CO2 System Presentation
CO2 System Presentation
•Principle of Extinguishments.
Combination System
Design Basis
• Applicable Standard : NFPA 12, 2015 Ed.
• Room temperature considered : 21 Deg.C
• Minimum conc. of agent as per :
(For Dry Electrical Hazard ) : 50% (Class ‘A’ and ‘C’ Fire).
(For Record (bulk paper) storage, ducts, : 65% (Class ‘A’ Fire).
covered trenches)
(For Fur storage vaults, dust collectors) : 75% (Class ‘A’ Fire).
• System pressure : 60 Bar
• Maximum discharge time : Total flooding 60 Seconds.
Local flooding 30 Seconds
• Safety during maintenance : As per NFPA 12, 2015 edition , A
manually operated Supervisory
lockout valve which can be locked in
close position
CO2 GAS Engineered System
Smoke Detectors
Distribution Pipe
Discharge Nozzle
Containers
Manual
Station
Raised Floor
SAMPLE CALCULATION .
Electric Generators.
Switchgear Equipments.
Panels.
Transformers.
Drawing Offices.
Diesel & Electrical Locomotives.
Cables Galleries.
Record Data Storages
Engine test cells
DATA REQUIRED FROM OWNER