0% found this document useful (0 votes)
186 views32 pages

SDM230 Modbus

This document is the user manual for the Eastron SDM230-Modbus single-phase energy meter. It provides specifications for the meter such as voltage and current ranges, accuracy levels, communication protocols, and display features. The manual also describes the meter's operation including initializing displays, scrolling through measurement values, and entering setup mode to configure settings like the Modbus address and baud rate.

Uploaded by

Bouzekri ARIOUA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
186 views32 pages

SDM230 Modbus

This document is the user manual for the Eastron SDM230-Modbus single-phase energy meter. It provides specifications for the meter such as voltage and current ranges, accuracy levels, communication protocols, and display features. The manual also describes the meter's operation including initializing displays, scrolling through measurement values, and entering setup mode to configure settings like the Modbus address and baud rate.

Uploaded by

Bouzekri ARIOUA
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Eastron SDM230-Modbus User Manual

SDM230-Modbus

Single-Phase Two Module DIN rail Meters

 Measures kWh, Kvarh, KW, Kvar, KVA, PF, Hz, dmd, V, A, etc.
 Bi-directional measurement IMP & EXP
 Two pulse outputs
 RS485 Modbus
 Din rail mounting 35mm
 100A direct connection
 Better than Class 1 / B accuracy

User Manual V1.4


2015
-1-
Eastron SDM230-Modbus User Manual

Application

The energy-meters “with a blue back-lighted LCD screen for prefect reading” are used to measure single-phase like
residential, Utility and Industrial application. The unit measures and displays various important electrical
parameters, and provide a communication port for remote reading and monitoring. Bi-directional energy
measurement makes the unit a good choice for solar PV energy metering.

PART 1 Specification
General Specifications

Voltage AC (Un) 230V


Voltage Range 176~276V AC
Base Current (Ib) 10A
Max. Current (Imax) 100A
Mini Current (Imin) 0.5A
Starting current 0.4% of Ib
Power consumption <2W/10VA
Frequency 50/60Hz(±10%)
AC voltage withstand 4KV for 1 minute
Impulse voltage withstand 6KV-1.2uS wavform
Overcurrent withstand 30Imax for 0.01s
Pulse output rate 1000imp/kWh (default)
1000/100/10/1 imp/kWh/kVarh (configurable)
Display LCD with blue backlit
Max. Reading 999999.9kWh

Accuracy

Voltage 0.5% of range maximum


Current 0.5% of nominal
Frequency 0.2% of mid-frequency
Power factor 1% of Unity
Active power 1% of range maximum
Reactive power 1% of range maximum
Apparent power 1% of range maximum
Active energy Class 1 IEC62053-21
Class B EN50470-3
Reactive energy 1% of range maximum

-2-
Eastron SDM230-Modbus User Manual

Environment

Operating temperature -25℃ to +55℃


Storage and transportation temperature -40℃ to +70℃
Reference temperature 23℃±2℃
Relative humidity 0 to 95%, non-condensing
Altitude up to 2500m
Warm up time 10s
Installation category CAT III
Mechanical Environment M1
Electromagnetic environment E2
Degree of pollution 2

Output

Pulse Output
The meter provides two pulse outputs. Both pulse outputs are passive type.
Pulse output 1 is configurable. The pulse output can be set to generate pulses to represent total / import/export
kWh or kVarh.
The pulse constant can be set to generate 1 pulse per: 0.001(default) /0.01/0.1/1kWh/kVarh.
Pulse width: 200/100/60ms
Pulse output 2 is non-configurable. It is fixed up with import kWh. The constant is 1000imp/kWh.

RS485 output for Modbus RTU


The meter provides a RS485 port for remote communication. Modbus RTU is the protocol applied. For Modbus
RTU, the following RS485 communication parameters can be configured from the Set-up menu.
Baud rate: 1200, 2400, 4800, 9600
Parity: NONE/EVEN/ODD
Stop bits: 1 or 2
Modbus Address: 1 to 247

Mechanics

Din rail dimensions 36x99x63 (WxHxD) DIN 43880


Mounting DIN rail 35mm
Sealing IP51 (indoor)
Material self-extinguishing UL94V-0

-3-
Eastron SDM230-Modbus User Manual

LCD display

Item Descriptions
1 7 digits used to display measured values or RTC
2 Total value
4 Import information, Export information
5 Max. Demand for Power or Current
6 Pulse output 1 and Pulse output 2
7 Measurement units
8 PF = power factor Hz = frequency
9 Bar display of Power
10 Communication indicator
11 Time information
12 Low battery warning
13 Lock symbol

PART 2 Operation
Initialization Display

When it is powered on, the meter will initialize and do self-checking.

Full screen  software version  Modbus ID  Baud rate  total kWh

Scroll display by Button

After initialization and self-checking program, the meter display the measured values. The default page is total
kWh. If the user wants to check other information, he needs to press the scroll button on the front panel.

