FusionModule800 Smart Small Data Center

V100R022C10
Product Description
(02233RYC&02233RYD&02233RYE&02
233RYF&02233RYH)
Issue 01
Date 2022-04-30

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2022. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://www.huawei.com
Email: [email protected]

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. i


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) About This Document

About This Document

Purpose
This document describes how to install and connect cabinets, devices, pipes, and cables for
the FusionModule800 Smart Small Data Center (smart module for short), and how to
commission, operate, and maintain the product, providing operation guidance and technical
support for onsite installation personnel and technical support engineers.

Intended Audience
This document is intended for:
 Hardware installation engineers
 Technical support engineers
 Commissioning engineers
 Maintenance engineers

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided, could
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to personal injury.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. ii


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) About This Document

Symbol Description

Supplements the important information in the main text.


NOTE is used to address information not related to personal injury,
equipment damage, and environment deterioration.

Issue 01 (2022-04-30)
This issue is the first official release.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. iii


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) Contents

Contents

About This Document .................................................................................................................... ii


1 Product Description ...................................................................................................................... 1
1.1 Positioning .................................................................................................................................................................... 1
1.2 Features ......................................................................................................................................................................... 3
1.3 Typical Application Scenarios and Configurations ....................................................................................................... 5
1.3.1 Typical Scenarios ....................................................................................................................................................... 5
1.3.2 Single-Row Cold and Hot Aisle Containment ........................................................................................................... 5
1.3.3 Typical Configurations .............................................................................................................................................. 7

2 System Architecture .................................................................................................................... 11


2.1 Structure System ......................................................................................................................................................... 11
2.1.1 Cabinet ..................................................................................................................................................................... 11
2.1.2 Converged Cabinet .................................................................................................................................................. 13
2.1.3 Components of Single-Row Cold and Hot Aisle Containment ................................................................................ 15
2.1.3.1 Layout of Single-Row Cold and Hot Aisle Containment ...................................................................................... 15
2.1.3.2 Cabinet Door......................................................................................................................................................... 15
2.1.3.3 Cable Troughs ....................................................................................................................................................... 16
2.2 Power Supply and Distribution System ...................................................................................................................... 17
2.2.1 Technical Specifications .......................................................................................................................................... 18
2.2.2 Working Principles .................................................................................................................................................. 19
2.2.3 Key Hardware Devices ............................................................................................................................................ 20
2.2.3.1 Power Distribution Module................................................................................................................................... 20
2.2.3.2 UPS2000-H-10 kVA ............................................................................................................................................. 21
2.2.3.3 UPS2000-G-20 kVA ............................................................................................................................................. 24
2.2.3.4 Lithium Battery SmartLi-ESM-24020P1 .............................................................................................................. 27
2.2.3.5 BBB Boxes ........................................................................................................................................................... 29
2.2.3.6 Battery .................................................................................................................................................................. 30
2.2.3.7 Battery Pack .......................................................................................................................................................... 32
2.2.3.8 PDU2000 .............................................................................................................................................................. 32
2.2.3.8.1 Basic PDU2000 ................................................................................................................................................. 32
2.2.3.8.2 Monitoring PDU2000 ........................................................................................................................................ 33
2.2.3.9 MCCB Subrack ..................................................................................................................................................... 34
2.2.3.10 Smart Meter ........................................................................................................................................................ 35

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. iv


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) Contents

2.2.3.11 ATS Power Distribution Module ......................................................................................................................... 37


2.3 Cooling System........................................................................................................................................................... 39
2.3.1 Technical Specifications .......................................................................................................................................... 39
2.3.2 Application Conditions ............................................................................................................................................ 42
2.3.3 Key Hardware Devices ............................................................................................................................................ 44
2.3.3.1 Indoor Unit............................................................................................................................................................ 44
2.3.3.2 Outdoor Unit ......................................................................................................................................................... 44
2.3.3.3 Fan Subrack .......................................................................................................................................................... 46
2.4 Management System ................................................................................................................................................... 47
2.4.1 Overview ................................................................................................................................................................. 47
2.4.2 System Functions ..................................................................................................................................................... 48
2.4.2.1 Monitoring ............................................................................................................................................................ 48
2.4.2.2 App View .............................................................................................................................................................. 49
2.4.2.3 Alarm .................................................................................................................................................................... 49
2.4.2.4 Historical Data Query ........................................................................................................................................... 49
2.4.2.5 Linkage Control .................................................................................................................................................... 49
2.4.3 Key Hardware Devices ............................................................................................................................................ 50
2.4.3.1 ECC800-Pro.......................................................................................................................................................... 50
2.4.3.1.1 Product Configuration........................................................................................................................................ 50
2.4.3.1.2 Main Control Module ........................................................................................................................................ 52
2.4.3.1.3 PSU .................................................................................................................................................................... 60
2.4.3.2 Smart Cooling Product Control Unit .................................................................................................................... 61
2.4.3.3 PAD....................................................................................................................................................................... 61
2.4.3.4 WiFi Module ......................................................................................................................................................... 62
2.4.3.5 UIM20A Expansion Module ................................................................................................................................. 63
2.4.3.6 ETH Converter...................................................................................................................................................... 67
2.4.3.7 Smart ETH Gateway ............................................................................................................................................. 68
2.4.3.8 (Optional) eLight (52221421) ............................................................................................................................... 70
2.4.3.9 Environment Monitoring System .......................................................................................................................... 73
2.4.3.9.1 WLDS900 Water Sensor (33010352) ................................................................................................................ 73
2.4.3.9.2 Electrode Water Sensor (33010444) .................................................................................................................. 73
2.4.3.9.3 T/H Sensor (02312PBL) .................................................................................................................................... 74
2.4.3.9.4 Temperature Sensor (33010348) ........................................................................................................................ 75
2.4.3.9.5 Ambient T/H Sensor (33010516) ....................................................................................................................... 76
2.4.3.9.6 Smoke Detector (33010293) .............................................................................................................................. 77
2.4.3.10 Cabinet Electronic Clasp Lock ........................................................................................................................... 78
2.4.3.11 Aisle Access Control System .............................................................................................................................. 80
2.4.3.11.1 Access Actuator ................................................................................................................................................ 81
2.4.3.11.2 Fingerprint and Card Reader with a Keypad .................................................................................................... 85
2.4.3.11.3 Fingerprint and Card Reader ............................................................................................................................ 86
2.4.3.11.4 Card Reader with a Keypad ............................................................................................................................. 87
2.4.3.11.5 Magnetic Lock ................................................................................................................................................. 88

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. v


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) Contents

2.4.3.12 Video Management System ................................................................................................................................ 89


2.4.3.12.1 Camera ............................................................................................................................................................. 89
2.4.3.12.2 IVS1800 ........................................................................................................................................................... 90
2.4.4 NetEco ..................................................................................................................................................................... 92
2.4.4.1 System Overview .................................................................................................................................................. 92
2.4.4.2 Server .................................................................................................................................................................... 92
2.4.4.3 LAN Switch .......................................................................................................................................................... 92
2.4.5 Edge Data Center Management System................................................................................................................... 93
2.5 Surge Protection and Grounding System .................................................................................................................... 93
2.5.1 Surge Protection Solution ........................................................................................................................................ 93
2.5.2 Grounding Solution ................................................................................................................................................. 93
2.6 Integrated Cabling System .......................................................................................................................................... 94
2.7 Fire Extinguishing System .......................................................................................................................................... 95

3 Technical Specifications ............................................................................................................ 97


A Acronyms and Abbreviations ................................................................................................ 100

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. vi


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

1 Product Description

1.1 Positioning
The FusionModule800 is a smart small data center solution applied to air cooled scenarios
where the equipment room area is less than 40 m2. This solution mainly applies to city-,
district-, and county-level data centers of the government vertical industry, small-sized
second-level branches and large-sized offices in the financial industry, and equipment rooms
of small- and medium-sized enterprises. The following figure shows the position of the
FusionModule800 in the product family.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 1


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

Figure 1-1 Position of the FusionModule800 in the financial industry

(1) FusionModule5000 (2) FusionModule2000


(3) FusionModule800 (4) FusionModule500

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 2


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

Figure 1-2 Position of the FusionModule800 in the government vertical industry

(1) FusionModule5000 (2) FusionModule2000


(3) FusionModule800 (4) FusionModule500

1.2 Features
The FusionModule800 is a next-generation smart modular data center. It features integration,
safety, reliability, small footprint, energy conservation, easy and quick installation, compatible
structure, rapid and flexible deployment, and comprehensive monitoring. The Converged
Cabinet integrates the uninterruptible power system (UPS), power distribution, smart cooling
product, and management system.

Integration
The smart module integrates the cabinet system, power supply and distribution system,
cooling system, management system, surge protection and grounding system, integrated
cabling system, and fire extinguishing system. It adopts a modular and integrated design to
provide a comprehensive solution.

Safety and Reliability


 Electrical and extra-low voltage (ELV) cables are routed separately to minimize
electromagnetic interference.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 3


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

 UPSs work in 1+1 redundancy mode to improve the system reliability.


 Each UPS is equipped with a manual maintenance bypass switch. When the smart
module is working properly, the switch is turned off to prevent electrical accidents
caused by misoperations.
 When the cooling system is faulty due to a power failure, the FusionModule800 uses the
equipment room environment to facilitate heat dissipation. In this way, the ambient
temperature of the equipment can be maintained in a period of time to avoid abrupt
temperature increase. This ensures the safe operation of servers and equipment until the
cooling system recovers.

Small Footprint and Energy Conservation


 The equipment room can be renovated from an office building room.
 The smart module can be directly installed on a concrete floor in a building, which
simplifies external engineering.
 The delivery cycle is short. The smart module can be installed and commissioned
quickly within three person-days (for a typical 8.5 kW/R3 module).

Easy and Quick Installation


 Standard solutions and engineering designs are adopted.
 Cabinets are assembled with the aisle containment for delivery, saving both space and
time.
 The rack-mounted smart cooling product indoor units are prefabricated, facilitating the
redundancy.

Architecture Compatibility
 The FusionModule800 supports T1, T1 low-temperature, and T3 environments.
 The FusionModule800 supports cold and hot aisle containment, saving energy and
reducing noise.
 Modular power distribution and smart cooling products facilitate flexible expansion.

Fast and Flexible Deployment


 The integrated design supports the relocation of primary equipment with offices.
 Flexible deployment based on the dimensions of the equipment room and the power
consumption of each cabinet is supported to meet the requirements of capacity
expansion.
 IT cabinets are flexibly configured with servers and storage and network devices to meet
enterprise requirements for web application and internal services and provide users with
more space.

Comprehensive Monitoring
 Various sensors monitor the functional modules in the equipment room in real time.
 The smart module provides a module-level PAD to easily manage the functional modules
locally.
 A maximum of three smart module cameras and in-room cameras can be monitored.
(Smart module cameras are installed in the smart module and the in-room cameras are
installed in the room.)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 4


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

 In-room access controllers can be monitored.


 ECC800-Pros in three smart modules can be cascaded.

1.3 Typical Application Scenarios and Configurations


1.3.1 Typical Scenarios
The solution mainly applies to government, education, medical care, transportation, energy,
finance, small- and medium-sized enterprises, and branches of large companies.
Target markets: Asia Pacific, Africa (including high-temperature areas in North Africa),
Europe, and Middle East. The 380–415 V, 3 Ph+N, 50/60 Hz power systems are supported.

