Unica Sensor 10 KW
Unica Sensor 10 KW
Moderator
UNICA SENSOR 10 ÷ 60kW Boilers
Operating Instructions
TABLE OF CONTENTS
2
Dear User,
1. Overview
The main condition of safe boiler operation is its correct connection to the
central heating installation. The manufacturer has undertaken all efforts to
ensure safe operation of the device. This will only be possible after all
connection and operation requirements discussed in these instructions are met
and complied with. Failure to perform any action, due to involved costs of
additional equipment installation will certainly affect the safety or cause the
equipment operating costs to raise in future.
All performance tests and trials of boilers have been performed using
carefully selected accessories (safety valves, thermal protections) and equipment
(air supply systems). In order to guarantee maintenance of declared high
performance of the boiler, manufacturer-recommended equipment must be used
exclusively.
We would like to hereby advise against using substitute solutions,
which have not been checked with that boiler and which do not have required
approvals (Technical Supervision Office - UDT) and certificates (declaration
of conformity, CE sign). We also advise against any unauthorized changes in
the boiler design.
Failure to follow these recommendations may lead to serious threats and
expose the operating personnel to health or life hazard.
3
In case of doubt, please consult our sales department or authorized
servicing agent.
Note: The washout located under the masking cover may be hot.
Pay special attention in the boiler room, as other parts of the boiler
and the installation may also be hot..
Keep in mind that in the boiler room various surfaces may have
different temperatures. You have to pay special attention to the fact,
that temperature of doors may be significantly higher than the
temperature of other boiler surfaces. This also applies to the smoke
breeching and supply and return piping. When in boiler room, always
pay special attention.
Keep in mind that ashes and fuel (in particular dry sawdust and
chips) may cause allergic reactions. We recommend wearing
protective gloves and dust masks.
Keep the boiler room clean. Fuel left or spilled on the floor may
cause a fire.
4
1.2. Warranty Terms and Conditions
1. Manufacturer grants 36-month warranty for the unit, which covers all
workmanship and material faults.
2. Manufacturer warrants fault-free operation of the central heating, which is
further attested by the production plant’s seal.
3. Manufacturer requires the guidelines below to be followed:
• the first starting of the unit shall be performed by the manufacture’s
technical support representative
4. The warranty shall not include damages resulting from misuse or normal
wear and tear, refund of assembly costs, travel costs, damages resulting
from modifications or repairs implemented or performed without
manufacturer’s consent, indirect and consequential damages, production
outage related losses or any other economic loses co caused.
5. The warranty shall not include faults resulting from:
• failure to follow assembly guidelines stated in these operating
instructions or resulting from regulations currently in force,
• incorrect servicing or maintenance or effects of boiler operation in a
way, which is incompatible with its operating instructions’ provisions
(use of incorrect fuel, leaving ash after the heating season, faults
resulting from central heating installation freezing, incorrect or blocked
flue system, loss of water in the installation)
• utilization of the boiler for purposes other than its intended use, as
specified in the operating instructions
• in case of incorrect selection of the boiler output to the object’s heat
demand
6. All warranty claims must always be sent to the boiler seller. Before
submitting a claim, please make ready the following details:
• photocopy of page 5 of the operating instructions, item 1.2. (with
entered date and legible signature of the user)
• description of the fault
• a document to prove the equipment purchase
• boiler rated power
• serial number
7. User statement:
I hereby declare to have acknowledged myself with the Moderator boiler operating instructions and I hereby confirm
that the equipment was delivered as ordered, new, complete and technically operational. Above that a specialized
company presented to me principles of the equipment operation and provided a complete set of documentation. I
hereby accept the Moderator boiler manufacturer’s recommendations. In case of an unjustified service request to the
Moderator company under a warranty repair, I undertake to bear all related costs (man hours and costs of shipping to
and from the service centre) up to their full amount.
5
Declaration of Conformity
We,
Moderator Spółka z o.o.
