FusionModule800 5.0 Smart Small Modular Data Center V100R022C10)
FusionModule800 5.0 Smart Small Modular Data Center V100R022C10)
V100R022C10
Product Description
(02233RYC&02233RYD&02233RYE&02
233RYF&02233RYH)
Issue 01
Date 2022-04-30
and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.
Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees or
representations of any kind, either express or implied.
The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.
Website: https://www.huawei.com
Email: [email protected]
Purpose
This document describes how to install and connect cabinets, devices, pipes, and cables for
the FusionModule800 Smart Small Data Center (smart module for short), and how to
commission, operate, and maintain the product, providing operation guidance and technical
support for onsite installation personnel and technical support engineers.
Intended Audience
This document is intended for:
Hardware installation engineers
Technical support engineers
Commissioning engineers
Maintenance engineers
Symbol Conventions
The symbols that may be found in this document are defined as follows.
Symbol Description
Indicates a hazard with a high level of risk which, if not avoided, will
result in death or serious injury.
Indicates a hazard with a medium level of risk which, if not avoided,
could result in death or serious injury.
Indicates a hazard with a low level of risk which, if not avoided, could
result in minor or moderate injury.
Indicates a potentially hazardous situation which, if not avoided, could
result in equipment damage, data loss, performance deterioration, or
unanticipated results.
NOTICE is used to address practices not related to personal injury.
Symbol Description
Issue 01 (2022-04-30)
This issue is the first official release.
Contents
1 Product Description
1.1 Positioning
The FusionModule800 is a smart small data center solution applied to air cooled scenarios
where the equipment room area is less than 40 m2. This solution mainly applies to city-,
district-, and county-level data centers of the government vertical industry, small-sized
second-level branches and large-sized offices in the financial industry, and equipment rooms
of small- and medium-sized enterprises. The following figure shows the position of the
FusionModule800 in the product family.
1.2 Features
The FusionModule800 is a next-generation smart modular data center. It features integration,
safety, reliability, small footprint, energy conservation, easy and quick installation, compatible
structure, rapid and flexible deployment, and comprehensive monitoring. The Converged
Cabinet integrates the uninterruptible power system (UPS), power distribution, smart cooling
product, and management system.
Integration
The smart module integrates the cabinet system, power supply and distribution system,
cooling system, management system, surge protection and grounding system, integrated
cabling system, and fire extinguishing system. It adopts a modular and integrated design to
provide a comprehensive solution.
Architecture Compatibility
The FusionModule800 supports T1, T1 low-temperature, and T3 environments.
The FusionModule800 supports cold and hot aisle containment, saving energy and
reducing noise.
Modular power distribution and smart cooling products facilitate flexible expansion.
Comprehensive Monitoring
Various sensors monitor the functional modules in the equipment room in real time.
The smart module provides a module-level PAD to easily manage the functional modules
locally.
A maximum of three smart module cameras and in-room cameras can be monitored.
(Smart module cameras are installed in the smart module and the in-room cameras are
installed in the room.)
IT ≤6 ≤6 ≤ 12 ≤ 12 ≤ 12 (including
cabine (including (including (including the (including the the network
t the network the network network network cabinet)
cabinet) cabinet) cabinet) cabinet)
Numb ≤ 15, including the Converged Cabinet, network cabinet, IT cabinet, and battery
er of cabinet
cabine
ts
Coolin One 12.5 Two 12.5 Three 12.5 Three 12.5 Five 12.5 kW
g kW kW kW kW rack-mounted
rack-mounte rack-mounte rack-mounted rack-mounted smart cooling
d smart d smart smart cooling smart cooling product indoor
cooling cooling product product units: one is
product product indoor units: indoor units: configured in
indoor unit: indoor units: two are two are the Converged
configured configured in configured in configured in Cabinet
in the the the the (without
Converged Converged Converged Converged heating and
Cabinet Cabinet Cabinet (only Cabinet (only humidification)
(without (only one one with one with , and the other
heating and with heating heating and heating and four are
humidificati and humidificatio humidificatio optional (only
on) humidificatio n), and the n), and the one with
n) other one is other one is heating and
optional. optional. humidification)
.