The display order by scroll button :


The display order by scroll button :
Total kWh import kWhexport kWh resettable KWh total kVarh import kVarh export kVarh
Total kWh import kWhexport kWh total kVarh import kVarh export kVarh
resettable kVarhMax. power demand voltage currentWVar VA power factor 
Max. power demand voltage currentWVar VA power factor 
frequency pulse constant Modbus ID  baud rate continuous running time.
frequency pulse constant Modbus ID baudrate.

-4-
Eastron SDM230-Modbus User Manual

Page Display Descriptions

1 Total active energy


Example:70.00kWh

2 Import active energy


Example: 50.00kWh

3 Export active energy


Example: 20.00kWh

4 Total resettable energy

5 Total reactive energy


Example: 10.00kVarh

6 Import reactive energy


Example: 5.00kVarh

7 Export reactive energy


Example: 5.00kVarh

-5-
Eastron SDM230-Modbus User Manual

8 Total resettable reactive energy

9 Total max. demand


Example: 6930W

10 Voltage
Example: 229.8V

11 Current
Example: 30.156A

12 Active Power
Example: 4700W

13 Reactive Power
Example: 1030Var

14 Apparent power
Example: 4811VA

-6-
Eastron SDM230-Modbus User Manual

15 Power factor
Example: 1.000

16 Frequency
Example: 49.99Hz

17 Pulse Constant
Example: 1000

18 Modbus Address
Example: 001

19 Baud rate
Example: 9600

20 Continuous running time(In total)

-7-
Eastron SDM230-Modbus User Manual

Set-up Mode

To get into Set-up Mode, the user need press the “Enter” button for 3 second.
Page Display Descriptions

The setting is done correctly

The entering information is wrong. The


operation fails.

1 Password
To get into Set-up mode, it asks a password
confirmation.
Default password: 1000

2 Address ID
Default ID is 001
Range: 001~247

2-1 Press the “Enter” button, the first digit


flash.
Press the “Scroll” button to change the
value. After choose the new address value,
the user need pressing the “Enter” button
to confirm the setting.
3 Baud rate
Default value: 2400bps
Range: 1200, 2400, 4800, 9600bps.

-8-
Eastron SDM230-Modbus User Manual

3-1 Press the “Enter” button, the red digit flash.


Press the “Scroll” button to change the
value.
After choose the new baud rate, the user
need pressing the “Enter” button to confirm
the setting.
4 Parity
Default: None
Option:None, Even, Odd

4-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new Parity, the user need
pressing the “Enter” button to confirm the
setting.
5 Pulse Output
Default: Export kWh
Option:kWh / KVarh / Imp. Kwh /
Exp.kWh / Imp.kVarh / Exp.kVarh

5-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new Pulse output option,
the user need pressing the “Enter” button
to confirm the setting.
6 Pulse Constant
Default: 1000
Option: 1000 / 100 / 10 / 1

6-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new Pulse constant option,
the user need pressing the “Enter” button
to confirm the setting.

-9-
Eastron SDM230-Modbus User Manual

7 Pulse duration
Default: 100mS
Option: 200 / 100 / 60ms

7-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new Pulse duration option,
the user need pressing the “Enter” button
to confirm the setting.
8 Demand Integration Time
Default: 15 minutes
Option: 0 / 5 / 10 / 15 / 30 / 60

8-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new DIT option, the user
need pressing the “Enter” button to confirm
the setting.
9 Automatic Scroll Time Interval
Default: 0 S
Option: 0 ~ 30S

9-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
option.
After choose the new “Scrl” option, the user
need pressing the “Enter” button to confirm
the setting.
10 Backlit lasting time set-up
Default: 60 min
Option: 0(OFF)/ 5/ 10/ 20/ 30/ 60
Long press “Enter” button to enter set-up
mode.

- 10 -
Eastron SDM230-Modbus User Manual

10-1 Press the “Scroll” button to change the


option.
After choose the new “Scrl” option, the user
need pressing the “Enter” button to confirm
the setting.

11 Clear
Long press “Enter” to enter clear interface.

11-1 Clear Max demand of active power


Long press “Enter” button to confirm the
operation.

11-2 Clear the resettable energy


Long press the Enter button to confirm the
operation.

10 Password
Default: 1000

10-1 Press the “Enter” button, the red part flash.


Press the “Scroll” button to change the
value.
After choose the new password, the user
need pressing the “Enter” button to confirm
the setting.

- 11 -
Eastron SDM230-Modbus User Manual

Wiring diagram

Dimensions

- 12 -
Eastron SDM230-Modbus User Manual

Installation

- 13 -
Eastron SDM230Modbus Protocol V1.2

1.Eastron SDM230Modbus Smart Meter Modbus Protocol Implementation V1.2

1.1 Modbus Protocol Overview

This section provides basic information for interfacing the Eastron Smart meter to a
Modbus Protocol network. If background information or more details of the Eastron
implementation is required, please refer to section 2 and 3 of this document.

Eastron offers the option of an RS485 communication facility for direct connection to
SCADA or other communications systems using the Modbus Protocol RTU salve protocol.
The Modbus Protocol establishes the format for the master’s query by placing into it the
device address, a function code defining the requested action, any data to be sent, and an
error checking field. The slave’s response message is also constructed using Modbus
Protocol. It contains fields confirming the action taken, any data to be returned, and an
error-checking field. If an error occurs in receipt of the message, SDM230Modbus will
make no response. If the SDM230Modbus is unable to perform the requested action, it will
construct an error message and send it as the response.

