s7 Plcs and Applications - Lesson 3 - Analog Process
s7 Plcs and Applications - Lesson 3 - Analog Process
Physical Standard :
quantity analog signal Result :
memory :
:
PIW ... :
:
ADC PIW ... L PIW 352
::: ...
SensorTransducer PIW ... ..
..
..
• Pressure ± 500mV ..
• Temperature ± 1V ..
• Flow ± 5V ..
• Speed ± 10V
..
..
• pH value ± 20mA ..
• Viscosity 4 to 20mA Analog output module ..
• etc. etc. ..
..
..
..
..
PQW ...
.
Physical Analog PQW ... T PQW 368
DAC
quantity actuator :::
PQW ...
:
Output Ethernet
4-20mA
Module
220V-AC
SSR-RM1E40AA25 0-100% Power
4-20mA or 1-5V
Oven
Heater
3 wires Pt100
U,V,W
CP
Profinet
Platform Modbus, Profibus
MICRO 420
V20
S7-1500 PLC
S7-1500 PLC
S7-1500 PLC
S7-1500 PLC
S7-1500 PLC
Manual S7400
FIE_2023 Mobi: 0908248231, Email: [email protected] 28
Analog Signal Process
Connection diagram for current and voltage Output
SM 432; AO 8 x 13 Bit (6ES74321HF000AB0)
S7-400 PLC
S7-1500 PLC
FIE_2023 Mobi: 0908248231, Email: [email protected] 30
Analog Signal Process
Temperature Control System using S7400
S7-400 PLC
S7-1500 PLC
S7-1500 PLC
S7-400 PLC
100 100
T T
mA ADC Value
0 0
mA 0 PIWx 27648
4 20
(T-0)/(100-0)=(PIWx-0)/(27648-0)
D=(((PIWx-Low_raw)/(High_raw-Low_raw))*(High_Limit-Low_Limit))
+ Low_Limit
mm mm
500 500
D D
60 60 ADC Value
mA
mA 0 PIWx 27648
4 20
(D-60)/(500-60)=(PIWx-0)/(27648-0)
D=(((PIWx-0)/(27648-0))*(500-60)) + 60
FIE_2023 Mobi: 0908248231, Email: [email protected] 45
Analog Signal Process
Scaling Sensors Data (Pressure Sensors)
Kpa Kpa
100 100
P P
Δ
A B
Δ
bipolar (M 0.0 = 1)
(Actuator is energized with positive and
negative values) OUT 27648
B
OUT
0
27648 IN
A 0.0 100.0
(LO_LIM) (HI_LIM)
unipolar (M 0.0 = ´0´)
(Actuator is energized
only with positive values)
0
IN -27648
0.0 100.0
(LO_LIM) (HI_LIM)
PV
Process
PV
S7-1500 PLC
FIE_2023 Mobi: 0908248231, Email: [email protected] 65
Analog Signal Process
PID_Ex2: Temperature Control using PID controller
S7-400 PLC
S7-1500 PLC
S7-1500 PLC
S7-400 PLC