Power One Two Three Two Three
distrib UPS2000-H UPS2000-H- UPS2000-H-1 UPS2000-G- UPS2000-G-20
ution -10 kVA, 10 kVAs, 0 kVAs, 20 kVAs, kVAs,
lithium/lead lithium/lead- lithium/lead-a lithium/lead- lithium/lead-aci
-acid battery acid battery cid battery acid battery d battery
Backu Lead-acid battery: 15 minutes, 30 minutes, and 60 minutes
p time Lithium battery: 30 minutes, 60 minutes, 120 minutes, 180 minutes, and 240
minutes
Monit ECC800-Pro, PAD, temperature and humidity (T/H) sensor, smoke detector,
oring intelligent lock, water sensor (optional), video system (optional), and NetEco
(optional)
Fire Fire extinguishing module (optional)
exting
uishin
g
device
The air conditioners work under normal temperature (outdoor unit: –20°C to +45°C),
high temperature (outdoor unit: –10°C to +55°C), and low temperature (outdoor unit:
–40°C to +45°C). The outdoor unit can be applied in class B environment.
If the equipment room is greater than 30 m2 or the ventilation rate is greater than 45 m3/h,
a high humidity alarm may be reported when the local ambient humidity is high (for
example, in coastal cities). In this case, a dehumidifier is needed.
Cooling load BC1 BC2 BC3 BC4 BC5 BC1L BC2 BC3 BC4 BC
L L L L L L L L 5L
Heat 10 20 25 30 40 8 16 20 24 32
dissipation
in the
equipment
room – IT
equipment
(kW)
Heat 0.5 1 1.25 1.5 2 0.4 0.8 1.2 1.5 1.6
dissipation
in the
equipment
room – UPS
(kW)
Heat 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.0
dissipation 5
in the
equipment
room – ECC
(kW)
Module 7.02 7.02 10.8 10.8 10.8 7.02 7.02 10.8 10.8 10.
footprint 8
(m2)
Heat transfer 0.35 0.35 0.54 0.54 0.54 0.351 0.351 0.54 0.54 0.5
of the 1 1 4
building
enclosure
(kW)
Heat gain 0.16 0.16 0.24 0.24 0.24 0.16 0.16 0.24 0.24 0.2
from 4
lighting
devices
(kW)
Number of 1 2 3 3 5 1 2 3 3 5
air
conditioners
(without
backup)
(PCS)
2 System Architecture
Signal cables are installed on the top of the front door of the cabinet, and power cables
are installed on the top of the rear door of the cabinet.
Cable troughs are installed on the top of cabinets for routing cables.
Figure 2-9 Conceptual diagram for the N+1 power distribution system
Maximum 20 kW 20 kW 25 kW 30 kW 40 kW 40 kW
load
General 125 125 A/3P 125 A/3P 125 A/3P / 250 A/3P
input A/3P
UPS input 63 A/1P 63 A/1P 63 A/3P 63 A/3P 63 A/3P /
UPS 63 A/1P 63 A/1P 63 A/1P 63 A/3P 63 A/3P /
output
UPS 125 125 A/2P 125 A/2P 63 A/4P 125 A/4P /
bypass A/2P
Power Indoor Indoor Indoor Indoor unit: Indoor /
distributio unit: 32 unit: 32 unit: 32 32 A/1P unit: 32
n for A/1P A/1P A/1P Outdoor A/1P
smart Outdoor Outdoor Outdoor unit: 40 Outdoor
cooling unit: 40 unit: 40 unit: 40 A/1P unit: 40
products A/1P A/1P A/1P A/1P
IT power 40 A/1P 40 A/1P 40 A/1P 40 A/1P 40 A/1P /
distributio
n
a: Scan the QR codes close to the SN to download the app, connect to the WiFi network, and view
documents such as user manual and quick guide. The information on the label is for reference only. The
actual parameters may vary.
The UPS2000-G-20 kVA is an online transformerless UPS. It consists of main power circuits
such as EMI and PFC/INV, and the monitoring unit. The UPS supports lead-acid battery input,
and multiple UPSs can be connected in parallel. The UPS provides USB, RS232, and RS485
ports.
