Ficha Tecnica Paquete Convertible Carrier 50VL-K
Ficha Tecnica Paquete Convertible Carrier 50VL-K
Product Data
Convertible Duct Configuration
Unit is designed for use in either downflow or horizontal applications.
Each unit is converted from horizontal to downflow and includes
horizontal duct covers. Downflow operation is provided in the field to
allow vertical ductwork connections. The basepan seals on the bottom
openings to ensure a positive seal in the vertical airflow mode.
Efficient operation high-efficiency design offers SEER2 (Seasonal
Energy Efficiency Ratios) of 13.4. (See page 3.)
Durable, Dependable Components
ECM motor is standard on all models.
Direct-drive PSC (Permanent Split Capacitor) condenser-fan
motors are designed to help reduce energy consumption and provide for
cooing operation down to 40°F (4.4°C) outdoor temperature.
Motormaster II low ambient kit is available as a field-installed
accessory.
Refrigerant system is designed to provide dependability. Liquid filter
driers are used to promote clean, unrestricted operation. Each unit leaves
Fig. 1 – Unit 50VL
A09033 the factory with a full refrigerant charge. Refrigerant service connections
make checking operating pressures easier.
Single-Packaged Products with Energy-Saving Features and Puron®
refrigerant. High Pressure Switch provide added reliability for the compressor.
• 13.4 SEER2 / 11.05 EER2 Indoor and outdoor coils are computer-designed for optimum heat
• ECM Motor-Standard transfer and efficiency. The indoor coil is fabricated from aluminum tube
and aluminum fins and is located inside the unit for protection against
• Low Sound Levels
damage. The outdoor coil is internally mounted on the top tier of the
• Louver Condenser Coil Guard-Standard
unit.
• Cabinet air leakage of 2.0% or less at .5 in. W.C. when tested in
Low sound ratings ensure a quiet indoor and outdoor environment with
accordance with ASHRAE standard 193. (Low leak FIOP models
sound ratings as low as 70.7 dBA. (See page 3.)
only.)
Easy to service cabinets provide easy 3 panel accessibility to
Features/Benefits serviceable components during maintenance and installation. The
One-piece cooling unit with optional electric heater, low sound levels, basepan with integrated drain pan provides easy ground level installation
easy installation, low maintenance, and dependable performance. with a mounting pad. A nesting feature ensures a positive basepan to
roof curb seal when the unit is roof mounted. A convenient 3/4-in.
Puron is Carrier’s unique refrigerant designed to be environmentally
(19.05 mm) wide perimeter flange makes frame mounting on a rooftop
balanced. Puron is a HFC refrigerant which does not contain chlorine
easy.
that can harm the ozone layer. Puron refrigerant is in service in millions
of systems proving highly reliable and is non-ozone depleting. Standard horizontal metal duct covers with insulation come with the
unit and cover the horizontal duct openings. These can be left in place if
Easy Installation
the units are converted to downflow.
Factory-assembled package is a compact, fully self-contained, electric
Cabinets are constructed of heavyduty, phosphated, zinc-coated
cooling unit that is prewired, pre-piped, and pre-charged for minimum
prepainted steel capable of withstanding 500 hours in salt spray. Interior
installation expense. These units are available in a variety of standard
surfaces of the evaporatocr/heat exchanger compartment are insulated
cooling sizes with voltage options to meet residential and light
with cleanable semi-rigid insulation board, which keeps the conditioned
commercial requirements. Units are lightweight and install easily on a
air from being affected by the outdoor ambient temperature and provides
rooftop or at ground level. The high tech composite base eliminates rust
improved indoor air quality. (Conforms to American Society of Heating,
problems associated with ground level applications.
Refrigeration and Air Conditioning Engineers No. 62P.) The sloped
Innovative Unit Base Design drain pan minimizes standing water in the drain. An external drain is
On the inside a high-tech composite material will not rust and provided.
incorporates a sloped drain pan which improves drainage and helps
inhibit mold, algae and bacterial growth. On the outside metal base rails
provide added stability as well as easier handling and rigging.
