IP-IO
SmartX IP Controller

Introduction • BACnet/IP communications


SmartX IP Controller – IP-IO module provides I/O • DHCP for easy network configuration
expansion to your HVAC application over BACnet/IP.
The module can share its I/O resources across The IP-IO module has a dual-port Ethernet switch,
applications running in SmartX servers, SmartX IP which enables flexible network topologies:
controllers, or third-party systems. With the support of
local alarms and local trend logs, the IP-IO module • Star
avoids unnecessary traffic over the network while being
• Daisy chain
able to log important information locally. The IP-IO
module can be installed near facilities in the field, away • Rapid Spanning Tree Protocol (RSTP) ring
from the SmartX server or the SmartX IP controller. All
IP-IO models support an optional display that provides In a star topology, the IP-IO module and the parent
insight and control of the inputs and outputs. EcoStruxure BMS server are individually connected to
an Ethernet switch. Daisy-chain multiple IP-IO modules
The IP-IO module has the following features: together to reduce the installation time and cost. Use
an RSTP ring topology when you want a non-
• IP enabled with dual-port Ethernet switch operational IP-IO module to be detected and recovered
quickly and efficiently.
• Versatile onboard I/O point mix
• Highly reliable Models with a versatile mix of I/O points
• Mobile commissioning application The IP-IO module comes in three models with different
I/O point count and a versatile mix of I/O point types
• Full EcoStruxure Building Operation software
that match a wide variety of applications. The universal
support, providing efficient engineering tools
inputs/outputs are highly flexible and can be
configured as either inputs or outputs.
IP connectivity and flexible network topologies
The IP-IO module is based on open protocols that
simplify interoperability, IP configuration, and device
management:

• IP addressing

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 2

IP-IO
SmartX IP Controller

I/O Point Types by IP-IO Models

I/O Point Types IP-IO-DI10 IP-IO-UIO10 IP-IO-UIO5DOFA4


Digital inputs 10 - -
Universal I/O - 10 5
Type Ub
Relay outputs - - 3
Form A
High power relay outputs - - 1
Form A

Configurations by I/O Point Types

Configurations Digital Inputs Universal I/O Relay Outputs High Power Relay
Type Ub Form A Outputs
Form A
Digital inputs yes yes - -
Counter inputs yes yes - -
Supervised inputs - yes - -
Voltage inputs - yes - -
(0 to 10 VDC)
Current inputs - yes - -
(0 to 20 mA)
Temperature inputs - yes - -
Resistive inputs - yes - -
2-wire RTD temperature - yes - -
inputs
Voltage outputs - yes - -
(0 to 10 VDC)
Digital outputs - - yes yes
Digital pulsed outputs - - yes yes
PWM outputs - - yes yes
Tristate outputs - - yes -
Tristate pulsed outputs - - yes -

Digital inputs Universal inputs/outputs


The digital inputs can be used for cost effective The universal inputs/outputs are ideal for any mix of
sensing of multiple dry contact digital inputs in temperature, pressure, flow, status points, and similar
applications, such as equipment status monitoring or point types in a building control system.
alarm point monitoring. As counter inputs, digital inputs
are commonly used in energy metering applications.

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 3

IP-IO
SmartX IP Controller

As counter inputs, the universal inputs/outputs are


commonly used in energy metering applications. As
RTD inputs, they are ideal for temperature points in a
building control system. As supervised inputs, they are
used for security applications where it is critical to know
whether or not a wire has been cut or shorted. These
events provide a separate indication of alarms and
events in the system.