Ul. 11 Listopada 16a
17-200 Hajnówka, POLAND
tel. +48 (0)85 682 75 20
hereby declare under our own and sole responsibility that the product: MODERATOR
central-heating boiler, serial nos. from 400, to which this declaration applies, meets the
following requirements and standards, as applicable:
Directives Standards
97/23/WE EN-PN- 303-5
Hajnówka, on 2004.02.01
1.3. Fuel
6
1.3.1. Burning Other Fuels
Uncontaminated paper and cardboard may only be used for igniting fire in
the boiler. Mixtures of various clean paper and cardboard may only be burned
with wood. Papers and magazines must not be burned and should be recycled.
One shall keep in mind that impregnates, inks and other components used for
their production will significantly pollute the natural environment.
We also advise against burning plastics in various forms. Keep in mind
that smoke generated during combustion of plastics will contain substances,
which are poisonous and harmful to human and that these substances will fall
down in direct vicinity of the chimney. Do not burn PVC products under any
circumstances, e.g.:
- butter or margarine boxes
- transparent plastic bottles
- jewel boxes (cassettes/CDs) or toys
- plastic building materials
- polyamide (PA) products, such as textiles
Some plastics identified as PE, PP, PET may be burned, provided that
their volume does not exceed 5% of the fuel volume (e.g. of wood) and the
combustion temperature is not lower than 850o C.
7
doors) equipped with mechanical air supply throttle (used in case of a power
outage or in versions without an air supply system).
Boilers are equipped with directional air supply to the combustion
chamber with autogenous primary and secondary air distribution. On its way to
the combustion chamber air is heated. This significantly contributes to correct
burning process.
1.5. Equipment
2. Installation
8
8 12 13
9
6
4 5 11 7 10
1. Charging flap
2. Grate doors
3. Ash-pan doors
4. Air throttle
5. Mobile grate lever
6. Fan
7. Return pipe
8. Top washout cover (20 and 25kW boilers)
9. Supply pipe
10. Ash pan washout cover
11. Straight-through valve G½ muff
12. Tech ST-81 controller (10 to 30kW boilers)
13. G½ muff
9
8 12 9
13
6
4 5 11 7 10
1. Charging flap
2. Grate doors
3. Ash-pan doors
4. Air throttle
5. Mobile grate lever
6. Fan
7. Return pipe
8. Top washout cover (20 to 60kW boilers)
9. Supply pipe
10. Ash pan washout cover
11. Thermometer
12. ecoMAX 200 controller (40 to 60kW boilers)
13. G½ muff
10
2.2. Boiler Room
11
steel ones) shall be insulated over the whole height with at least 5-cm mineral
wool layer.
When installing the smoke breeching in the chimney, one shall pay
attention to the chimney damper lever (it is necessary to provide a space needed
for its easy opening and closing).
up to 15 18 x 18 14 x 27 18 6÷8
20 ÷ 32 20 x 20 14 x 27 24 8 ÷ 10
40 ÷ 50 25 x 25 - 28 8 ÷ 10
60 ÷ 150 30 x 30 - 35 8 ÷ 10
If the boiler is fitted with a thermal safety valve, the valve’s sensor
shall be installed in the dedicated G½ muff (item 13 on fig.1a,b), then
install the safety valve.
12
In order to ensure correct operation of the boiler, manufacturer
recommends installation of a four-way mixing valve or a heat accumulation
tank. (Fig. 2)
Connect water supply pipe through the G½ valve (11, fig. 1a) using a
flexible hose, which after filling is completed shall be disconnected. When
filling open all venting valves in the installation and slowly close them until
water overflows in the overflow pipe of the expansion vessel (in case of open
systems). Lossless installations may be supplied with raw water, as long as its
hardness is less than 10 n. Otherwise the water shall be pre-treated.
Install boiler accessories (handles and bakelite knobs ).
13
2. Before commencing with assembly, repair or maintenance works and when
performing all connections, it is necessary to disconnect power supply from
the device and verify that power lines are disconnected from mains.
3. Boiler house shall be equipped with 230V/50Hz electric installation,
compatible with relevant regulations applicable in this scope.