50VL-K: Product Data
Table of Contents
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Connection Wiring Schematic 208/230-1-60 . . . . . . . . . . . . . . . . . . 22
Model Number Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Ladder Wiring Schematic 208/230-1-60 . . . . . . . . . . . . . . . . . . . . . 23
AHRI* Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Connection Wiring Schematic 208/230-3-60 . . . . . . . . . . . . . . . . . 24
Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Ladder Wiring Schematic 208/230-3-60 . . . . . . . . . . . . . . . . . . . . . 25
Roof Curb Accessory - 24-60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Connection Wiring Schematic 460-3-60 . . . . . . . . . . . . . . . . . . . . . 26
Selection Procedure (with example) . . . . . . . . . . . . . . . . . . . . . . . . . 11 Ladder Wiring Schematic 460-3-60 . . . . . . . . . . . . . . . . . . . . . . . . . 27
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Controls. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Guide Specifications. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Application Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
SAP ORDERING NO. NOMINAL COOLING CAPACITY (Btuh) VOLTS-PHASE (60 HZ) APPROX SHIP WT (LB)
50VL-K24---3** 24,000 208/230-1 307
50VL-K30---3** 30,000 208/230-1 316
50VL-K36---3** 36,000 208/230-1 354
50VL-K36---5** 36,000 208/230-3 354
50VL-K36---6** 36,000 460-3 354
50VL-K42---3** 42,000 208/230-1 388
50VL-K42---5** 42,000 208/230-3 388
50VL-K42---5** 42,000 460-3 388
50VL-K48---3** 48,000 208/230-1 437
50VL-K48---5** 48,000 208/230-3 437
50VL-K48---6** 48,000 460-3 437
50VL-K60---3** 60,000 208/230-1 497
50VL-K60---5** 60,000 208/230-3 497
50VL-K60---6** 60,000 460-3 497
** LW = Low cabinet air leakage option available.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
50VL-K: Product Data
AHRI* Capacities
Cooling Capacities and Efficiencies
UNIT SIZE NOMINAL TONS STANDARD CFM COOLING CAPACITY EER2 SEER2
24 2 750 22800 11.05 13.4
30 2.5 950 28000 11.05 13.4
36 3 1150 33800 11.05 13.4
42 3.5 1350 39000 11.05 13.4
48 4 1600 47000 11.05 13.4
60 5 1750 56000 11.05 13.4
LEGEND
dB-Sound Levels (decibels)
db—Dry Bulb
SEER—Seasonal Energy Efficiency Ratio
wb—Wet Bulb
COP-Coefficient of Performance
* Air Conditioning, Heating & Refrigeration Institute.
**At “A” conditions-80°F (26.7°C) indoor db/67°F (19.4°C) indoor wb & 95°F (35°C) outdoor db.
† Rated in accordance with U.S. Government DOE Department of Energy) test procedures and/or AHRI Standards 210/240.
Notes:
1. Ratings are net values, reflecting the effects of circulating fan heat.
Ratings are based on:
Cooling Standard: 80°F (26.7°C) db, 67°F wb (19.4°C) indoor entering-air temperature and 95°F db (35°C) outdoor entering-air temperature.
2. Before purchasing this appliance, read important energy cost and efficiency information available from your retailer.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
50VL-K: Product Data
Physical Data-Unit
UNIT SIZE 24 30 36 42 48 60
NOMINAL CAPACITY (ton) 2 2-1/2 3 3-1/2 4 5
SHIPPING WEIGHT lb. 307 316 354 388 437 451
SHIPPING WEIGHT (kg) 139 143 161 176 198 205
COMPRESSORS Scroll
Quantity 1
REFRIGERANT (R-410A)
Quantity lb 6.4 6.0 5.75 6.0 9.0 10.75
Quantity (kg) 2.9 2.7 2.6 2.7 4.1 4.9