For all analog inputs, maximum and minimum levels


can be defined to automatically detect over-range and
under-range values.
Display module
The universal inputs/outputs can also be used as
In WorkStation, you update the firmware of multiple IP-
voltage outputs, without the need for external bias
IO modules at the same time and with minimum down
resistors. Therefore, the universal inputs/outputs
time. The EcoStruxure BMS server keeps track of the
support a wide range of devices, such as actuators.
installed firmware to support backup, restore, and
replacement of the IP-IO modules. The server can host
Relay outputs
IP-IO modules of different firmware versions.
The relay outputs support digital Form A point types.
The Form A relays are designed for direct load Mobile commissioning application
applications.
The eCommission SmartX Controllers mobile
High power relay output application is designed for local configuration, field
The high power relay output is ideal for switching loads deployment, and commissioning of IP-IO modules. The
of up to 12 A, such as electrical heating elements. mobile application reduces the commissioning time,
allows flexibility in project execution, and eliminates
dependencies on network infrastructure.
Highly reliable
The IP-IO module supports local trends and alarms, The mobile application is designed for use with
enabling local operation when the IP-IO module is Android, Apple (iOS), and Microsoft Windows 10
offline. devices. For more information, see the eCommission
SmartX Controllers Specification Sheet.
The battery-free power backup of the memory and real-
time clock prevents data loss and ensures seamless
and quick recovery after a power failure.

All IP-IO models can be equipped with a display add-


on module (same module as used for the MP-C), which
features an LCD display and five keys. With this
module, you can manually override analog and digital
outputs for testing, commissioning, and maintenance of
equipment connected to the outputs. The display
module's dedicated processing power ensures reliable
override for maintenance applications. The override
status can be viewed in EcoStruxure Building
Operation WorkStation and WebStation, enabling
precise monitoring and reliable control.

eCommission SmartX Controllers mobile app

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 4

IP-IO
SmartX IP Controller

Using the eCommission SmartX Controllers mobile Device discovery


application, you can connect to IP-IO modules and MP The enhanced Device Discovery in WorkStation
Series controllers over the network. Using a wireless enables you to easily identify IP-IO modules on a
access point or a network switch, you can connect to a BACnet network and to associate the IP-IO modules
network of IP-IO modules and MP Series controllers on with their parent server.
the local IP network.
Engineering efficiency
Device configuration
The engineering and maintenance of IP-IO modules
With the eCommission SmartX Controllers mobile can be done very efficiently using the EcoStruxure
application, you can easily discover IP-IO modules and Building Operation reusability features. With these
MP Series controllers on the IP network. You can features, you can create library items (Custom Types)
change the configuration of each module and for a complete IP-IO application that contains I/O point
controller, including the BACnet and IP network configurations and all necessary objects such as
settings, location, and parent server. To save trends and alarms. The IP-IO application in the Custom
engineering time, you can save common device Types library is reusable across all IP-IO modules of the
settings and then reuse them for devices of the same same model. You can use the IP-IO application as a
type and model. base for creating new IP-IO modules intended for
similar applications. You can then edit the IP-IO
Field deployment and I/O checkout application, and the changes are automatically
The eCommission SmartX Controllers mobile replicated to all IP-IO modules, while each IP-IO
application does not require an EcoStruxure BMS module keeps its local values.
server or a network infrastructure to be in place. You
can use the mobile application to load the IP-IO WorkStation supports both online and offline
application directly into the local IP-IO module and engineering of IP-IO modules. You can make the
deploy the IP-IO module. The IP-IO application can be configuration changes online or use database mode to
created offline using Project Configuration Tool or make the changes offline. In database mode, the
WorkStation while preserving all external bindings to changes are saved to the EcoStruxure Building
server and controller applications using the IP-IO Operation database so that you can apply the changes
module's I/O points. You can also perform an I/O to the IP-IO modules later.
checkout to ensure that the IP-IO module's I/O points
are configured, wired, and operating correctly. Project Configuration Tool enables you to perform all
the engineering off site, without the need for physical
Full EcoStruxure Building Operation software hardware, which minimizes the time you need to spend
support on site. You can run the EcoStruxure BMS servers
virtually and engineer the MP Series controllers and IP-
The power of the IP-IO module is fully realized when it is IO modules before you deploy your server, controller,
part of an EcoStruxure BMS, which provides the and IP-IO applications to the servers, controllers, and
following benefits: IP-IO modules on site. For more information, see the
Project Configuration Tool specification sheet.
• WorkStation/WebStation interface
• Device discovery In addition, you can use Automated Engineering Tool to
facilitate your engineering process when using IP-IO
• Engineering efficiency modules. This tool provides access to a library of
standard IP-IO applications that can be quickly
WorkStation/WebStation interface configured and customized using the wizards and
WorkStation and WebStation provide a consistent user mass edit functions provided in the tool. You can then
experience regardless of which EcoStruxure BMS load these customized applications into your target
server the user is logged on to. The user can log on to server. The tool also enables the quick creation of your
the parent EcoStruxure BMS server to engineer, own templates based on IP-IO applications that you
commission, supervise, and monitor IP-IO modules and have developed. These templates facilitate a standard
MP Series controllers. For more information, see the approach and easy reuse and duplication of common
WorkStation and WebStation specification sheets. IP-IO applications. For more information, see the
Automated Engineering Tool specification sheet.

