SmartX AS-B Server - SmartX Controller Specification Sheet
SmartX AS-B Server - SmartX Controller Specification Sheet
com/buildings | 1
Introduction Models
At the core of an EcoStruxure BMS is a SmartX server, The SmartX AS-B server comes in eight models with
such as the SmartX AS-B server. The SmartX AS-B different I/O point count and I/O mix.
server performs key functionality, such as control logic,
trend logging, and alarm supervision, provides built-in Model I/O Points
I/O, and supports communication and connectivity to AS-B-24 24
the field buses. The distributed intelligence of the
EcoStruxure BMS ensures fault tolerance in the system AS-B-24H 24
and provides a fully featured user interface through AS-B-24L 24
WorkStation and WebStation. AS-B-24HL 24
AS-B-36 36
Feature
AS-B-36H 36
The SmartX AS-B server is a powerful device with built-
in power supply and I/O. The SmartX AS-B server can AS-B-36L 36
act as a standalone server using its built-in I/O and also AS-B-36HL 36
monitor and manage field bus devices. In a small
installation, the embedded SmartX AS-B server acts as SmartX AS-B servers with “H” in the product name are
a standalone server, mounted in a small footprint. In equipped with a display for output override.
medium and large installations, functionality is
distributed over multiple SmartX servers that SmartX AS-B servers with “L” in the product name do
communicate over TCP/IP. not support Modbus, BACnet MS/TP, or hosting of
BACnet/IP devices. The RS-485 port is not used.
Communications hub
Capable of coordinating traffic from above and below SmartX AS-B servers with 36 I/O points have the same
its location, the SmartX AS-B server can deliver data small footprint as SmartX AS-B servers with 24 I/O
directly to you or to other servers throughout the site. points.
The SmartX AS-B server can run multiple control
programs, manage built-in I/O, alarms, and users, Versatile and flexible mix of I/O points
handle scheduling and logging, and communicate The SmartX AS-B server offers a mix of I/O point types
using a variety of protocols. Because of this, most parts that match a wide variety of HVAC applications. Most of
of the system function autonomously and continue to the I/O points are universal inputs/outputs, which are
run as a whole even if communication fails or individual highly flexible and can be configured as either inputs or
EcoStruxure BMS servers or devices go offline. outputs.
SmartX AS-B servers with 24 I/O points have the The universal inputs/outputs are capable of supporting
following types: analog outputs of type voltage outputs. Therefore, the
universal inputs/outputs support a wide range of
• 12 Universal inputs/outputs, Ua type devices, such as actuators.
• 4 Universal inputs/outputs, Ub type
Digital inputs
• 4 Digital inputs The digital inputs can be used for cost effective
• 4 Relay outputs sensing of multiple dry contact digital inputs in
applications, such as equipment status monitoring or
SmartX AS-B servers with 36 I/O points have the alarm point monitoring. As counter inputs, digital inputs
following types: are commonly used in energy metering applications.
Variety of connectivity options monitor the SmartX AS-B server and its built-in I/O as
A SmartX AS-B server has numerous ports that enable well as its attached field bus devices. See the
it to communicate with a wide range of protocols, WorkStation and WebStation specification sheets for
devices, and servers. additional information.
A SmartX AS-B server has the following ports: Open building protocol support
One of the cornerstones of the EcoStruxure BMS is
• Two 10/100 Ethernet ports support for open standards. The SmartX AS-B server
can natively communicate with two of the most popular
• One RS-485 port
standards for buildings: BACnet and Modbus.