4. The electric installation (regardless of its type) shall be terminated with a
power receptacle equipped with a protective earth terminal. Use of power
receptacles without properly wired protective earth terminal will
constitute electric shock hazard!!!
5. The boiler shall be connected to a separately installed power supply line,
protected with suitably chosen fast-blow fuse and differential-current circuit
breaker (shock protection). The value and the type of the fuse is defined in
the controller’s operational documentation. No other equipment must be
connected to this line.
6. The box, in which electric accessories are contained, may only be opened by a
competent electric engineer, knowledgeable with the equipment operation.
7. Location of the power receptacle used for the boiler connection shall be
selected in such a way so that the plug is easily accessible to allow quick
boiler disconnection in case of an emergency.
8. Wires shall be routed away from the parts of the boiler that may get hot, and
in particular away from hot elements of the flue breeching.
9. The controller must not be exposed to flooding or to conditions causing
vapour condensation, e.g. rapid ambient temperature changes.
10.The controller must not be operated if its enclosure is damaged.
11.Protect the controller against access of children.
12.During thunderstorms, the controller shall be disconnected from mains.
14
A B C
A. Blower
B. Connecting cable
C. Tech ST-81 controller
15
Connecting domestic hot water pump
The pump used to charge the household hot water tank shall be 2 connected
to the socket (Fig. 4.) identified as “Pompa cwu”, using a cable with cross-
section of at least 3x0.75mm2 using suitable socket (included). The household
hot water tank’s temp. sensor 3 shall be connected to the socket located
above the power supply socket.
1 3 4 5
16
2.6.2 Boilers rated 40 to 60 kW
Unica SENSOR boilers rated 40 - 60 kW have preinstalled air supply system,
which consists of the following elements: A B C (see fig. 5)..
A B C
A. Dmuchawa
B. Przewód łączący
C. Sterownik z regulatorem ecoMAX 200
Other parts used to connect power supply and pumps driven by the controller
are located in the box attached to the boiler.
1 2 3 4 5 6
Fig.6. Controller sockets – rear view.
Fig. 6 shows the real panel of the controller, where the following sockets are
located:
1. Local thermostat
2. Hot household water temperature sensor
3. Hot household water pump
17
4. Central heating pump
5. Air blower
6. Power supply socket
18
2.7. Protection of the Installation
Installation requirements:
• pressure vessel with the volume of at least 4% of the total water
charge
shape: cylindrical, type A. acc. to PN-91/B-02413-1-2
rectangular, type B, acc. to PN-91/B-02413-1-3
• safety riser tube (RB) with inner diameter of:
25 mm for boilers rated up to 25 kW, inclusively
19
32 mm for boilers rated 40 to 60 kW
• riser pipe (RW) with inner diameter of 25 mm
• overflow pipe RP
inner diameters as RW and RB
• circulation pipe (RC) with inner diameter of 20 mm
• venting pipe (RO) and signalling pipe (RS) with inner diameters of
15 mm.
No fittings permitting complete or partial closure of flow may be
installed on RB, RW and RO pipes. The protective equipment and
pipes shall be protected against freezing.
5 5 5
4 3 1 2 4 2 1 3 1 2 4 3
a) 10 to 15kW b) 20 to 30kW c) 40 to 60kW
1. Supply muff (G1½ 10 to 30kW, G2 40 to 60kW)
2. Safety valve stub pipe (G½ 10 to 15kW, G¾ 20 to 60kW)
3. G½ thermometer stub pipe (in 40 to 60kW boilers must be plugged)
4. The G½ muff of the thermal protection (SYR type)
5. Washout cover
Fig. 8. Placement of muffs and stub pipes on the upper panel of Unica Sensor
boilers.
