0% found this document useful (0 votes)
89 views

Ammonia Detection System Codes and Design Specifications

The document provides design specifications for an ammonia detection system, including sensor types and locations, alarm thresholds, and shutdown actions. Key points include: - Sensors in compressor rooms should alarm at 25ppm and trigger emergency ventilation at 150ppm. A high range sensor should shutdown equipment at 20,000ppm. - Vent line sensors should alarm at 1% to detect relief valve discharges. - Refrigerated rooms should alarm at 25ppm and potentially shutdown valves at 35ppm. - Areas with machinery under 100HP should alarm and take shutdown actions at 25ppm. - Packaged systems and enclosed equipment should have sensors to alarm or disable ignition sources.

Uploaded by

luv muv
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
89 views

Ammonia Detection System Codes and Design Specifications

The document provides design specifications for an ammonia detection system, including sensor types and locations, alarm thresholds, and shutdown actions. Key points include: - Sensors in compressor rooms should alarm at 25ppm and trigger emergency ventilation at 150ppm. A high range sensor should shutdown equipment at 20,000ppm. - Vent line sensors should alarm at 1% to detect relief valve discharges. - Refrigerated rooms should alarm at 25ppm and potentially shutdown valves at 35ppm. - Areas with machinery under 100HP should alarm and take shutdown actions at 25ppm. - Packaged systems and enclosed equipment should have sensors to alarm or disable ignition sources.

Uploaded by

luv muv
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 10

Ammonia Detection System

Codes and Design Specifications


October 27, 2021
Revision 10
Ammonia Detection System Codes and Design Specifications
Following is a discussion of ammonia detection system design for facilities utilizing ammonia refrigeration
systems. Regulations for the ammonia refrigeration industry have dramatically changed in the last 10 years.
Beginning with 2021 editions of the Uniform, International, NFPA, and ASHRAE codes and standards, you
only need to consider recommendations from IIAR when you evaluate your ammonia detection system for
compliance.
In addition to IIAR standards, you should always consider any local amendments or supplemental
requirements of your local authority having jurisdiction (AHJ), recognized and generally accepted good
engineering practices (RAGAGEP), and your insurance company. Many insurance carriers impose their own
requirements to mitigate the risk of loss of life and product in a facility.
What follows is a system design that meets the requirements all of the above-mentioned influences. This
document is updated periodically, and it is recommended that you check our website (www.ctiengineering.
com) for the latest revision.

Table 1: Ammonia Detection System Overview


Location Sensor Actions
Compressor Room GG-NH3-250 25 ppm - Alarm to monitored location
(minimum 2 sensors) (low range 25 ppm - Horn Strobe outside each entrance and inside engine room
detector) 150 ppm - Emergency Ventilation

Compressor Room GG-NH3-2% 10,000 ppm - Redundant Emergency Ventilation*


(minimum 1 sensor) (high range 20,000 ppm - De-energize pumps, compressors, and normally closed valves
detector)
Vent Line* GG-VL2-NH3 1% - Alarm to monitored location*

Refrigerated Areas GG-NH3-100 25 ppm - Alarm to monitored location


25 ppm - Horn Strobe*
35 ppm - Close liquid and hot gas solenoid valves*
Packaged Systems See Table 1.2

Enclosed Equipment GG-NH3-2% 20,000 ppm - Disable ignition sources

Machinery under 100 HP and GG-NH3-100 25 ppm - Alarm to monitored location


equipment Pits (not in machine 25 ppm - Close liquid and hot gas solenoid valves
rooms) 25 ppm - Horn Strobe inside room
25 ppm - De-energize pumps, motors, and non-emergency fans
25 ppm - Emergency Ventilation

*Not required by code

Table 1.2: Packaged System Detection Overview


Location Specification 1 Specification 2 Detection Level (See Appendix 3, page 8)

Over 100 HP Inside a


Machinery Room Detection Level
Compressor Room
Indoor
Potential of 40,000ppm? Yes Level 3 Detection
Under 100 HP Outside a
Compressor Room
Potential of 40,000ppm? No Level 1 Detection

Free Aperture? Yes No detection required

Outdoor Under 100 HP Level 1 Detection


Free Aperture? No
Over 100 HP Machinery Room Detection Level
2
Compressor Room (0-250 ppm sensors)
Code requires audio-visual indication inside the compressor room and outside each entrance to the
compressor room at 25 ppm. From the gas detection control panel or PLC, the warning outputs can be set at
25 ppm to activate a horn / strobe unit inside the engine room and outside each entrance. Entrance monitor
display units can be located outside each doorway to warn personnel of ammonia concentrations prior to
entry. Audio-visual alarms can automatically reset if the ammonia concentration drops below 25 ppm.