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 5

IP-IO
SmartX IP Controller

Library of standard HVAC applications

Part Numbers

Product Part number


IP-IO-DI10 SXWIPIOAA10001
IP-IO-UIO10 SXWIPIOBA10001
IP-IO-UIO5DOFA4 SXWIPIOCA10001
MP-C DISPLAY SXWMPCDSP10001
(MP-C override display module)
DIN-RAIL-CLIP, DIN-rail end clip SXWDINEND10001
package of 25 pieces

Specifications
AC input
Nominal voltage......................................................................................................................................................24 VAC
Operating voltage range........................................................................................................................................+/-20 %
Frequency ............................................................................................................................................................50/60 Hz
Maximum power consumption ..................................................................................................................................17 VA
Power input protection................................................................................................MOV suppression and internal fuse
DC input
Nominal voltage.............................................................................................................................................24 to 30 VDC
Operating voltage range ...............................................................................................................................21 to 33 VDC
Maximum power consumption .....................................................................................................................................9 W
Power input protection................................................................................................MOV suppression and internal fuse
Environment
Ambient temperature, operating .................................................................0 to 50 °C (32 to 122 °F) at normal operationa
..........................................................-40 to +60 °C (-40 to +140 °F) for rooftop applications, horizontal installation onlya

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 6

IP-IO
SmartX IP Controller

a) MP-C Display has an operating temperature range of -30 to +60 °C (-22 to +140 °F).
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating ...............................................................................................................................................UL94-5V
Ingress protection rating ............................................................................................................................................IP 20
Mechanical
Dimensions...................................................................................... 153 W x 110 H x 64 D mm (6.0 W x 4.3 H x 2.5 D in.)

Weight, IP-IO-DI10
Including terminal blocks .....................................................................................................................0.337 kg (0.742 lb)
Weight, IP-IO-UIO10
Including terminal blocks .....................................................................................................................0.336 kg (0.740 lb)
Weight, IP-IO-UIO5DOFA4
Including terminal blocks..................................................................................................................... 0.357 kg (0.787 lb)
Installation.....................................................................................................DIN rail or other flat surface inside a cabinet
Terminal blocks ................................................................................................................................................Removable
Software compatibility
EcoStruxure Building Operation software .............................................................................................version 2.0 or later
Agency compliances
Emission...............................................................RCM; EN 61000-6-3; EN 50491-5-2; FCC Part 15, Sub-part B, Class B
Immunity ...............................................................................................................................EN 61000-6-2; EN 50491-5-3
Safety standards........................................................EN 60730-1; EN 60730-2-11; EN 50491-3; UL 916 C-UL US Listed
Real-time clock
Accuracy, at 25 °C (77 °F) ..............................................................................................................+/-1 minute per month
Backup time, at 25 °C (77 °F) ...................................................................................................................7 days minimum

