DIMS New 1
DIMS New 1
User Manual
Configuration Tool
CONTENTS
1. ELECTRICAL CONNECTIONS 1
2. PARAMETERS 4
3. MECHANICAL DIMENSIONS 10
Section 1
ELECTRICAL CONNECTIONS
WARNING
MISHANDLING / NEGLIGENCE CAN RESULT
IN PERSONAL DEATH OR SERIOUS INJURY.
2. Do not make any connections to the unused terminals for making a tie-point for other wires (or for any other reasons) as
they may have some internal connections. Failing to observe this may result in permanent damage to the indicator.
3. Run power supply cables separated from the low-level signal cables (like RTD, Thermocouples, DC Linear Current /
Voltage etc.). If the cables are run through conduits, use separate conduits for power supply cable and low-level signal
cables.
4. Use appropriate fuses and switches, wherever necessary, for driving the high voltage loads to protect the module from any
possible damage due to high voltage surges of extended duration or short-circuits on loads.
5. Take care not to over-tighten the terminal screws while making connections.
6. Make sure that the module supply is switched-off while making/removing any connections.
CONNECTION DIAGRAM
The Figure 1.1 illustrates Electrical Connection Diagrams. For 8 Channel Version, the connectors from 24 to 41are not fitted.
38 39 40 41 34 35 36 37 30 31 32 33 26 27 28 29 24 25 22 23
D W D W D W D W D W D W D W D W
Com
+12V
24 VDC Supply
+12V
Com
Each of the 8 or 16 input channels are identical from wiring connection viewpoint. The descriptions below apply to all the
channels with no deviations. Refer Figures 1.2 (a) to 1.2 (f) below for different Input Types.
D W
5 to 30
VDC
+
Com - Com
Module Module
Com
Com
GND
GND
Sensor Module Sensor Module
Com
Com
GND
GND
Sensor Module Sensor Module
Figure 1.3
Functional Ground 19
+ + 20
DC Power Flyback
Source Design
- - 21
2 Pole
Isolating Switch
As standard, the Module is supplied with power connections suited for 18 to 32 VDC power source. The accuracy /
performance of the Module is not affected by the variations in the supply within specified limits of 18 to 32 VDC. Use well-
insulated copper conductor wire of the size not smaller than 0.5mm² for power supply connections ensuring proper polarity as
shown in Figure 1.3. The Module is not provided with power switch. If necessary, mount separately.
For safety and enhanced electrical noise immunity, it is highly recommended to connect Main Power Supply ‘Earth’
to terminal 19.
The wiring connections for interfacing the Host (PC/HMI) with DIMS is shown in the figure 1.4.
For reliable noise free communication, use a pair of twisted wires inside screened cable. The wire should have less than 100
ohms / km nominal DC resistance (Typically 24 AWG or thicker). Connect the terminating resistor (Typically 100 to 150 ohm) at
one end to improve noise immunity.
Figure 1.4
DIMS-8/16
Terminating Resistor
Module
(100 to 150 Ohms) Host (PC/HMI)
RS485 Port Twisted
Wire Pair
22 (B+)
RS485
Port
23 (B-)
Serial Comm. Terminals
Screened Cable
Note
In case of non-availability of RS485 port on Host PC, use appropriate Serial Protocol Converter to match the available serial
port on the host like “USB to RS485” and “RS232 to RS485” (Refer few images below). Please ensure that the appropriate
Device Driver for the selected converter is installed on the Host PC.
Section 2
PARAMETERS
The communication parameter settings and the data packet format have been discussed in Section 4 : Configuring
Communication Parameters.
For user convenience, most parameters are accessible both as Bit-Mapped Modbus Registers & Discrete Input Coils.
Table 2.1
Run Time Parameter (Read Only)
DI-8 Status
DI-16 Status
Table 2.2
DI-8 Low-to-High
Latched Status
DI-16 Low-to-High
Latched Status
Table 2.3
DI-8 Low-to-High
Acknowledge
DI-16 Low-to-High
Acknowledge
Table 2.4
DI-8 High-to-Low
Latched Status
DI-16 High-to-Low
Latched Status
Table 2.5
DI-8 High-to-Low
Acknowledge
DI-16 High-to-Low
Acknowledge
4. Digital Filter
This parameter helps remove any unwarranted signal noise on PNP / NPN Sensor Inputs or mechanical de-bounce on Dry /
Wet Contact Closure Inputs. As illustrated in Figure 2.1 (a) & 2.1 (b) any state change (transition) is accepted only if the
changed state is held constant for the time period (in milli-Second) set for the Digital Filter parameter.
High (Close)
State
State Change
Change
Accepted
Ignored
Low (Open)
High (Close)
State
State Change
Change
Accepted
Ignored
Low (Open)
Table 2.6
Configuration Parameter (Stored in Non-Volatile memory)
Section 3
MECHANICAL DIMENSIONS
W
D
22.5 mm 119 mm
H
101 mm
The Serial Communication Port specification are shown in Table 4.1 below.
Table 4.1
The Module is shipped from the factory with the following default values for the Communication Parameters.
The above parameters can be altered to match with the Host (Master) parameters by putting the Module in Configuration
Mode. In Configuration Mode, the Module always communicates with the host with the fixed communication parameter
values (Slave ID : 1, Baud Rate : 9600 & Parity : None) regardless of the actual set values. The user set values are applicable
only when the Module is put back in the Normal Operation Mode.
A Slide Switch Set is provided on the Module, as shown in the Figure 4.1, to select between the Configuration and Normal
Operation modes. The Table 4.2 shows the Switch Positions and the respective mode.
It is important to note that the switch position is detected only upon power-up. Select the desired Mode while the
Module is OFF. That is changing the switch position while the Module is powered does not have any effect on the
Mode.
Figure 4.1
POWER
CPU ST
S
RX
COMM
TX
ALARM
1
9
2
10
3
11
4
12
5
13
6
14
7
15
8
16
CO
NFIG
Slide Switch Set ON
Table 4.2
ON ON
The Communication Parameters values can be altered by using the MODBUS RTU protocol while the Module is in
Configuration Mode. Set the host (Master) Baud Rate to “9600 bps” and Parity to “None”. The MODBUS Addresses and
Settings for the Module communication parameters are listed in the Table 4.3 below.
Table 4.3
MODBUS Settings
Parameter Description
Address (Default Value)
Module Slave ID 1
ProcessPrecisionInstruments(AnISO9001:2008Company)
101,DiamondIndustrialEstate,Navghar,VasaiRoad(E),Dist.Palghar-401210,Maharashtra,India
Sales:8208199048/8208141446Support:07498799226/08767395333
[email protected] www.ppiindia.net
Jun 2023