0% found this document useful (0 votes)
228 views2 pages

VPRA2M

The document summarizes the features and specifications of a voltage protection relay device. It monitors for under voltage, over voltage, phase asymmetry, phase failure, and phase sequence. It has adjustable trip levels and delays, LED indicators, and DPDT relay contacts. It is designed for DIN rail mounting and has inputs for 1Ø-2 wire or 3Ø-4 wire configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
228 views2 pages

VPRA2M

The document summarizes the features and specifications of a voltage protection relay device. It monitors for under voltage, over voltage, phase asymmetry, phase failure, and phase sequence. It has adjustable trip levels and delays, LED indicators, and DPDT relay contacts. It is designed for DIN rail mounting and has inputs for 1Ø-2 wire or 3Ø-4 wire configurations.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

VPRA2M Voltage Protection Relay

Features :
1Ø - 2 Wire, 3Ø - 4 Wire Input
!
Monitors Under Voltage, Over Voltage, Phase Asymmetry,
!
Phase Failure, Phase Sequence
LED Indication : Power ON / Phase Failure, Under Voltage, Over Voltage,
!
Phase Sequence / Asymmetry
DIN Rail Mount
!
Adjustable Over and Under Voltage Trip Level
!
Adjustable Trip Time Delay
!

Certification :
DIN 35mm

Display Specifications
Trip Delay
Type Analog Power On Delay 0 - 15sec (for 0 setting : <400msec)
No. of LED 4 Trip Time Delay 0 - 15sec (for 0 setting : <100msec)
No. of Knob 3 Recovery Time Delay 5sec (Fixed) ±200ms
Phase Sequence Trip Delay <250msec
LED Indication Chart Hysteresis
Voltage 7V (±2V) of Trip setting
Power Under Voltage Over Voltage Phase Reverse /
Condition Assymetry LED
LED LED LED Accuracy
Nominal Condition ON OFF OFF OFF Trip Setting Accuracy ±5% of Full Scale
Time Setting Accuracy ±10% of Full Scale
Under Voltage ON ON OFF OFF

Over Voltage ON OFF ON OFF Output Specifications


Phase Sequence ON OFF OFF ON Relay Contact 2 C/O (DPDT)
Relay Rating 5A@250V AC / 28V DC
Phase Asymmetry ON OFF OFF Blink

Phase Failure (L2 / L3) Blink OFF OFF OFF


Auxiliary Supply Specifications

Nominal Input Voltage 230V AC (L-N)


Input Specifications
Operating Voltage 127 to 288V AC (L-N)
Functions Frequency 48 / 63Hz
Measurements Under Voltage, Over Voltage, Phase Power Consumption 5VA max
Asymmetry, Phase Failure & Phase Sequence
Reset Auto
Environmental Specifications
Electrical Connection 1Ø - 2 wire, 3Ø - 4 wire
Trip Settings Temperature Operating Temperature : -10o to 55oC
Storage Temperature : -25o to 70oC
Under Voltage 55 to 95% of Un
Humidity (non-condensing) Upto 95% RH
[127 to 219V AC (L - N)]
Pollution Degree
Over Voltage 105 to 125% of Un
For PCB 2
[242 to 288V AC (L - N)]
For Product 3
Phase Sequence Yes
Degree of Protection Devices IP20
Phase Failure Yes
Phase Asymmetry >10%
Mechanical Specifications

Mounting DIN Rail


Weight 150 gms

www.selec.com 1
VPRA2M Voltage Protection Relay

Dimensions Compliance

35mm Applicable EMI / EMC Standards


Product Standard : IEC 60947-2
Category Reference Standards Testing Level
Electrostatic Discharge
67.5mm
IEC 61000-4-2 Level-3

45mm
90mm

Electrical Fast Transient / Brust IEC 61000-4-4 Level-3

Electromagnetic Field IEC 61000-4-3 Level-3

Surge IEC 61000-4-5 Level-3


60mm
Conducted RF IEC 61000-4-6 Level-2

Rated Power Frequency IEC 61000-4-8 Level-4


Terminal Connection
Voltage Dip / Short Interruptions IEC 61000-4-11 Level-3

Conducted Emissions CISPR-11 Class-B


26 25 28 16 15 18 Radiated Emission CISPR-22 Class-A
COM2 COM1 Emission & Immunity
NC2 NC1 IEC 61326-1
NO2 NO1 Safety IEC 61010-1

Ordering Information
N L3 L2 P L1 Product Code Operating Range Certification

VPRA2M-CE 127 to 288V AC


Note: Short L1 and P for 1Ø - 2 Wire connection

Timing Diagram
Monitored Over trip
~
3 Supply } Hysteresis
Phases reversed
L1 - N
L2 - N
Phase failure
L3 - N
Neutral loss
N
} Hysteresis
Under trip

Output

Td T t T t tr t T t tr
Td = Power on delay
T = Trip time delay + Response time (tr)
tr = Response time
t = Recovery delay

www.selec.com 2

You might also like