Code requires emergency ventilation at 150 ppm. The alarm setpoints should be set at 150 ppm and trigger
the emergency ventilation fan starter. Emergency ventilation and visual alarms should be latched until
manually reset by a switch located in the machinery room. Audible alarms shall continue to operate until they
are manually reset by a switch located in the machinery room, or an area remote from the machinery room.

The compressor room is the highest risk location in most plants. It has the most potential leak sources, and
the most ammonia available for disastrous concentrations. Using a minimum of two 0-250 ppm sensors is
necessary for complete coverage and redundancy. Use two 0-250 ppm ammonia gas sensors in Engine
Rooms 4,000 square feet or less. Install an additional sensor for each additional 2000 square feet. Locate
sensors in the breathing zone ~ 5 feet off the floor. Locate one sensor below the ventilation fan so it samples
airflow from throughout the room when the fan is on. Locate other sensor(s) evenly distributed throughout
the room.

Compressor Room Shutdown (0-2% sensor)


In the compressor room, code also requires shutdown of compressors, pumps, and normally closed solenoid
valves at a very high concentration (20,000 ppm is industry standard). The alarm output can be used to
shut down at 2% (20,000 ppm). For redundancy at no cost, the warning output can be used to also trigger
emergency ventilation at 1% (10,000 ppm). Use one 0-2% sensor located ~ 5 feet off the floor below the
emergency ventilation fan so it samples airflow from throughout the room in an emergency condition. Note
that a sensor in this range cannot be used to detect lower concentrations covered by the 0-250 ppm sensor.

Vent Line
Vent line sensors are used to provide an alarm to a monitored location in the event of a safety relief valve
opening from an overpressure condition. This alerts operators to discharges of ammonia to atmosphere
through the vent line so they can take action to mitigate the release. An alarm setpoint of 1.0% (10,000
ppm) is recommended for this application to minimize alarms due to “weeping” relief valves. Locate vent line
sensors outdoors, 3 ft off the roof, utilizing the provided mounting kit with the tee test-port facing down.

Refrigerated Rooms
In refrigerated rooms, code requires alarming to a monitored location. Some insurance companies require
shutdown of liquid feed and hot gas solenoids in the event of a leak (but the major codes currently do not).
Use 0-100 ppm sensors in these rooms. This range gives the best accuracy at very low concentrations
which is appropriate in these unrestricted areas. From the gas detection panel or PLC, the warning output
can alarm to a monitored location at 25 ppm. Additionally, the alarm output can be used to shut down the
liquid feed and hot gas solenoids at 35 ppm to mitigate the leak.

Locate sensors in the breathing zone ~ 5 feet off of the floor. The quantity of sensors should be determined
by locating at least one sensor within 30 horizontal feet of each potential leak source (one sensor located
between 2 evaporators could cover them both if they are 60 feet apart). In large, open cold storage
warehouse rooms where this results in more than 3 sensors in a room, distances can reasonably be relaxed
to 50 horizontal feet from a potential leak source, with a minimum of 3 sensors.

3
Machinery under 100 HP not in Machine Rooms, and Equipment Pits
Where an ammonia refrigeration system or equipment is installed outside of a machinery room, the area
containing the system or equipment shall comply with the following. At 25 ppm, alarm to a monitored
location, close liquid feed and hot gas solenoid valves, activate audio/visual devices inside the area, activate
emergency exhaust and de-energize all pumps, motors and non-emergency fans.

Use 0-100 ppm sensors in these rooms. This range gives the best accuracy at very low concentrations
which is appropriate in these areas. Locate sensor(s) in the breathing zone ~ 5 feet off of the floor.

Packaged Systems
Packaged systems and equipment shall comply with the following. At 25 ppm, alarm to a monitored location
and activate audio/visual devices inside the area.

Use 0-100 ppm sensors in these areas. This range gives the best accuracy at very low concentrations which
is appropriate in these areas. Locate sensor(s) in the breathing zone ~ 5 feet off of the floor.