(1) Control panel (2) AC input (3) Battery ports (4) EPO port
ports (mains and
bypass)
(5) Maintenance (6) Parallel (7) CAN (8) USB port
bypass port (MBS) ports communications ports (protected by a
(MON1 & MON2) security mechanism)
(9) Battery (10) Optional (11) AC output ports (pL
temperature sensor card slot & sL)
port
It is recommended that the length of the cable connected to the MBS port be less than or equal to 10 m.
Item Specifications
The lithium battery uses lithium cells with superior charge and discharge characteristics
and high cycle performance to provide comprehensive battery management. It provides
comprehensive battery management functions to implement overcharge, overdischarge,
and overtemperature protection.
Management functions:
− Detects the cell voltage, current, and temperature.
− Detects the state of health (SOH) of the lithium battery module and reports the
result to the network management system (NMS).
− Detects the state of charge (SOC) of the lithium battery module.
− Counts the number of charge and discharge cycles.
− Detects faults in certain key circuits (such as charging, discharging, and protection
circuits) and reports alarms.
− Stores historical data.
(1) Running (2) Alarm indicator (3) Activate button (4) Fault indicator
indicator
(5) WiFi indicator (6) Battery SOC (7) Labela (8) Power output
indicator ports
(9) AC activation (10) WiFi restart (11) Battery parallel (12) Network ports
port button ports
(13) Dry contacts (14) Intelligent slot
a: This area shows the SN and QR code. Scan the QR code to download the app, connect to the WiFi
network, and view documents such as user manual and quick guide.
Item Specifications
(1) BBB (2) BBB box (3) Battery module (4) BBB box (5) BBB box
box switch ground ports connection ports output ports (+) output ports (–)
2.2.3.6 Battery
Lead-acid batteries are placed in the battery cabinet.
A battery cabinet provides space for installing batteries and routing battery cables in a
data center. The battery cabinet can be deployed inside or outside the smart module. A
maximum of two battery cabinets can be deployed inside the smart module.
Battery cabinets are classified into master cabinets and slave cabinets. Conversion
copper bars are required for the input and output of circuit breakers in the master cabinet.
The required battery backup time is 15 minutes or 30 minutes.
26 Ah 40
40 Ah
65 Ah 20
100 Ah
Appearance
Technical Specifications
2.2.3.8 PDU2000
2.2.3.8.1 Basic PDU2000
By default, IEC sockets are configured for all PDU2000s. GB sockets are optional.
Model PDU2000-32-1PH-20/4-M1
Item Specifications
Table 2-15
Item Specifications
Item Specifications
Table 2-16
Item Specifications
Dimensions (L x W x H) Host: 72 mm x 76 mm x 63 mm
Transformer: 90 mm x 68 mm x 21 mm
Measured parameters and range Voltage: 30–600 V (line voltage), 20–400 V (phase
voltage); continuous overload: phase voltage 500 V
(continuous)
Current: 0–250 A; continuous overload: 300 A
(continuous), 10 times the measurement range (1s)
Single-phase power: 0–100000 W/var/VA
Total power: 0–300000 W/var/VA
Power factor: –1 to +1
Frequency: 45–60 Hz
Auxiliary power supply: 85–300 V AC or 85–350 V
DC; power consumption ≤ 2 W
Measurement precision Current:
–10°C to +50°C: 1.0% (10–250 A), 0.1 A (less than
10 A)
–40°C to –10°C, +50°C to +70°C: 2% (10–250 A),
0.2 A (less than 10 A)
Phase voltage: –10°C to +50°C: 0.5% (20–400 V);
–40°C to –10°C, +50 to +70°C: 1% (20–400 V)
Power: 2.0%
Power factor: 2.0%
Frequency: ±0.1 Hz (45–60 Hz)
Electricity: 2.0%
Item Specifications
(1) Dual input indicator (2) Monitoring board (3) Route II switch button
(4) Route I/II status display window (5) Handle
Installation Requirements
Vertical Difference Outdoor unit placed higher than the indoor unit: ≤ 30 m
Between the Indoor and Indoor unit placed higher than the indoor unit: ≤ 8 m
Outdoor Units
Thermal Insulation ≥ 13 mm
Foam Thickness
Water Supply The inlet water pressure should be in the range of 0.1–0.7
Requirements MPa, and the temperature should be in the range of
1°C–40°C.
