2) Then remove the connector for the I/O module.

-Even if this order is reversed, the setting device and the I/O module will not be damaged.

3. Notifying us of the changed setting value


If you change the setting value, notify us of the ship number, setting address, changed
item, and changed setting value, which are required to update our database.

End