Enclosed equipment with a potential to reach 40,000 ppm that has either open flame or hot surfaces, or
has unclassified equipment shall comply with the following. Use one 0-2% detector to disable the ignition
sources at 2% (20,000 ppm).
ppm). Note that a sensor in this range cannot be used to detect lower concentrations
covered by the 0-250 ppm sensor.

Installation Design Requirements


General
Detectors shall use supervised wire runs such that any faults in the wiring are reported to a monitored
location. Loss of communication between the detector and the control system(s) that enables response
shall be reported to a monitored location. Detectors shall actively monitor primary sensing elements and
report any trouble signal to a monitored location. Audible alarms should provide an SPL of 15 decibels (dBA)
above the average ambient sound level, and 5 dBA above the maximum sound level of the area in which it
is installed.All
installed.All ammonia detectors shall be designed and tested in accordance with UL-61010-1 or ANSI/ISA
92.0.01.

Sensor Mounting Height


There is much confusion in the industry concerning the best height to mount ammonia sensors. This is
because there are valid reasons for different heights. Codes simply say “locate sensor where it is expected
to be the most effective, and can be accessed for maintenance and testing ”. Ammonia vapor is lighter
than air so vapor leaks will rise to the ceiling in normal conditions. A liquid leak will drop to the floor and if
large enough can cool down a room so quickly that high concentrations are found on the floor with very low
concentrations at the ceiling. In refrigerated areas there is normally enough air flow from evaporator fans to
mix the refrigerant fairly well in the room. In all locations, 25 ppm is the first alarm point and this is intended
for personnel protection. To best protect personnel, the sample should be representative of what they are
breathing ~ 5 feet off of the floor. Most importantly, the sensor needs to be easily accessible for the required
6-month calibration and output testing. An untested safety system only takes a few years to become a
nonworking safety system. The breathing zone is the best height to satisfy all of the above concerns.

4
Gas Detection Panel (or PLC)
The gas detection system should be powered with a dedicated branch circuit from an emergency generator
backup system that can operate the system in the event of a power outage. An uninterruptable power supply
(UPS) that can run the system for a few minutes during the transition to emergency generator power should
be utilized. All wire runs should be supervised with the controller indicating a fault if communication with a
sensor is lost. Loss of power to the system should send a fault indication to a monitored location.

Any alarm condition should send a signal to a monitored location. This can be in the facility such as a control
room or guard shack. It can also be a building monitoring company, an auto-dialer, or other notification
system that notifies responsible personnel 24/7.

All output functions should be configured to latch, so even if ammonia concentrations fall below the setpoint,
a manual reset is required under the supervision of a qualified operator. This is necessary to protect against
repeating a leak scenario that has been successfully detected and mitigated.

CO2 Cascade systems


For CO2 cascade systems, ammonia and CO2 detection are both required in the compressor room which
contains the ammonia system and the cascade heat exchanger. CO2 detection is required instead of
ammonia detection in refrigerated and process areas. Detection system design and output functions are
similar with the difference being the CO2 sensor selected, warning setpoints at 0.5% (5,000 ppm) (OSHA 8
hour TWA) and alarm setpoints at 1.0%.

One controller can support a combination of ammonia and CO2 sensors. One caveat to keep in mind is that
unlike ammonia, CO2 is always present in air, and concentrations can build up to these levels in a facility
from sources other than a leak in the refrigeration system. Common examples are dry ice usage and normal
personnel respiration in a non-ventilated room. CO2 sensors should be mounted in the breathing zone ~ 5
feet off of the floor.

5
Specifications:
Table 2: Equipment table

Part Number Description Application


GG-6 Six channel controller Monitor gas detection system
GG-XM Eight channel expansion module Additional monitoring capability
GG-RD1 Remote display for GG-6 Remote monitoring of gas detection system
EM2 Entrance monitor Outside compressor room doorways
UPS-1000VA-LCD Uninterruptible power supply Backup Power for GG-6
SHA-24-BLUE Strobe/Horn assembly 24vdc Audio Visual
GG-NH3-100 0/100 ppm electrochemical sensor Refrigerated Area
GG-NH3-250 0/250 ppm electrochemical sensor Compressor Room
GG-NH3-2% 0/2% catalytic bead sensor Compressor Room shutdown
GG-VL2-NH3 0/1% vent line sensor HP relief header, above roofline
GG-CO2-3% 0/3% infrared sensor CO2 refrigeration systems