20
KOMIN – CHIMNEY ZAWÓR BEZPIECZEŃSTWA - SAFETY VALVE
CZUJNIK ZAWORU TERMICZNEGO – THERMAL PROTECTION VALVE SENSOR
CZUJNIK TEMPERATURY - TEMPERATURE SENSOR KOCIOŁ - BOILER
STEROWNIK – CONTROLLER WENTYLATOR – BLOWER
ZAWÓR SPUSTOWY – DRAINAGE VALVE ZABEZPIECZENIE TERMICZNE – THERMAL PROTECTION
ZAWÓR MIESZAJĄCY– MIXING VALVE ZBIORNIK AKUMULACYJNY – HEAT ACCUMULATION TANK
WĘŻOWNICA - COIL INSTALACJA GRZEWCZA – HEATING INSTALLATION
ZASILANIE Z SIECI - WATER PIPE SUPPLY ODPROWADZENIE WODY – WATER DRAINAGE
Fig.9. Installation protection for boilers operated in closed central heating systems
21
Boiler installation without a reliable device to discharge the excessive
thermal power is forbidden.
THERMAL PROTECTION
Applications:
5067 thermal protection is designed to protect solid fuel boilers in heating installations fitted with thermostatic valves conforming to the PN-EN303-5
Polish Standard. It is particularly recommended for boilers, which are not equipped with cooling exchanger. Figure 1 presents installation principle, at a
close distance from the boiler, with special consideration for such guiding and sizing of pipes so that no pressure losses occur.
Installation and operating principle: The 5067 thermal protection valve consists of the following elements: non-return valve (1), pressure reducer (2),
thermally-controlled filling valve (3) and ejection valve (4), pressure sensor with a capillary tube(5).
The pressure reduction valve (2) is connected to the water pipe network. The output of the thermally-controlled filling valve (3) is connected to boiler’s
return line. The supply line to the input of thermally controlled ejection valve (4), which output side leads to the outlet. The pressure sensor is installed
in the warmest part, optimally in the upper part of the boiler. The pressure reduction valve is firmly set to 1.2 bar, thus the operating pressure in the
heating device shall be by 0.2 to 0.3 bar higher. This prevents opening of the safety valve in the installation. It is recommended to use a safety valve
with settings of at least 2 bars.
If the preset opening temperature of ca. 90OC is exceeded, the filling valve (3) starts to open. In order to maintain stable pressure in the heating
installation, the ejection valve opens at 97OC. After the ejection valve opens, hot water flows out of the installation and cold water may flow in from the
supply line, this cools down the boiler. When boiler temperature drops to 94OC, the ejection valve closes. Thermally controlled filling valve and
temperature sensor help to restore the correct flow pressure in the heating installation.
When the temperature reaches 88°C, also the filling valve closes.
Build:
The thermal protecting device is controlled by two independent valves: the filling valve and the ejection valve. The body of the device is a die stamped
brass element whilst other parts that contact water are made of stainless steel and temperature resistant plastic. All sealing elements are made of resilient
and high-temperature resistant, heavy duty elastomeric rubber material. Springs are made of stainless spring steel. The sensor and capillary tube are
made of copper, whereas the sleeve is additionally nickel-plated.
Valve opening is controlled by doubled temperature sensor. The fittings are self-venting. Elements of the valve, the valve seat and seal may be removed
and cleaned without any change to pre-set opening temperature. Compact head of the temperature sensor may be conveniently disassembled during the
valve body installation. The capillary tube from the sensor to actuator is protected by a special, metal flexible hose.
22
3. Boiler operation
1 2 3 4
23
3.1.2. Boilers rated 40 to 60 kW
24
Periodical maintenance notes
3.2. Igniting
Ignition of a cold boiler may only be started after prior checking that the
slot is correctly filled with water.
Open ash pan doors (or open the throttle on ash pan doors). Ignite using
dry wood for about 1.5 hours, gradually reaching the temperature of 80OC. We
recommend to perform first ignition without using the air supply system,
adjusting the air supply by opening and closing ash pan doors (or the throttle),
remembering to switch on the pump after the temperature exceeds 40OC (during
further operation, when using the air supply system, the pump coupled with the
controller will start automatically). NOTE! For 3 to 4 days, it is recommended to
maintain continuous (non-stop) burning in the boiler with the supply water at 70
to 80O C. Further ignitions may be performed by programming boiler operation
on the electronic controller, according to principles described in the controller
instructions. When igniting, do not fill the whole combustion chamber (for wood
- 50% fill rate, for coal - maximum 20% fill rate).