• One USB host port
Native BTL-listed BACnet support
• One USB device port
A SmartX AS-B server communicates directly to
The first Ethernet port is dedicated to the site network. BACnet/IP and BACnet MS/TP networks. The SmartX
The second Ethernet port is fully configurable. The AS-B servers are BTL-listed as BACnet Building
second port can be configured to extend the site Controllers (B-BC), the most advanced BACnet Device
network so that various devices and clients can be Profile. This capability provides access to an extensive
connected. Another option is to configure the second range of BACnet devices from Schneider Electric and
port as a separate network, which means that the port other vendors. See the BTL Product Catalog for up-to-
can host a private network or act as a client to a second date details on BTL listed firmware revisions on BACnet
site network. If the second port is not used, it can be International's home page. A SmartX AS-B server can
disabled. also serve as a BACnet Broadcast Management Device
(BBMD) to facilitate BACnet systems that span multiple
The USB device port allows you to upgrade and IP subnets.
interact with the SmartX AS-B server using Device
Administrator. Native Modbus support
The SmartX AS-B server natively integrates Modbus
Using a USB Ethernet adapter, you can connect a RS-485 master and slave configurations, as well as
laptop PC to the USB host port and run Device Modbus TCP client and server. This allows full access
Administrator, WorkStation, and WebStation to to third-party products and the range of Schneider
upgrade, configure, and access the SmartX AS-B Electric products that communicate on the Modbus
server. The USB host port can also be used to provide protocol, such as power meters, UPS, circuit breakers,
power and communications for the AD touchscreen and lighting controllers.
display.
Web Services support
Authentication and permissions The SmartX AS-B server supports the use of Web
An EcoStruxure BMS provides a powerful permission Services based on open standards, such as SOAP and
system that is easy to manage, flexible, and adapts to REST, to consume data into the EcoStruxure BMS. Use
all kinds of system sizes. The permission system incoming third-party data (temperature forecast,
provides a security level of the highest standards. energy cost) over the Web to determine site modes,
Authentication is done against the built-in user account scheduling, and programming.
management system or against Windows Active
Directory Domains. The built-in account management EcoStruxure Web Services support
system allows an administrator to establish password EcoStruxure Web Services, Schneider Electric’s Web
policies that meet stringent cybersecurity guidelines. Services standard, is natively supported in the SmartX
When Windows Active Directory is used, the AS-B server. EcoStruxure Web Services offers extra
administration costs are lower because users do not features between compliant systems whether within
have to be managed in multiple directories. Schneider Electric or other authorized systems. These
features include system directory browsing, read/write
WorkStation/WebStation interface of current values, alarm receipt and acknowledgement,
Through any client, the user experience is similar and historical trend log data. EcoStruxure Web
regardless of which EcoStruxure BMS server the user is Services is secure. User name and password are
logged on to. The user can log directly on to a SmartX required to log on to the system.
AS-B server to engineer, commission, supervise, and
Specifications
AC input
Nominal voltage......................................................................................................................................................24 VAC
Operating voltage range........................................................................................................................................+/-20 %
Frequency ............................................................................................................................................................50/60 Hz
Maximum current.................................................................................................................................................0.5 A rms
Recommended transformer rating......................................................................................................................... ≥15 VA
DC input
Nominal voltage.............................................................................................................................................24 to 30 VDC
Operating voltage range ...............................................................................................................................21 to 33 VDC
Maximum power consumption................................................................................................................................... 10 W
Environment
Ambient temperature, operating ..................................................................................................0 to 50 °C (32 to 122 °F)
Ambient temperature, storage ..............................................................................................-20 to +70 °C (-4 to +158 °F)
Maximum humidity.....................................................................................................................95 % RH non-condensing
Material
Plastic flame rating .............................................................................................................................................UL94-5VB
Enclosure ...............................................................................................................................................................PC/ABS
Ingress protection rating ............................................................................................................................................IP 20
Mechanical
Dimensions ......................................................................................198 W x 110 H x 64 D mm (7.8 W x 4.3 H x 2.5 D in.)
a) The weight includes the display and keys, which are 0.022 kg (0.049 lb).