1.3.2 Single-Row Cold and Hot Aisle Containment


Figure 1-3 Single-row cold and hot aisle containment

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 5


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

Figure 1-4 Layout of single-row cold and hot aisle containment

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 6


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

1.3.3 Typical Configurations


Converged Cabinet

Table 1-1 Typical configurations


Item Converged Converged Converged Converged Converged
Cabinet Cabinet Cabinet Cabinet Cabinet
Basic BC1L BC2L BC3L BC4L BC5L
config
uratio
n

BOM 02233RYC 02233RYD 02233RYE 02233RYF 02233RYH


numbe
r

Model FusionMod FusionModul FusionModul FusionModul FusionModule8


ule800-U10 e800-U102A e800-U103A1 e800-U202A 00-U203A11M
1A11ML 12ML 2ML 12ML L
IT load ≤ 10 kW ≤ 20 kW ≤ 25 kW ≤ 30 kW ≤ 40 kW
power

Aisle Single-row cold and hot aisle containment


type

IT ≤6 ≤6 ≤ 12 ≤ 12 ≤ 12 (including
cabine (including (including (including the (including the the network
t the network the network network network cabinet)
cabinet) cabinet) cabinet) cabinet)
Numb ≤ 15, including the Converged Cabinet, network cabinet, IT cabinet, and battery
er of cabinet
cabine
ts

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 7


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

Coolin One 12.5 Two 12.5 Three 12.5 Three 12.5 Five 12.5 kW
g kW kW kW kW rack-mounted
rack-mounte rack-mounte rack-mounted rack-mounted smart cooling
d smart d smart smart cooling smart cooling product indoor
cooling cooling product product units: one is
product product indoor units: indoor units: configured in
indoor unit: indoor units: two are two are the Converged
configured configured in configured in configured in Cabinet
in the the the the (without
Converged Converged Converged Converged heating and
Cabinet Cabinet Cabinet (only Cabinet (only humidification)
(without (only one one with one with , and the other
heating and with heating heating and heating and four are
humidificati and humidificatio humidificatio optional (only
on) humidificatio n), and the n), and the one with
n) other one is other one is heating and
optional. optional. humidification)
.
Power One Two Three Two Three
distrib UPS2000-H UPS2000-H- UPS2000-H-1 UPS2000-G- UPS2000-G-20
ution -10 kVA, 10 kVAs, 0 kVAs, 20 kVAs, kVAs,
lithium/lead lithium/lead- lithium/lead-a lithium/lead- lithium/lead-aci
-acid battery acid battery cid battery acid battery d battery
Backu Lead-acid battery: 15 minutes, 30 minutes, and 60 minutes
p time Lithium battery: 30 minutes, 60 minutes, 120 minutes, 180 minutes, and 240
minutes
Monit ECC800-Pro, PAD, temperature and humidity (T/H) sensor, smoke detector,
oring intelligent lock, water sensor (optional), video system (optional), and NetEco
(optional)
Fire Fire extinguishing module (optional)
exting
uishin
g
device

1. The lithium/lead-acid batteries distributed by the BC1L/BC2L/BC3L communicate with


each other through UPS.
2. The lithium/lead-acid batteries distributed by the BC4L/BC5L communicate with each
other through ECC800.

Smart Cooling System


 The cooling system uses rack-mounted air cooled DC variable frequency air conditioners
that support heating and humidification. The cooling capacity of the air conditioners is
12.5 kW under standard working conditions.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 8


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

 The air conditioners work under normal temperature (outdoor unit: –20°C to +45°C),
high temperature (outdoor unit: –10°C to +55°C), and low temperature (outdoor unit:
–40°C to +45°C). The outdoor unit can be applied in class B environment.
 If the equipment room is greater than 30 m2 or the ventilation rate is greater than 45 m3/h,
a high humidity alarm may be reported when the local ambient humidity is high (for
example, in coastal cities). In this case, a dehumidifier is needed.

Table 1-2 Typical configurations


Air Normal/Low-Temperature Air High-Temperature Air
Conditione Conditioner Conditioner
r Model

Cooling load BC1 BC2 BC3 BC4 BC5 BC1L BC2 BC3 BC4 BC
L L L L L L L L 5L
Heat 10 20 25 30 40 8 16 20 24 32
dissipation
in the
equipment
room – IT
equipment
(kW)
Heat 0.5 1 1.25 1.5 2 0.4 0.8 1.2 1.5 1.6
dissipation
in the
equipment
room – UPS
(kW)
Heat 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.0
dissipation 5
in the
equipment
room – ECC
(kW)
Module 7.02 7.02 10.8 10.8 10.8 7.02 7.02 10.8 10.8 10.
footprint 8
(m2)
Heat transfer 0.35 0.35 0.54 0.54 0.54 0.351 0.351 0.54 0.54 0.5
of the 1 1 4
building
enclosure
(kW)
Heat gain 0.16 0.16 0.24 0.24 0.24 0.16 0.16 0.24 0.24 0.2
from 4
lighting
devices
(kW)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 9


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 1 Product Description

Air Normal/Low-Temperature Air High-Temperature Air


Conditione Conditioner Conditioner
r Model

Number of 1 2 3 3 5 1 2 3 3 5
air
conditioners
(without
backup)
(PCS)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 10


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2 System Architecture

2.1 Structure System


2.1.1 Cabinet
 Cabinets are classified into the Converged Cabinet, IT cabinet, and network cabinet.
 A cabinet provides stable installation space for servers to ensure safe operation of
servers.

Figure 2-1 Cabinet

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 11


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-1 Cabinet technical specifications


Item Technical Specifications

Dimensions (H x W x D)  IT cabinet: 2000 mm x 600 mm x 1350 mm


 Network cabinet: 2000 mm x 800 mm x 1350 mm
 Converged Cabinet: 2000 mm x 600 mm x 1350 mm
 Battery cabinet (built-in): 2000 mm x 600 mm x 1350 mm
 Battery cabinet (external): 2000 mm x 600 mm x 1100 mm
NOTE
The IT cabinet, network cabinet, and Converged Cabinet consist of
cabinets and aisles. The cabinet is 1100 mm deep, and the aisle is 250
mm deep.

Reference net weight  IT cabinet: 160 kg


 Network cabinet:160 kg
 Converged Cabinet: 410 kg
Color Black
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Ventilation channel Front and rear ventilation channels
Space for installing the IT  Each cabinet provides 42 U available space, the position of
cabinet and network each U is marked on the vertical mounting bars.
cabinet  The maximum depth for installing devices inside the
cabinet is 750 mm.
 Positions for vertically installing two PDU2000s are
provided at the rear of the cabinet.
Installation mode Installed on a base (concrete floor or ESD floor)
Static load 2400 kg
Dynamic load 1000 kg
Standard IEC 60297-1
Protection level IP20

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 12


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-2 Mounting hole positions at the cabinet bottom

Table 2-2 Technical specifications of mounting holes at the cabinet bottom


Cabinet Model Mounting Hole (L x W)

IT cabinet 980 mm x 400 mm


Network cabinet 980 mm x 600 mm

2.1.2 Converged Cabinet


 The Converged Cabinet consists of the indicator module, rack-mounted UPS module,
input and output power distribution module, monitoring module, smart cooling product
control unit, and rack-mounted smart cooling product.
 The Converged Cabinet has five different configurations. The modules are installed in
different positions in the Converged Cabinet based on the configurations.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 13


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-3 Modules in the Converged Cabinet (BC1L)

(1) Power distribution module (2) UPS2000 (3)


ECC800-Pro
(4) Smart cooling product control (5) Smart cooling product indoor -
unit unit

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 14


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.1.3 Components of Single-Row Cold and Hot Aisle


Containment
The components of single-row aisle containment include an enclosed framework, door
components, and binding plates (or M-shaped cable troughs).

2.1.3.1 Layout of Single-Row Cold and Hot Aisle Containment

Figure 2-4 Layout of single-row cold and hot aisle containment

2.1.3.2 Cabinet Door


 In cold and hot aisle containment, a sealed glass door is configured at the front and a
sealed sheet metal door at the rear.
 By default, the front and rear doors of a cabinet are equipped with electronic clasp locks,
which can be unlocked only by using dedicated keys.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 15


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-5 Front door

Figure 2-6 Rear door

2.1.3.3 Cable Troughs


 Cable troughs are clamped one by one to form a whole. A cable trough is assembled by
clamping two side panels, one pallet, and one baffle (used to separate ELV optical fiber
cables from ELV network cables and electrical route A from electrical route B).
 Signal cables and power cables are routed in different cable troughs to separate electrical
cables from ELV cables.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 16


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

 Signal cables are installed on the top of the front door of the cabinet, and power cables
are installed on the top of the rear door of the cabinet.
 Cable troughs are installed on the top of cabinets for routing cables.

Figure 2-7 Cable trough

2.2 Power Supply and Distribution System


 The Converged Cabinet houses the UPS input and output, IT load, smart cooling product
power distribution, and management system power distribution, and supports single and
dual power inputs.
 The rack-mounted power distribution module consists of the surge protective device
(SPD), UPS input, output, and maintenance bypass, power supply to IT loads, and smart
cooling products. The ATS power distribution module is configured in dual-power
supply scenarios.
 N and N+1 UPS systems are supported, and 10 kVA and 20 kVA UPSs can be selected
based on the actual load power. The power distribution module for IT loads supports a
maximum of 12 cabinets. Choose an appropriate power distribution module based on the
load configuration.
 The air cooled smart cooling product consists of the indoor unit and outdoor unit and is
supplied with mains power.
 The management system consists of the ECC800-Pro, IVS1800 (optional), camera
(optional), cabinet electronic clasp lock, temperature sensor, temperature and humidity
sensor (T/H sensor), smoke detector, and water sensor. They are powered by the power
supply and distribution system.
 240 V lithium batteries or lead-acid batteries are configured.
 The battery cabinet can be deployed inside or outside the smart module. It uses the
battery cabinet tray of the smart module 3.0 and is compatible with 26 Ah, 40 Ah, 65 Ah,
and 100 Ah batteries. The battery input switch and intelligent battery monitoring are
included.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 17


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.2.1 Technical Specifications


Table 2-3 Technical specifications
Category Item Specifications

Power supply Input voltage range 342–456 V


Input frequency 50/60 Hz (±10 Hz)
Power Maximum power  Normal temperature and low
consumption of a single IT temperature: 7 kW
cabinet  High temperature: 6 kW
Power supply Single power supply Supported
mode
Dual power supplies Supported
UPS selection  UPS2000-H-10 kVA
 UPS2000-G-10 kVA
 UPS2000-G-20 kVA
Power supply and Normal temperature: N/N+1
distribution mode
Power system 380 V/400 V/415 V; 50/60 Hz; 3
Ph+N+PE
PDU2000 Input voltage range 187–264 V AC, 1 Ph
Maximum input current 32 A

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 18


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.2.2 Working Principles


Conceptual Diagram for the N Power Distribution System

Figure 2-8 Conceptual diagram for the N power distribution system

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 19


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Conceptual Diagram for the N+1 Power Distribution System

Figure 2-9 Conceptual diagram for the N+1 power distribution system

2.2.3 Key Hardware Devices


2.2.3.1 Power Distribution Module

Table 2-4 Power distribution module specifications


Item PDU1 PDU2 PDU3 PDU4 PDU5 PDU6
(BC1L) (BC2L) (BC3L) (BC4L) (BC5L) (BC5L)

Maximum 20 kW 20 kW 25 kW 30 kW 40 kW 40 kW
load

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 20


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item PDU1 PDU2 PDU3 PDU4 PDU5 PDU6


(BC1L) (BC2L) (BC3L) (BC4L) (BC5L) (BC5L)

General 125 125 A/3P 125 A/3P 125 A/3P / 250 A/3P
input A/3P
UPS input 63 A/1P 63 A/1P 63 A/3P 63 A/3P 63 A/3P /
UPS 63 A/1P 63 A/1P 63 A/1P 63 A/3P 63 A/3P /
output
UPS 125 125 A/2P 125 A/2P 63 A/4P 125 A/4P /
bypass A/2P
Power Indoor Indoor Indoor Indoor unit: Indoor /
distributio unit: 32 unit: 32 unit: 32 32 A/1P unit: 32
n for A/1P A/1P A/1P Outdoor A/1P
smart Outdoor Outdoor Outdoor unit: 40 Outdoor
cooling unit: 40 unit: 40 unit: 40 A/1P unit: 40
products A/1P A/1P A/1P A/1P
IT power 40 A/1P 40 A/1P 40 A/1P 40 A/1P 40 A/1P /
distributio
n

2.2.3.2 UPS2000-H-10 kVA


The UPS2000-H-10 kVA can be used to deploy a minimum uninterruptible power supply
system. The UPS contains main power circuits such as rectifier circuit, inverter circuit, and
bypass circuit, as well as extra-low voltage (ELV) circuits such as the monitoring circuit and
parallel control circuit. Its external ports include power input and output ports, parallel ports,
communications ports, and communications slots.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 21


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-10 Appearance

Figure 2-11 Front and rear views

(1) Button (2) Indicators (3) Labela (4) Battery ports


(5) AC input ports (6) AC output (7) Battery (8) RESET button

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 22


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

ports temperature sensor


port
(9) USB port (10) (11) COM3_IN port (12) Parallel ports
BATT.COM1
port
(13) Optional card (14) (15) COM2/CAN (16) Maintenance
slot COM3_OUT port bypass port (MBS)
port
(17) Emergency
power-off (EPO) port

a: Scan the QR codes close to the SN to download the app, connect to the WiFi network, and view
documents such as user manual and quick guide. The information on the label is for reference only. The
actual parameters may vary.

