FC2000 Migration-Guide en
FC2000 Migration-Guide en
Device Type
FC2000
Migration Guide
How to exchange FC2000 with
enCore FC1 Devices
55252 Mainz-Kastel/Germany
Email: [email protected]
Website: www.elster-instromet.com
Email: [email protected]
Website: www.elster-instromet.com
3 FAQ 15
3.1 enCore FC manual at a Glance 15
5 Appendix 18
1.1 Background
The FC2000 was discontinued on 31.12.2015. At least until end of 2020 Honeywell Elster© provide spare
parts, solutions and service, but after that date we can no longer be guarantee that all spare parts are still
available.
The next generation Flow Computer enCore FC1 (in short FC1) offers a wide range of functionalities and
has proven itself over the last years to be the logical successor for the FC2000. This migration guide aims
to assist you to replace a FC2000 with an enCore FC1.
1.2 Applicability
Due to the complexity of applications and the difference of the devices this document focuses the following
standard applications:
Please contact our ⇨ technical support team directly in case you have special requirements,
such as:
This document focuses on the hardware setup and does not describe the parameterization nor the
operation of the devices.
Honeywell Elster© will offer a special software configuration service and an on-site migration service.
Please contact your local Honeywell Service team for further details.
The approach of the FC2000 and enCore FC1 differ greatly. Therefore, readers of this
document should not only know how flow computers work and how gas is measured in general,
but also be familiar with the modular hardware and software design of enCore devices, its
mounting, commissioning, parameterization and maintenance.
Honeywell Elster© offers general trainings regarding industrial gas metering and special
trainings for the Flow Computer enCore FC1. (⇨ section 4.1 enCore FC manual at a Glance,
p. 15)
1.4 Lists with supported Gas Chromatographs and Ultra Sonic Meters
The enCore FC1 does not support all gas chromatographs (GCs) and Ultrasonic Gas Meters (USMs) that
are supported by the FC2000. Please check the following lists carefully!
In case you are using thru-port functionality with the FC2000, you need to use an external
converter like an Adam-4520 in combination with the FC1.
2.1 Analyzing the current FC2000 Setup and corresponding FC1 options
Housing
The housing of the FC2000 is deeper than For a 1:1 migration we recommend the use
enCore FC1! Therefore, all wires on the enCore FC1 in 1/2-unit width.
FC2000 should have a reserve length of
20cm.
Mounting
☐ 19’’ mounting frame for FC2000 – 19'' rack for cabinet mounting an enCore FC
(for 2 × 1/2-units) (for 2 × 1/2-units or 3 × 1/3-units)
☐ panel mounting with mounting brackets – Please contact Elster in this case.
Please note that the boards used for FC2000 and enCore FC device series vary regarding the
available interfaces.
In general:
☐ Ultrasonic flow meter – 1 or 2 flow direction(s): – Ultrasonic flow meter – 1 or 2 flow directions:
1 × MPU 1 × CPU3
1 × PSU
1 × Input (2) 1 × MFE7
1 × Comms
1 × Output board 1 × MFA8
Modules/boards in detail:
Ethernet connector available only in Unlike the PSU, the CPU3 has no power
additional Network 2 module. output.
Network boards
– ESER4 (optional)
1 × Ethernet connector (LAN)
3 × RJ45 style (RS232, RS485, RS422 serial channels)
External options
Modbus
☐ Modbus (ASCII, RTU) via serial RS232/RS485 – Modbus (ASCII, RTU) via serial RS232/RS485
communication communication and additionally RS422
(MPU or Comms module) (serial channels of CPU or ESER4)
Master and Slave operation mode
☐ Modbus TCP via a standard TCP/IP network – Modbus TCP via a standard TCP/IP network
(LAN of Network 2 module) (LAN of CPU or ESER4)
Server and Client operation mode
Prerequisite active connection between PC and FC2000... active connection between PC and FC1 ...
• via LAN (Ethernet 2 module) • via network (LAN of CPU or ESER4), or
• locally via USB connection
Access • via web browser (e.g. Microsoft Edge) using • currently via web browser (e.g. Microsoft
the IP address of the device Edge) using the IP address of the device
(outdated)
• via enSuite
Retrieving archives
2.2.1 Turbine meter (EEx i): FC2000 Input module vs. FC1 MFE7 input board
24V 0V
MFE7 board
D1+
D2+
12 345 67,8
D3+
GND
SH
Turbine: Isolated pulse
encoder and amplifier
2 LF/HF sensors (active output)
2.2.2 HART Measurement Transmitter (EEx i): FC2000 Input module vs. FC1 MFE7 input
board
0V 24V
MFE7 board
+ A1+ or A2+
− A1− or A2−
HART pressure
SH
transmitter, EEx i
Isolated current
repeater barrier
(HART compatible,
source mode)
HART temperature
transmitter, EEx i
(sink mode)
HART
communicator
In our docuthek you can download the latest versions of our manuals:
www.docuthek.com
Communication ports:
Calibration
function tested
None
Installatio
Installation
19“ mounting frame
n
Bitte senden Sie das ausgefüllte Formular zusammen mit Ihrer Bestellung an: Seite 1 / 2
Elster GmbH Steinern Straße 19-21 D-55252 Mainz-Kastel Fax: +49 6134 / 605 – 390
enCore FC1 Product Ordering Sheet V1 17.11.2017
Honeywell
EBL 50 EBL160 EBL 250
STT850 (HART)
Customer:
Contact Person:
Tel.: E-Mail:
Bitte senden Sie das ausgefüllte Formular zusammen mit Ihrer Bestellung an: Seite 2 / 2
Elster GmbH Steinern Straße 19-21 D-55252 Mainz-Kastel Fax: +49 6134 / 605 – 390