The electrical interface is 2-wire RS485, via 2 screw terminals. Connection should be
made using twisted pair screened cable (Typically 22 gauge Belden 8761 or equivalent).
All "A" and "B" connections are daisy chained together. Line topology may or may not
require terminating loads depending on the type and length of cable used. Loop (ring)
topology does not require any termination load. The impedance of the termination load
should match the impedance of the cable and be at both ends of the line. The cable
should be terminated at each end with a 120 ohm (0.25 Watt min.) resistor. A total
maximum length of 1200 meters is allowed for the RS485 network. A maximum of 32
electrical nodes can be connected, including the controller. The address of each Eastron
can be set to any value between 1 and 247. Broadcast mode (address 0) is supported.

The format for each byte in RTU mode is:


Coding System: 8-bit per byte
Data Format: 4 bytes (2 registers) per parameter.
Floating point format ( to IEEE 754)
Most significant register first (Default). The default may be changed if
required -See Holding Register "Register Order" parameter.
Error Check Field: 2 byte Cyclical Redundancy Check (CRC)
Framing: 1 start bit
8 data bits, least significant bit sent first
1 bit for even/odd parity (or no parity)
1 stop bit if parity is used; 1 or 2 bits if no parity
Data Coding
All data values in the SDM230Modbus smart meter are transferred as 32 bit IEEE754

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

floating point numbers, (input and output) therefore each SDM230Modbus meter value is
transferred using two Modbus Protocol registers. All register read requests and data write
requests must specify an even number of registers. Attempts to read/write an odd number
of registers prompt the SDM230Modbus smart meter to return a Modbus Protocol
exception message. However, for compatibility with some SCADA systems,
SDM230Modbus Smart meter will response to any single input or holding register read
with an instrument type specific value.

The SDM230Modbus can transfer a maximum of 40 values in a single transaction;


therefore the maximum number of registers requestable is 80. Exceeding this limit
prompts the SDM230Modbus to generate an exception response.

Data transmission speed is selectable between 1200,2400, 4800, 9600

1.2 Input register


Input registers are used to indicate the present values of the measured and calculated
electrical quantities. Each parameter is held in two consecutive16 bit register. The
following table details the 3X register address, and the values of the address bytes within
the message. A (*) in the column indicates that the parameter is valid for the particular
wiring system. Any parameter with a cross(X) will return the value zero. Each parameter is
held in the 3X registers. Modbus Protocol function code 04 is used to access all
parameters.
For example, to request: Amps 1 Start address=0006
No. of registers =0002
Amps 2 Start address=0008
No. of registers=0002
Each request for data must be restricted to 40 parameters or less. Exceeding the 40
parameter limit will cause a Modbus Protocol exception code to be returned.

Modbus
SDM230-Modbus Input Register
Protocol Start
Parameter
Address Address Hex
(Register) Hi Lo
Description Units
Byte Byte
30001 Line to neutral volts. Volts 00 00
30007 Current. Amps 00 06
30013 Active power. Watts 00 0C
30019 Apparent power VoltAmps 00 12
30025 Reactive power VAr 00 18
30031 Power factor None 00 1E
30037 Phase angle. Degree 00 24
30071 Frequency Hz 00 46

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

30073 Import active energy kwh 00 48


30075 Export active energy kwh 00 4A
30077 Import reactive energy kvarh 00 4C
30079 Export reactive energy kvarh 00 4E
30085 Total system power demand W 00 54
30087 Maximum total system power demand W 00 56
30089 Current system positive power demand W 00 58
30091 Maximum system positive power demand W 00 5A
30093 Current system reverse power demand W 00 5C
30095 Maximum system reverse power demand W 00 5E
30259 Current demand. Amps 01 02
30265 Maximum current demand. Amps 01 08
30343 Total active energy kwh 01 56
30345 Total reactive energy kvarh 01 58
30385 Current resettable total active energy kwh 01 80
30387 Current resettable total reactive energy kvarh 01 82

1.3 Modbus Protocol Holding Registers and Digital meter set up

Holding registers are used to store and display instrument configuration settings. All holding
registers not listed in the table below should be considered as reserved for manufacturer use
and no attempt should be made to modify their values.
The holding register parameters may be viewed or changed using the Modbus Protocol. Each
parameter is held in two consecutive 4X registers. Modbus Protocol Function Code 03 is used
to read the parameter and Function Code 16 is used to write. Write to only one parameter per
message.
Modbus
Protocol
Address Parameter Start
Register Address Valid range Mode
Hex
High Low
Byte Byte
Write relay on period in
Pulse Milliseconds: 60, 100 or 200,
40013 output 1 00 0C default 100. r/w
Width Data Format:float(length:4
byte)
Write the network port
Network
40019 00 12 parity/stop bits for MODBUS r/w
Parity
Protocol, where: 0 = One stop bit