Table 2-5 Technical specifications


Item Specifications

Rated capacity 10 kVA


Input power cable  1 Ph (L/N) + PE, single-phase input
 3 Ph (L1/L2/L3/N) + PE, three-phase input
Input power factor > 0.99
Output power factor 1
Rated input voltage  208 V AC/220 V AC/230 V AC/240 V AC (single-phase
input)
 380 V AC/400 V AC/415 V AC (three-phase input)
Input voltage range  Single-phase 80–280 V AC (When the ambient
temperature ranges from 0°C to 40°C, the load is linearly
derated from 100% to 40% when the voltage ranges from
80 V AC to 176 V AC.)
 Three-phase 138–485 V AC (When the ambient
temperature ranges from 0°C to 40°C, the load is linearly
derated from 100% to 40% when the voltage ranges from
138 V AC to 305 V AC.)
Rated output voltage 220 V AC/230 V AC/240 V AC
Output voltage precision ±1%
System efficiency 96% (maximum)
Dimensions (H x W x D) 86 mm x 430 mm x 514 mm
Weight 17 kg
IP rating IP20

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 23


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.2.3.3 UPS2000-G-20 kVA

Figure 2-12 Appearance

The UPS2000-G-20 kVA is an online transformerless UPS. It consists of main power circuits
such as EMI and PFC/INV, and the monitoring unit. The UPS supports lead-acid battery input,
and multiple UPSs can be connected in parallel. The UPS provides USB, RS232, and RS485
ports.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 24


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-13 Front and rear views of the UPS2000-G-20 kVA

(1) Control panel (2) AC input (3) Battery ports (4) EPO port
ports (mains and
bypass)
(5) Maintenance (6) Parallel (7) CAN (8) USB port
bypass port (MBS) ports communications ports (protected by a
(MON1 & MON2) security mechanism)
(9) Battery (10) Optional (11) AC output ports (pL
temperature sensor card slot & sL)
port

It is recommended that the length of the cable connected to the MBS port be less than or equal to 10 m.

Table 2-6 Technical specifications


Item Specifications

Rated capacity 20 kVA


Input power cable  1 Ph (L/N) + PE, single-phase input
 3 Ph (L1/L2/L3/N) + PE, three-phase input
Input power factor > 0.99

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 25


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Output power factor 0.9


Rated input voltage  208 V AC/220 V AC/230 V AC/240 V AC (single-phase
input)
 380 V AC/400 V AC/415 V AC (three-phase input)
Input voltage range  Single-phase 80–280 V AC (When the voltage ranges
from 80 V AC to 176 V AC, the load power is linearly
derated to 40%–100%.)
 Three-phase 138–485 V AC (When the voltage ranges
from 138 V AC to 305 V AC, the load power is linearly
derated to 40%–100%.)
Rated output voltage  208 V AC/220 V AC/230 V AC/240 V AC (single-phase
output; a voltage system can be selected by setting a
voltage level on the LCD.)
 380 V AC/400 V AC/415 V AC (three-phase output; a
voltage system can be selected by setting a voltage level
on the LCD.)
Output voltage precision ±1%
System efficiency 95%
Dimensions (H x W x D) 430 mm x 130 mm x 757 mm
Weight 32 kg
IP rating IP20

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 26


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.2.3.4 Lithium Battery SmartLi-ESM-24020P1

Figure 2-14 Lithium battery appearance

 The lithium battery uses lithium cells with superior charge and discharge characteristics
and high cycle performance to provide comprehensive battery management. It provides
comprehensive battery management functions to implement overcharge, overdischarge,
and overtemperature protection.
 Management functions:
− Detects the cell voltage, current, and temperature.
− Detects the state of health (SOH) of the lithium battery module and reports the
result to the network management system (NMS).
− Detects the state of charge (SOC) of the lithium battery module.
− Counts the number of charge and discharge cycles.
− Detects faults in certain key circuits (such as charging, discharging, and protection
circuits) and reports alarms.
− Stores historical data.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 27


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-15 SmartLi-ESM-24020P1 appearance

(1) Running (2) Alarm indicator (3) Activate button (4) Fault indicator
indicator
(5) WiFi indicator (6) Battery SOC (7) Labela (8) Power output
indicator ports
(9) AC activation (10) WiFi restart (11) Battery parallel (12) Network ports
port button ports
(13) Dry contacts (14) Intelligent slot

a: This area shows the SN and QR code. Scan the QR code to download the app, connect to the WiFi
network, and view documents such as user manual and quick guide.

Table 2-7 Technical specifications


Item Specifications

Dimensions (H x W x D) 160 mm × 442 mm × 520 mm (excluding mounting ears)


Weight 53 kg
Nominal voltage 240 V DC
Operating voltage range 70–320 V DC
Rated capacity 20 Ah
Maximum charge/discharge 20 A/40 A@35ºC
current

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 28


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Cycle life 2500 [email protected]/1C, 85% DOD, 70% EOL, 35ºC


Operating temperature 0–40ºC: not derated; 40ºC–50ºC: linearly derated
Storage temperature 0–60ºC
Transport temperature –40°C to +60°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m
0–1000 m: not derated; above 1000 m: derated as specified in IEC 62040-3
Maximum number of 16
batteries connected in
parallel
IP rating IP20

2.2.3.5 BBB Boxes


The BBB box converges two to four battery outputs into one output and connects to the UPS.

Figure 2-16 BBB box appearance

Figure 2-17 Rear ports of the BBB box

(1) BBB (2) BBB box (3) Battery module (4) BBB box (5) BBB box

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 29


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

box switch ground ports connection ports output ports (+) output ports (–)

2.2.3.6 Battery
 Lead-acid batteries are placed in the battery cabinet.
 A battery cabinet provides space for installing batteries and routing battery cables in a
data center. The battery cabinet can be deployed inside or outside the smart module. A
maximum of two battery cabinets can be deployed inside the smart module.
 Battery cabinets are classified into master cabinets and slave cabinets. Conversion
copper bars are required for the input and output of circuit breakers in the master cabinet.
 The required battery backup time is 15 minutes or 30 minutes.

Figure 2-18 Battery cabinet

Table 2-8 Battery cabinet technical specifications


Item Technical Specifications

Dimensions (H x W x D)  Deployed inside the smart module: 2000 mm x 600 mm x


1350 mm
 Deployed outside the smart module: 2000 mm x 600 mm x
1100 mm
Color Black
Material High-intensity class A carbon cold rolled steel plate and
zinc-coated steel plate
Air channel Front and rear air channels
Installation space 42 U available space

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 30


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Technical Specifications

Installation mode Installed on a concrete floor or ESD floor


Weight (excluding  Deployed inside the smart module: 160 kg
batteries)  Deployed outside the smart module: 140 kg
Static load 1500 kg
Dynamic load 1000 kg
IP rating IP20

Table 2-9 Battery tray specifications


Item Technical Specifications

Dimensions (W x D) 421 mm x 930 mm

Table 2-10 Lead-acid battery specifications


Battery Battery Vendor Battery Battery Dimensions (H x W x D)
Specifi and Model Weight
cations

26 Ah Shoto 6-GFM-26 10.0 kg 172 mm x 125 mm x 165 mm


40 Ah Shoto 6-GFM-40 14.0 kg 172 mm x 165 mm x 197 mm
65 Ah Shoto 6-GFM-65 22.0 kg 214 mm x 168 mm x 258 mm
100 Ah Shoto 6-GFM-100 30.0 kg 222 mm x 174 mm x 330 mm

Table 2-11 Maximum number of batteries inside a battery cabinet


Battery Specifications Maximum Number of Batteries
Inside a Battery Cabinet

26 Ah 40
40 Ah
65 Ah 20
100 Ah

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 31


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.2.3.7 Battery Pack


 The battery pack is a lead-acid battery. It is built in the cabinet as required and occupies
3 U space.
 The battery pack provides 9 Ah power supply.

Appearance

Figure 2-19 Battery pack

Technical Specifications

Table 2-12 Battery pack specifications


Battery Pack Dimensions (L x W x H) Weight
Specifications

9 Ah 685 mm x 430 mm x 130 mm 69 kg

2.2.3.8 PDU2000
2.2.3.8.1 Basic PDU2000
By default, IEC sockets are configured for all PDU2000s. GB sockets are optional.

Figure 2-20 Full-height PDU2000

Figures provided in this document are for reference only.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 32


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-13 PDU2000 specifications


Type Model Output Port

IEC PDU2000-32-1PH-20/4-B9 20 x C13 + 4 x C19


(full-height)
GB PDU2000-32-1PH-20/4-B10 20 x 10 A + 4 x 16 A
(full-height)

2.2.3.8.2 Monitoring PDU2000


The monitoring PDU2000 accurately and effectively monitors the real-time status changes of
the current, voltage, power, and electric energy of electrical devices in the data center.
The following monitoring functions must be supported:
 Detect and display the input current.
 Detect and display the total input current.
 Detect and display the input voltage; display the voltage and current alternately.
 Provide remote input management.
 Remotely query the input voltage, total input current, input power, and input energy
through a serial port.
 Remotely query the PDU status through a serial port. The status that can be queried
includes normal input power, overcurrent, overvoltage, and undervoltage, as well as the
communication status (normal or abnormal) of the monitoring board.
 Remotely set the input overcurrent warning threshold, overvoltage alarm threshold, and
undervoltage alarm threshold through a serial port, or locally set these parameters.
 Working status indicator: The PDU has a built-in input status indicator, which indicates
the working status of the PDU.
 Input alarm: If any of input overcurrent, overvoltage, and undervoltage occur, the
working status indicator indicates the fault, and an alarm is reported over the Modbus
port.

Figure 2-21 Monitoring PDU2000

Table 2-14 Technical specifications of the monitoring PDU2000


Item Specifications

Model PDU2000-32-1PH-20/4-M1

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 33


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Function Supports single-phase 200–240 V AC power supply, twenty 10


A outputs, and four 16 A outputs.
Dimensions (H x W x D) 1732 mm x 50 mm x 45 mm
Output quantity and 20 x C13 + 4 x C19
system
Monitoring function Monitors the input power, voltage, current, power factor, and
electric energy.

2.2.3.9 MCCB Subrack


 If the Converged Cabinet is configured with the BC5L, use the molded case circuit
breaker (MCCB) subrack.
 The MCCB subrack protects cables and power equipment from surge, overload, short
circuit, and undervoltage.
 The MCCB subrack can accurately and quickly measure and calculate various electrical
parameters in the smart module.

Figure 2-22 MCCB subrack

Table 2-15
Item Specifications

Dimensions (H x W x D) 105 mm x 105 mm x 220 mm


Rated current 250 A
Rated voltage 208 V AC, 380/400/415 V AC, 660/690 V AC
Rated insulation voltage 1000 V

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 34


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Power frequency withstand 3500 V


voltage
Rated impulse withstand voltage 8 kV
Breaking capacity level M

2.2.3.10 Smart Meter


 If the Converged Cabinet is configured with BC1, BC2, BC3, or BC4, use a smart meter.
 The smart meter can accurately and quickly measure and calculate various electrical
parameters in the smart module.
 The smart meter consists of a host and a transformer. It is small and easy to install.

Figure 2-23 Smart meter host

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 35


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-24 Smart meter transformer

Table 2-16
Item Specifications

Dimensions (L x W x H)  Host: 72 mm x 76 mm x 63 mm
 Transformer: 90 mm x 68 mm x 21 mm
Measured parameters and range  Voltage: 30–600 V (line voltage), 20–400 V (phase
voltage); continuous overload: phase voltage 500 V
(continuous)
 Current: 0–250 A; continuous overload: 300 A
(continuous), 10 times the measurement range (1s)
 Single-phase power: 0–100000 W/var/VA
 Total power: 0–300000 W/var/VA
 Power factor: –1 to +1
 Frequency: 45–60 Hz
 Auxiliary power supply: 85–300 V AC or 85–350 V
DC; power consumption ≤ 2 W
Measurement precision  Current:
–10°C to +50°C: 1.0% (10–250 A), 0.1 A (less than
10 A)
–40°C to –10°C, +50°C to +70°C: 2% (10–250 A),
0.2 A (less than 10 A)
 Phase voltage: –10°C to +50°C: 0.5% (20–400 V);
–40°C to –10°C, +50 to +70°C: 1% (20–400 V)
 Power: 2.0%
 Power factor: 2.0%
 Frequency: ±0.1 Hz (45–60 Hz)
 Electricity: 2.0%

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 36


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Operating environment  Operating temperature: –40°C to +70°C


 Storage temperature: –40°C to +85°C
 Relative humidity: 5%–95% RH (non-condensing)
 Altitude: 0–4000 m. When the altitude ranges from
2000 m to 4000 m, the temperature decreases by 1ºC
for each additional 200 m.
 Service life ≥ 10 years
 Annual failure rate ≤ 1%
Safety  Withstand voltage:
AC input-communications: 3.0 kV/min, 30 mA
Power-communications: 3.0 kV/min, 30 mA
 Insulation strength: output, input, and power to the
shell > 5 MΩ
 Short-circuit protection: The power input port
supports short-circuit protection.