REFRIGERANT METERING DEVICE Orifice TXV
ORIFICE ID in./mm .059 / 1.5 .063 / 1.60 .070 / 1.78 .073 / 1.85 .080 / 2.03 N/A
OUTDOOR COIL
Rows...Fins/in. 1...21 1...21 1...21 1...21 1...21 2...21
Face Area (sq ft) 11.9 13.6 13.6 13.6 23.3 17.5
OUTDOOR FAN
Nominal Cfm 2500 3200 3500 3500 3500 3500
Diameter in. 24 24 26 26 26 26
Diameter (mm) 609.6 609.6 660.4 660.4 660.4 660.4
Motor Hp (Rpm) 1/12 (810) 1/5 (810) 1/5 (810) 1/5 (810) 1/5 (810) 1/5 (810)
INDOOR COIL
Rows...Fins/in. 3...17 3...17 2...17 3...17 3...17 3...17
Face Area (sq ft) 3.7 3.7 5.6 4.7 5.6 5.6
INDOOR BLOWER
Nominal Cooling Airflow (Cfm) 750 950 1150 1350 1600 1750
Size in. 10x10 10x10 11x10 11x10 11x10 11x10
Size (mm.) 254x254 254x254 279.4x254 279.4x254 279.4x254 279.4x254
Motor HP (RPM) 1/2 (1050) 1/2 (1050) 1/2(1000) 3/4 (1075) 1.0 (1075) 1.0 (1040)
HIGH-PRESSURE SWITCH 650 +/- 15
(psig) Cut-out Reset (Auto) 420 +/- 25
LOSS-OF-CHARGE / LOW-PRESSURE
N/A
SWITCH (psig) cut-out Reset (auto)
1 each 24x18x1 1 each 24x14 x1 1 each 24x18x1
RETURN-AIR FILTERS* † 2 each 20x12x1 (610x457x25) (610x356x25) (610x457x25)
Throwaway Size in. (508x305x25) 24x16x1 24x16x1 24x16x1
Throwaway Size (mm) (610x406x25) (610x406x25) (610x406x25)
*. Required filter sizes shown are based on the larger of the AHRI (Air Conditioning Heating and Refrigeration Institute) rated cooling airflow or the heating airflow velocity of 300 to 350
ft/minute for throwaway type or 450 ft/minute for high-capacity type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. W.C.
†. If using accessory filter rack refer to the filter rack installation instructions for correct filter sizes and quantity.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
50VL-K: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
50VL-K: Product Data
ACCESSORIES
PART NUMBER DESCRIPTION USED WITH
CPRFCURB011B00* Roof Curb, 14-in. High 24 - 30
CPRFCURB013B00 Roof Curb, 14-in. High 36 - 60
CPADCURB001A00† Adapter curb for use with NPRFCURB006A00 & NPRFCURB007A00 24 - 30
CPADCURB002A00† Adapter curb for use with NPRFCURB008A00 & NPRFCURB009A00 36 - 60
CPGSKTKIT001A00 Gasket Kit for existing roof curb with new base rail unit All
CPECOMZR007B00 Dedicated Vertical Economizer - Internal with solid state controller, gear driven, fully modulating damper, 24 - 30
CPECOMZR008A00 spring return actuator, up to 50% barometric relief, supply and dry bulb outdoor air sensors. Includes filter rack 42
CPECOMZR009A00 with 1” filters. 36, 48, 60
CPECOMZR010A00 Dedicated Horizontal Economizer - Internal with solid state controller, fully modulating damper, spring return 24 - 30
CPECOMZR011A00 actuator, supply and dry bulb outdoor air sensor, and low ambient compressor lockout switch included. 42
CPECOMZR012A00 Includes filter rack with 1-inch filters. 36, 48, 60
AXB078ENT‡ Outdoor Enthalpy Control ALL
CPMANDPR007A00 24 - 30
CPMANDPR008A00 Manual Outside Air Damper - (Includes filter rack and 1” filter, same as CPFILTRK kit) 42
CPMANDPR009A00 36, 48, 60
CPFILTRK007A00 24 - 30
CPFILTRK008A00 Internal Filter Rack 42
CPFILTRK009A00 36, 48, 60
CPCRKHTR008A00 24 - 36
240V Crankcase Heater
CPCRKHTR004A00 42 - 60
Low Ambient Control - enables cooling system to operate down to 0 Deg. F by cycling condenser fan on and
CPLOWAMB001A00 ALL
off.