The wet film humidifier should use tap water that meets the
following requirements:
Non-freezing and nephelometric turbidity units (NTU) <
3
No visible substances
6.5 ≤ pH value ≤ 8.5
Total hardness (in CaCO3) ≤ 450 mg/L
For details, refer to the GB 5749-2006 Standards for
Drinking Water Quality.
Drainage Requirements The distance between the upper drainage of the water pump
and the cabinet installation floor should not exceed 4 m.
(BSPT 1/2 inch drainpipe connectors with external threads
are provided in standard configuration. Drainpipes and BSPP
1/2 inch connectors with internal threads should be prepared
by the customer.)
Ports
Refrigerant gas pipe L ≤ 60 m, reserved port: 5/8 inch (15.9 mm), thread connection
60 m < L ≤ 80 m, reserved port: 7/8 inch (22.2 mm), thread
connection
Refrigerant liquid L ≤ 60 m, reserved port: 3/8 inch (9.52 mm), thread connection
pipe 60 m < L ≤ 80 m, reserved port: 1/2 inch (12.77 mm), thread
connection
Item Specifications
Item Specifications
Fan quantity 2
Weight 5 kg
Dimensions (H x 250 mm x 600 mm x 50 mm
W x D)
The access actuator should be installed near the door, have a maximum of 3.5 m cabling distance away
from the magnetic lock, and have a maximum of 5 m cabling distance away from other switches and the
access control device.
2.4.2.3 Alarm
The system monitors the status of smart cooling products, power distribution, and
environment. If a fault or parameter error occurs, the system generates an alarm in real
time. You can view the alarm cause and solution in the alarm details.
Alarms can be classified into four severities: critical, major, minor, and warning. The
alarm severities can be user-defined.
Active alarms can be filtered by device and alarm severity.
Alarms can be linked with the eLight. The eLight light colors vary with alarm severities.
Alarm notifications can be sent by email and SMS.
A maximum of 500 concurrent active alarms are supported.
The aisle smoke sensor alarm cannot trigger the customer's fire extinguishing system. Only dry contact
alarm signals are provided.
If the cabinet is configured with an integrated rack-mounted fire extinguishing module
and a smoke alarm is generated, the cabinet door does not bounce. If the cabinet door has
bounced, an alarm (door open alarm) is generated.
Power Port
The ECC800-Pro provides four power ports, including two AC input ports (AC_INPUT1 and
AC_INPUT2) and two DC output ports (DC_OUTPUT1 and DC_OUTPUT2). Table 2-26
provides the power port pin definitions.
AC Pin1 L
Pin2 PE
Pin3 N
DC Pin1 48V+
Pin2 48VGND
Specifications
Item Specifications
Item Specifications
Item Specifications
Communications Port
The ECC800-Pro provides the following communications ports. Figure 2-38 shows the pins
of the RJ45 port.
There are four GE ports, that is, two WAN ports (WAN1 and WAN2) and two LAN ports
(LAN1/POE and LAN2/POE).
Item Description
Pin3 -
Pin4 RS485+
Pin5 RS485-
Pin6 -
Pin7 CAN_H
Pin8 CAN_L
The following provides the AIDI_1, AIDI_2 and AIDI_3 ports pin definitions.
Item Description
Indicators
RUN Green Running status Steady on The power supply is normal, the
indicator program is being loaded.
Off The power supply is abnormal.
Blinking at The software runs properly (the
long indicator blinks at 0.5 Hz, on for
intervals 1s and then off for 1s) or the
ECC800-Pro registers with the
NetEco successfully.
Blinking at The ECC800-Pro does not
short register with the NetEco (the
intervals indicator blinks at 5 Hz, on for
0.125s and then off for 0.125s).
SW Button
2.4.3.1.3 PSU
Indicator
Main Functions
Single unit control: When only one unit is running, the controller provides logic control
over components in the unit to meet the indoor temperature and humidity requirements.