2.2.3.11 ATS Power Distribution Module

Figure 2-25 ATS

(1) Dual input indicator (2) Monitoring board (3) Route II switch button
(4) Route I/II status display window (5) Handle

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 37


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-26 ATS monitoring board

Table 2-17 Indicators on the monitoring board


Indic Indication Status Description
ator

(1) ATS running  Steady green: working properly


status  Steady yellow: warning or minor alarm
 Steady red: major or critical alarm
(2) ATS working  Steady green: automatic mode
mode  Steady red: manual mode, non-firefighting power
disconnection
(3) Route I power  Steady green: normal
status  Steady red: abnormal
(4) Route I switch  Steady green: route I switched on
status  Steady red: route I switched on abnormally
 Off: route I disconnected
(5) Route II switch  Steady green: route II switched on
status  Steady red: route II switched on abnormally
 Off: route II disconnected

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 38


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indic Indication Status Description


ator

(6) Route II power  Steady green: normal


status  Steady red: abnormal

2.3 Cooling System


2.3.1 Technical Specifications
All models (indoor and outdoor units) of this product meet the environmental protection
requirements. The following figure shows the environmental protection mark.

Figure 2-27 Environmental protection mark

Table 2-18 Indoor unit technical specifications


Item NetCol5000-A013HXWE1 NetCol5000-A013HX0E1
(with Heating and (without Heating and
Humidification) Humidification)

Power system 208–240 V AC, 50 Hz/60 Hz, 1Ph+N+PE/2Ph+PE


Voltage If upstream voltage fluctuation exceeds the rated voltage±10%, you are
tolerance advised to add a voltage regulator. Otherwise, the smart cooling product
will generate alarms frequently and fail to work properly.
Frequency ±3 Hz
tolerance
Certification Normal-temperature model: REACH, RoHS, CE, CCC, and CQC
Low-temperature model: REACH, RoHS, CE, CCC, CQC, EAC
High-temperature model: REACH, RoHS, CE, and SASO
Maximum 17.3 A 3.3 A
current
Cooling mode Air cooled Air cooled
Refrigerant R410A R410A

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 39


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item NetCol5000-A013HXWE1 NetCol5000-A013HX0E1


(with Heating and (without Heating and
Humidification) Humidification)

Cooling 12.5 kWa 12.5 kWa


capacity
Humidifying Available Unavailable
function
Humidification 1.0 kg/h -
capacity
Heating function Available Unavailable
Heating capacity 3 kW -
Air supply mode Horizontal flow Horizontal flow
Maximum air 2600 m3/h 2600 m3/h
volume
Condensate Available Available
pump
Power supply Single power supply Single power supply
Dimensions (H 486 mm x 442 mm x 800 mm 486 mm x 442 mm x 800 mm
x W x D)b
Package 710 mm x 610 mm x 1000 mm 710 mm x 610 mm x 1000 mm
dimensions (H x
W x D)
Net 52.6 kg/70 kg 49.4 kg/66.8 kg
weight/Gross
weightb
IP rating IP20 IP20
a: The cooling capacity of the smart cooling product is obtained when the indoor dry-bulb
temperature is 37.8°C, the indoor wet-bulb temperature is 20.8°C, and the outdoor dry-bulb
temperature is 35°C. The actual cooling capacity varies depending on the indoor and
outdoor ambient temperatures and relative humidity.
b: The dimensions, net weight, and gross weight of the indoor unit include those of the
control unit.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 40


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-19 Technical specifications for a normal-temperature outdoor unit


Item NetCol500-A018 NetCol500-A021 NetCol500-A020
(Normal-Tempera (Low-Temperatur (High-Temperatur
ture Outdoor e Outdoor Unit) e Outdoor Unit)
Unit)

Power system 208–240 V AC, 220–240 V AC, 220–240 V AC,


50/60 Hz, 1 50/60 Hz, 1 50/60 Hz, 1
PH+N+PE PH+N+PE PH+N+PE
Maximum operating 24 A 30 A 30 A
current
Number of fans 1 PCS 1 PCS 2 PCS
Dimensions (H x W 966 mm x 1057 mm 1350 mm x 1270 1327 mm x 966 mm
x D) x 339 mm mm x 730 mm x 320 mm
Package dimensions 1210 mm x 1105 1530 mm x 1355 1485 mm x 1082
(H x W x D) mm x 435 mm mm x 777 mm mm x 435 mm
Net weight/Gross 83 kg/99 kg 196 kg/229 kg 101 kg/114 kg
weight
Certification REACH, RoHS, CE, REACH, RoHS, CE, REACH, RoHS, CE,
CCC, and CQC CCC, CQC, and and SASO
EAC
Environment type Class B Class B Class B
IP rating IPX4 IPX4 IPX4

Outdoor unit application environments are classified by severity as follows:


 Class A (controlled environment): indoor environments where the ambient temperature
and humidity are controlled, including rooms where people live
 Class B (uncontrollable environment): indoor environments where the ambient
temperature and humidity are not controlled or general outdoor environments with
simple shielding measures where the humidity reaches 100% occasionally
 Class C (harsh environment): sea environments, or outdoor land environments or
environments with simple shielding measures, which are within 3.7 km away from the
sea or within 1.2 km away from a pollution source
 Class D (marine environment): environments within 500 m away from the coast

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 41


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.3.2 Application Conditions


Operating Environment

Table 2-20 Operating environment


Item Specifications

Indoor unit operating 0–40°C


temperature
Indoor unit operating 5%–95% RH (non-condensing)
humidity
Outdoor unit For high-temperature outdoor units: –10°C to +55°C
operating temperature For normal-temperature outdoor units: –20°C to +45°C
For low-temperature outdoor units: –40°C to +45°C
Storage temperature Without refrigerant: –40°C to +70°C
With refrigerant: –40°C to +55°C
Storage humidity 5%–95% RH (non-condensing)
Altitude 1000–4000 m. The performance of the smart cooling product is
derated when the altitude ranges from 1000 m to 4000 m. The
maximum outdoor operating temperature decreases 1°C and the
nominal cooling capacity decreases by 1% for each additional 200
m.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 42


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Installation Requirements

Table 2-21 Installation requirements


Installation Mode Rack-mounted

Vertical Difference  Outdoor unit placed higher than the indoor unit: ≤ 30 m
Between the Indoor and  Indoor unit placed higher than the indoor unit: ≤ 8 m
Outdoor Units

Maximum Equivalent 80 m. If the length exceeds 80 m, contact technical support.


Length of One-way Pipe

Thermal Insulation ≥ 13 mm
Foam Thickness

Water Supply The inlet water pressure should be in the range of 0.1–0.7
Requirements MPa, and the temperature should be in the range of
1°C–40°C.
The wet film humidifier should use tap water that meets the
following requirements:
 Non-freezing and nephelometric turbidity units (NTU) <
3
 No visible substances
 6.5 ≤ pH value ≤ 8.5
 Total hardness (in CaCO3) ≤ 450 mg/L
For details, refer to the GB 5749-2006 Standards for
Drinking Water Quality.
Drainage Requirements The distance between the upper drainage of the water pump
and the cabinet installation floor should not exceed 4 m.
(BSPT 1/2 inch drainpipe connectors with external threads
are provided in standard configuration. Drainpipes and BSPP
1/2 inch connectors with internal threads should be prepared
by the customer.)

Ports

Table 2-22 Ports


Item Specifications

Refrigerant gas pipe  L ≤ 60 m, reserved port: 5/8 inch (15.9 mm), thread connection
 60 m < L ≤ 80 m, reserved port: 7/8 inch (22.2 mm), thread
connection
Refrigerant liquid  L ≤ 60 m, reserved port: 3/8 inch (9.52 mm), thread connection
pipe  60 m < L ≤ 80 m, reserved port: 1/2 inch (12.77 mm), thread
connection

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 43


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Humidifier water Reserved port: BSPP 1/2 inch, thread connection


inlet pipe
Pipe and cable Top or bottom routing
routing

2.3.3 Key Hardware Devices


2.3.3.1 Indoor Unit
The indoor unit consists of the EC fan, evaporator, electronic expansion valve, electric heater
(optional), wet film humidifier (optional), light load dehumidifier, and condensate pump.

Figure 2-28 Indoor unit

2.3.3.2 Outdoor Unit


The outdoor unit consists of the DC variable-frequency compressor, oil separator, gas-liquid
separator, filter dryer, fan, and refrigerant pump (only for the low-temperature outdoor unit).

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 44


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-29 Exterior of the outdoor unit of a normal-temperature model

Figure 2-30 Exterior of the outdoor unit of a high-temperature model

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 45


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-31 Exterior of the outdoor unit of a low-temperature model

2.3.3.3 Fan Subrack


 If the dew point temperature in a room is below 23°C, add a fan module to solve the
condensation problem in low-load scenarios.
 By collecting the ambient temperature and humidity, the system automatically starts and
shuts down the fan for dehumidification to save the energy.

Figure 2-32 Fan subrack

Table 2-23 Technical specifications


Item Specifications

Installation mode Rack-mounted


Installation Lower part of the rear door of the Converged Cabinet
position
Input voltage –48 V
Power supply Obtain power from the 53.5 V output port (DC_OUT1) at the
mode downstream of the ECC.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 46


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Fan quantity 2
Weight 5 kg
Dimensions (H x 250 mm x 600 mm x 50 mm
W x D)

2.4 Management System


2.4.1 Overview
 The management system implements data collection and management for various
processes and infrastructure of the smart module.
 The ECC800-Pro manages the real-time status, alarms, and configuration information
about the devices inside the smart module. It also provides a graphical user interface
(GUI) for ease of operating and maintaining devices inside the smart module.
 The management system provides a GUI to implement comprehensive management
functions based on requirements. The system can monitor the following equipment:
− Power equipment: such as the smart cooling product and UPS
− Environment equipment: such as the smoke detector and water sensor
− Video equipment: camera and VCN/IVS1800 (network video recorder). Room-level
cameras and smart module-level cameras can be monitored at the same time.
− Access control equipment: A standard room-level access management system is
integrated to manage and monitor key information such as door status, card swiping,
and permission setting.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 47


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-33 Layout of the access control system

The access actuator should be installed near the door, have a maximum of 3.5 m cabling distance away
from the magnetic lock, and have a maximum of 5 m cabling distance away from other switches and the
access control device.

2.4.2 System Functions


2.4.2.1 Monitoring
 Temperature and humidity monitoring: Detects and collects statistics on the ambient
temperature and humidity inside the smart module.
 Water leakage monitoring: Detects water leakage at the bottom of the smart module and
provides real-time alarm signals.
 Smoke monitoring: Detects smoke in the smart module and provides real-time alarm
signals.
 Power distribution monitoring: Monitors the input voltage, frequency, and current of the
UPS inside the smart module.
 Smart cooling product monitoring: Monitors the temperature and humidity of supply air
and return air in real time; allows users to configure the supply air temperature setpoint
in a unified manner so they do not need to set it for each smart cooling product; monitors
and displays the fan speed and running percentage; displays the cooling load rate in
percentage; monitors and displays the operating status of compressors.
 Video surveillance: Connects to three cameras and provides PoE power supply; accesses
real-time video images on the WebUI and invokes historical monitoring data.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 48


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.2.2 App View


 Generates a 2.5D layout view that matches the actual layout of the smart module,
including the power distribution module, IT cabinet, and T/H sensor. In addition, the
ambient temperature and humidity inside the smart module are displayed on the home
screen of the app.
 Displays the real-time status monitoring data and alarms of the aisle temperature and
humidity on the floor plan.
 Facial recognition is supported through an app installed on a tablet computer. After facial
recognition information is added, click Facial Enter to start the facial recognition. If you
do not have facial recognition permission or an error occurs during facial recognition,
you can use the user name and password login manner.
 After logging in to the app installed on the tablet, you can open the cabinet door on the
corresponding screen.

2.4.2.3 Alarm
 The system monitors the status of smart cooling products, power distribution, and
environment. If a fault or parameter error occurs, the system generates an alarm in real
time. You can view the alarm cause and solution in the alarm details.
 Alarms can be classified into four severities: critical, major, minor, and warning. The
alarm severities can be user-defined.
 Active alarms can be filtered by device and alarm severity.
 Alarms can be linked with the eLight. The eLight light colors vary with alarm severities.
 Alarm notifications can be sent by email and SMS.
 A maximum of 500 concurrent active alarms are supported.