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

and no parity, default.1 = One


stop bit and even parity. 2 = One
stop bit and odd parity.3 = Two
stop bits and no parity.
Data Format:float(length:4
byte)
Write the network port node
Address: 1 to 247 for MODBUS
Network
40021 00 14 Protocol, default 1. r/w
port Node
Data Format:float(length:4
byte)
Write the network port baud rate
for MODBUS Protocol, where:
0 = 2400 bps( default). 1 =
Network 4800 bps.
40029 00 1C r/w
Baud Rate 2 = 9600 bps.
5=1200 bps
Data Format:float(length:4
byte)
Write MODBUS Protocol
input parameter for pulse
relay 1:
1=Import Wh;
2=Import and ExportWh;
Pulse1
4=Export Wh;(default)
40087 Energy 00 56 r/w
Type
5=Import VArh;
6=Import and Export VArh;
8=Export VArh.
Data Format:float(length:4
byte)
Demand min-min-s-min
interval , scroll time=0:the display does
slide time, not scroll automatically.
automatic Backlight time=0 Backlight
scroll always on
462721 display F5 00 r/w
interval Data Format: BCD(length:4
(scroll byte)
Time),
Backlight
time

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

463761 0000: 0.001kwh(kvarh)


/imp(default)
0001: 0.01kwh(kvarh)/imp
Pulse 1
F9 10 0002: 0.1kwh(kvarh)/imp r/w
constant
0003: 1kwh(kvarh)/imp
Data Format:Hex(length:2
byte)
463776 0001:mode 1(total = import)
0002:mode 2(total = import
Measure + export) (default)
ment F9 20 0003:mode 3 (total = import - r/w
mode export)
Data Format:Hex(length:2
byte)
463792 Continuous working period--hour
Running
F9 30 Data Format:float(length:4 r/w
time
byte)

Note:
Mode 1: Measure imported energy, Total energy=Imported energy.
Mode 2: Measure imported energy and exported energy, Total energy=Import
energy + export energy(default).
Mode 3: Measure imported energy and exported energy, Total energy=Imported
energy- exported energy.

2 RS485 General Information


Some of the information in this section relates to other Eastron Digital meter product families,
and is included to assist where a mixed network is implemented.RS485 or EIA (Electronic
Industries Association) RS485 is a balanced line, half-duplex transmission system allowing
transmission distances of up to 1.2 km. The following table summarizes the RS-485 Standard:

PARAMETER
Mode of Operation Differential
Number of Drivers and Receivers 32 Drivers, 32 Receivers
Maximum Cable Length 1200 m
Maximum Data Rate 10 M baud
Maximum Common Mode Voltage 12 V to –7 V
Minimum Driver Output Levels (Loaded) +/– 1.5 V
Minimum Driver Output Levels (Unloaded) +/– 6 V
Drive Load Minimum 60 ohms

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Driver Output Short Circuit Current Limit 150 mA to Gnd,


250 mA to 12 V
250 mA to –7 V
Minimum Receiver Input Resistance 12 kohms
Receiver Sensitivity +/– 200 mV

Further information relating to RS485 may be obtained from either the EIA or the various
RS485 device manufacturers, for example Texas Instruments or Maxim Semiconductors. This
list is not exhaustive.

2.1 Half Duplex

Half duplex is a system in which one or more transmitters (talkers) can communicate with one
or more receivers (listeners) with only one transmitter being active at any one time. For
example, a “conversation” is started by asking a question, the person who has asked the
question will then listen until he gets an answer or until he decides that the individual who was
asked the question is not going to reply.
In a 485 network the “master” will start the “conversation” with a “query” addressed to a
specific “slave”, the “master” will then listen for the “slave’s” response. If the “slave” does not
respond within a pre-defined period, (set by control software in the “master”), the “master” will
abandon the “conversation”.

2.2 Connecting the Instruments

If connecting an RS485 network to a PC use caution if contemplating the use of an RS232 to


485 converter together with a USB to RS485 adapter. Consider either an RS232 to RS485
converter, connected directly to a suitable RS232 jack on the PC, or use a USB to RS485
converter or, for desktop PCs a suitable plug in RS485 card. (Many 232:485 converters draw
power from the RS232 socket. If using a USB to RS232 adapter, the adapter may not have
enough power available to run the 232:485 converter.)
Screened twisted pair cable should be used. For longer cable runs or noisier environments,
use of a cable specifically designed for RS485 may be necessary to achieve optimum
performance. All “A” terminals should be connected together using one conductor of the
twisted pair cable, all “B” terminals should be connected together using the other conductor in
the pair. The cable screen should be connected to the “Gnd” terminals.
A Belden 9841 (Single pair) or 9842 (Two pair) or similar cable with a characteristic impedance
of 120 ohms is recommended. The cable should be terminated at each end with a 120 ohm,
quarter watt (or greater) resistor. Note: Diagram shows wiring topology only. Always follow
terminal identification on Eastron Digital meter product label.

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

There must be no more than two wires connected to each terminal, this ensures that a “Daisy
Chain or “straight line” configuration is used. A “Star” or a network with “Stubs (Tees)” is not
recommended as reflections within the cable may result in data corruption.