NRTIMEGD001A00 Five Minute Compressor Delay ALL
CPHSTART002A00 PTC Compressor Start Assist Kit (single phase only) ALL
CPDUCGFLG002A00 Square to Round Duct Transitions (1 set of 2, use with horizontal duct flanges only) 24 - 48
ELECTRIC HEATERS (208/230 — SINGLE PHASE — 60 Hz)
Nominal Capacity (kW) Fuses
CPHEATER052B0** 5.0 No All
CPHEATER064B0** 5.0 Yes All
CPHEATER069B0** 7.2 No All
CPHEATER070B0** 7.2 Yes All
CPHEATER065B0** 10.0 No 24 - 42
CPHEATER050B0** 10.0 Yes All
CPHEATER051B0** 15.0 Yes 42
CPHEATER066B0** 15.0 Yes 42 - 60
CPHEATER133B0** 15.0 Yes 30
CPHEATER053B0** 20.0 Yes 42
CPHEATER054B0** 20.0 Yes 42 - 60
ELECTRIC HEATERS (208/230 — THREE PHASE — 60 Hz)
CPHEATER055B0** 5.0 No 36 - 60
CPHEATER056B0** 10.0 No 36 - 60
CPHEATER068B0** 10.0 Yes 36 - 60
CPHEATER057B0** 15.0 No 36 - 60
CPHEATER058B0** 15.0 Yes 36 - 60
CPHEATER059B0** 20.0 Yes 42 - 60
ELECTRIC HEATERS (460 THREE PHASE — 60 Hz)
CPHEATER061B0** 10.0 No 36 - 60
CPHEATER062B0** 15.0 No 36 - 60
CPHEATER063B0** 20.0 No 42 - 60
*. CPRFCURB011B00 can be used with 42-60 size units with some overhang.
†. Can also be used when replacing other manufacturer’s older generation units that contain a composite base without a metal base rail.
‡. Outdoor enthalpy available as field installed accessory; Filter rack and 1-in. filter, same as CPFILTRK kit.
**. Denotes digit can be 0, 1 or 2.
Note: If installing an accessory heater, the thermostat must have capability to energize “G” (fan) on a call for “W” (electric heat). TSTAT0406 and TSTAT0408 contain this. feature.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
50VL-K: Product Data
ECONOMIZER
COIL
FILTER
ECONOMIZER
FI LTER
Vertical Economizer
COIL
ECONOMIZER
BASE
FLANGE
ON BASE DETAIL
FILTER RACK
BEND FLANGE AT 90° -SCREW TO
DIVIDER WITH 1-IN. (25 mm)SCREW
Horizontal Economizer
TOP FILTER RACK
EV APORATOR
COIL
MANUAL OUTSIDE AIR DAMPER
REPLACEMENT
PANEL
MANUAL OUTSIDE
AIR HOOD
DAMPER
BLADE
BOTTOM FILTER
RACK
A09375
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
50VL-K: Product Data
Unit Dimensions
24-30
A230127
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
50VL-K: Product Data
Unit Dimensions
36-60
A230128
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
50VL-K: Product Data
A180216
B
A B C D E F
UNIT CATALOG (small/common G H
IN. (large base) IN. IN. IN. IN.
SIZE NUMBER base) IN. (mm) IN. (mm)
(mm) IN. (mm)* (mm) (mm) (mm) (mm)
IN. (mm)*
Small or 32.4
CPRFCURB011B00 14 (356) 10 (254) 30.6 (778)
Large 47.8 (822)
14 (356) 16 (406) 2.7 (69) 46.1 (1170)
(1214) 43.9
Large CPRFCURB013B00 14 (356) 14 (356) 42.2 (1072)
(1116)
*. Part Number CPRCURB011B00 can be used on both small and large basepan units. The cross supports must be located based on whether the unit is a small basepan or a large basepan.
NOTES:
1.Roof curb must be set up for unit being installed.
2.Seal strip must be applied, as required, to unit being installed.
3.Roof curb is made of 16-gauge steel.
4.Attach ductwork to curb (flanges of duct rest on curb).