Teamwork control: When multiple smart cooling products work cooperatively, the
controller optimally distributes the heat load, greatly lowering the power consumption.
Multiple smart cooling products provide backup for higher reliability.
Remote management: You can monitor and manage one or more smart cooling products
using the remote management function provided by the Company.
Configuration synchronization: You can synchronize parameters between smart cooling
products on the touchscreen (optional) of the Converged Cabinet, ECC800-Pro WebUI,
or ECC800-Pro app.
One-click export: You can export the alarms and logs of a smart cooling product on the
ECC800-Pro WebUI.
Software upgrade: You can perform a remote upgrade on the touchscreen (optional) of
the Converged Cabinet, ECC800-Pro WebUI, or ECC800-Pro app.
Alarm details query: You can view the possible causes of alarms and handling
suggestions on the ECC800-Pro WebUI.
2.4.3.3 PAD
The PAD allows the wireless access from the data center management system. You can
monitor the equipment in the data center and environmental parameters in real time over the
app.
(1) DIP switch (reserved) (2) COM_OUT (reserved) (3) COM_IN (reserved)
Width 120 mm
Depth 200 mm
Height 43 mm
Operating –30°C to +65°C
temperature
Installation Installed in a 19-inch rack
requirements
Environmenta RoHS5
l protection
Specifications
Item Specifications
Communications Port
The following table describes the pin assignment for ports COM1/AIDI_1 to COM8/AIDI_8.
The following table describes the pin assignments for the COM_IN and COM_OUT ports.
Table 2-46 Pin assignment for the COM_IN and COM_OUT ports
Item Description
Item Description
Blinking Press the button for The RUN indicator blinks at super short
less than 2s. intervals for 0.5s and then off for 0.5s; last
10s (blinking at super short intervals for 10
Hz, on for 0.05s and then off for 0.05s).
(1) Status indicator (2) BLINK button (3) COM1 communications port
(4) COM2 communications port (5) 48 V power port (6) PoE port
Specifications
Indicators
(1) PWR_IN (2) FE_1 cascading (3) POE_1–2 (4) POE_3–4 ports
cascading power port signal port ports
(5) 48V_OUT1 (6) 48V_OUT2 (7) FE_2 (8) PWR_OUT
power output port power output port cascading signal cascading power port
port
(9) BLINK button (10) Status indicator
Specifications
Power input PWR_IN D-type power input terminal, for power cascading, input voltage
range: 45–55 V DC
Power of a single smart ETH gateway: max (2.7 A, 48 V DC); power of
cascaded smart ETH gateways: max (25 A, 48 V DC)
Power output PWR_OUT D-type power output terminal, for power cascading, output
voltage range: 45–55 V DC
48V_OUT1 and 48V_OUT2, terminal (1 A, 48 V DC), output voltage
range: 45–55 V DC
FE port Two FE ports, RJ45 terminal with an indicator, 10/100M communication
rate, for the cascading between smart ETH gateways and the
communication with the upper computer
PoE port Four PoE ports, RJ45 terminal with an indicator, 10/100M
communications rate, complying with IEEE802.3, IEEE802.3u,
IEEE802.3af/at
BLINK If you press the BLINK button, the RUN indicator blinks intermittently at
button super short intervals (blinking at super short intervals for 0.5s and then off
for 0.5s) for 5 seconds.
Indicators
PWR Green Power status Steady The power supply works properly.
indicator on
Off There is no power input, or the internal
power supply fails.
RUN Green Running status 0.5 Hz The software runs properly: The indicator
indicator blinks at 0.5 Hz (on for 1s and then off for
1s).
4 Hz Communication is disconnected (no
communication for 30s): The indicator
blinks at 4 Hz (on for 0.125s and off for
0.125s).
Off There is no power input, or the internal
power supply fails.