Agency compliances
Emission...............................................................RCM; EN 61000-6-3; EN 50491-5-2; FCC Part 15, Sub-part B, Class B
Immunity ...............................................................................................................................EN 61000-6-2; EN 50491-5-3
Safety standards........................................................EN 60730-1; EN 60730-2-11; EN 50491-3; UL 916 C-UL US Listed
Product ............................................................................................................................................................EN 50491-1
Real-time clock
Accuracy, at 25 °C (77 °F) .........................................................................................................+/-52 seconds per month
Backup time, at 25 °C (77 °F).................................................................................................................................10 days
Communication ports
Ethernet ................................................................................................................................ Dual 10/100BASE-TX (RJ45)
USB ....................................................................................................................................1 USB 2.0 device port (mini-B)
........................................................................................................................1 USB 2.0 host port (type-A), 5 VDC, 2.5 W
RS-485 ....................................................................................................................................... 2-wire port, bias 5.0 VDC
Communications
BACnet..........................................................................................................BACnet/IP, port configurable, default 47808
BACnet profile.........................................................................................BACnet Building Controller (B-BC), AMEV AS-B
BACnet certification...........................................................................................BTL Certification (BTL Listinga, WSPCert)
a) See the BTL Product Catalog for up-to-date details on BTL listed firmware revisions on BACnet
International'shomepage.
Modbus .............................................................................................................................Modbus TCP, client and server
...........................................................................................................................................Serial, RS-485, master or slave
TCP................................................................................................................................................Binary, port fixed, 4444
HTTP ..................................................................................................................Non-binary, port configurable, default 80
HTTPS............................................................Encrypted supporting TLS 1.2, 1.1, and 1.0, port configurable default 443
SMTP ............................................................................................................Email sending, port configurable, default 25
SMTPS ........................................................................................................Email sending, port configurable, default 587
SNMP ...................................................................................................................................................................version 3
............................................................................................................................ Network supervision using poll and trap
............................................................................................................................Application alarm distribution using trap
CPU
Frequency ........................................................................................................................................................... 333 MHz
Type..........................................................................................................................................SPEAr320S, ARM926 core
DDR2 SDRAM ....................................................................................................................................................... 256 MB
eMMC memory ..........................................................................................................................................................4 GB
Memory backup........................................................................................................... Yes, battery-free, no maintenance
Display
Display resolution .......................................................................................................................................128 x 64 pixels
Display size .................................................................................................................36 W x 17 H mm (1.4 W x 0.7 H in.)
Display type......................................................................... FSTN monochrome LCD, white color transflective backlight
Part numbers
SmartX Controller – AS-B-24............................................................................................................... SXWASB24X10001
SmartX Controller – AS-B-24H
Includes display ................................................................................................................................. SXWASB24H10001
SmartX Controller – AS-B-24L
No support for Modbus, BACnet MS/TP, or hosting of BACnet/IP devices..........................................SXWASB24X10002
SmartX Controller – AS-B-24HL
Includes display
No support for Modbus, BACnet MS/TP, or hosting of BACnet/IP devices .........................................SXWASB24H10002
SmartX Controller – AS-B-36............................................................................................................... SXWASB36X10001
SmartX Controller – AS-B-36H
Includes display ................................................................................................................................. SXWASB36H10001
SmartX Controller – AS-B-36L
No support for Modbus, BACnet MS/TP, or hosting of BACnet/IP devices..........................................SXWASB36X10002
SmartX Controller – AS-B-36HL
Includes display
No support for Modbus, BACnet MS/TP, or hosting of BACnet/IP devices .........................................SXWASB36H10002
AS-B connector kit (includes terminal blocks) .................................................................................. SXWASBCON10001
AS-B installer kit .................................................................................................................................. SXWASBINS10001
Add-on options
SW-EWS-1, EcoStruxure Web Services (run-time) option
Consume only for one EcoStruxure BMS server ................................................................................SXWSWEWSX00001
SW-EWS-2, EcoStruxure Web Services (run-time) option
Serve & Consume for one EcoStruxure BMS server ..........................................................................SXWSWEWSX00002
SW-EWS-3, EcoStruxure Web Services (run-time) option
Serve & Consume, plus Historical trend log data for one EcoStruxure BMS server ..........................SXWSWEWSX00003
SW-GWS-1, Web Services (Generic Consume) option
For one EcoStruxure BMS server ......................................................................................................SXWSWGWSX00001
SW-SNMP-1, Alarm notifications via SNMP option
For one EcoStruxure BMS server.......................................................................................................SXWSWSNMP00001
SW-SMART-CONNECT, Smart Connector deployment license
For one Smart Connector deployment ...............................................................................................SXWSWSCDL10000
SW-ASDBTS-1, TimescaleDB connection option
For one SmartX server ......................................................................................................................SXWSWASDBXS001
Software requirements
External log storage option .....................................................PostgreSQL 11.0 (or higher), TimescaleDB 1.2 (or higher)
Quality assurance testing has been performed by Schneider Electric with TimescaleDB and PostgreSQL installed
natively in Windows 10, Windows Server 2012, and Windows Server 2016. Other deployment scenarios have not been
tested by Schneider Electric.