5.Insulated panels: 1-in. (25.4 mm) thick fiberglass 1 lb. density.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
50VL-K: Product Data
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
Performance Data
60 Size
14
LEGEND
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
COOLING NOTES:
1. Ratings are net; they account for the effects of the evaporator-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
t Sensible capacity (Btuh)
ldb = tedb -
1.10 x CFM
t
Wet-bulb temperature corresponding to enthalpy
lwb =
air leaving evaporator coil (hlwb)
h
lwb = hewb - total capacity (Btuh)
(4.5 x CFM)
CFM 1080 1025 969 910 852 787 718 638 541 457
24 Medium** Red
BHP 0.21 0.22 0.23 0.23 0.24 0.24 0.25 0.25 0.26 0.27
CFM 1101 1046 993 936 878 816 749 676 599 498
Med-High Orange
BHP 0.22 0.23 0.24 0.24 0.25 0.26 0.26 0.27 0.27 0.28
CFM 1222 1173 1123 1072 1021 967 912 853 787 712
High Black
BHP 0.29 0.29 0.30 0.31 0.31 0.32 0.33 0.34 0.34 0.34
CFM 643 552 455 348 225 --- --- --- --- ---
Low Blue
BHP 0.09 0.10 0.11 0.11 0.11 --- --- --- --- ---
CFM 817 744 673 597 516 431 325 190 --- ---
Med-Low Pink
BHP 0.14 0.15 0.15 0.16 0.17 0.17 0.18 0.18 --- ---
CFM 1159 1104 1045 990 937 878 821 759 693 618
30 Medium Red
BHP 0.31 0.32 0.33 0.33 0.34 0.35 0.36 0.37 0.37 0.38
CFM 1201 1147 1095 1037 987 934 877 818 755 671
Med-High** Orange
BHP 0.34 0.35 0.36 0.37 0.37 0.38 0.39 0.40 0.41 0.40
CFM 1291 1236 1181 1131 1080 1033 978 909 792 661
High Black
BHP 0.41 0.42 0.43 0.43 0.44 0.45 0.46 0.45 0.43 0.40
CFM 1096 1044 994 945 892 837 780 717 664 612
Low Blue
BHP 0.14 0.15 0.16 0.18 0.19 0.19 0.20 0.21 0.22 0.23
CFM 1151 1103 1056 1002 953 897 845 788 729 678
Med-Low Pink
BHP 0.16 0.17 0.18 0.19 0.20 0.21 0.22 0.23 0.24 0.25
16
CFM 1299 1252 1204 1155 1106 1059 1007 959 905 844
36 Medium Red
BHP 0.22 0.23 0.24 0.25 0.26 0.27 0.28 0.29 0.30 0.31
CFM 1382 1335 1292 1246 1202 1152 1106 1058 1007 957
Med-High** Orange
BHP 0.26 0.27 0.28 0.29 0.30 0.31 0.32 0.33 0.34 0.35
CFM 1530 1485 1442 1398 1354 1309 1263 1217 1169 1120
High Black
BHP 0.33 0.35 0.36 0.37 0.38 0.39 0.40 0.41 0.42 0.43
CFM 956 899 843 786 729 676 621 558 504 435
Low Blue
BHP 0.13 0.13 0.14 0.15 0.16 0.16 0.17 0.18 0.18 0.19
CFM 1201 1153 1107 1060 1012 965 917 871 828 782
Med-Low Pink
BHP 0.21 0.22 0.22 0.23 0.24 0.25 0.26 0.27 0.28 0.29
CFM 1443 1402 1361 1322 1284 1243 1204 1164 1124 1084
42 Medium Red
BHP 0.32 0.33 0.34 0.35 0.36 0.37 0.38 0.39 0.40 0.42
CFM 1529 1491 1451 1411 1376 1338 1300 1261 1223 1185
Med-High** Orange
BHP 0.37 0.39 0.40 0.41 0.42 0.43 0.44 0.45 0.46 0.47
CFM 1604 1565 1529 1490 1455 1421 1385 1348 1310 1274
High Black
BHP 0.42 0.44 0.45 0.46 0.47 0.48 0.49 0.50 0.51 0.52
Blue CFM 641 551 462 385 289 216 163 115 --- ---
Low
BHP 0.05 0.06 0.06 0.07 0.07 0.08 0.08 0.09 --- ---
CFM 1437 1395 1351 1307 1265 1221 1176 1132 1084 1039
Med-Low Pink
BHP 0.29 0.30 0.31 0.32 0.33 0.34 0.35 0.36 0.37 0.38
CFM 1771 1735 1699 1664 1627 1592 1557 1522 1486 1450
48 Medium** Red
BHP 0.51 0.52 0.53 0.55 0.56 0.57 0.58 0.59 0.61 0.62
CFM 1928 1897 1862 1830 1796 1764 1732 1698 1620 1512
Med-High Orange
BHP 0.64 0.65 0.67 0.68 0.69 0.71 0.72 0.73 0.71 0.66
CFM 2212 2167 2124 2061 1976 1892 1794 1699 1567 1438
High Black
BHP 0.97 0.99 1.00 0.97 0.95 0.91 0.86 0.82 0.77 0.71
Dry Coil Air Delivery* - Horizontal and Downflow Discharge Sizes 24-60 (Continued)
CFM 1928 1897 1862 1830 1796 1764 1732 1698 1620 1512
Med-High Orange
BHP 0.64 0.65 0.67 0.68 0.69 0.71 0.72 0.73 0.71 0.66
CFM 2212 2167 2124 2061 1976 1892 1794 1699 1567 1438
High Black
BHP 0.97 0.99 1.00 0.97 0.95 0.91 0.86 0.82 0.77 0.71
Shaded areas indicate speed/static combinations that are not permitted for dehumidification speed.