Item Specifications
Item Specifications
Pin1 or Pin 4 A
Pin2 or Pin 5 B
Pin3 V+
Pin Description
Pin6 V-
Pin7 Reserved
(1) LED indicator (2) DIP switch (3) RJ45 power port
1 RS485+ RS485+
2 RS485- RS485-
3 +12 V power supply +12VDC
4 RS485+ RS485+
5 RS485- RS485-
6 - -
7 - -
8 Ground GND
RUN Green Module running / Blinkin The door lock is paired with
indicator g the host, and the power
supply is normal: The
indicator blinks at 0.5 Hz
(on for 1s and then off for
1s).
The door lock fails to pair
with the host: The indicator
blinks at 4 Hz (on for 0.125s
and then off for 0.125s).
Off The power supply is abnormal.
Press Blinkin The indicator blinks at super
SW. g short intervals for 0.5s, and
intermi then off for 0.5s.
ttently The indicator blinks at super
at short intervals (blinking at
super 10 Hz, on for 0.05s and then
short off for 0.05s). The cycle
interva lasts for 5s.
ls
ALM Red Alarm indicator / Steady A system failure alarm is
on generated.
Off The system is normal.
If the IC cards used by the access control device need to be purchased, the IC card chip specifications
are as follows.
Item Specifications
The emergency button or emergency door release button is used to open a door in
emergencies.
The emergency button can disconnect the power supply to the lock and therefore unlock
the door in case of emergency.
In case of emergency, break the glass of the emergency door release button to disconnect
the power supply to the lock and therefore unlock the door.
(1) 48 V power port (2) PoE port (3) RS485 port COM2
(4) RS485 port COM1 (5) Address DIP switch (6) Status indicator
(7) BLINK button (8) WG_2 Wiegand (9) WG_1 Wiegand interface
interface
(10) AI/DI_2 dry contact (11) AI/DI_1 dry contact (12) LOCK/GND/GATE/COM
(reserved port for linkage (reserved port for exit door status or magnetic lock port
control or third-party fire button)
extinguishing system dry
contacts)
Specifications
Indicators
Communications Ports
The access actuator provides one DO port (LOCK/GND) and one DI port (GATE/COM).
Table 2-68 lists the LOCK/GND/GATE/COM port pin definitions.
Table 2-69 Specifications for the fingerprint and card reader with a keypad
Item Specifications
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC±15%
Rated operating current 300 mA±15%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Communications mode RS485 and Wiegand communications ports
Dimensions (L x W x H) 156 mm x 53 mm x 38 mm
Rated operating voltage 12 V DC±5%
Rated operating current 300 mA±5%
Card type supported IC card
Authorized storage A maximum of 3000 authorized users, with a maximum
of 6000 fingerprints
Item Specifications
Dimensions (L x W x H) 114 mm x 63 mm x 25 mm
Operating voltage Operating voltage range: 10.8–13.2 V DC; rated voltage:
12 V DC
Operating current Static standby current: 80 mA; dynamic operating current
(card swiping, key pressing): 150 mA; minimum input
current: 12 V DC/300 mA
Communication mode Wiegand communications port
2.4.3.12.1 Camera
The C3220 camera is a two-megapixel infrared zoom dome camera that can be
ceiling-mounted.
Item Specifications
Minimum illumination Color: 0.002 lux (F1.2, AGC ON, 1/30s shutter
speed)
Black/White: 0.0005 lux (F1.2, AGC ON, 1/30s
shutter speed); 0 lux (infrared illuminator enabled)
Wide dynamic range 120 dB
Focal length 2.8–12 mm
Video compression standard H.265/H.264/MJPEG
Maximum resolution 1920x1080
Power supply 12 V DC, PoE
IP rating IP67
Vandal resistant rating IK10
2.4.3.12.2 IVS1800
2.4.4 NetEco
2.4.4.1 System Overview
With a flexible structure and modular design, the NetEco can manage facilities of one data
center or centrally manage facilities of multiple data centers in different regions.
The management system provides a GUI to implement comprehensive management functions
based on requirements. The system mainly monitors following devices:
Power equipment: smart cooling product, Power distribution module, UPS, and so on
Environment equipment: water sensor, temperature and humidity sensor, and so on
Video equipment: camera, and so on
Access control equipment: A standard access management system is integrated to
manage and monitor key information such as door status, card swiping, and permission
setting.