Universal inputs/outputs, Ua and Ub
Channels, SmartX AS-B servers with 24 I/O points .............................................................................12 Ua, Ua1 to Ua12
................................................................................................................................................................4 Ub, Ub1 to Ub4
Channels, SmartX AS-B servers with 36 I/O points ........................................................................... 20 Ua, Ua1 to Ua20,
................................................................................................................................................................8 Ub, Ub1 to Ub8
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
Xenta....................................................................................................................................................................1.8 kohm
Balco.......................................................................................................................................................................1 kohm
Measurement accuracy
20 kohm...................................................................................................-50 to -30 °C: +/-1.5 °C (-58 to -22 °F: +/-2.7 °F)
...................................................................................................................-30 to 0 °C: +/-0.5 °C (-22 to +32 °F: +/-0.9 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
10 kohm, 2.2 kohm, and 1.8 kohm.......................................................-50 to -30 °C: +/-0.75 °C (-58 to -22 °F: +/-1.35 °F)
..........................................................................................................-30 to +100 °C: +/-0.2 °C (-22 to +212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
Linearized 10 kohm .................................................................................-50 to -30 °C: +/-2.0 °C (-58 to -22 °F: +/-3.6 °F)
...............................................................................................................-30 to 0 °C: +/-0.75 °C (-22 to +32 °F: +/-1.35 °F)
.................................................................................................................. 0 to 100 °C: +/-0.2 °C (32 to 212 °F: +/-0.4 °F)
.............................................................................................................100 to 150 °C: +/-0.5 °C (212 to 302 °F: +/-0.9 °F)
1 kohm ..............................................................................................-50 to +150 °C: +/-1.0 °C (-58 to +302° F: +/-1.8 °F)
RTD temperature
Supported RTDs ..............................................................................................................Pt1000, Ni1000, and LG-Ni1000
Pt1000
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Measurement accuracy ......................................................................-50 to +70 °C: +/-0.5 °C (-58 to +158 °F: +/-0.9 °F)
...............................................................................................................70 to 150 °C: +/-0.7 °C (158 to 302 °F: +/-1.3 °F)
Ni1000
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Measurement accuracy ......................................................................................................................+/-0.5 °C (+/-0.9 °F)
LG-Ni1000
Range................................................................................................................................-50 to +150 °C (-58 to +302 °F)
Measurement accuracy ......................................................................................................................+/-0.5 °C (+/-0.9 °F)
RTD temperature wiring
Maximum wire resistance.........................................................................................................20 ohm/wire (40 ohm total)
Maximum wire capacitance.......................................................................................................................................60 nF
The wire resistance and capacitance typically corresponds to a 200 m wire.
