R230 Manual Macfarlane Generators
R230 Manual Macfarlane Generators
2006 / b
Armature
6-
T4
Field
iven to
to be g
s
ual i er 75 mm
h i s man e end us
T t h 110 0V E+ E-
140 mm
Slow-blow fuse
F1 250V 8 A
P1 Voltage
R 230
P2 Stability
R230
A.V.R.
Installation and maintenance
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
This manual concerns the alternator A.V.R. which you have just purchased.
SAFETY MEASURES
The various operations described in this Warning symbol for general danger to
manual are accompanied by recommen- personnel.
dations or symbols to alert the user to
potential risks of accidents. It is vital that
you understand and take notice of the
following warning symbols.
2
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
CONTENTS
1 - SUPPLY .............................................................................................................................4
1.1 - SHUNT excitation system............................................................................................4
All such operations performed on the A.V.R. should be undertaken by personnel trained
in the commissioning, servicing and maintenance of electrical and mechanical
components.
3
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
Varistor
Armature
5+ 6-
T4 T10 T5 T11 T6 T12
Field
75 mm
50 x 75 mm
Slow-blow fuse
F1 250V 8 A
P1 Voltage
R 230
P2 Stability
P3 Under-
speed
Frequency
ST4 Option ST3
Potentiometer for remote 50Hz
voltage adjustment 60Hz
4
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
2 - R230 A.V.R.
2.1 - Characteristics
- Voltage regulation: around ± 0.5%.
- Voltage supply/sensing range 85 to 139 V
(50/60 Hz)
- Rapid response time (500 ms) for a
transient voltage variation amplitude of ±
20%
- Voltage setting P1
- Stability setting P2.
5
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
3.2 - Settings
E+
0V
110
E-
The machine is tested and set at the
factory. When first used with no load, The exciter is switched off by disconnecting
make sure that the drive speed is the AVR power supply (1 wire - 0 or 110V).
correct and stable (see the nameplate). Contact rating : 16A - 250V alt.
After operational testing, replace all
access panels or covers. 3.2.2.2 - R230 field forcing
The only possible adjustments to the (400V - 10A) Diode
machine should be made on the AVR.
t - +
3.2.1 - R 230 settings (shunt system) Battery (B Volt)
E-
6
LEROY-SOMER Installation and maintenance 3973 en - 11.2006 / b
R230
A.V.R.
Voltage Run at no load and - Check the speed (or U/F bend set too
correct at no check the voltage high)
load and too between E+ and E- on - Faulty rotating diodes
low when on the AVR - Short-circuit in the main field. Check the
load (*) resistance
- Faulty exciter armature.
(*) Caution : For single-phase operation, check that the sensing wires coming from the AVR are correctly connected to
the operating terminals
Voltage Check the AVR, the The voltage does not return to the - Exciter winding open circuit
disappears surge suppressor, the rated value. - Faulty exciter armature
during rotating diodes, and - Faulty AVR
operation replace any defective - Main field open circuit or short-circuited
components