* Air delivery values are without air filter and are for dry coil (See Wet Coil Pressure Drop Table).
** Factory-shipped cooling speed
"High Static Cooling" = Only to be used for cooling function (not allowed for heating function)
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain static pressure available for ducting.
15 kW 0.00 0.00 0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16 0.18
20 kW 0.00 0.00 0.02 0.04 0.06 0.08 0.09 0.11 0.13 0.15 0.17 0.19
RETURN
AIR
FROM
TOP COVER POWER
SOURCE
DISCONNECT
PER NEC*
POWER ENTRY
CONTROL ENTRY
Application Data
Condensate trap — A 2-in. (50.8 mm) condensate trap must be field
supplied.
Ductwork — Secure downflow discharge ductwork to roof curb. For
horizontal discharge applications, attach ductwork to unit with flanges.
To convert a unit to downflow discharge — Units are equipped with
factory-installed inserts in the downflow openings. Removal of the
inserts is similar to removing an electrical knock-out.
Maximum cooling airflow — To minimize the possibility of
condensate blow-off from the evaporator, airflow through the units
should not exceed 450 cfm per ton.
Minimum cooling airflow — Minimum cooling airflow is 350 cfm per
ton.
Minimum ambient cooling operation temperature — All standard
units have a minimum ambient operating temperature of 40_F (4_C).
With accessory low ambient temperature kit, units can operate at
temperatures down to 0_F (-17_C).
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
50VL-K: Product Data
Electrical Data
NOMINAL
VOLTAGE
NOMINAL COMPRESSOR OFM IFM ELECTRIC POWER SUPPLY
MODEL RANGE
V-PH-HZ HEAT
MIN MAX RLA LRA FLA FLA kW FLA MCA MOCP
-/- -/- 18.4 25
3.8/5 18.1/20.8 27.5/30.9 30/35
24 208/230-1-60 197 253 11.1 59.5 0.6 3.9
5.4/7.2 25.9/30 37.3/42.4 40/45
7.5/10 36.1/41.7 50/57 50/60
-/- -/- 22.6 30
3.8/5 18.1/20.8 27.5/30.9 30/35
30 208/230-1-60 197 253 14.1 67.9 1.05 3.9 5.4/7.2 25.9/30 37.3/42.4 40/45
7.5/10 36.1/41.7 50/57 50/60
11.3/15 54.2/62.5 72.6/83 80/90
-/- -/- 23.3 35
3.8/5 18.1/20.8 27.4/30.8 35/35
36 208/230-1-60 197 253 14.7 75 1.05 3.8 5.4/7.2 25.9/30 37.1/42.3 40/45
7.5/10 36.1/41.7 49.9/56.9 50/60
11.3/15 54.2/62.5 72.5/82.9 80/90
-/- -/- 15.5 25
3.8/5 10.4/12 17.8/19.8 25/25
36 208/230-3-60 197 253 8.5 70 1.05 3.8
5.4/7.2 20.8/24.1 30.8/34.9 35/35
11.3/15 31.2/36.1 43.8/49.9 45/50
- - 6.5 15
36 460-3-60 414 506 3.8 31 0.53 1.2 10 12 16.5 20
15 18 24 25
-/- -/- 27.8 40
3.8/5 18.1/20.8 35.9/37.9 40/40
5.4/7.2 25.9/30 39.6/44.8 40/45
42 208/230-1-60 197 253 16.7 109 1.05 5.8
7.5/10 36.1/41.7 52.4/59.4 60/60
11.3/15 54.2/62.5 75/85.4 80/90
15/20 72.2/83.3 97.5/111.4 100/125
-/- -/- 20.9 30
3.8/5 10.4/12 20.9/22.3 30/30
42 208/230-3-60 197 253 11.2 84 1.05 5.8 5.4/7.2 20.8/24.1 33.3/37.4 35/40
11.3/15 31.2/36.1 46.3/52.4 50/60
15/20 41.4/47.9 59/67.1 60/70
- - 9.2 15
10 12 17.1 20
42 460-3-60 414 506 5.6 44 0.53 1.7
15 18 24.6 25
20 24.1 32.3 35
-/- -/- 32.5 50
3.8/5 18.1/20.8 32.5/34.6 50/50
5.4/7.2 25.9/30 41/46.1 50/50
48 208/230-1-60 197 253 19.6 130 1.05 6.9
7.5/10 36.1/41.7 53.8/60.8 60/70
11.3/15 54.2/62.5 76.4/86.8 80/90
15/20 72.2/83.3 98.9/112.8 100/125
-/- -/- 25.1 35
3.8/5 10.4/12 25.1/25.1 35/35
48 208/230-3-60 197 253 13.7 83.1 1.05 6.9 5.4/7.2 20.8/24.1 34.6/38.8 35/40
11.3/15 31.2/36.1 47.6/53.8 50/60
15/20 41.4/47.9 60.4/68.5 70/70
- - 10.6 15
10 12 17.9 20
48 460-3-60 414 506 6.2 41 0.53 2.3
15 18 25.4 30
20 24.1 33 35
-/- -/- 37.9 60
3.8/5 18.1/20.8 37.9/37.9 60/60
5.4/7.2 25.9/30 41/46.1 60/60
