Ammonia Detection System Codes and Design Specifications
Ammonia Detection System Codes and Design Specifications
Code requires emergency ventilation at 150 ppm. The alarm setpoints should be set at 150 ppm and trigger
the emergency ventilation fan starter. Emergency ventilation and visual alarms should be latched until
manually reset by a switch located in the machinery room. Audible alarms shall continue to operate until they
are manually reset by a switch located in the machinery room, or an area remote from the machinery room.
The compressor room is the highest risk location in most plants. It has the most potential leak sources, and
the most ammonia available for disastrous concentrations. Using a minimum of two 0-250 ppm sensors is
necessary for complete coverage and redundancy. Use two 0-250 ppm ammonia gas sensors in Engine
Rooms 4,000 square feet or less. Install an additional sensor for each additional 2000 square feet. Locate
sensors in the breathing zone ~ 5 feet off the floor. Locate one sensor below the ventilation fan so it samples
airflow from throughout the room when the fan is on. Locate other sensor(s) evenly distributed throughout
the room.
Vent Line
Vent line sensors are used to provide an alarm to a monitored location in the event of a safety relief valve
opening from an overpressure condition. This alerts operators to discharges of ammonia to atmosphere
through the vent line so they can take action to mitigate the release. An alarm setpoint of 1.0% (10,000
ppm) is recommended for this application to minimize alarms due to “weeping” relief valves. Locate vent line
sensors outdoors, 3 ft off the roof, utilizing the provided mounting kit with the tee test-port facing down.
Refrigerated Rooms
In refrigerated rooms, code requires alarming to a monitored location. Some insurance companies require
shutdown of liquid feed and hot gas solenoids in the event of a leak (but the major codes currently do not).
Use 0-100 ppm sensors in these rooms. This range gives the best accuracy at very low concentrations
which is appropriate in these unrestricted areas. From the gas detection panel or PLC, the warning output
can alarm to a monitored location at 25 ppm. Additionally, the alarm output can be used to shut down the
liquid feed and hot gas solenoids at 35 ppm to mitigate the leak.
Locate sensors in the breathing zone ~ 5 feet off of the floor. The quantity of sensors should be determined
by locating at least one sensor within 30 horizontal feet of each potential leak source (one sensor located
between 2 evaporators could cover them both if they are 60 feet apart). In large, open cold storage
warehouse rooms where this results in more than 3 sensors in a room, distances can reasonably be relaxed
to 50 horizontal feet from a potential leak source, with a minimum of 3 sensors.
3
Machinery under 100 HP not in Machine Rooms, and Equipment Pits
Where an ammonia refrigeration system or equipment is installed outside of a machinery room, the area
containing the system or equipment shall comply with the following. At 25 ppm, alarm to a monitored
location, close liquid feed and hot gas solenoid valves, activate audio/visual devices inside the area, activate
emergency exhaust and de-energize all pumps, motors and non-emergency fans.
Use 0-100 ppm sensors in these rooms. This range gives the best accuracy at very low concentrations
which is appropriate in these areas. Locate sensor(s) in the breathing zone ~ 5 feet off of the floor.
Packaged Systems
Packaged systems and equipment shall comply with the following. At 25 ppm, alarm to a monitored location
and activate audio/visual devices inside the area.
Use 0-100 ppm sensors in these areas. This range gives the best accuracy at very low concentrations which
is appropriate in these areas. Locate sensor(s) in the breathing zone ~ 5 feet off of the floor.
Enclosed equipment with a potential to reach 40,000 ppm that has either open flame or hot surfaces, or
has unclassified equipment shall comply with the following. Use one 0-2% detector to disable the ignition
sources at 2% (20,000 ppm).
ppm). Note that a sensor in this range cannot be used to detect lower concentrations
covered by the 0-250 ppm sensor.
4
Gas Detection Panel (or PLC)
The gas detection system should be powered with a dedicated branch circuit from an emergency generator
backup system that can operate the system in the event of a power outage. An uninterruptable power supply
(UPS) that can run the system for a few minutes during the transition to emergency generator power should
be utilized. All wire runs should be supervised with the controller indicating a fault if communication with a
sensor is lost. Loss of power to the system should send a fault indication to a monitored location.