2.3 A and B terminals

The A and B connections to the Eastron Digital meter products can be identified by the signals
present on them whilst there is activity on the RS485 bus:

2.4 Troubleshooting

·Start with a simple network, one master and one slave. With Eastron Digital meter products
this is easily achieved as the network can be left intact whilst individual instruments are

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

disconnected by removing the RS485 connection from the rear of the instrument.
·Check that the network is connected together correctly. That is all of the “A’s” are connected
together, and all of the “B’s” are connected together, and also that all of the “Gnd’s” are
connected together.
·Confirm that the data “transmitted” onto the RS485 is not echoed back to the PC on the
RS232 lines.(This facility is sometimes a link option within the converter). Many PC based
packages seem to not perform well when they receive an echo of the message they are
transmitting. SpecView and PCView (PC software) with a RS232 to RS485 converter are
believed to include this feature.
·Confirm that the Address of the instrument is the same as the “master” is expecting.
·If the “network” operates with one instrument but not more than one check that each
instrument has a unique address.
· Each request for data must be restricted to 40 parameters or less. Violating this requirement
will impact the performance of the instrument and may result in a response time in excess of
the specification.
·Check that the MODBUS Protocol mode (RTU or ASCII) and serial parameters (baud rate,
number of data bits, number of stop bits and parity) are the same for all devices on the
network.
·Check that the “master” is requesting floating-point variables (pairs of registers placed on
floating point boundaries) and is not “splitting” floating point variables.
·Check that the floating-point byte order expected by the “master” is the same as that used by
Eastron Digital meter products.
·If possible obtain a second RS232 to RS485 converter and connect it between the RS485
bus and an additional PC equipped with a software package, which can display the data on the
bus. Check for the existence of valid requests.
3 MODBUS Protocol General Information
Communication on a MODBUS Protocol Network is initiated (started) by a “Master” sending a
query to a “Slave”. The “Slave“, which is constantly monitoring the network for queries
addressed to it, will respond by performing the requested action and sending a response back
to the ”Master”. Only the “Master” can initiate a query.

In the MODBUS Protocol the master can address individual slaves, or, using a special
“Broadcast” address, can initiate a broadcast message to all slaves. The Eastron Digital meter
do not support the broadcast address.

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

3.1 MODBUS Protocol Message Format


The MODBUS Protocol defines the format for the master’s query and the slave’s response.
The query contains the device (or broadcast) address, a function code defining the requested
action, any data to be sent, and an error-checking field.
The response contains fields confirming the action taken, any data to be returned, and an
error-checking field. If an error occurred in receipt of the message then the message is ignored,
if the slave is unable to perform the requested action, then it will construct an error message
and send it as its response. The MODBUS Protocol functions used by the Eastron Digital
meters copy 16 bit register values between master and slaves. However, the data used by the
Eastron Digital meter is in 32 bit IEEE 754 floating point format. Thus each instrument
parameter is conceptually held in two adjacent MODBUS Protocol registers. Query
The following example illustrates a request for a single floating point parameter i.e. two 16-bit
Modbus Protocol Registers.

First Byte Last Byte


Number Number
Start Start Error Error
Slave Function of of
Address Address Check Check
Address Code Points Points
(Hi) (Lo) (Lo) (Hi)
(Hi) (Lo)

Slave Address: 8-bit value representing the slave being addressed (1 to 247), 0 is reserved for
the broadcast address. The Eastron Digital meters do not support the broadcast address.
Function Code: 8-bit value telling the addressed slave what action is to be performed. (3, 4, 8
or 16 are valid for Eastron Digital meter)
Start Address (Hi): The top (most significant) eight bits of a 16-bit number specifying the start
address of the data being requested.
Start Address (Lo): The bottom (least significant) eight bits of a 16-bit number specifying the
start address of the data being requested. As registers are used in pairs and start at zero, then
this must be an even number.
Number of Points (Hi): The top (most significant) eight bits of a 16-bit number specifying the
number of registers being requested.
Number of Points (Lo): The bottom (least significant) eight bits of a 16-bit number specifying
the number of registers being requested. As registers are used in pairs, then this must be an
even number.
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.

Response
The example illustrates the normal response to a request for a single floating point parameter
i.e. two 16-bit Modbus Protocol Registers.

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

First Byte Last Byte


First First Second Second Error Error
Slave Function Byte
Register Register Register Register Check Check
Address Code Count
(Hi) (Lo) (Hi) (Lo) (Lo) (Hi)

Slave Address: 8-bit value representing the address of slave that is responding.
Function Code: 8-bit value which, when a copy of the function code in the query, indicates that
the slave recognised the query and has responded. (See also Exception Response).
Byte Count: 8-bit value indicating the number of data bytes contained within this response
First Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the
first register requested in the query.
First Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing
the first register requested in the query.
Second Register (Hi)*: The top (most significant) eight bits of a 16-bit number representing the
second register requested in the query.
Second Register (Lo)*: The bottom (least significant) eight bits of a 16-bit number representing
the second register requested in the query.
Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.
*These four bytes together give the value of the floating point parameter requested.