2.4.2.4 Historical Data Query


 Historical alarm: You can view the alarms that have been generated in the system. The
historical alarm information includes the device name, alarm name, alarm severity, alarm
generation time, and alarm clearance time.
 Performance data statistics: You can view historical data of devices to help analyze data
or problems.
 Operation log: You can view logs of key operations, such as user login, parameter
modification, data export, device upgrade, and access control events.
 Data export: You can export historical data of the ECC800-Pro and some southbound
devices.

2.4.2.5 Linkage Control


 Supports the linkage logic of aisle smoke alarms or high temperature alarms. By default,
the IT cabinet doors are opened through linkage by default.

The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only dry contact
alarm signals are provided.
 If the cabinet is configured with an integrated rack-mounted fire extinguishing module
and a smoke alarm is generated, the cabinet door does not bounce. If the cabinet door has
bounced, an alarm (door open alarm) is generated.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 49


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

 If the cabinet is not configured with an integrated rack-mounted fire extinguishing


module and a smoke alarm is generated, the rear door of the linked cabinet opens.

2.4.3 Key Hardware Devices


2.4.3.1 ECC800-Pro
2.4.3.1.1 Product Configuration
The ECC800-Pro data center controller is used to monitor the devices and environment in the
smart module. It consists of the power supply unit (PSU) and main control module. You can
insert and remove the PSU.

Figure 2-34 ECC800-Pro

(1) PSU (2) Main control module

Table 2-24 ECC800-Pro environmental specifications


Item Specifications

Operating temperature –20°C to +50°C


Storage temperature –40°C to +70°C
Relative humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m (When the altitude is between 3000 m and 4000 m,
the temperature decreases by 1°C for each additional 200 m.)

Table 2-25 ECC800-Pro structural specifications


Item Specifications

Dimensions (L x W x H) 442 mm x 330 mm x 43.6 mm


Weight 7.5 kg (dual power supplies + main control
module)
Color Black
Installation requirements Can be installed in a 1 U space in a standard
19-inch cabinet
Environmental protection RoHS5, REACH, WEEE

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 50


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-35 ECC800-Pro (rear view)

(1) 53.5V DC_OUT1 (2) 53.5V DC_OUT2 (3) AC_INPUT1


(4) AC_INPUT2

Power Port
The ECC800-Pro provides four power ports, including two AC input ports (AC_INPUT1 and
AC_INPUT2) and two DC output ports (DC_OUTPUT1 and DC_OUTPUT2). Table 2-26
provides the power port pin definitions.

Table 2-26 Power port pin definitions


Port Type Pin Description
sequence

AC Pin1 L
Pin2 PE
Pin3 N
DC Pin1 48V+
Pin2 48VGND

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 51


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.3.1.2 Main Control Module

Figure 2-36 ECC800-Pro collector main control module

(1) USB (2) Status indicator (3) AIDI_1 (4) AIDI_2


(5) COM1/AIDI_4 (6) COM3/12V (7) WAN1 (8) LAN1/POE
(9) LAN2/POE (10) WAN2 (11) COM4/CAN (12) COM2/AIDI_5
(13) AIDI_3 (14) DO/12V (15) RF_Z (16) WLAN
(17) 4G (18) SW button

Figure 2-37 ECC800-Pro main control module (side view)

(1) SIM card slot (2) Micro SD card slot (reserved)

Specifications

Table 2-27 Technical specifications of the ECC800-Pro main control module


Item Specifications

Power input  Supports one AC input or two AC inputs


 Rated voltage: 200–240 V AC
 Rated frequency: 50/60 Hz

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 52


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Power output  Output voltage: 42–58 V DC (rated voltage: 53.5 V DC)


 Output power of two power module supplies: 2000 W (200–240 V
AC); 940 W (linear derating at 85–175 V AC)
 Output power of a single power module supply: 1000 W (200–240 V
AC); 470 W (linear derating at 85–175 V AC)
WAN port  Supports two WAN ports. WAN1 is used to connect to the
management system, and WAN2 is used for maintenance. The ports
support autonegotiation of 10/100/1000 Mbit/s communication rates.
 Connect shielded network cables to the WAN ports.
LAN port  Supports two LAN ports, which can be connected to the LAN. The
ports support autonegotiation of 10/100/1000 Mbit/s communication
rates.
 Connect shielded network cables to the LAN ports.
RS485 serial  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)
port expansion  Four RS485 ports with the default communications rate of 9600 bit/s
 COM1–COM3 ports provide 12 V DC power.
 The power supply can be switched on or off and is on by default.
PoE expansion Supports two PoE (GE) ports for expansion of the PoE bus, and
supports network isolation and ring network.
AIDI expansion  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)
(RJ45)  Provides five universal AIDI ports for connecting to sensors such as
smoke sensors, water sensors, and NTC sensors. AIDI_1 to AIDI_3
are full-function AIDI ports, and AIDI_4 to AIDI_5 are simplified
AIDI ports without type identification.
 The power supply can be switched on or off and is on by default.
DO expansion  Output voltage: 13–15 V DC (rated voltage: 14.5 V DC)
(RJ45)  Supports one active DO port.
 The power supply can be switched on or off and is on by default.
Fault isolation There are three groups of 12 V ports. A group has a maximum current
of 660 mA, a route has a maximum current of 800 mA, and the
maximum total current is 2 A.
Group 1: AIDI_1 and DO/12V ports
Group 2: AIDI_2, COM1/AIDI_4, and COM3/12V ports
Group 3: AIDI_3 and COM2/AIDI_5 ports
Wireless Supports wireless communication that complies with IEEE802.15.4.
communication

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 53


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

4G Supports the 4G module, SMS sending, and 3G communication, and


provides a standard SIM card slot.
1. China: 2G and 4G networks support China Unicom or China Mobile
SIM cards, and 3G networks support only China Unicom SIM cards.
2. Outside China: Select SIM cards according to the following wireless
modes and frequency bands:
 4G: wireless mode (FDD-LTE and TDD-LTE), coverage
frequency band (B1, B3, B5, B7, B8, and B20)
 3G: wireless mode (WCDMA), coverage frequency bands (B38,
B40, and B41)
 2G: wireless mode (GSM), coverage frequency band (900/1800
MHz)
NOTE
 The prerequisite for using a SIM card is that the site has signal coverage.

 Due to the performance limitation of the wireless module, China Telecom


SIM cards are not supported.

USB  Supports USB 2.0 and 5 V, 1 A power supply.


 After installing the WiFi module, connect the WiFi module to the
ECC800-Pro using the app on the mobile phone or PAD to view the
basic information about the smart module, such as layout, resources,
energy efficiency, environment, and alarms.
 You can insert a USB flash drive to export historical data and
configuration files and import configuration files.
SW button  Restores the default IP address, factory settings, and user
information.
 Supports RF_Z networking.

Table 2-28 ECC800-Pro RF_Z parameters


Item Specifications

RF_Z Operation 2405–2480 MHz


Frequency
RF_Z EIRP (max.) 8 dBm

Table 2-29 ECC800-Pro 4G parameters


Item Specifications

3G/4G operation LTE (FDD): BAND1, BAND2, BAND3, BAND4, BAND5,


frequency BAND7, BAND8, BAND20
DC-HSPA+/HSPA+/HSPA/UMTS: 850/900/1900/2100 MHz
GSM/GPRS/EDGE: 850/900/1800/1900 MHz

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 54


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

3G/4G EIRP (max.) 23 dBm

Communications Port
The ECC800-Pro provides the following communications ports. Figure 2-38 shows the pins
of the RJ45 port.

Figure 2-38 RJ45 port pins

There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN ports
(LAN1/POE and LAN2/POE).

Table 2-30 GE port pin definitions


Item Description

Pin sequence Pin1 GE1+


Pin2 GE1-
Pin3 GE2+
Pin4 GE3+
Pin5 GE3-
Pin6 GE2-
Pin7 GE4+
Pin8 GE4-
Indicator Green Linked, steady on
indicator
Yellow ACT data communication, blinking
indicator

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 55


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-31 COM1/AIDI_4, COM2/AIDI_5 port pin definitions


Item Description

Pin sequence Pin1 RS485+


Pin2 RS485-
Pin3 12V DC_OUT
Pin4 RS485+
Pin5 RS485-
Pin6 DI-
Pin7 DI+
Pin8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 2-32 COM3/12V port pin definitions


Item Description

Pin sequence Pin1 RS485+


Pin2 RS485-
Pin3 12V DC_OUT
Pin4 RS485+
Pin5 RS485-
Pin6 -
Pin7 -
Pin8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 2-33 COM4/CAN port pin definitions


Item Description

Pin sequence Pin1 RS485+


Pin2 RS485-

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 56


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Description

Pin3 -
Pin4 RS485+
Pin5 RS485-
Pin6 -
Pin7 CAN_H
Pin8 CAN_L

The following provides the AIDI_1, AIDI_2 and AIDI_3 ports pin definitions.

 Pins 1, 2, 4, and 5 identify sensor types.


 Pin 3 and Pin 8 are power output ports.
 Pin 6 and Pin 7 collect sensor data. Pin 7 can detect current type sensors (4–20 mA). Pin 6 and Pin 7
can detect the output status of passive dry contact type sensors. Pin 3 and Pin 7 can detect
temperature sensors.

Table 2-34 AIDI_1, AIDI_2 and AIDI_3 ports pin definitions


Item Description

Pin sequence Pin1 Type_1


Pin2 Type_2
Pin3 12V DC
Pin4 Type_3
Pin5 Type_4
Pin6 DI-
Pin7 DI+
Pin8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 2-35 DO/12V port pin definitions


Item Description

Pin sequence Pin1 -


Pin2 -

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 57


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Description

Pin3 12V DC_OUT


Pin4 -
Pin5 -
Pin6 DO_OUT+
Pin7 DO_OUT-
Pin8 GND
Indicator Green Power output indicator
indicator  Steady on: The 12 V DC output is normal.
 Off: No 12 V DC output is provided.

Table 2-36 USB port pin definitions


Item Description

Pin sequence Pin1 5V


Pin2 DM
Pin3 DP
Pin4 GND

Indicators

Table 2-37 Indicators on the ECC800-Pro main control module


Indicat Color Name Status Status Description
or

RUN Green Running status Steady on The power supply is normal, the
indicator program is being loaded.
Off The power supply is abnormal.
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for
intervals 1s and then off for 1s) or the
ECC800-Pro registers with the
NetEco successfully.
Blinking at The ECC800-Pro does not
short register with the NetEco (the
intervals indicator blinks at 5 Hz, on for
0.125s and then off for 0.125s).

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 58


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indicat Color Name Status Status Description


or

ALM Red Alarm indicator Steady on A system failure alarm is


generated.
Off The system is normal.
RF_Z Green Communication Blinking at A network is set up, and no
status indicator long node access is allowed (the
intervals indicator blinks at 0.5 Hz, on for
1s and then off for 1s).
Blinking at A network is set up, and node
super short access is allowed (the indicator
intervals blinks at 10 Hz, on for 0.05s and
then off for 0.05s).

SW Button

Table 2-38 SW button description


Function Operation Description Indicator Status
Description

Wireless network In non-wireless network (802.15.4) The RF_Z indicator is


RF_Z (802.15.4) pairing mode, press and hold down the blinking at super short
pairing button for 3s to 5s to enter the wireless intervals.
network pairing mode.
In wireless network (802.15.4) pairing The RF_Z indicator is
mode, press and hold down the button for blinking at long
3s to 5s to exit the pairing mode; or the intervals.
system automatically exits the pairing
mode after 30 minutes without pressing
the button.
Press and hold down the button for more The RF_Z indicator is
than 8s to clear network parameters. steady on.
WLAN enabling Press and hold down the button for 1s to None
enable WLAN.
Restoring the Press and hold down the button for 1 None
default IP address, minute.
factory settings,
and user
information

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 59


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.3.1.3 PSU

Indicator

Table 2-39 PSU indicator description


Indicator Colo Name Status Description
r

Gree Power Steady on The PSU has input power.


n indicator
Off The PSU has no input power or is
faulty.
Blinking at The PSU is being queried (the
long intervals indicator blinks at 0.5 Hz, on for 1s
and then off for 1s).
Blinking at The PSU application program is
short intervals being loaded (blinking at 4 Hz, on
for 0.125s and then off for 0.125s).
Yell Alarm Steady on Power limiting warning due to
ow indicator ambient overtemperature; protection
shutdown alarm due to ambient
overtemperature or
undertemperature
Power input overvoltage or
undervoltage protection
Reverse DC input connection
Slight current imbalance
Output overvoltage
Hibernation
Off The PSU generates no protection
alarms.
Blinking at The communication between the
long intervals PSU and the outside is interrupted
(the indicator blinks at 0.5 Hz, on
for 1s and then off for 1s).
Red Fault Steady on The PSU locks out due to output
indicator overvoltage.
The PSU has no output due to
internal faults.
Off The PSU is normal.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 60


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.3.2 Smart Cooling Product Control Unit


The control unit of the smart cooling product consists of a main control board and a display
unit that is integrated in the Converged Cabinet. The controller implements functions such as
logic control, data collection, control signal sending, alarm reporting, data storage, and
teamwork control. The smart cooling product connects to the ECC over the FE port using the
MAC protocol, and the ECC connects to the NMS to realize remote control.