Table 3: Warning and Alarm Setpoints table


Room Warning / Alarm setpoints
Refrigerated areas 25 ppm / 35 ppm
Compressor Room (0-250 ppm) 25 ppm / 150 ppm
Compressor Room Shutdown (0-2%) 1% / 2%
Vent Line 1.0%
Carbon Dioxide refrigerated area 0.5% / 1.0%
1. Equipment
a. Equipment notes
i. All controllers and sensors shall be manufactured by CTI - phone number 866-394-5861.
ii. See Equipment table for part numbers and function descriptions.
iii. See Warning and Alarm setpoints table for recommended setpoints.
b. Controller
i. Provide a GG-6 controller and necessary Expansion Modules to monitor all fixed sensors. The controller
shall be equipped with programmable alarm relays to activate external horn/strobes, exhaust fans,
monitoring systems, and shut down equipment.
ii. The controller shall provide three alarm setpoints per channel.
iii. The controller and expansion modules shall provide 4/20 mA signal inputs.
iv. The controller and expansion modules shall provide +24 Vdc to power all connected sensors.
v. The controller shall provide an LCD operator interface for simple menu-driven programming.
vi. The controller shall provide a watertight enclosure to protect electronics and allow for outdoor installations
where necessary.
vii. The controller shall provide a horn relay which is silenceable from front panel silence key.
viii. The controller shall provide an alarm log to record and store all events.
ix. The controller shall provide a calibration mode which locks relay outputs for sensor maintenance and
calibration.
x. Controller shall supervise wire runs and indicate a fault if communication with sensors is lost.
xi. Power controller with dedicated branch circuit using Uninterruptable power supply (UPS) backed up by
emergency generator to provide 24 hour operation in the event of a power outage.
c. Entrance Monitors
i. Provide an EM2 entrance monitor outside each compressor room entrance.
ii. Entrance monitor shall terminate 4-20 mA signal from sensor and retransmit same to controller.
iii. Entrance monitor to provide a digital display to warn operators of ammonia concentration present prior to
entering compressor room.
iv. Entrance monitor shall have on-board 8 amp relay.
v. Entrance monitor shall have potted electronics to protect circuit board and components from & corrosion.
vi. Entrance monitor shall have a polycarbonate enclosure to prevent corrosion.
vii. Entrance monitor shall have a linear 4/20 mA output signal.

6
d. Horn/strobes
i. Provide (1) or more SHA-24-Blue horn/strobes inside the compressor room and one at each outside
entrance of the compressor room
ii. Horn/strobe shall be labeled “Ammonia” for easy at-a-glance interpretation of the alarm.
iii. Horn/strobe shall be rated for outdoor use to prevent corrosion.
iv. The sound level shall be at least 15 dBA above the average ambient sound level and 5 dBA above the
maximum sound level of the area.
e. Reset Switch
i. Provide (1) SB-R1 reset switch inside the compressor room.
ii. The switch shall be wired to the remote reset wire terminals of the GG-6 controller
2. Sensors
a. Compressor Room 0-250 ppm
i. Provide (2) GG-NH3-250 ammonia gas sensors in Compressor Rooms 4000 square feet or less. Install
an additional sensor for each 2000 square feet.
ii. Locate sensors in the breathing zone – 5 feet off the floor.
iii. Locate one sensor below the continuous ventilation fan so it samples airflow from throughout the room.
iv. Locate other sensor(s) evenly distributed throughout the room.
v. The sensor shall have potted electronics to protect circuit board and components.
vi. The sensor shall have a polycarbonate enclosure to prevent corrosion.
vii. The sensor shall provide a temperature controlled enclosure for use in any area for improved cell life.
viii. The sensor shall have a linear 4/20 mA output signal.
b. Compressor Room Shutdown 0-2%
i. Provide (1) GG-NH3-2% ammonia gas sensor for each Compressor Room.
ii. Locate sensor 5 feett off the floor below the emergency ventilation fan so it samples airflow from
throughout the room.
iii. The sensor shall have potted electronics to protect circuit board and components.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. The sensor shall provide a temperature controlled enclosure for use in any area for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.
c. Vent Lines
i. Provide (1) GG-VL2-NH3 ammonia vent line sensor for each high-pressure relief line discharge to
atmosphere.
ii. Install vent line sensor utilizing supplied mounting kit. Locate outdoors, 3 feet off of the roof. Install
utilizing supplied mounting kit with tee test port pointed down.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a stainless-steel enclosure to prevent corrosion.
v. The sensor shall have a linear 4/20 mA output signal.
d. Ammonia refrigerated areas
i. Provide GG-NH3-100 ammonia gas sensors near evaporators, valve groups, and other equipment with
sensors installed no further than 30 horizontal feet from the potential leak source (50 feet if more than 3
sensors in a room).
ii. Locate sensors in the breathing zone – 5 feet off of the floor.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. Sensor shall provide a temperature controlled enclosure for use in any environment for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.
e. Carbon Dioxide refrigerated areas
i. Provide GG-CO2-3% carbon dioxide gas sensors near evaporators, valve groups, and other equipment
with sensors installed no further than 30 feet from the potential leak source (50 feet if more than 3
sensors in a room).
ii. Locate sensors in the breathing zone – 5 feet off of the floor.
iii. The sensor shall have potted electronics to protect circuit board and components from moisture and
corrosion.
iv. The sensor shall have a polycarbonate enclosure to prevent corrosion.
v. Sensor shall provide a temperature controlled enclosure for use in any environment for improved cell life.
vi. The sensor shall have a linear 4/20 mA output signal.