Exception Response
If an error is detected in the content of the query (excluding parity errors and Error Check
mismatch), then an error response (called an exception response), will be sent to the master.
The exception response is identified by the function code being a copy of the query function
code but with the most-significant bit set. The data contained in an exception response is a
single byte error code.

First Byte Last Byte


Error Error
Slave Function Error
Check Check
Address Code Code
(Lo) (Hi)

Slave Address: 8-bit value representing the address of slave that is responding.
Function Code: 8 bit value which is the function code in the query OR'ed with 80 hex,
indicating that the slave either does not recognise the query or could not carry out the action
requested.
Error Code: 8-bit value indicating the nature of the exception detected. (See “Table Of
Exception Codes“ later).

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Error Check (Lo): The bottom (least significant) eight bits of a 16-bit number representing the
error check value.
Error Check (Hi): The top (most significant) eight bits of a 16-bit number representing the error
check value.

3.2 Serial Transmission Modes


There are two MODBUS Protocol serial transmission modes, ASCII and RTU. Eastron Digital
meters do not support the ASCII mode.
In RTU (Remote Terminal Unit) mode, each 8-bit byte is used in the full binary range and is not
limited to ASCII characters as in ASCII Mode. The greater data density allows better data
throughput for the same baud rate, however each message must be transmitted in a
continuous stream. This is very unlikely to be a problem for modern communications
equipment.

Coding System: Full 8-bit binary per byte. In this document, the value of each byte will be
shown as two hexadecimal characters each in the range 0-9 or A-F.
Line Protocol: 1 start bit, followed by the 8 data bits. The 8 data bits are sent with least
significant bit first.
User Option Of Parity No Parity and 2 Stop Bits
And Stop Bits: No Parity and 1 Stop Bit
Even Parity and 1 Stop Bit
Odd Parity and 1 Stop Bit.
User Option of Baud 1200,2400,4800 ,9600

The baud rate, parity and stop bits must be selected to match the master’s settings.

3.3 MODBUS Protocol Message Timing (RTU Mode)


A MODBUS Protocol message has defined beginning and ending points. The receiving
devices recognizes the start of the message, reads the “Slave Address” to determine if they
are being addressed and knowing when the message is completed they can use the Error
Check bytes and parity bits to confirm the integrity of the message. If the Error Check or parity
fails then the message is discarded.
In RTU mode, messages starts with a silent interval of at least 3.5 character times.
The first byte of a message is then transmitted, the device address.
Master and slave devices monitor the network continuously, including during the ‘silent’
intervals. When the first byte (the address byte) is received, each device checks it to find out if
it is the addressed device. If the device determines that it is the one being addressed it records
the whole message and acts accordingly, if it is not being addressed it continues monitoring for
the next message.
Following the last transmitted byte, a silent interval of at least 3.5 character times marks the
end of the message. A new message can begin after this interval.
The entire message must be transmitted as a continuous stream. If a silent interval of more

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

than 1.5 character times occurs before completion of the message, the receiving device
flushes the incomplete message and assumes that the next byte will be the address byte of a
new message.
Similarly, if a new message begins earlier than 3.5 character times following a previous
message, the receiving device may consider it a continuation of the previous message. This
will result in an error, as the value in the final CRC field will not be valid for the combined
messages.

3.4 How Characters are Transmitted Serially


When messages are transmitted on standard MODBUS Protocol serial networks each byte is
sent in this order (left to right):
Transmit Character = Start Bit + Data Byte + Parity Bit + 1 Stop Bit (11 bits total):
Least Significant Bit (LSB) Most Significant Bit (MSB)

Start 1 2 3 4 5 6 7 8 Party Stop

Transmit Character = Start Bit + Data Byte + 2 Stop Bits (11 bits total):
Start 1 2 3 4 5 6 7 8 Stop Stop

Eastron Digital meters additionally support No parity, 1 stop bit.


Transmit Character = Start Bit + Data Byte + 1 Stop Bit (10 bits total):
Start 1 2 3 4 5 6 7 8 Stop

The master is configured by the user to wait for a predetermined timeout interval. The master
will wait for this period of time before deciding that the slave is not going to respond and that
the transaction should be aborted. Care must be taken when determining the timeout period
from both the master and the slaves’ specifications. The slave may define the ‘response time’
as being the period from the receipt of the last bit of the query to the transmission of the first bit
of the response. The master may define the ‘response time’ as period between transmitting the
first bit of the query to the receipt of the last bit of the response. It can be seen that message
transmission time, which is a function of the baud rate, must be included in the timeout
calculation.

3.5 Error Checking Methods

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Standard MODBUS Protocol serial networks use two error checking processes, the error
check bytes mentioned above check message integrity whilst Parity checking (even or odd)
can be applied to each byte in the message.

3.5.1 Parity Checking


If parity checking is enabled – by selecting either Even or Odd Parity - the quantity of “1’s” will
be counted in the data portion of each transmit character. The parity bit will then be set to a 0
or 1 to result in an Even or Odd total of “1’s”.
Note that parity checking can only detect an error if an odd number of bits are picked up or
dropped in a transmit character during transmission, if for example two 1’s are corrupted to 0’s
the parity check will not find the error.
If No Parity checking is specified, no parity bit is transmitted and no parity check can be made.
Also, if No Parity checking is specified and one stop bit is selected the transmit character is
effectively shortened by one bit.

