Power Factor Controller 9055
Power Factor Controller 9055
MODEL - PFC9055
INDEX
1. GENERAL FEATURE
2. ALARM FUNCTIONS
3. WIRING DIAGRAM
5. CONTROL OPERATIONS
6. PROGRAMMING INSTRUCTIONS
8. TECHNICAL SPECIFICATION
3
Installation
General consideration
The meter is panel mountable and fits into a cut out of 138 X 138 mm
dimension. Place the meter through the panel cut out and fix the mounting
clamps provided with the meter on each side of the meter. Tighten the fixing
clamps with limit amount of force so as to hold the meter firmly.
The power factor controller is used to measure power factor, when
mounted in instrument panels and is to be installed only by trained
electricians and technicians. The PT’s and CT’s used for measurement
should be of instrument class 1 or better for accurate measurement
results. Also PT’s and CT’s should have adequate VA rating to support the
burden on the secondaries.
4
2. ALARM FUNCTIONS
After all outputs are ON, required kVAr(Lag) > 70% of 1st
capacitor value, the alarm LED will be ON and the display shows ALr 01
After all outputs are OFF, required kVAr(Lead) > 70% of 1st
capacitor value, the alarm relay will be ON and the display shows ALr 02
Note
Index (#) key is used to acknowledge the alarm relay.
5
UPPER TERMINALS
M
IB
L
The CT must be placed at any point on the entrance of the power system
where the whole current consumed by both load and capacitors can be
measured.
M
CT
L
M
Capacitor
Capacitor
M
CT CT
Load
Load
L L
Load
Capacitor
System works
normally
All the capacitors are None of the capacitors
connected. The power are connected - No
system may be over compensation for PF
compensated
7
2 4 6 8 1 2 4 5 7 8
M L
R
IR CT’s
M L
Y
IY TO Load
B M L
IB
N
1/5 Amp
110/415 VAC
NO NO NO NO NO NO
C C 7 8 9 10 11 12
C C 1 2 3 4 5 6 NC P NO
NO NO NO NO NO NO ALARM
8
Wiring Diagram
b) Three phase four wire HT systems (3 watt meter measurement)
Voltage Input : 110V AC RMS (L-L) (-20% to +10%)
Current Input : 5/1A provided through 3 CT’s
2 4 6 8 1 2 4 5 7 8
M L
R
IR CT’s
M L
Y
IY
B M L
IB
N
110/415 VAC 1/5 Amp
NO NO NO NO NO NO
C C 7 8 9 10 11 12
C C 1 2 3 4 5 6 NC P NO
NO NO NO NO NO NO ALARM
9
Wiring Diagram
C) TThree phase three wire HT systems (2 watt meter measurement)
Voltage Input : 110 VAC (L - L)(Through PT)
Current input : 5/1A provided through 2 CT’sWir
2 4 6 8 1 2 4 5 7 8
M L
R
IR CT’s
Y
IY
B M L
IB
110/415 VAC 1/5 Amp
NO NO NO NO NO NO
C C 7 8 9 10 11 12
C C 1 2 3 4 5 6 NC P NO
NO NO NO NO NO NO ALARM
10
The three phase voltage wiring and current wiring are to be properly done
for the correct measurement. Any wrong connections done either during
installation or rewiring can produce wrong measurement.
The reverse condition occurs when the voltages R,Y & B are not con-
nected in proper sequence and also when the respective current is not given
according to its respective voltage.
240 VAC N
L
L C12
NO NO NO NO NO NO
7 8 9 10 11 12
C C
NO NO NO NO NO NO
C C 1 2 3 4 5 6 NC P NO
ALARM
240 VAC
L
L
C6
C1 C2 C3
Neutral
C1 - C12 are the coils of the contactors to which the capacitors are
connected. The coils are energised through 240 VAC supply via the output
relays.
PF CONTROLLER
0.5 “ 7
segment
red LED 8. 8. 8. 8. 8. 8. 8
Status
LED’s AUTO 1 2 3 4 5 6
MAN 7 8 9 10 11 12 ALARM
5 ↵
# 4 AUTO
MAN
The display is a 0.5” 7 segment red LED. The LED display shows
power factor, Actual kVAr, Target kVAr, Alarm status (Alr 01/Alr 02/Alr
3r/y/b/Alr 4r/y/b) and CT polarity status.
The key pad consists of four key namely index, shift, increment and enter
key. These keys are used to program various control parameters and switch
on/off the capacitors in manual mode.
5. Control operations
The power factor controller is provided with two type of control modes
namely Auto mode and Manual mode. The control mode is selected by
pressing ↵ key in run mode. The AUTO or MAN LED illuminates
Auto/man
according to the mode of control selected.
Auto mode
The power factor controller calculates the reactive power (kVAr)
and power factor (cosφ ) from the voltage and current inputs. It also
computes the reactive power necessary for the target PF. When required
reactive power exceeds the 70% of kVAr (lag) value of the smallest ca-
pacitor in the network, the capacitor stages are automatically connected.
Similarly when the required reactive power exceeds the 70% of kVAr
(lead) value of the smallest capacitor in the network, the capacitor stages
are automatically disconnected.
Manual mode
In manual operation, the capacitor banks can be connected/disconnected
irrespective of system power factor and setting. The capacitors are discon-
6. Programming Instructions
The power factor controller is provided with four keys for program-
ming purpose. The various functions of the keys are given below
keys together
for three seconds. The display indicates enter pass word as EP- - - -
The valid pass word set in configuration item new pass word has to
be entered by using shift, increment and enter keys (refer changing the
configuration items for using shift, increment and enter keys). After valid
pass word is entered the meter enters into program mode by showing it in
display as P r o g
Note: If the user enters the enter pass word for the first time, or if the user
fails to remember the pass word set in new pass word, the default pass
word ‘0386’ can be entered.
In program mode, the configuration items can be selected by pressing
the index (#) key. The heading displays are used to differentiate the various
configuration items.
16
7. The heading display pages for various
configuration items are given below.
PRESS 4& 5KEYS TOGETHER
EP - - - Enter pass word
The increment key increments the digit from 0 to 9 and then wraps
down to 0 once again. In setpoint and number of capacitors mode, the
increment key is used to increment the values by one. Once the required
values are set in the configuration items press the enter key to store it in the
memory. If the change is accepted the display indicates E otherwise an error
message is displayed as Err. When number of capacitors and oprating
sequence are altered, the controller restarts again.
Once the configuration items are programmed hold in the 4&5keys
together for 3 seconds to come back to normal operating mode.
8. TECHINICAL SPECIFICATION
Type : ICD MAKE MICROCONTROLLER
BASED POWER FACTOR CONTROLLER
Model : PFC 9055
Voltage Circuit
Rated voltage : 415 V AC 3 phase R, Y & B phase for LT
110 VAC 3 phase R, Y & B phase for HT
Tolerance : -20% to 10%
Frequency : 40.00 to 60.00 Hz
Current Circuit
Rated current : 1A/5A 3phase, R,Y & B
Burden : Less than 0.5VA
Isolation : available through CT
Power Factor Measurement
1) Un- balanced load : From a 3phase voltage & 3 phase current
PF is computed
2) Balanced load : Using line to line voltage and current, PF is
computed
Indicating accuracy (PF) : ± 1% of reading + 2 least digit
Display parameter : Average P.F, Total kVAr, kVar required to
reach target P.F, CT NIL & Alarm status
18