MG LFP 24V Technical Specification en 1.2.0.0
MG LFP 24V Technical Specification en 1.2.0.0
- Technical specifications -
MGLFP24x230 (LFP 230Ah)
MGLFP24x280 (LFP 280Ah)
MGLFP24x304 (LFP 304Ah)
www.mgenergysystems.eu
Innovation in energy storage
Technical specifications
MGLFP24x230 MGLFP24x280 MGLFP24x304
Technical specifications
25.6 V / 230 Ah 25.6 V / 280 Ah 25.6 V / 304 Ah
Technology Lithium-Ion next generation LiFePo4
Cell configuration 8S1P
Nominal voltage 25.6 V
Nominal capacity 230 Ah 280 Ah 304 Ah
Nominal energy 5.8 kWh 7.2 kWh 7.8 kWh
Cycle Life DOD 80% 1 > 3500 > 3500 > 4000
Specific energy 2 143 Wh/kg 136 Wh/kg 145 Wh/kg
Weight 41 kg 53 kg 54 kg
Discharge 5
Discharge cut-off voltage 24.0 V
Recommended discharge current < 115 A (< 0.5C) < 140 A (< 0.5C) < 152 A (< 0.5C)
Continuous discharge current 230 A (1.0 C) 280 A (1.0 C) 304 A (1.0 C)
Maximum discharge current 3 345 A (1.5 C) 420 A (1.5 C) 456 A (1.5 C)
Fuses 4 300A, fuse inside
Charge 5
Charge voltage 28.2 V
Recommended charge current < 115 A (< 0.5C) < 140 A (< 0.5C) < 152 A (< 0.5C)
Continuous charge current 230 A (1.0 C) 280 A (1.0 C) 304 A (1.0 C)
Maximum charge current (10 s) 3 345 A (1.5 C) 280 A (1.0 C) 304 A (1.0 C)
Configuration
Series configuration7 Up to 6 modules Up to 6 modules Up to 6 modules
Parallel configuration Up to 96 modules.
Environmental
Operating temperature charge 0 to +45°C
Operating temperature discharge -20 to +55°C
Recommended operating temperature 20 to +30°C
Recommended storage temperature 10 to +35°C
Humidity (non-condensing) ≤ 95 %
Mechanical
Power connections M8 stud, 20 Nm
IP-Protection class IP30
Cooling Air, convection
Dimensions ( l x h x w ) 517 x 294 x 193 mm 652 x 294 x 193 mm
Safety
Battery Management System (BMS) Integrated slave BMS
Balancing Passive
Compatible BMS master controller MG Master LV, MG Master HV
Communication CAN-Bus, RJ45 or M12 connection
Standards
EMC: Emission EN-IEC 61000-6-3:2007/A1:2011/C11:2012
EMC: Immunity EN-IEC 61000-6-1:2007
Low voltage directive EN 60335-1:2012/AC:2014
Approvals IEC-EN62619, IEC-EN62620 (ES-TRIN6)
This document is subject to changes without notification. All rights reserved. The information in this datasheet is carefully checked and is
considered to be reliable, however MG Energy Systems assumes no responsibility for any inaccuracies.
www.mgenergysystems.eu
Innovation in energy storage
Footnotes
1
End-of-Life is 70% of initial capacity at 25 °C. Cycle life is depending on the battery temperature. Higher
battery temperature will result in a lower number of cycles.
2
Including BMS and enclosure.
3
Duration is depending on battery temperature.
4
Fuses can be replaced with non-fused battery poles for high power and high voltage applications. In this case
each battery string needs to be fused elsewhere in the circuit.
5
Charge and discharge rates are depending on battery temperature and State-Of-Charge.
6
In progress for 230 Ah and 304 Ah module.
7
More than six in series on request.
www.mgenergysystems.eu