Main Functions
 Single unit control: When only one unit is running, the controller provides logic control
over components in the unit to meet the indoor temperature and humidity requirements.
 Teamwork control: When multiple smart cooling products work cooperatively, the
controller optimally distributes the heat load, greatly lowering the power consumption.
Multiple smart cooling products provide backup for higher reliability.
 Remote management: You can monitor and manage one or more smart cooling products
using the remote management function provided by the Company.
 Configuration synchronization: You can synchronize parameters between smart cooling
products on the touchscreen (optional) of the Converged Cabinet, ECC800-Pro WebUI,
or ECC800-Pro app.
 One-click export: You can export the alarms and logs of a smart cooling product on the
ECC800-Pro WebUI.
 Software upgrade: You can perform a remote upgrade on the touchscreen (optional) of
the Converged Cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
 Alarm details query: You can view the possible causes of alarms and handling
suggestions on the ECC800-Pro WebUI.

2.4.3.3 PAD
The PAD allows the wireless access from the data center management system. You can
monitor the equipment in the data center and environmental parameters in real time over the
app.

Figure 2-39 PAD

Table 2-40 PAD structural specifications


Item Specifications

Dimensions (L x W x 243 mm x 164 mm x 7.8 mm


H)
Weight About 460 g

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 61


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-41 PAD technical specifications


Item Specifications

Touchscreen 10.1-inch, 1920 x 1200 resolution, IPS screen, and multi-touch


Storage  Machine: 32 GB
 Memory: 3 GB
 Extension card: Micro SD, a maximum of 256 GB
(non-standard configuration)
Button/Port  Touch button + power switch and volume button
 3.5 mm stereo headphones port
 Micro SD card port
 MicroUSB port
Camera  Rear camera: 8-megapixel, F2.4 aperture, automatic focus
 Front camera: 2-megapixel, F2.4 aperture, fixed focus
 Sensor type: BSI
 Flash: not supported
 Video recording: rear camera up to 1080 pixels at 30 FPS;
front camera up to 720 pixels at 30 FPS
 Zoom mode: digital zoom
 Photo resolution: rear camera up to 8 M (3264 x 2448
pixels); front camera up to 1.9 M (1600x1200 pixels)
Battery  Materials: Li-polymer
 Capacity: 5100 mAh (typical value) or 4980 mAh (rated
value)
 WiFi connection/web page browse time: about 6.5 hours
 Power adapter charge time: about 3.5 hours (5 V 2 A
adapter)

2.4.3.4 WiFi Module


The WiFi module provides WiFi signals for equipment such as pads and mobile phones to
interact with the host computer.

Figure 2-40 WiFi module

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 62


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-42 Technical specifications


Item Specifications

Wireless standard IEEE 802.11n, IEEE 802.11g, and IEEE 802.11b


Network  11n: up to 150 Mbps
bandwidth  11g: up to 54 Mbps
 11b: up to 11 Mbps
Frequency band 2.4–2.4835 GHz
Wireless 20 dBm (MAX EIRP)
transmission
power
Supported Windows 2000/XP/Vista/Linux/Win 7
operating system
Port USB 2.0 Hi-Speed connector
Voltage range 5.0 V DC±5%
Operating –20°C to +70°C
temperature
Storage –40°C to +90°C
temperature
Relative humidity 10%–90% RH (non-condensing)
Storage humidity 5%–90% RH (non-condensing)
Power < 0.8 W

2.4.3.5 UIM20A Expansion Module

Figure 2-41 Front panel of the UIM20A expansion module

(1) Indicators and button (2) COM1/AI/DI_1–COM8/AI/DI_8 (3) PoE

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 63


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-42 Rear panel of the UIM20A expansion module

(1) DIP switch (reserved) (2) COM_OUT (reserved) (3) COM_IN (reserved)

Table 2-43 UIM20A expansion module specifications


Item Specifications

Width 120 mm
Depth 200 mm
Height 43 mm
Operating –30°C to +65°C
temperature
Installation Installed in a 19-inch rack
requirements
Environmenta RoHS5
l protection

Specifications

Table 2-44 UIM20A technical specifications


Item Specifications

Power input Supports the RS485 or PoE power supply.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 64


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

COM/AIDI (RJ45)  Supports eight RS485 or AI/DI signal inputs.


 Can connect to sensors such as the smoke detector, water sensor,
door status sensor, and infrared sensor.
 Each port can supply power. Two RJ45 ports share one 12 V DC
power supply that is controlled independently. The maximum
output current is 900 mA when the voltage is 12 V.
(COM1/AIDI_1 and COM2/AIDI_2 form a group,
COM3/AIDI_3 and COM4/AIDI_4 form a group,
COM5/AIDI_5 and COM6/AIDI_6 form a group, and
COM7/AIDI_7 and COM8/AIDI_8 form a group).
 The 12 V DC power supply can be switched on or off and is on
by default.
PoE Connects to the ECC800 through the PoE port.
E-label 4.0 Supported

Communications Port
The following table describes the pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8.

Table 2-45 Pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8


Item Description

Pin sequence Pin 1 RS485+


Pin 2 RS485-
Pin 3 12V
Pin 4 RS485+
Pin 5 RS485-
Pin 6 D-
Pin 7 D+
Pin 8 GND

The following table describes the pin assignments for the COM_IN and COM_OUT ports.

Table 2-46 Pin assignment for the COM_IN and COM_OUT ports
Item Description

Pin sequence Pin 1 RS485+


Pin 2 RS485-

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 65


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Description

Pin 3 12 V (input power, supplying power to the module)


Pin 4 RS485+
Pin 5 RS485-
Pin 6 -
Pin 7 -
Pin 8 GND

Indicators and Buttons

Table 2-47 UIM20A indicators


Indicator Status Status Description

RUN Steady on A board application is being loaded.


Off The board is not running.
Blinking The module successfully registers with the ECC800 and the
at long software runs properly (the indicator blinks at 0.5 Hz, on for 1s
intervals and then off for 1s).
Blinking The communication is interrupted or the ECC800 is
at short unsuccessfully registered (blinking at 2.5 Hz, on for 0.2s and
intervals then off for 0.2s).
Blinking Blinking at super short intervals for 0.5s and then off for 0.5s;
last 10s (blinking at super short intervals: 10 Hz, on for 0.05s
and then off for 0.05s)
ALM Steady on A system fault alarm is raised.
Off The system is normal.

Table 2-48 BLINK button description


Function Operation Indicator Status
Description Description

Blinking Press the button for The RUN indicator blinks at super short
less than 2s. intervals for 0.5s and then off for 0.5s; last
10s (blinking at super short intervals for 10
Hz, on for 0.05s and then off for 0.05s).

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 66


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.3.6 ETH Converter


The ETH converter is used to convert the Modbus–RTU protocol or CAN protocol to the
Modbus-MAC protocol for connecting to the PoE bus.

Figure 2-43 ETH converter

(1) Status indicator (2) BLINK button (3) COM1 communications port
(4) COM2 communications port (5) 48 V power port (6) PoE port

Specifications

Table 2-49 ETH converter technical specifications


Item Specifications

Power input  DC input: terminal, with an input voltage of 36 V DC–60 V DC


 PoE power supply: one PoE port, 10/100M communication rate,
complying with IEEE802.3at
RS485/CA Provides two RS485/CAN ports. The default communications rate for the
N RS485 port is 9600 bit/s, and that for the CAN port is 125 kbit/s. Both ports
match the RJ45 terminal shared by RS485 and CAN.
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 10 seconds.
E-label Supported

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 67


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indicators

Table 2-50 ETH converter indicators


Indicato Color Name Status Description
r

PWR Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

RUN Green Operating Off The power supply is abnormal.


status
indicator Blinking at The ETH converter successfully
long intervals registers with the ECC800-Pro
and the software runs properly
(the indicator blinks at 0.5 Hz,
on for 1s and then off for 1s).
Blinking at The communication fails or the
short intervals ETH converter fails to register
with the ECC800-Pro (the
indicator blinks at 4 Hz, on for
0.125s and then off for 0.125s).
Blinking The indicator blinks at super
short intervals for 0.5s (blinking
at 10 Hz, on for 0.05s and then
off for 0.05s) and then turns off
for 0.5s. The cycle lasts for 10s.
ALM Red Alarm Steady on A system failure alarm is
indicator generated.
Off No system alarm is generated.

2.4.3.7 Smart ETH Gateway


A smart ETH gateway allows the extension of the 53.5 V DC power supply and FE
communication for the ECC800-Pro and can be flexibly deployed in a smart module.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 68


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-44 Smart ETH gateway

(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator

Specifications

Table 2-51 Technical specifications for a smart ETH gateway


Item Specifications

Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output  PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
 48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 69


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indicators

Table 2-52 Indicators on a smart ETH gateway


Indica Color Name Status Description
tor

PWR Green Power input Steady on The power input is normal.


status
indicator Off There is no power input.

RUN Green Module Off The power supply is


running abnormal.
status
indicator Blinking at The smart ETH gateway
long successfully registers with the
intervals ECC800-Pro and the software
runs properly (the indicator
blinks at 0.5 Hz, on for 1s and
then off for 1s).
Blinking The indicator blinks at super
short intervals for 0.5s
(blinking at 10 Hz, on for
0.05s and then off for 0.05s)
and then turns off for 0.5s.
The cycle lasts for 5s.
ALM Red Alarm Steady on The PoE output current is
indicator overloaded.
Off The PoE output is normal or
not connected.

2.4.3.8 (Optional) eLight (52221421)


The eLight system consists of the eLight power actuator, eLight light, and cables.

Figure 2-45 eLight light

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 70


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-46 eLight actuator

The appearance of the eLight actuator depends on the actual delivery.

Table 2-53 Actuator indicator description


Indic Color Function Statu Status Description
ator Definition s

PWR Green Power status Steady The power supply works properly.
indicator on
Off There is no power input, or the internal
power supply fails.
RUN Green Running status 0.5 Hz The software runs properly: The indicator
indicator blinks at 0.5 Hz (on for 1s and then off for
1s).
4 Hz Communication is disconnected (no
communication for 30s): The indicator
blinks at 4 Hz (on for 0.125s and off for
0.125s).
Off There is no power input, or the internal
power supply fails.

Table 2-54 Description of eLight light colors


Scenario Light Color Remarks

Not associated with Blue -


an alarm severity NOTE
On the ECC800-Pro WebUI, set Associated
Alarm Severity to None.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 71


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Scenario Light Color Remarks

Associated alarm  Mapping between smart module  Critical and major


severity alarm severities and strip light colors: alarms are
− Critical: red associated by
default. Alarms of
− Major: orange any severity can be
− Minor: yellow manually associated.
− Warning: grayish-white  When alarms of
 No alarm: off multiple severities
are generated, the
strip light displays
only the color of the
alarm with the
highest severity.
Door alarm White
eLight fault The eLight disconnects from the -
ECC800-Pro and blinks in red.

Table 2-55 eLight system technical specifications


Item Specifications

eLight power actuator  Rated input voltage: 220–240 V AC


 Frequency: 50/60 Hz
 Output: 24 V DC
 There are two output channels. The output of channel I is
connected to the RGBW light. The output voltage of
different ports is controlled based on the command from the
host to display different colors. The 24 V output can be
connected and disconnected. Channel II is the same as
channel I.
 Modbus communications protocol, RS485 port, two RJ45
ports
 Certification: CE
eLight light  Rated input voltage: 24 V DC
 Light type: RGBW LED light, in different colors depending
on commands
 Power: P ≈ 6 W/m under maximum working conditions
(RGB all on or W white light on)
 Installation mode: attached to the cabinet top or side beam
by magnet
 Certification: CE
IP rating ≥ IP20

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 72


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Operating environment  Indoor normal temperature 30°C


 Operating temperature range: 4°C to 40°C
 Humidity range: 5%–95%, non-condensing

2.4.3.9 Environment Monitoring System


2.4.3.9.1 WLDS900 Water Sensor (33010352)
The WLDS900 water sensor with the BOM number of 33010352 consists of a water detection
cable, a water detector, and a conversion cable.