60 208/230-1-60 197 253 23.9 124.5 1.05 6.9
7.5/10 36.1/41.7 53.8/60.8 60/70
11.3/15 54.2/62.5 76.4/86.8 80/90
15/20 72.2/83.3 98.9/112.8 100/125
-/- -/- 24.9 35
3.8/5 10.4/12 24.9/24.9 35/35
60 208/230-3-60 197 253 13.5 93 1.05 6.9 5.4/7.2 20.8/24.1 34.6/38.8 35/40
11.3/15 31.2/36.1 47.6/53.8 50/60
15/20 41.4/47.9 60.4/68.5 70/70
- - 10.8 15
10 12 17.9 20
60 460-3-60 414 506 6.4 60 0.53 2.3
15 18 25.4 30
20 24.1 33 35
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
50VL-K: Product Data
LEGEND
A06564
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
21
50VL-K: Product Data
A221589
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
50VL-K: Product Data
A221590
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
50VL-K: Product Data
A221587
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
50VL-K: Product Data
A221588
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
50VL-K: Product Data
A221585
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
50VL-K: Product Data
A221586
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
50VL-K: Product Data
Controls
Operating Sequence
Cooling — When the system thermostat calls for cooling, 24 V is
supplied to the “Y” and “G” terminals of the thermostat. This completes
the circuit to the contactor coil (C) and indoor (evaporator) fan relay
(IFR). The normally open contacts of energized C close and complete
the circuit through compressor motor (COMP) to outdoor (condenser)
fan motor (OFM). Both motors start instantly. The set of normally open
contacts of energized IFR close and complete the circuit through IFM.
The IFM starts instantly.
NOTE: On the loss of the thermostat call for cooling, 24 V is removed
from both the “Y” and “G” terminals (provided the fan switch is in the
“AUTO” position) de-energizing the compressor contactor and opening
the contacts supplying power to compressor/OFM. After a 90-second
delay, the IFM shuts off. If the thermostat fan selector switch is in the
“ON” position, the IFM will run continuously. On units with a Time
Guard II device: Once the compressor has started and then stopped, it
cannot be restarted again until 5 minutes have elapsed.
Heating — If accessory electric heaters are installed, on a call for heat,
circuit R-W is made through the thermostat contacts. Circuit R-G is
made which energizes the IFR. If the heaters are staged, then the
thermostat closes a second set of contacts (W2) when second stage is
required. When thermostat is satisfied, contacts open, deenergizing the
heater relay and the IFR.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28
50VL-K: Product Data
Guide Specifications
Packaged Air Conditioner System
Constant Volume Application
HVAC Guide Specifications
Size Range:2 to 5 Tons, Nominal Cooling Coils:
Indoor coils shall have aluminum plate fins mechanically bonded to
Part 1 — General seamless aluminum tubes with all joints brazed. Tube sheet openings
SYSTEM DESCRIPTION shall be belled to prevent tube wear. Outdoor coil shall have aluminum
Outdoor rooftop mounted or ground mounted, electric cooling unit fins with copper tubing.
utilizing a hermetic scroll compressor for cooling duty. Unit shall Refrigerant Components:
discharge supply air vertically or horizontally as shown on contract Refrigerant expansion device shall be of the TXV (thermostatic
drawings. Condenser fan/coil section shall have a draw-thru design with expansion valve) or fixed orifice type.
vertical discharge for minimum sound levels.