RTD resistive
1,000 ohm
Range .....................................................................................................................................................500 to 2,200 ohm
.................................................................................................................................................Including wiring resistance
Measurement accuracy..........................................................................................................+/-(0.2 + 1.5 x 10-3 x R) ohm
R = resistance in ohm
Resolution ..............................................................................................................................................................0.1 ohm
RTD resistive wiring
Maximum wire capacitance.......................................................................................................................................60 nF
Voltage outputs
Range ..............................................................................................................................................................0 to 10 VDC
Accuracy..............................................................................................................................................................+/-60 mV
Resolution.................................................................................................................................................................10 mV
Minimum load resistance ........................................................................................................................................5 kohm
Load range.......................................................................................................................................................-1 to +2 mA
Digital inputs, DI
Channels, SmartX AS-B servers with 24 I/O points........................................................................................ 4, DI1 to DI4
Channels, SmartX AS-B servers with 36 I/O points...........................................................................................................0
Absolute maximum ratings .......................................................................................................................-0.5 to +24 VDC
Digital inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ..............................................................................................................................................120 ms
Counter inputs
Range .........................Dry contact switch closure or open collector/open drain, 24 VDC, typical wetting current 2.4 mA
Minimum pulse width ................................................................................................................................................20 ms
Maximum frequency..................................................................................................................................................25 Hz
Relay outputs, DO
Channels, SmartX AS-B servers with 24 I/O points .................................................................................... 4, DO1 to DO4
Channels, SmartX AS-B servers with 36 I/O points .................................................................................... 4, DO1 to DO4
Contact rating......................................................................................................250 VAC/30 VDC, 2 A, Pilot Duty (C300)
Switch type....................................................................................................................................................Form A Relay
....................................................................................................................................................Single Pole Single Throw
....................................................................................................................................................................Normally Open
Isolation contact to system ground.....................................................................................................................3000 VAC
Cycle life (Resistive load) ..............................................................................................................At least 100,000 cycles
Minimum pulse width ..............................................................................................................................................100 ms
Triac outputs, DO
Channels, SmartX AS-B servers with 24 I/O points...........................................................................................................0
Channels, SmartX AS-B servers with 36 I/O points .................................................................................... 4, DO5 to DO8
Output rating......................................................................................................................................................Max. 0.8 A
Voltage......................................................................................................................................................24 VAC +/-20 %
Commons ....................................................................................................................................COM1 for DO5 and DO6
.....................................................................................................................................................COM2 for DO7 and DO8
The common terminals COM1 and COM2 can be connected to 24 VAC or to ground.
Common voltage, high side output.........................................................................................................................24 VAC
Common voltage, low side output .............................................................................................................0 VAC (ground)
Minimum pulse width ..............................................................................................................................................100 ms
Terminals
For protection from excess current that could be • Individual 24 VDC power sources to the field must
produced by field wiring, follow these instructions: be current limited to maximum 4 A for UL
compliant installations, and maximum 6 A in other
• Connect RET terminal number 4 or 5 to a common areas.
chassis/signal ground rail in the control panel
using a size 2.5 mm² (13 AWG) or larger wire. The For more information on wiring, see Hardware
wire must have a current rating greater than or Reference Guide.
equal to 16 A.
• SmartX AS-B servers with 24 I/O points have more
RET terminals for connection of I/O returns, so the
common chassis/signal ground rail is optional and
may not be needed.
Regulatory Notices
Federal Communications Commission CE - Compliance to European Union (EU)
FCC Rules and Regulations CFR 47, Part 15, Class B 2014/30/EU Electromagnetic Compatibility Directive
This device complies with part 15 of the FCC Rules. Operation is subject to the following two 2014/35/EU Low Voltage Directive
conditions: (1) This device may not cause harmful interference. (2) This device must accept 2011/65/EU Restriction of Hazardous Substances (RoHS) Directive
any interference received, including interference that may cause undesired operation. 2015/863/EU amending Annex II to Directive 2011/65/EU
This equipment complies with the rules, of the Official Journal of the European Union, for
Industry Canada governing the Self Declaration of the CE Marking for the European Union as specified in the
This Class B digital apparatus complies with Canadian ICES-003. above directive(s) per the provisions of the following standards: EN 50491-1 Product
Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada. Standard; EN 60730-1, EN 60730-2-11, and EN 50491-3 Safety Standards.
UL 916 Listed products for the United States and Canada, Open Class Energy
Management Equipment. UL file E80146.
www.schneider-electric.com