7
Explanatory Material
Back in 2012, there were six different U.S. model codes and standards written by different agencies regulating
ammonia refrigeration, including ANSI/IIAR 2-2014, ASHRAE 15, NFPA-1, UMC, IFC, and IMC. Gradually, these
agencies have started to adopt IIAR-2 standards, rather than continue to write their own. As of 2021, the IIAR-2
standards have become the generally accepted industry standard to which most other organizations now defer.

Appendix 1: Summary of Ammonia Detection Code Requirements


ANSI/IIAR 2-2021 ASHRAE 15-2019 NFPA 1-2021 UMC-2021 IFC-2021 IMC-2021

Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2 Comply with IIAR 2

Appendix 2: IIAR 2-2021 Standards


Location Description/Details Detection Level
Machinery Room Machinery Room Detection
Area containing Potential of 40,000 ppm? Yes Level 3 Detection
refrigeration equipment Less than
located outside of a 100 HP
Potential of 40,000 ppm? No Level 1 Detection
machinery room
Equipment Pits Level 3 Detection
Refrigerated Spaces Level 1 Detection
Over 100 HP Inside a machinery room Machinery Room Detection
Indoor Under 100 HP Outside of Potential of 40,000 ppm? Yes Level 3 Detection
machinery room Potential of 40,000 ppm? No Level 1 Detection
Packaged Systems
Free Aperture*? Yes No detection needed
Outdoor Under 100 HP Level 1
Free Aperture*? No
Over 100 HP Machinery Room Detection

Appendix 3: Detection Levels Defined


IIAR 2-2021 Minimum Standard CTI Recommendation

At least 2 detectors with identical sensing ranges At least 2 detectors with identical sensing ranges
Plus 1 high range detector

25 ppm Notify a monitored location 25 ppm Notify a monitored location


Machinery
Room Activate audio alarms and visual indicators Activate audio alarms and visual indicators
Detection 150 ppm Activate emergency ventilation 150 ppm Activate emergency ventilation

40,000 ppm De-energize refrigerant compressors, pumps, 20,000 ppm De-energize refrigerant compressors, pumps,
and normally closed valves and normally closed valves

At least 1 detector At least 1 detector within 30 feet of potential leak sources


Level 1 25 ppm Notify a monitored location 25 ppm Notify a monitored location
Detection
Activate audio and visual indicators

At least 1 detector At least 1 detector

25 ppm Notify a monitored location 25 ppm Notify a monitored location


Activate Audio alarms and visual indicators Activate audio alarms and visual indicators
Level 3
Detection Close valves feeding liquid and hot gas Close valves feeding liquid and hot gas
De-energize pumps, fans, and motors that De-energize pumps, fans, and motors that
are part of the refrigeration system are part of the refrigeration system
Activate emergency exhaust systems Activate emergency exhaust systems

8
Additional Audio-Visual Requirements
Audible alarms shall provide a sound pressure level of 15 dBA above the average ambient sound level and 5 dBA above
the maximum sound level of the area in which it is installed.
Alarms shall be identified by signage adjacent to visual and audible alarm devices.
Audible alarms, visual indicators and emergency exhaust systems that are activated at 25 ppm can by automatically reset
when concentration drops below 25 ppm.
Visual indicators and emergency exhaust systems that are activated at 150 ppm or higher must continue to operate until
they are manually reset by a switch located inside the machinery room. Audio alarms that are activated at 150 ppm or
higher can be reset remotely.