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 7

IP-IO
SmartX IP Controller

Communication ports
Ethernet ................................................................................................................................ Dual 10/100BASE-TX (RJ45)
USB ....................................................................................................................................1 USB 2.0 device port (mini-B)
........................................................................................................................1 USB 2.0 host port (type-A), 5 VDC, 2.5 W
Communications
BACnet..........................................................................................................BACnet/IP, port configurable, default 47808
.......................................................................................................BTL B-ASC (BACnet Application Specific Controller)a
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet International's home
page.
CPU
Frequency ........................................................................................................................................................... 500 MHz
Type...........................................................................................................................................ARM Cortex-A7 dual-core
DDR3 SDRAM ........................................................................................................................................................128 MB
NOR flash memory ...................................................................................................................................................32 MB
Memory backup.......................................................................................................................128 kB, FRAM, non-volatile
MP-C Display (Optional)
Removable .....................................................................................................................................................................No
Display size .................................................................................................................36 W x 17 H mm (1.4 W x 0.7 H in.)
Display resolution .......................................................................................................................................128 x 64 pixels
Display type......................................................................... FSTN monochrome LCD, white color transflective backlight
Power consumption............................................................................................................. max. 0.15 W (45 mA at 3.3 V)
Ambient temperature, operating .........................................................................................-30 to +60 °C (-22 to +140 °F)
Ambient temperature, storage ............................................................................................-40 to +70 °C (-40 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Weight ..................................................................................................................................................0.035 kg (0.077 lb)
Compliance with standards ......................................................................................................................EN ISO 16484-2
Digital inputs, DI
Channels, IP-IO-DI10..................................................................................................................................10, DI1 to DI10
Channels, IP-IO-UIO10.....................................................................................................................................................0
Channels, IP-IO-UIO5DOFA4 ...........................................................................................................................................0
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
Digital input protection........................................................................Transient voltage suppressor on each digital input
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 8

IP-IO
SmartX IP Controller

Universal inputs/outputs, Ub
Channels, IP-IO-DI10........................................................................................................................................................0
Channels, IP-IO-UIO10 ...................................................................................................................... 10 Ub, Ub1 to Ub10
Channels, IP-IO-UIO5DOFA4 .................................................................................................................5 Ub, Ub1 to Ub5
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
A/D converter resolution ..........................................................................................................................................16 bits
Universal input/output protection........................................Transient voltage suppressor on each universal input/output
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................150 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Supervised inputs
5 V circuit, 1 or 2 resistors
Monitored switch combinations.............................................................Series only, parallel only, and series and parallel
Resistor range ................................................................................................................................................1 to 10 kohm
For a 2-resistor configuration, each resistor must have the same value +/- 5 %
Voltage inputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy...............................................................................................................................+/-(7 mV + 0.2 % of reading)
Resolution................................................................................................................................................................1.0 mV
Impedance..........................................................................................................................................................100 kohm
Current inputs
Range ................................................................................................................................................................0 to 20 mA
Accuracy..........................................................................................................................+/-(0.01 mA + 0.4 % of reading)
Resolution....................................................................................................................................................................1 μA
Impedance .............................................................................................................................................................47 ohm
Resistive inputs
10 ohm to 10 kohm accuracy .......................................................................................................+/-(7 + 4 x 10-3 x R) ohm
R = Resistance in ohm
10 kohm to 60 kohm accuracy .....................................................................................+/-(4 x 10-3 x R + 7 x 10-8 x R2) ohm
R = Resistance in ohm
Temperature inputs (thermistors)
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Supported thermistors
Honeywell .............................................................................................................................................................20 kohm
Type I (Continuum) ...............................................................................................................................................10 kohm

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 9

IP-IO
SmartX IP Controller

Type II (I/NET) .......................................................................................................................................................10 kohm


Type III (Satchwell) ...............................................................................................................................................10 kohm
Type IV (FD) ......................................................................................................................................................... 10 kohm
Type V (FD w/ 11k shunt) ....................................................................................................................Linearized 10 kohm
Satchwell D?T......................................................................................................................................Linearized 10 kohm
Johnson Controls .................................................................................................................................................2.2 kohm
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
...................................................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
10 kohm, 2.2 kohm, and 1.8 kohm.......................................................-50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
..........................................................................................................-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
Linearized 10 kohm .................................................................................-50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
...............................................................................................................-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
1 kohm ..............................................................................................-50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)
RTD temperature inputs
Supported RTDs......................................................................................................................................................Pt1000
Pt1000
Sensor range .....................................................................................................................-50 to +150 °C (-58 to +302 °F)

SmartX IP Controller device environment Sensor range Measurement accuracy


0 to 50 °C (32 to 122 °F) -50 to +70 °C (-58 to +158 °F) +/-0.5 °C (+/-0.9 °F)
0 to 50 °C (32 to 122 °F) 70 to 150 °C (158 to 302 °F) +/-0.7 °C (+/-1.3 °F)
-40 to +60 °C (-40 to +140 °F) -50 to +150 °C (-58 to +302 °F) +/-1.0 °C (+/-1.8 °F)