Any alarm condition should send a signal to a monitored location. This can be in the facility such as a control
room or guard shack. It can also be a building monitoring company, an auto-dialer, or other notification
system that notifies responsible personnel 24/7.
All output functions should be configured to latch, so even if ammonia concentrations fall below the setpoint,
a manual reset is required under the supervision of a qualified operator. This is necessary to protect against
repeating a leak scenario that has been successfully detected and mitigated.
One controller can support a combination of ammonia and CO2 sensors. One caveat to keep in mind is that
unlike ammonia, CO2 is always present in air, and concentrations can build up to these levels in a facility
from sources other than a leak in the refrigeration system. Common examples are dry ice usage and normal
personnel respiration in a non-ventilated room. CO2 sensors should be mounted in the breathing zone ~ 5
feet off of the floor.
5
Specifications:
Table 2: Equipment table
6
d. Horn/strobes
i. Provide (1) or more SHA-24-Blue horn/strobes inside the compressor room and one at each outside
entrance of the compressor room
ii. Horn/strobe shall be labeled “Ammonia” for easy at-a-glance interpretation of the alarm.
iii. Horn/strobe shall be rated for outdoor use to prevent corrosion.
iv. The sound level shall be at least 15 dBA above the average ambient sound level and 5 dBA above the
maximum sound level of the area.
e. Reset Switch
i. Provide (1) SB-R1 reset switch inside the compressor room.
ii. The switch shall be wired to the remote reset wire terminals of the GG-6 controller
2. Sensors
a. Compressor Room 0-250 ppm
i. Provide (2) GG-NH3-250 ammonia gas sensors in Compressor Rooms 4000 square feet or less. Install
an additional sensor for each 2000 square feet.
ii. Locate sensors in the breathing zone – 5 feet off the floor.
iii. Locate one sensor below the continuous ventilation fan so it samples airflow from throughout the room.
iv. Locate other sensor(s) evenly distributed throughout the room.
v. The sensor shall have potted electronics to protect circuit board and components.
vi. The sensor shall have a polycarbonate enclosure to prevent corrosion.
vii. The sensor shall provide a temperature controlled enclosure for use in any area for improved cell life.
viii. The sensor shall have a linear 4/20 mA output signal.
b. Compressor Room Shutdown 0-2%
i. Provide (1) GG-NH3-2% ammonia gas sensor for each Compressor Room.
ii. Locate sensor 5 feett off the floor below the emergency ventilation fan so it samples airflow from
throughout the room.
iii. The sensor shall have potted electronics to protect circuit board and components.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. The sensor shall provide a temperature controlled enclosure for use in any area for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.
c. Vent Lines
i. Provide (1) GG-VL2-NH3 ammonia vent line sensor for each high-pressure relief line discharge to
atmosphere.
ii. Install vent line sensor utilizing supplied mounting kit. Locate outdoors, 3 feet off of the roof. Install
utilizing supplied mounting kit with tee test port pointed down.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a stainless-steel enclosure to prevent corrosion.
v. The sensor shall have a linear 4/20 mA output signal.
d. Ammonia refrigerated areas
i. Provide GG-NH3-100 ammonia gas sensors near evaporators, valve groups, and other equipment with
sensors installed no further than 30 horizontal feet from the potential leak source (50 feet if more than 3
sensors in a room).
ii. Locate sensors in the breathing zone – 5 feet off of the floor.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. Sensor shall provide a temperature controlled enclosure for use in any environment for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.
e. Carbon Dioxide refrigerated areas
i. Provide GG-CO2-3% carbon dioxide gas sensors near evaporators, valve groups, and other equipment
with sensors installed no further than 30 feet from the potential leak source (50 feet if more than 3
sensors in a room).
ii. Locate sensors in the breathing zone – 5 feet off of the floor.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. Sensor shall provide a temperature controlled enclosure for use in any environment for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.
7
Explanatory Material
Back in 2012, there were six different U.S. model codes and standards written by different agencies regulating
ammonia refrigeration, including ANSI/IIAR 2-2014, ASHRAE 15, NFPA-1, UMC, IFC, and IMC. Gradually, these
agencies have started to adopt IIAR-2 standards, rather than continue to write their own. As of 2021, the IIAR-2
standards have become the generally accepted industry standard to which most other organizations now defer.
Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2
At least 2 detectors with identical sensing ranges At least 2 detectors with identical sensing ranges
Plus 1 high range detector
40,000 ppm De-energize refrigerant compressors, pumps, 20,000 ppm De-energize refrigerant compressors, pumps,
and normally closed valves and normally closed valves
8
Additional Audio-Visual Requirements
Audible alarms shall provide a sound pressure level of 15 dBA above the average ambient sound level and 5 dBA above
the maximum sound level of the area in which it is installed.
Alarms shall be identified by signage adjacent to visual and audible alarm devices.
Audible alarms, visual indicators and emergency exhaust systems that are activated at 25 ppm can by automatically reset
when concentration drops below 25 ppm.
Visual indicators and emergency exhaust systems that are activated at 150 ppm or higher must continue to operate until
they are manually reset by a switch located inside the machinery room. Audio alarms that are activated at 150 ppm or
higher can be reset remotely.
Definitions
Packaged System: A stand-alone, complete, plug-and-play refrigeration system that is built off-site, mounted on
a steel base or skid and delivered as a single unit to an end-user facility. A packaged system can be designed for
indoor or outdoor installation and can be enclosed or unenclosed.
Enclosure: An area that is surrounded by walls or a fence. IIAR 5.15.1 states that enclosures for ammonia
equipment shall be suitable for the installation location and shall be provided with protection from physical and
environmental damage as required for the installed location.
Free Aperture: Free aperture refers to the amount of natural, passive ventilation of an enclosed or partially enclosed
area. Packaged systems that are located outdoors and do not have sufficient free aperture must have ammonia detection.
To calculate the free aperture of an enclosure, use the formula listed in IIAR 7.3.2 as follows:
The free-aperture cross-section for natural ventilation shall not be less than:
F = G 0.5 (I-P) (using ft2 and lbs of NH3)
F = 0.138G 0.5 (SI) (using m2 and kgs of NH3)
where:
F= the free opening of the area, ft 2 (m 2)
G= the mass of ammonia in the largest independent circuit, any part of which is located within the enclosure
or structure, lbs. (kg)
Exceptions
1. In machinery rooms, the use of a single detector is permitted if the failure or maintenance of the detector that causes the detection
system to become inoperable, starts emergency ventilation system that shall continue to operate until the detection system is
restored.
2. Unoccupied areas with continuous piping that has been joined by welding and does not include valves, valve assemblies,
equipment, or equipment connections do not require level 1 detection and alarm.
3. Where not prohibited by the AHJ, rooms or areas in industrial occupancies that are normally occupied 24 hours/day and are
regularly patrolled when the rooms’ functions are idled for scheduled downtime and are provided with an alternative to fixed
detection and alarm equipment do not require level 1 detection and alarm. A means for emergency notification and initiation of
alarm response shall be provided.
4. Where not prohibited by the AHJ, alternatives to fixed ammonia leak detectors shall be permitted for areas with high humidity or
other harsh environmental conditions that are incompatible with detection devices. A means for emergency notification and initiation
of alarm response shall be provided.
9
Ammonia Detection System Layout Example
Refrigerated Spaces (Freezers, Coolers, Docks, Process areas, Air Handlers, etc.)
SHA-24
GG-NH3-100-ST GG-NH3-100-ST Horn/Strobe (25 ppm) GG-NH3-100 GG-NH3-100
Sensor 0/100 ppm Sensor 0/100 ppm Sensor 0/100 ppm Sensor 0/100 ppm
UPS-1000VA-LCD
Battery Backup Output (20,000 ppm)
Compressor Room
shutdown
GG-6 GG-XM
Controller Expansion Module
SHA-24 EM2-24
Horn/Strobe (25 ppm) Entrance Monitor
Compressor Room
GG-NH3-250 SHA-24
Sensor 0/250 ppm GG-NH3-2% Horn/Strobe (25 ppm)
Sensor 0/2% SHA-24
Horn/Strobe (25 ppm)