3.5.2 CRC Checking


The error check bytes of the MODBUS Protocol messages contain a Cyclical Redundancy
Check (CRC) value that is used to check the content of the entire message. The error check
bytes must always be present to comply with the MODBUS Protocol, there is no option to
disable it.
The error check bytes represent a 16-bit binary value, calculated by the transmitting device.
The receiving device must recalculate the CRC during receipt of the message and compare
the calculated value to the value received in the error check bytes. If the two values are not
equal, the message should be discarded.
The error check calculation is started by first pre-loading a 16-bit register to all 1’s (i.e. Hex
(FFFF)) each successive 8-bit byte of the message is applied to the current contents of the
register. Note: only the eight bits of data in each transmit character are used for generating the
CRC, start bits, stop bits and the parity bit, if one is used, are not included in the error check
bytes.
During generation of the error check bytes, each 8-bit message byte is exclusive OR'ed with
the lower half of the 16 bit register. The register is then shifted eight times in the direction of
the least significant bit (LSB), with a zero filled into the most significant bit (MSB) position. After
each shift the LSB prior to the shift is extracted and examined. If the LSB was a 1, the register
is then exclusive OR'ed with a pre-set, fixed value. If the LSB was a 0, no exclusive OR takes
place.
This process is repeated until all eight shifts have been performed. After the last shift, the next
8-bit message byte is exclusive OR'ed with the lower half of the 16 bit register, and the process
repeated. The final contents of the register, after all the bytes of the message have been
applied, is the error check value. In the following pseudo code “Error Word” is a 16-bit value
representing the error check values.

BEGIN

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Error Word = Hex (FFFF)


FOR Each byte in message
Error Word = Error Word XOR byte in message
FOR Each bit in byte
LSB = Error Word AND Hex (0001)
IF LSB = 1 THEN Error Word = Error Word – 1
Error Word = Error Word / 2
IF LSB = 1 THEN Error Word = Error Word XOR Hex (A001)
NEXT bit in byte
NEXT Byte in message
END

3.6 Function Codes


The function code part of a MODBUS Protocol message defines the action to be taken by the
slave. Eastron Digital meters support the following function codes:
MODBUS Protocol
Code Description
name
Read Holding Read the contents of read/write
03
Registers location(4X references)
Read the contents of read only
04 Read Input Registers
location(3X references)

3.7 IEEE floating point format


The MODBUS Protocol defines 16 bit “Registers” for the data variables. A 16-bit number would
prove too restrictive, for energy parameters for example, as the maximum range of a 16-bit
number is 65535.
However, there are a number of approaches that have been adopted to overcome this
restriction. Eastron Digital meters use two consecutive registers to represent a floating-point
number, effectively expanding the range to +/- 1x1037.
The values produced by Eastron Digital meters can be used directly without any requirement
to “scale” the values, for example, the units for the voltage parameters are volts, the units for
the power parameters are watts etc.
What is a floating point Number?
A floating-point number is a number with two parts, a mantissa and an exponent and is written
in the form 1.234 x 105. The mantissa (1.234 in this example) must have the decimal point
moved to the right with the number of places determined by the exponent (5 places in this
example) i.e. 1.234x 105 = 123400. If the exponent is negative the decimal point is moved to
the left.
What is an IEEE 754 format floating-point number?
An IEEE 754 floating point number is the binary equivalent of the decimal floating-point
number shown above. The major difference being that the most significant bit of the mantissa
is always arranged to be 1 and is thus not needed in the representation of the number. The

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

process by which the most significant bit is arranged to be 1 is called normalization, the
mantissa is thus referred to as a “normal mantissa”. During normalization the bits in the
mantissa are shifted to the left whilst the exponent is decremented until the most significant bit
of the mantissa is one. In the special case where the number is zero both mantissa and
exponent are zero.

The bits in an IEEE 754 format have the following significance:


Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte. Lo Byte. Hi Byte. Lo Byte.
SEEE EMMM MMMM MMMM
EEEE MMMM MMMM MMMM

Where:
S represents the sign bit where 1 is negative and 0 is positive
E is the 8-bit exponent with an offset of 127 i.e. an exponent of zero is represented by 127, an
exponent of 1 by 128 etc.
M is the 23-bit normal mantissa. The 24th bit is always 1 and, therefore, is not stored.

Using the above format the floating point number 240.5 is represented as 43708000 hex:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte
43 70 80 00

The following example demonstrates how to convert IEEE 754 floating-point numbers from
their hexadecimal form to decimal form. For this example, we will use the value for 240.5
shown above
Note that the floating-point storage representation is not an intuitive format. To convert this
value to decimal, the bits should be separated as specified in the floating-point number storage
format table shown above.

For example:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte
0100 0011 0111 0000 1000 0000 0000 0000

From this you can determine the following information.