Figure 2-47 WLDS900 water sensor

Table 2-56 Technical specifications of the WLDS900 water sensor


Item Specification

Operating 12 V DC (9–16 V DC)


voltage
Operating –20°C to +70°C
temperature
Storage –40°C to +85°C
temperature
Humidity 10%–80% RH (non-condensing)

2.4.3.9.2 Electrode Water Sensor (33010444)


The electrode water sensor with the BOM number of 33010444 contains electrode probes and
cables.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 73


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-48 Electrode water sensor

Table 2-57 Technical specifications of the electrode water sensor


Item Specification

Operating –40°C to +80°C


temperature
Storage –40°C to +80°C
temperature

2.4.3.9.3 T/H Sensor (02312PBL)


The T/H sensor is installed inside the cabinet to detect the temperature and humidity of the
cabinet.

Figure 2-49 T/H sensor

(1) RS485-OUT (2) RS485-IN (3) DIP switch (4) Button


(5) NTC1–3 (6) NTC4–6 (7) Display

T/H Sensor (BOM Number: 02312PBL)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 74


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-58 T/H sensor specifications


Item Temperature Humidity

Measurement range –40°C to +70°C 1%–99% RH


Measurement ≤ ±1°C (25°C) ≤ ±5% RH (25°C, 20%–80% RH)
precision
Extended Provides two RJ45 ports to connect to six NTC temperature sensors,
temperature each RJ45 port connecting to three NTC temperature sensors.
collection port
Signal port RS485
Power supply 5–16 V DC (typical value 12 V DC)
Power consumption < 280 mW
Storage –40°C to +70°C
environment
Weight About 85 g

2.4.3.9.4 Temperature Sensor (33010348)


The temperature sensor (BOM number: 33010348) is used for surface temperature
measurement, industrial process control, and measurement instruments.

Figure 2-50 Temperature sensor

Table 2-59 Temperature sensor specifications


Item Specifications

Measurement range –20ºC to +70ºC


Measurement precision ±1ºC (25ºC)
Operating temperature –10ºC to +55ºC

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 75


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Operating voltage 10–16 V DC


Storage temperature –40ºC to +70ºC

2.4.3.9.5 Ambient T/H Sensor (33010516)


 The ambient T/H sensor is installed at the remote end of the smart cooling product to
monitor the ambient temperature and humidity.
 T/H sensor configuration depends on the number of smart cooling products. (For
example, if there are three smart cooling products, three T/H sensors are configured.)

Figure 2-51 T/H sensor

The T/H sensor (BOM number: 33010516) uses an RJ45 port.

The appearance of the T/H sensor depends on the onsite delivery.

Figure 2-52 RJ45 port pins

Table 2-60 RJ45 port pin definitions


Pin Description

Pin1 or Pin 4 A
Pin2 or Pin 5 B
Pin3 V+

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 76


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Pin Description

Pin6 V-
Pin7 Reserved

Table 2-61 T/H sensor specifications


Item Specifications

Temperature measuring range –20°C to +80°C


Temperature accuracy ±0.5°C (25°C)
≤ ±1°C (full measuring range)
Operating temperature –20°C to +80°C
Operating voltage 9–16 V DC
Storage temperature –40°C to +80°C
Output Two RJ45 ports, bidirectional cascading

2.4.3.9.6 Smoke Detector (33010293)


A smoke detector detects smoke around cabinets.

Figure 2-53 Appearance of the smoke detector (JTY-GD-S839)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 77


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-54 Appearance of the smoke detector (LH-09A)

(1) Wiring terminal (2) Base


(3) Indicator

Table 2-62 Smoke detector technical specifications


Item Specifications Specifications (LH-09A)
(JTY-GD-S839)

Operating voltage 9–27 V 9–27 V


Alarm current 1–20 mA 3–8 mA
Working status Monitoring: The red Monitoring: The indicator blinks
indication indicator blinks once once every 4 to 6 seconds.
every 3 to 8 seconds. Alarm reporting: The indicator is
Alarm reporting: The red steady on.
indicator is steady on.
Operating temperature –10°C to +55°C –10°C to +55°C
Ambient humidity ≤ 95% RH ≤ 95% RH (non-condensing at
(non-condensing at 40°C±2°C)
40°C±2°C)
Dimensions (H x W x D) 31 mm x 75 mm x 51 mm 74.8 mm x 58.8 mm x 30.4 mm
(with the base)
Weight 50 g 60 g

2.4.3.10 Cabinet Electronic Clasp Lock


The cabinet electronic clasp lock is used to manage access control. It can be automatically
unlocked, or manually locked and unlocked.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 78


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-55 Cabinet electronic clasp lock

(1) LED indicator (2) DIP switch (3) RJ45 power port

Table 2-63 RJ45 port definitions


No. Pin Description Description

1 RS485+ RS485+
2 RS485- RS485-
3 +12 V power supply +12VDC
4 RS485+ RS485+
5 RS485- RS485-
6 - -
7 - -
8 Ground GND

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 79


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-64 LED indicator status


Indi Color Name Operat Status Description
cator ion

RUN Green Module running / Blinkin  The door lock is paired with
indicator g the host, and the power
supply is normal: The
indicator blinks at 0.5 Hz
(on for 1s and then off for
1s).
 The door lock fails to pair
with the host: The indicator
blinks at 4 Hz (on for 0.125s
and then off for 0.125s).
Off The power supply is abnormal.
Press Blinkin  The indicator blinks at super
SW. g short intervals for 0.5s, and
intermi then off for 0.5s.
ttently  The indicator blinks at super
at short intervals (blinking at
super 10 Hz, on for 0.05s and then
short off for 0.05s). The cycle
interva lasts for 5s.
ls
ALM Red Alarm indicator / Steady A system failure alarm is
on generated.
Off The system is normal.

2.4.3.11 Aisle Access Control System


The access control system collects and monitors data about the access of devices and
personnel to ensure access security.
Diverse access control devices such as the fingerprint and card reader with a keypad,
fingerprint and card reader, and card reader with a keypad are supported. Note that the
communication distance between an access control device and an access actuator should be
less than or equal to 5 meters.

If the IC cards used by the access control device need to be purchased, the IC card chip specifications
are as follows.

Table 2-65 IC card chip specifications


Item Specifications

Chip model S50


Chip name Mifare 1K (S50) card

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 80


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Chip type Philips Mifare 1 IC S50


Operating frequency 13.56 MHz
Read/write distance 1–3 cm
Storage capacity 8 kbit, 16 partitions

The emergency button or emergency door release button is used to open a door in
emergencies.
 The emergency button can disconnect the power supply to the lock and therefore unlock
the door in case of emergency.
 In case of emergency, break the glass of the emergency door release button to disconnect
the power supply to the lock and therefore unlock the door.

2.4.3.11.1 Access Actuator


The access actuator is the control component for the aisle door in a smart module. It connects
to the ECC800-Pro controller over FE port, wireless networking (802.15.4). It opens the
magnetic lock by detecting the card swiping information of the card reader, door open button
information, and fire linkage information. It has access right management, access event record,
and alarm record functions.

Figure 2-56 Access actuator

(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM
(reserved port for linkage (reserved port for exit door status or magnetic lock port
control or third-party fire button)
extinguishing system dry
contacts)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 81


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Specifications

Table 2-66 Access actuator technical specifications


Item Specifications

Power input  DC input: terminal, with an input voltage of 36 V DC–60 V DC


 PoE power supply: one PoE port that complies with IEEE802.3at
PoE port FE communication with the rate of 10/100 Mbit/s
Wireless One wireless communication port that complies with IEEE 802.15.4,
communicatio mutual backup with FE communication
n
AI/DI port Two AI/DI ports, can connect to the fire alarm and exit button
DO/DI port  One 12 V DC power output that controls magnetic locks, terminal
 One DI input port for connecting to the door status switch
RS485 serial Two RS485 ports (one route) with the default communication rate of 9600
port bit/s, physical port cascading supported (reserved function)
expansion
Wiegand port Two Wiegand ports, 12 V DC card reader operating power output; two
routes of card readers can operate at the same time.
BLINK  Press the button for less than 1 second to start blinking.
button  Hold down the button for 1–5 seconds to search for a network and start
networking.
 Hold down the button for more than 10 seconds to clear network
parameters.
Address DIP 4-pin address DIP switch
switch
E-label Supported

Indicators

Table 2-67 Access actuator indicators


Indicator Color Name Status

PWR Green Power input status  Steady on: The power


indicator input is normal.
 Off: There is no power
input.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 82


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indicator Color Name Status

RUN Green Communication  Off: The power is


status indicator abnormal or the board
program is loading.
 Blinking at long
intervals: The access
actuator successfully
registers with the
ECC800-Pro and the
software runs properly
(the indicator blinks at
0.5 Hz, on for 1s and
then off for 1s).
 Blinking at short
intervals: The
communication fails or
the access actuator
fails to register with
the ECC800-Pro (the
indicator blinks at 4
Hz, on for 0.125s and
then off for 0.125s).
 Blinking: The indicator
blinks at super short
intervals for 0.5s
(blinking at 10 Hz, on
for 0.05s and then off
for 0.05s) and then
turns off for 0.5s. The
cycle lasts for 5s.
ALM Red Alarm indicator  Steady on: A system
failure alarm is
generated.
 Off: No system alarm
is generated.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 83


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Indicator Color Name Status

RF_Z Green Wireless  Steady on: No network


communication parameters exist, or a
status indicator network is to be
created.
 Blinking at long
intervals: A network is
set up, and no node
access is allowed (the
indicator blinks at 0.5
Hz, on for 1s and then
off for 1s).
 Blinking intermittently
at super short intervals:
The access actuator is
searching for a
network (the indicator
blinks at super short
intervals for 0.5s and
then turns off for 0.5s).

Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 2-68 lists the LOCK/GND/GATE/COM port pin definitions.

Table 2-68 LOCK/GND/GATE/COM port pin definitions


Item Description

LOCK/GND LOCK 12V_OUT


(control
magnetic GND GND
locks) pin
sequence
GATE/COM GATE DI1
(door status)
pin sequence COM COM

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 84


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

2.4.3.11.2 Fingerprint and Card Reader with a Keypad

Figure 2-57 Fingerprint and card reader with a keypad

(1) Fingerprint reader (2) LED indicator

Table 2-69 Specifications for the fingerprint and card reader with a keypad
Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC±15%
Rated operating current 300 mA±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports

Table 2-70 Access control device operating status


Item New Version

Standby LED indicator The indicator is steady blue.


Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 85


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item New Version

Buzzer sounds The buzzer sounds three.


Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

2.4.3.11.3 Fingerprint and Card Reader

Figure 2-58 Fingerprint and card reader

(1) Fingerprint reader (2) LED indicator

Table 2-71 Specifications of a fingerprint and card reader


Item Specifications

Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC±5%
Rated operating current 300 mA±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 86


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Communications mode RS485 and Wiegand communications ports

Table 2-72 Access control device operating status


Item New Version

Standby LED indicator The indicator is steady blue.


Fingerprint reader The indicator is off.
Unauthorized fingerprint LED indicator The indicator blinks blue,
collection red, blue, red, and blue in
order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds three.
Authorized fingerprint LED indicator The indicator blinks blue,
collection red, and blue in order.
Fingerprint reader The indicator turns on
(white).
Buzzer sounds The buzzer sounds once.
Card swiping LED indicator The indicator blinks blue,
red, and blue in order.
Buzzer sounds The buzzer sounds once.

2.4.3.11.4 Card Reader with a Keypad

Figure 2-59 Card reader with a keypad

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 87


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-73 Technical specifications of a card reader with a keypad


Item Specifications

Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current: 80 mA; dynamic operating current
(card swiping, key pressing): 150 mA; minimum input
current: 12 V DC/300 mA
Communication mode Wiegand communications port

2.4.3.11.5 Magnetic Lock

Figure 2-60 Double-door magnetic lock

Figure 2-61 Single-door magnetic lock

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 88


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-62 Sliding-door magnetic lock

(1) Magnetic lock fastener (2) Magnetic lock


(3) Magnet (4) Magnet fastener

2.4.3.12 Video Management System


The video surveillance subsystem consists of the camera and network video recorder and
implements real-time monitoring, video storage, and video playback.