Filters:
QUALITY ASSURANCE
Filter section shall consist of field-installed, throwaway, 1-in. (25 mm)
– Unit shall be rated in accordance with AHRI Standards 210/240 and
thick fiberglass filters of commercially available sizes.
270-1995.
– Unit shall be designed in accordance with UL Standard 1995. Controls and Safeties:
– Unit shall be manufactured in a facility registered to ISO 9001 – Unit controls shall be complete with a self-contained low voltage
manufacturing quality standard. control circuit.
– Unit shall be UL listed and c-UL certified as a total package for – Compressors shall incorporate a solid-state compressor protector
safety requirements. that provides reset capability.
– Roof curb shall be designed to conform to NRCA Standards. Operating Characteristics:
– Insulation and adhesives shall meet NFPA 90A requirements for – Unit shall be capable of starting and running at 125_F (51_C)
flame spread and smoke generation. ambient outdoor temperature per maximum load criteria of AHRI
– Cabinet insulation shall meet ASHRAE Standard 62P. Standard 210.
DELIVERY, STORAGE AND HANDLING – Compressor with standard controls shall be capable of operation
down to 40_F (4_C) ambient outdoor temperature.
Unit shall be stored and handled per manufacturer’s recommendations.
– Units shall be provided with fan time delay to prevent cold air
Part 2 — Products delivery before the heat exchanger warms up.
– Unit shall be provided with 60-second fan time delay after the
EQUIPMENT
thermostat is satisfied.
General:
Electrical Requirements:
Factory-assembled, single-piece, heating and cooling unit. Contained
All unit power wiring shall enter the unit cabinet at a single location.
within the enclosure shall be all factory wiring, piping, controls,
refrigerant charge with R-410A refrigerant, and special features Motors:
required prior to field start-up. – Compressor motors shall be of the refrigerant-cooled type with
line-break thermal and current overload protection.
Unit Cabinet:
– All fan motors shall have permanently lubricated bearings, and
– Unit cabinet shall be constructed of phosphated, zinc-coated,
inherent, automatic reset, thermal overload protection.
pre-painted steel capable of with-standing 500 hours in salt spray.
– Normal service shall be through 3 removable cabinet panels. Special Features:
– The unit shall be constructed on a rust proof unit base that has an – Compressor Start Kit (single phase units only):
externally trapped, integrated sloped drain. Shall provide additional starting torque for single-phase
– Evaporator fan compartment top surface shall be insulated with a compressors.
minimum 1/2-in. (12.7 mm) thick, flexible fiberglass insulation, – Thermostat:
coated on the air side and retained by adhesive and mechanical To provide for one-stage heating and cooling in addition manual or
means. The evaporator wall sections will be insulated with a automatic changeover and indoor fan control.
minimum semi-rigid foil-faced board capable of being wiped clean. – Crankcase Heater:
Aluminum foil-faced fiberglass insulation shall be used in the entire Shall provide anti-floodback protection for low-load cooling
indoor air cavity section. applications.
– Unit shall have a field-supplied condensate trap. – Economizer:
(Horizontal - Field installed accessory)
Fans:
(Vertical - Field installed accessory )
– The evaporator fan shall be an ECM Motor.
a. Economizer controls capable of providing free cooling using
– Fan wheel shall be made from steel, be double-inlet type with
outside air.
forward curved blades with corrosion resistant finish. Fan wheel
b. Equipped with low leakage dampers not to exceed 3% leakage, at
shall be dynamically balanced.
1.0 IN. W.C. pressure differential.
– Condenser fan shall be direct drive propeller type with aluminum
c. Spring return motor shuts off outdoor damper on power failure.
blades riveted to corrosion resistant steel spiders, be dynamically
– Electric Heaters:
balanced, and discharge air vertically.
a. Electric heater shall be available as a field-installed option.
Compressor: b. Heater elements shall be open wire type, adequately supported
– Fully hermetic compressors with factory-installed vibration and insulated with ceramic bushings.
isolation. c. Electric heater packages must provide single point power
connection capability.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
29
50VL-K: Product Data
© 2023 Carrier. All rights reserved. Edition Date: 06/23 Catalog No: 50VL-24PD
Replaces: 50VL-23PD