RTD temperature wiring


Maximum wire resistance.........................................................................................................20 ohm/wire (40 ohm total)
Maximum wire capacitance.......................................................................................................................................60 nF
The wire resistance and capacitance typically corresponds to a 200 m wire.
Voltage outputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy..............................................................................................................................................................+/-60 mV
Resolution.................................................................................................................................................................10 mV
Minimum load resistance ........................................................................................................................................5 kohm
Load range.......................................................................................................................................................-1 to +2 mA

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 10

IP-IO
SmartX IP Controller

Relay outputs, DO
Channels, IP-IO-DI10........................................................................................................................................................0
Channels, IP-IO-UIO10.....................................................................................................................................................0
Channels, IP-IO-UIO5DOFA4..................................................................................................................... 3, DO1 to DO3
Contact rating......................................................................................................250 VAC/30 VDC, 2 A, Pilot Duty (C300)
Switch type....................................................................................................................................................Form A Relay
....................................................................................................................................................Single Pole Single Throw
....................................................................................................................................................................Normally Open
Isolation contact to system ground.....................................................................................................................3000 VAC
Cycle life (Resistive load) ..............................................................................................................At least 100,000 cycles
Minimum pulse width ..............................................................................................................................................100 ms
High power relay outputs, DO
Channels, IP-IO-DI10........................................................................................................................................................0
Channels, IP-IO-UIO10.....................................................................................................................................................0
Channels, IP-IO-UIO5DOFA4................................................................................................................................. 1, DO4
Contact rating....................................................................................................250 VAC/24 VDC, 12 A, Pilot Duty (B300)
Switch type....................................................................................................................................................Form A Relay
....................................................................................................................................................Single Pole Single Throw
....................................................................................................................................................................Normally Open
Isolation contact to system ground.....................................................................................................................5000 VAC
Cycle life (Resistive load) ..............................................................................................................At least 100,000 cycles
Minimum pulse width ..............................................................................................................................................100 ms

Terminals • Individual 24 VDC power sources to the field must


be current limited to maximum 4 A for UL
Follow proper installation wiring diagrams and compliant installations, and maximum 6 A in other
instructions, including these instructions: areas.
• All IP-IO models have several RET terminals for • For more information on wiring, see Hardware
connection of I/O returns, so a common Reference Guide.
chassis/signal ground rail is optional and may not
be needed.

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 11

IP-IO
SmartX IP Controller

IP-IO-DI10

IP-IO-UIO10

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 12

IP-IO
SmartX IP Controller

IP-IO-UIO5DOFA4

Part Numbers in AMER Region for Network Connectivity Accessories

Product descriptiona Part number (AMER region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 1000 ft (305 m), CMP, green ACT4P6UCP1ARXGR
Cat 6 patch cord, UTP, 30 ft (9 m), CMP, green ACTPC6UBCP30AGR
Cat 6 patch cord, UTP, 50 ft (15 m), CMP, green ACTPC6UBCP50AGR
Cat 6 patch cord, UTP, 70 ft (21 m), CMP, green ACTPC6UBCP70AGR
Cat 6 patch cord, UTP, 90 ft (27 m), CMP, green ACTPC6UBCP90AGR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 1000 ft (305 m), CMP, green ACT4P5EUCP1ARXGR
Cat 5e patch cord, UTP, 30 ft (9 m), CMP, green ACTPC5EUBCP30AGR
Cat 5e patch cord, UTP, 50 ft (15 m), CMP, green ACTPC5EUBCP50AGR
Cat 5e patch cord, UTP, 70 ft (21 m), CMP, green ACTPC5EUBCP70AGR

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 13

IP-IO
SmartX IP Controller

Continued

Product descriptiona Part number (AMER region)


Cat 5e patch cord, UTP, 90 ft (27 m), CMP, green ACTPC5EUBCP90AGR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable)