Definitions
Packaged System: A stand-alone, complete, plug-and-play refrigeration system that is built off-site, mounted on
a steel base or skid and delivered as a single unit to an end-user facility. A packaged system can be designed for
indoor or outdoor installation and can be enclosed or unenclosed.

Enclosure: An area that is surrounded by walls or a fence. IIAR 5.15.1 states that enclosures for ammonia
equipment shall be suitable for the installation location and shall be provided with protection from physical and
environmental damage as required for the installed location.

Free Aperture: Free aperture refers to the amount of natural, passive ventilation of an enclosed or partially enclosed
area. Packaged systems that are located outdoors and do not have sufficient free aperture must have ammonia detection.
To calculate the free aperture of an enclosure, use the formula listed in IIAR 7.3.2 as follows:

The free-aperture cross-section for natural ventilation shall not be less than:
F = G 0.5 (I-P) (using ft2 and lbs of NH3)
F = 0.138G 0.5 (SI) (using m2 and kgs of NH3)
where:
F= the free opening of the area, ft 2 (m 2)
G= the mass of ammonia in the largest independent circuit, any part of which is located within the enclosure
or structure, lbs. (kg)

Level 2 Ammonia Detection and Alarm.


Alarm. The normative parts of this standard currently require only level 1 and
level 3 ammonia detection and alarm levels. Information regarding level 2 is retained here for reference. Designers
or end users may wish to use level 2 in lieu of level 1. If level 2 ammonia detection and alarm are implemented, it
would have the following features:
1. At least one ammonia detector would be provided in the room or area.
2. The detector would activate an alarm that reports to a monitored location so that corrective action can be taken
at an indicated concentration of 25 ppm or higher.
3. Audible and visual alarms would be provided inside the room to warn that when the alarm has activated access
to the room is restricted to authorized personnel and emergency responders.

Exceptions
1. In machinery rooms, the use of a single detector is permitted if the failure or maintenance of the detector that causes the detection
system to become inoperable, starts emergency ventilation system that shall continue to operate until the detection system is
restored.
2. Unoccupied areas with continuous piping that has been joined by welding and does not include valves, valve assemblies,
equipment, or equipment connections do not require level 1 detection and alarm.
3. Where not prohibited by the AHJ, rooms or areas in industrial occupancies that are normally occupied 24 hours/day and are
regularly patrolled when the rooms’ functions are idled for scheduled downtime and are provided with an alternative to fixed
detection and alarm equipment do not require level 1 detection and alarm. A means for emergency notification and initiation of
alarm response shall be provided.
4. Where not prohibited by the AHJ, alternatives to fixed ammonia leak detectors shall be permitted for areas with high humidity or
other harsh environmental conditions that are incompatible with detection devices. A means for emergency notification and initiation
of alarm response shall be provided.
9
Ammonia Detection System Layout Example

Refrigerated Spaces (Freezers, Coolers, Docks, Process areas, Air Handlers, etc.)

SHA-24
GG-NH3-100-ST GG-NH3-100-ST Horn/Strobe (25 ppm) GG-NH3-100 GG-NH3-100
Sensor 0/100 ppm Sensor 0/100 ppm Sensor 0/100 ppm Sensor 0/100 ppm

Output (35 ppm)


Liquid feed and hot gas
solenoid valve shutoff

Output (25 ppm)


SHA-24 Alarm to monitored
Horn/Strobe (25 ppm) location
Audio/Visual at controller

Output (150 ppm)


Emergency Ventilation

UPS-1000VA-LCD
Battery Backup Output (20,000 ppm)
Compressor Room
shutdown

GG-6 GG-XM
Controller Expansion Module

SHA-24 EM2-24
Horn/Strobe (25 ppm) Entrance Monitor

Compressor Room

GG-NH3-250 SHA-24
Sensor 0/250 ppm GG-NH3-2% Horn/Strobe (25 ppm)
Sensor 0/2% SHA-24
Horn/Strobe (25 ppm)

GG-VL2-NH3 SB-R1 GG-NH3-250 EM2-24


Sensor 0/1% Reset Switch Sensor 0/250 ppm Entrance Monitor

866-394-5861 www.ctiengineering.com [email protected]


10

You might also like