2.4.3.12.1 Camera
The C3220 camera is a two-megapixel infrared zoom dome camera that can be
ceiling-mounted.

Figure 2-63 C3220 camera

Table 2-74 C3220 camera technical specifications


Item Specifications

Image sensor 1/2.7'' two-megapixel progressive scan CMOS

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 89


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Item Specifications

Minimum illumination  Color: 0.002 lux (F1.2, AGC ON, 1/30s shutter
speed)
 Black/White: 0.0005 lux (F1.2, AGC ON, 1/30s
shutter speed); 0 lux (infrared illuminator enabled)
Wide dynamic range 120 dB
Focal length 2.8–12 mm
Video compression standard H.265/H.264/MJPEG
Maximum resolution 1920x1080
Power supply 12 V DC, PoE
IP rating IP67
Vandal resistant rating IK10

2.4.3.12.2 IVS1800

Figure 2-64 Appearance

Table 2-75 Performance specifications


Categ Item IVS1800-C08-04T (16CH) IVS1800-C08-04T (64CH)
ory

Devic Netwo 16-channel 1080p, up to 160 64-channel 1080p, up to 320


e rk Mbit/s access bandwidth Mbit/s access bandwidth
perfor video Up to 160 Mbit/s access
mance inputs bandwidth with intelligent services
enabled
Video 16-channel 1080p, up to 160 64-channel 1080p, up to 320
transfe Mbit/s forwarding bandwidth Mbit/s forwarding bandwidth
r Up to 160 Mbit/s forwarding
bandwidth with intelligent services
enabled

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 90


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Categ Item IVS1800-C08-04T (16CH) IVS1800-C08-04T (64CH)


ory

Playba 16-channel 1080p, up to 80 Mbit/s 32-channel 1080p, up to 160


ck/Do playback bandwidth Mbit/s playback bandwidth
wnloa
d
Platfor IP 16 cameras to one IVS1800 64 cameras to one IVS1800
m camer
perfor as
mance conne
cted

Table 2-76 Hardware specifications


Category Item Specifications

Storage Hard disk 8


capacity quantity
Hard disk SATA3.0
port
Hard disk Enterprise-level disks: 4 TB, 6 TB, 8 TB, or 10 TB
type Monitoring-level disks: 4 TB or 6 TB
Controller Processor Hi3559A
Memory 8 GB DDR4
External Network Two 10/100/1000 Mbit/s Ethernet ports
ports port
USB ports Three USB ports (two USB 2.0 ports on the front panel and
one USB 3.0 port on the rear panel)
Audio input 1 channel, RCA port
Audio 1 channel, RCA port
output
Alarm port 4-channel alarm input, 2-channel alarm output
Other Power 124 W
specification consumption
s (8 hard disks
included)
Power 110–220 V AC
supply
Weight 6.60 kg
(hard disks
excluded)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 91


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Category Item Specifications

Dimensions 86 mm x 442 mm x 467 mm


(H x W x D)

2.4.4 NetEco
2.4.4.1 System Overview
With a flexible structure and modular design, the NetEco can manage facilities of one data
center or centrally manage facilities of multiple data centers in different regions.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system mainly monitors following devices:
 Power equipment: smart cooling product, Power distribution module, UPS, and so on
 Environment equipment: water sensor, temperature and humidity sensor, and so on
 Video equipment: camera, and so on
 Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
 Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.

2.4.4.2 Server
The NetEco can be deployed on one of the following servers according to the management
capability requirement.

Table 2-77 Server


Model Configuration

TaiShan 200 (Model 2280) standard 2 x Kunpeng 920 [email protected] GHz, 4 x 32 GB


configuration memory, 2 x 1.2 TB + 8 x 1.8 TB drives
TaiShan 200 (Model 2180) basic 1 x Kunpeng 920 [email protected] GHz, 2 x 32 GB
configuration memory, 2 x 1.2 TB drives
2288X V5-H22X-standard 2 x 5218 [email protected] GHz CPU, 4 x 32 GB
configuration memory, 2 x 1.2 TB + 8 x 1.8 TB SAS drives
2288X V5-H22X-basic configuration 2 x 4208 [email protected] GHz CPU, 2 x 32 GB
memory, 2 x 1.2 TB SAS drives

2.4.4.3 LAN Switch


Select LAN switches based on site requirements.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 92


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Table 2-78 LAN switch


Model Maximum Number of Ports

S5331-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four 10GE


SFP+ ports
S5731-H24P4XC Twenty-four 10/100/1000BASE-T Ethernet ports, four 10GE
SFP+ ports

2.4.5 Edge Data Center Management System


The edge data center management system monitors the status of the entire network on the GIS
home page. After an abnormal site is detected, you can double-click it to access the site
monitoring page. Information about environment, energy consumption, key devices, alarm,
and security monitoring is provided on the site monitoring page without requiring additional
hardware.
 Environment monitoring: Monitors the temperature, humidity, water, and smoke.
 Key device monitoring: Monitors the UPS, air conditioners, and related power
distribution devices in real time, and displays the energy flow diagram and air
conditioner link diagram.
 Alarm monitoring: Displays site alarm information in real time and quickly locates
device faults.
 Security monitoring: Monitors the cabinet door status and cameras in sites.

2.5 Surge Protection and Grounding System


2.5.1 Surge Protection Solution
The smart module is mainly used for building data centers. Its power distribution system is a
subsystem of the building power distribution system. Class I surge protective devices (SPDs)
of the power system are provided by the general low-voltage power distribution room or
cabinet of the building.

2.5.2 Grounding Solution


Equipotential Grounding for Cabinets in the Module
A general ground bar is configured in the Converged Cabinet. The ground terminals in other
cabinets are connected to the general ground bar by cables with a cross-sectional area no less
than 16 mm2. The general ground bar is connected to the floor ground bar (FEB) or collective
ground bar (25 mm x 3 mm copper bar laid along cable trays or walls) of the equipment room
by ground cables with a cross-sectional area no less than 35 mm2.

The AC input power is from the upstream power distribution system. The cross-sectional areas of
ground cables are determined according to IEC 60364-5-54.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 93


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-65 Equipotential connection of the cabinet system

(1) General ground bar

Cabinet Grounding
 Metal components and parts of cabinets are properly connected. A structural connection
area is protected and applied with antioxidants. An area protected with painting should
ensure proper metal surface contact for two connected components. The DC resistance is
within 0.1 ohm between any two connected metal components. Use a ground cable to
connect two metal components that cannot be directly connected, such as cabinets and
cabinet doors. A cable for connecting these two metal components has a minimum
cross-sectional area of 6 mm2.
 A ground bar or main ground point is provided in each cabinet for equipment grounding.
The ground bar does not have to be insulated.
 The ground terminal should be greater than or equal to M8. A yellow ground label such
as is attached close to the main ground terminal for cabinets.
 Connect equipotential cables to metal components without carrying currents in the
module, such as metal doors and windows, cable trays, and ESD floor supports. Each
equipotential cable has a minimum cross-sectional area of 6 mm2.

2.6 Integrated Cabling System


Power Cable
Power cables include the input power cables for the Converged Cabinet, power cables from
the UPS to the busbar and BCB box, power cables from the BCB box to lithium batteries,
smart cooling product power cables, PDU2000 power cables, AC power cables (such as the
ECC800-Pro power cables and IVS power cables).

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 94


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Ground Cable
Ground cables include those for the Converged Cabinet, IT cabinet, lithium battery, and smart
cooling product.

Signal Cable
Signal cables include the signal cables for the Converged Cabinet, UPS, from lithium batteries
to the UPS, and between lithium batteries, as well as the signal cables for the smart cooling
product, water sensor, T/H sensor, smoke detector, video, and intelligent spring lock.

2.7 Fire Extinguishing System


If a rack-mounted integrated fire extinguishing module is configured in the cabinet, it is used
to put out the fire when a fire signal is detected. If a rack-mounted integrated fire
extinguishing module is not configured, the cabinet door is automatically opened when a
smoke signal is detected in the cabinet. Then the fire extinguishing system of the building is
used to put out the fire.

Fire Extinguishing Module Functions


 The controller and fire cylinder are integrated. Total flooding fire extinguishing is used
for the protected area.
 Built-in point-type smoke and heat detectors are used for dual-channel interlock startup
(the fire cylinder is started only when both smoke and heat detectors report alarms).
 Multiple devices can be connected in parallel for communication linkage. Three types of
dry contact signals (fire extinguishing, fault, and fire alarm) can be reported, and audible
and visual (indicator) alarms are provided. Users can press the specific button to clear
the alarms.

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 95


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 2 System Architecture

Figure 2-66 Rack-mounted integrated fire extinguishing module

Table 2-79 Technical specifications of the rack-mounted integrated fire extinguishing module
Item Specifications

Storage pressure (at 20℃) ≤ 1.6 MPa


Filling capacity Perfluorohexanone ≥ 6.3 kg
Backup time 24 hours
Startup mode Active startup, dual-channel interlock startup for smoke
and heat detectors
Alarming mode Dry contact signal feedback
Operating Operating 0–50°C
environment temperature
Storage –20°C to +60°C
temperature
Humidity ≤ 95% RH (non-condensing at 40°C)
Dimensions ≤ 6 U (height) x 700 mm (depth) x 442 mm (width)

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 96


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 3 Technical Specifications

3 Technical Specifications

Cate Item FusionModule800


gory
BC1L BC2L BC3L BC4L BC5L
Syste Power system 380/400/415 VAC, 3 Ph, 50/60 Hz
m
para Aisle type Single-row cold and hot aisle containment
mete
IP rating IP20
rs
Operating Outdoor: normal temperature: –20°C to +45°C; high temperature:
temperature –10°C to +55°C; low temperature: –40°C to +45°C
Indoor: 0°C to 40°C, 5% to 95% (non-condensing)
Rack quantity 1–7 1–15
per module
IT rack 6 6 12 12 12
quantity
Maximum 10 20 25 30 40
power
consumption
of IT loads
(kW)
Maximum 7
power density
per rack (kW)
Dimensions (600–9200) x 1350 x 2000
(W x D x H)
(unit: mm)
Installation Installed on a concrete floor or an ESD floor
mode
Cable and Supports top cabling and bottom pipe routing.
pipe routing
Cooli Cooling mode Direct expansion cooling, rack-mounted installation

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 97


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 3 Technical Specifications

ng Cooling 12.5 kW
syste capacity per
m unit
Air volume 2600 m3/h
per unit
Configured 1 2/3 3/4 3/4 4/5
quantity of
cooling
systems
Powe Power input Single input
r
suppl Continuous Not Supported Not Supported Not
y and cooling supported (manual supported (manual supported
distri switchover switchover
butio ) )
n
Capacity of a 10 10 10 20 20
syste
single UPS
m
(kVA)
Output power 1 1 1 0.9 0.9
factor
UPS 96% 95%
efficiency
UPS 1 2 3 2 3
configuration
Power backup Lead-acid/Lithium battery
Backup time 15–240 min
rPDU Common type: IEC socket or Chinese standard socket; Intelligent
type: IEC socket
Moni Monitoring Supports remote web-based access and centralized monitoring of
torin system multiple sites.
g
mana Local Standard 10-inch PAD
geme monitoring
nt
Monitoring Smoke sensor, T/H sensor, water Smoke sensor, T/H
syste
function sensor, intelligent lock, 10-inch LCD, sensor, water sensor,
m
SMS/email alarm, local app O&M, intelligent lock, 10-inch
PUE display, and video surveillance LCD, SMS/email alarm,
(optional) local app O&M, PUE
display (optional), and
video surveillance
(optional)
Management Local network management/cloud SaaS, unified management of
system multiple branches

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 98


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) 3 Technical Specifications

Fire Fire Fire extinguishing module (optional)


extin extinguishing
guish module
ing
syste
m

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 99


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) A Acronyms and Abbreviations

A Acronyms and Abbreviations

A
AC alternating current
ATS auto transformer switch
ATSE auto transformer switch equipment
ASIC application-specific integrated circuit

B
BIM battery interface module

C
CAN control area network
CIM communication interface module
CPLD complex programmable logical device

D
DC direct current
DSP digital signal processing

E
ECO economy control operation
EOD end of discharge
EPO emergency power-off
ESM energy storage module

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 100


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) A Acronyms and Abbreviations

ESMU energy storage management unit


ESN equipment serial number

H
HTTPS Hypertext Transfer Protocol Secure

L
LCD liquid crystal display
LSI large-scale integrated
LUI LCD user interface

M
MIB management information base

N
NMS network management system

P
PE protective earthing
PFC power factor correction
PL parallel load

R
RS232 Recommended Standard 232
RS485 Recommended Standard 485

S
SELV safety extra-low voltage
SOC state of charge
SOH state of health
SPD surge protective device
SSH Secure Shell

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 101


FusionModule800 Smart Small Data Center
Product Description
(02233RYC&02233RYD&02233RYE&02233RYF&022
33RYH) A Acronyms and Abbreviations

T
THDv total harmonic distortion of output voltage
TNV telecommunication network voltage

U
UPS uninterruptible power system
USB Universal Serial Bus

V
VRLA valve regulated lead acid

Issue 01 (2022-04-30) Copyright © Huawei Technologies Co., Ltd. 102