Part Numbers in EMEA Region for Network Connectivity Accessories

Product descriptiona Part number (EMEA region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 305 m (1000 ft), Euroclass D, green VDICD116118
Cat 6 patch cord, UTP, 10 m (32 ft), LSZH, green ACTPC6UBLS100GR
Cat 6 patch cord, UTP, 15 m (49 ft), LSZH, green ACTPC6UBLS150GR
Cat 6 patch cord, UTP, 20 m (65 ft), LSZH, green ACTPC6UBLS200GR
Cat 6 patch cord, UTP, 25 m (82 ft), LSZH, green ACTPC6UBLS250GR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 1000 ft (305 m), Euroclass D, green VDICD115118
Cat 5e patch cord, UTP, 10 m (32 ft), LSZH, green ACTPC5EUBLS100GR
Cat 5e patch cord, UTP, 15 m (49 ft), LSZH, green ACTPC5EUBLS150GR
Cat 5e patch cord, UTP, 20 m (65 ft), LSZH, green ACTPC5EUBLS200GR
Cat 5e patch cord, UTP, 25 m (82 ft), LSZH, green ACTPC5EUBLS250GR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), CMP (Plenum-rated
cable), LSZH (Low Smoke Zero Halogen)

Part Numbers in Pacific Region for Network Connectivity Accessories

Product descriptiona Part number (Pacific region)


Cat 6 field-term plug, UTP ACTPG6TLU001
Cat 6 pass-through plug, UTP, 100-pack ACTPG6PTU100
Actassi crimping tool ACTTLCPT
Cat 6 cable, UTP, 305 m (1000 ft), PVC, green 2D4P6IPV3B-GR
Cat 6 patch lead, UTP, 10 m (32 ft), PVC, green RJ6_100PL-GR
Cat 6 patch lead, UTP, 15 m (49 ft), PVC, green RJ6_150PL-GR
Cat 6 patch lead, UTP, 20 m (65 ft), PVC, green RJ6_200PL-GR
Cat 6 patch lead, UTP, 25 m (82 ft), PVC, green RJ6_250PL-GR
Cat 5e pass-through plug, UTP, 100-pack ACTPG5EPTU100
Cat 5e cable, UTP, 305 m (1000 ft), PVC, green 2D4P5IPV3B-GR

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.
EcoStruxure™ Building www.schneider-electric.com/buildings | 14

IP-IO
SmartX IP Controller

Continued

Product descriptiona Part number (Pacific region)


Cat 5e patch lead, UTP, 10 m (32 ft), PVC, green RJ5_100PL-GR
Cat 5e patch lead, UTP, 15 m (49 ft), PVC, green RJ5_150PL-GR
Cat 5e patch lead, UTP, 20 m (65 ft), PVC, green RJ5_200PL-GR
Cat 5e patch lead, UTP, 25 m (82 ft), PVC, green RJ5_250PL-GR

a) For more information, see the Product Selection Guide (SmartX IP Controllers - Accessories). Abbreviations: UTP (Unshielded Twisted Pair), PVC (Polyvinyl
chloride)

Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2014/35/EU Low Voltage Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
any interference received, including interference that may cause undesired operation. 2015/863/EU amending Annex II to Directive 2011/65/EU
This equipment complies with the rules, of the Official Journal of the European Union, for
Industry Canada governing the Self Declaration of the CE Marking for the European Union as specified in the
This Class B digital apparatus complies with Canadian ICES-003. above directive(s) per the provisions of the following standards: EN 60730-1, EN 60730-2-
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. 11, and EN 50491-3 Safety Standards.

Regulatory Compliance Mark (RCM) - Australian Communications and Media


Authority (ACMA) WEEE - Directive of the European Union (EU)
This equipment complies with the requirements of the relevant ACMA standards made under This equipment and its packaging carry the waste of electrical and electronic equipment
the Radiocommunications Act 1992 and the Telecommunications Act 1997. These (WEEE) label, in compliance with European Union (EU) Directive 2012/19/EU, governing the
standards are referenced in notices made under section 182 of the Radiocommunications disposal and recycling of electrical and electronic equipment in the European community.
Act and 407 of the Telecommunications Act.

UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.

www.schneider-electric.com

03-20014-02-en, May 2019


© 2019 Schneider Electric. All rights reserved. Trademarks and registered trademarks are the property of their respective owners.