Standard network management interface: The NetEco provides SNMP interfaces to
communicate with third-party NMSs. The system can be customized to support other
protocols for the access from different devices.
2.4.4.2 Server
The NetEco can be deployed on one of the following servers according to the management
capability requirement.
The AC input power is from the upstream power distribution system. The cross-sectional areas of
ground cables are determined according to IEC 60364-5-54.
Cabinet Grounding
Metal components and parts of cabinets are properly connected. A structural connection
area is protected and applied with antioxidants. An area protected with painting should
ensure proper metal surface contact for two connected components. The DC resistance is
within 0.1 ohm between any two connected metal components. Use a ground cable to
connect two metal components that cannot be directly connected, such as cabinets and
cabinet doors. A cable for connecting these two metal components has a minimum
cross-sectional area of 6 mm2.
A ground bar or main ground point is provided in each cabinet for equipment grounding.
The ground bar does not have to be insulated.
The ground terminal should be greater than or equal to M8. A yellow ground label such
as is attached close to the main ground terminal for cabinets.
Connect equipotential cables to metal components without carrying currents in the
module, such as metal doors and windows, cable trays, and ESD floor supports. Each
equipotential cable has a minimum cross-sectional area of 6 mm2.
Ground Cable
Ground cables include those for the Converged Cabinet, IT cabinet, lithium battery, and smart
cooling product.
Signal Cable
Signal cables include the signal cables for the Converged Cabinet, UPS, from lithium batteries
to the UPS, and between lithium batteries, as well as the signal cables for the smart cooling
product, water sensor, T/H sensor, smoke detector, video, and intelligent spring lock.
Table 2-79 Technical specifications of the rack-mounted integrated fire extinguishing module
Item Specifications
3 Technical Specifications
ng Cooling 12.5 kW
syste capacity per
m unit
Air volume 2600 m3/h
per unit
Configured 1 2/3 3/4 3/4 4/5
quantity of
cooling
systems
Powe Power input Single input
r
suppl Continuous Not Supported Not Supported Not
y and cooling supported (manual supported (manual supported
distri switchover switchover
butio ) )
n
Capacity of a 10 10 10 20 20
syste
single UPS
m
(kVA)
Output power 1 1 1 0.9 0.9
factor
UPS 96% 95%
efficiency
UPS 1 2 3 2 3
configuration
Power backup Lead-acid/Lithium battery
Backup time 15–240 min
rPDU Common type: IEC socket or Chinese standard socket; Intelligent
type: IEC socket
Moni Monitoring Supports remote web-based access and centralized monitoring of
torin system multiple sites.
g
mana Local Standard 10-inch PAD
geme monitoring
nt
Monitoring Smoke sensor, T/H sensor, water Smoke sensor, T/H
syste
function sensor, intelligent lock, 10-inch LCD, sensor, water sensor,
m
SMS/email alarm, local app O&M, intelligent lock, 10-inch
PUE display, and video surveillance LCD, SMS/email alarm,
(optional) local app O&M, PUE
display (optional), and
video surveillance
(optional)
Management Local network management/cloud SaaS, unified management of
system multiple branches
A
AC alternating current
ATS auto transformer switch
ATSE auto transformer switch equipment
ASIC application-specific integrated circuit
B
BIM battery interface module
C
CAN control area network
CIM communication interface module
CPLD complex programmable logical device
D
DC direct current
DSP digital signal processing
E
ECO economy control operation
EOD end of discharge
EPO emergency power-off
ESM energy storage module
H
HTTPS Hypertext Transfer Protocol Secure
L
LCD liquid crystal display
LSI large-scale integrated
LUI LCD user interface
M
MIB management information base
N
NMS network management system
P
PE protective earthing
PFC power factor correction
PL parallel load
R
RS232 Recommended Standard 232
RS485 Recommended Standard 485
S
SELV safety extra-low voltage
SOC state of charge
SOH state of health
SPD surge protective device
SSH Secure Shell
T
THDv total harmonic distortion of output voltage
TNV telecommunication network voltage
U
UPS uninterruptible power system
USB Universal Serial Bus
V
VRLA valve regulated lead acid