3.3. Burning
25
Note: avoid burning fine fuels, in which dusts concentration exceeds 5%.
Pay attention when burning very dry sawdust (moisture content up to 15%),
do not compact them tightly in the combustion chamber. Having charged
sawdust, leave free space in the rear part of the chamber to ensure air
access. Failure to meet these requirements may result with gases from
combustion chamber backdrafting during sudden opening of the charging
flap. (When the charging flap is opened, this may cause sudden growth of
the air volume in the combustion chamber and explosive combustion of
dusts.). When operating a boiler with air supply system, do not open the
charging flap while the fan is operating. Before supplementing the fuel,
switch off the controller.
! Always make sure that back drafting is not caused by closed flue damper
or use of elbows or connectors making flue gases difficult to leave the boiler.
26
of surfaces, these washouts may be opened and cleaning may be performed only
after the boiler has been shut down.
27
the air blower and remove deposit that may accumulate on duct’s horizontal
connector.
After the fuel burns out, open all doors and maximally open the damper in
the smoke conduit. Remove ash, clean the boiler. Do not drain the circulating
water. Cool down time is equal to the ignition time.
28
4. Boiler Troubleshooting
29
• wear protective gloves and goggles
• do not block charging flaps and ash pan doors
• perform grate readjustment using the ash pan lever
• use portable 24V lamps
• maintain order and cleanness in the boiler room
• maintain good technical condition of the boiler and its related
installation
• during the winter season ensure that the heating process is
continuous
It is forbidden to:
- spill water onto the grate
- ignite the boiler using flammable liquids
After the end of the heating season (April to September), pay special
attention when using the boiler for heating the household hot water
only. Boiler power will be too high relative to the absorption capacity
of the boiler, therefore it will be necessary to charge less fuel than
during normal burning in winter season and to monitor the
thermometer.
Each Moderator boiler has a stub pipe for safety valve installation. The
valve must be unconditionally installed. Additionally the manufacturer
recommends installation of a thermal protection (in case of a closed-loop
system, see section 2.7.2, this is mandatory), to protect the boiler against
pressure build-up. Keep in mind that the thermal protection may only operate,
when the pressure in the installation is equal or greater than 2.3 bar and a safety
valve is installed.
30
6. Disposal
Assuming correct operation, the boiler shall operate without problems for
about 15 years. After that time its further operation may be economically
unjustified. The boiler is made of materials, which are fully recyclable. Its steel
parts shall be scrapped. Electrical components shall be provided for disposal to a
specialist company.
1. If you choose to install the automatic biomass feeder in future, as of now the
hole must be plugged. To plug the hole a plug must be used, which is mounted
directly on the boiler. The plug is made of special fire-proof materials and is
additionally protected by a steel screen. However keep in mind that the plug is a
temporary solution, until the feeder is installed. This means that in result of
intensive burning, the plug may deform. If the automatic feeder is fitted, it is not
needed to plug the hole.
Burning fuels without properly plugging the hole may cause a fire!
2. If a feeder with ceramic head is connected, slide in the head breeching fitting
matching it to the frame in the boiler, install a seal, level using head feet, secure
head alignment using bolts and then screw together the frame. Before seating,
the inner gap between the breeching and the frame shall be sealed with a fire-
resistant rope or a fire-resistant mortar (fire resistance up to 1200 degrees
Celsius). The fuel container must be levelled.
3. If a feeder with cast iron head is connected, the head hearth must be slid into
the hole in the boiler until resistance is felt, so that the hearth cover loosely
slides onto positioning hooks (the cover is installed through the charging flap,
through the top side). Screw on the head to the frame from the outside using
enclosed screws. The fuel container must be levelled.
31
7.2. Boilers intended for pellets burners
32
8. Boiler specifications
33