Chiller Unit Cost
Chiller Unit Cost
Building codes or other considerations may dictate the need for operating personnel. If this is the case, personnel costs must be
included. And don't forget to add the energy and water prices to the energy consumption rate of each chiller alternative on a
"level playing field" basis. Maintenance costs for screw and centrifugal chillers are typically lower than for absorption chillers,
since these chillers require more frequent replacement of mechanical components, tube stresses are higher, and there are
simply more tubes to replace. Costs for engine-driven chillers are even higher since they require engine maintenance in addition
to the same maintenance costs as an electric chiller.
In the absence of current, project-specific maintenance costs, these two charts and tables can be used to estimate annual
maintenance costs of non-CFC chillers.
http://tristate.apogee.net/cool/cmomc.asp 11/2/2009
Compare - Operating and Maintenance Costs - Chillers Page 2 of 3
With natural gas engine-driven chillers, engine maintenance is a costly item. The engine vibrations affect tube bundles and
compressor shaft seals. Higher speed (3,600 rpm) engines are less reliable than lower speed (1,200 rpm) engines. All spark-
ignited natural gas engines used on chillers require periodic service, (including spark plug and lubrication oil changes) every 500
to 750 hours of service. The technicians that would normally service the chiller may not be qualified to service the engine.
Multiple vendor responsibilities between the engine, controls, and chiller suppliers tends to complicate maintenance. In addition,
environmental legislation is likely to mandate emission controls which current engines may not be able to meet.
Engine maintenance is directly proportional to the operating (running) hours per year. Depending on the engine, a major overhaul
or engine replacement will be needed after a certain number of hours. This typically ranges from 8,000 hours on the relatively
high-speed 3,600 rpm automotive-type engines to 24,000 hours on 1,200 rpm industrial-grade engines. The engine maintenance
cost should be added to the maintenance costs of a like capacity electric chiller and include complete engine-only service plus a
sinking fund for overhaul and engine replacement.
Natural gas engine maintenance costs typically range from $0.006 to $0.020 and the average is $0.012 per ton per operating
hour. Add the engine maintenance cost ($ per ton per operating hour x chiller capacity x operating hours per year) to the
maintenance costs of a similarly sized electric chiller ($ per ton-year x chiller tons capacity). This total will include the chiller and
the full service and replacement cost of the engine.
Preventive Maintenance
http://tristate.apogee.net/cool/cmomc.asp 11/2/2009
Compare - Operating and Maintenance Costs - Chillers Page 3 of 3
With the rising costs of energy and refrigerants, plus the added concern about the environment, proper ongoing and preventive
maintenance of chilling equipment makes good sense. In most areas there are competent independent- or manufacturer-
operated service agencies who can provide this maintenance under contract. Owners or building managers with a large inventory
of equipment may choose to employ their own personnel. In all cases, technicians should be well trained in the equipment
serviced and stay up-to-date through periodic retraining.
For accurate economic comparisons, obtain local service contract quotations on the various alternatives. Lacking actual
quotations, this table provides estimates of the annual dollars per installation for single chiller installations including the cooling
tower and condenser water pump. These figures are based on median labor rates and no significant travel time. These values
also include an allowance for materials and supplies.
Multiple Units
For multiple units at a single location, make the calculation as if the units were singly installed and multiply the total dollar chiller
only maintenance cost of all units (not including gas engine maintenance) by a 0.80 multiplier for two units at single location, or a
0.70 multiplier for three or more units at single location. For engine-driven chillers, add in the engine-only maintenance costs.