·The sign bit is 0, indicating a positive number.
·The exponent value is 10000110 binary or 134 decimal. Subtracting 127 from 134 leaves 7,
which is the actual exponent.
·The mantissa appears as the binary number 11100001000000000000000
There is an implied binary point at the left of the mantissa that is always preceded by a 1. This
bit is not stored in the hexadecimal representation of the floating-point number. Adding 1 and

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

the binary point to the beginning of the mantissa gives the following:
1.11100001000000000000000
Now, we adjust the mantissa for the exponent. A negative exponent moves the binary point to
the left. A positive exponent moves the binary point to the right. Because the exponent is 7, the
mantissa is adjusted as follows:
11110000.1000000000000000
Finally, we have a binary floating-point number. Binary bits that are to the left of the binary
point represent
the power of two corresponding to their position. For example, 11110000 represents (1 x 2 7) +
(1 x 26) + (1x 25) + (1 x 24) + (0 x 23)+ (0 x 22) + (0 x 21)+ (0 x 20) = 240.
Binary bits that are to the right of the binary point also represent a power of 2 corresponding to
their position. As the digits are to the right of the binary point the powers are negative. For
example: .100 represents (1 x 2-1) + (0 x 2-2)+ (0 x 2-3) + … which equals 0.5.
Adding these two numbers together and making reference to the sign bit produces the number
+240.5.

For each floating point value requested two MODBUS Protocol registers (four bytes) must be
requested. The received order and significance of these four bytes for Eastron Digital meters is
shown below:
Data Hi Reg, Data Hi Reg, Data Lo Reg, Data Lo Reg,
Hi Byte Lo Byte Hi Byte Lo Byte

3.8 MODBUS Protocol Commands supported


All Eastron Digital meters support the “Read Input Register” (3X registers), the “Read Holding
Register” (4X registers) and the “Pre-set Multiple Registers” (write 4X registers) commands of
the MODBUS Protocol RTU protocol. All values stored and returned are in floating point format
to IEEE 754 with the most significant register first.

3.8.1 Read Input Registers


MODBUS Protocol code 04 reads the contents of the 3X registers.

Example
The following query will request ‘Volts 1’ from an instrument with node address 1:
Field Name Example(Hex)
Slave Address 01
Function 04
Starting Address High 00
Starting Address Low 00
Number of Points High 00
Number of Points Low 02
Error Check Low 71
Error Check High CB

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to request a floating point variable. If the “Starting Address” or
the “Number of points” is odd then the query will fall in the middle of a floating point variable
the product will return an error message.
The following response returns the contents of Volts 1 as 230.2. But see also “Exception
Response” later.
Field Name Example (Hex)
Slave Address 01
Function 04
Byte Count 04
Data, High Reg, High Byte 43
Data, High Reg, Low Byte 66
Data, Low Reg, High Byte 33
Data, Low Reg, Low Byte 34
Error Check Low 1B
Error Check High 38

3.9 Holding Registers


3.9.1 Read Holding Registers
MODBUS Protocol code 03 reads the contents of the 4X registers.
Example
The following query will request the prevailing ‘Pulse output 1 Width’:
Field Name Example (Hex)
Slave Address 01
Function 03
Starting Address High 00
Starting Address Low 0C
Number of Points High 00
Number of Points Low 02
Error Check Low 04
Error Check High 08
Note: Data must be requested in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to request a floating point variable. If the “Starting Address” or
the “Number of points” is odd then the query will fall in the middle of a floating point variable
the product will return an error message.

The following response returns the contents of Demand Time as 1, But see also “Exception
Response” later.
Field Name Example (Hex)
Slave Address 01
Function 03
Byte Count 04
%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Data, High Reg, High Byte 42


Data, High Reg, Low Byte C8
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error Check Low 6F
Error Check High B5

3.9.2 Write Holding Registers


MODBUS Protocol code 10 (16 decimal) writes the contents of the 4X registers.
Example
The following query will set the Pulse output 1 Width to 60 ms, which effectively resets the
Demand Time:
Field Name Example (Hex)
Slave Address 01
Function 10
Starting Address High 00
Starting Address Low 0C
Number of Registers High 00
Number of Registers Low 02
Byte Count 04
Data, High Reg, High Byte 42
Data, High Reg, Low Byte 70
Data, Low Reg, High Byte 00
Data, Low Reg, Low Byte 00
Error Check Low E6
Error Check High 59

Note: Data must be written in register pairs i.e. the “Starting Address“ and the “Number of
Points” must be even numbers to write a floating point variable. If the “Starting Address” or the
“Number of points” is odd then the query will fall in the middle of a floating point variable the
product will return an error message. In general only one floating point value can be written per
query

The following response indicates that the write has been successful. But see also “Exception
Response”later.
Field Name Example (Hex)
Slave Address 01
Function 10
Starting Address High 00
Starting Address Low 02
Number of Registers High 00

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH
Eastron SDM230Modbus Protocol V1.2

Number of Registers Low 02


Error Check Low E0
Error Check High 08

%*HWHFK*PE+)U0HKULQJ6WU'(/DXFKKDPPHU
7HO)D[
0DLOLQIR#EJHWHFKGH:HEZZZHDVWURQJHUPDQ\GH

You might also like