Vdocuments - MX Separator Sizing Spreadsheet
Vdocuments - MX Separator Sizing Spreadsheet
1 Discussion
2 Nomenclature
3 References
4 Standard Separator Sizes as per API
5 Separator sizing with mist extractor
5A Two Phase (Gas - Oil) Vertical Separator as per API 12J
5B Two Phase (Gas - Oil) Horizontal Separator as per API 12J
5C Three Phase (Gas - Oil - Water) Vertical Separator as per API 12J
5D Three Phase (Gas - Oil - Water) Horizontal Separator as per API 12J
6 Separator sizing without mist extractor
6A Two Phase (Gas - Oil) Vertical Separator As per Petroleum and Gas Field Processing
6B Two Phase (Gas - Oil) Horizontal Separator as per Petroleum and Gas Field Processing
6C Three Phase (Gas - Oil - Water) Vertical Separator as per Petroleum and Gas Field Processing
6D Three Phase (Gas - Oil - Water) Horizontal Separator as per Petroleum and Gas Field Processing
Prepared by:
Ajay S. Satpute
Sr. Process Engineer
Ramboll Consulting Engineering, Qatar
DISCUSSION
This spreadsheet provides an easy and simple approach to (2/3 phase and vertical/horizontal) separator
sizing. Formulae and references are also provided for process engineers to edit/duplicate this work (file is
NOT password protected).
There is as much art as there is science to properly design a separator. Three main factors should be
considered in separator sizing:
1) vapor capacity, 2) Liquid capacity, and 3) operability.
The vapor capacity will determine the cross-sectional area necessary for gravitational forces to remove the
liquid from the vapor. The liquid
capacity is typically set by determining the volume required to provide adequate residence time to “de-gas”
the liquid or allow immiscible liquid phases to separate. Operability issues include the separator’s
ability to deal with solids if present, unsteady flow/liquid slugs, turndown, etc. Finally, the optimal design will
usually result in an aspect ratio that satisfies these requirements in a vessel of reasonable cost. These factors
often result in an iterative approach to the calculations.
Typical K factors for the sizing of wire mesh demisters (Source: IPS-E-PR-880, 1997)
Separator type K factor (m/s)
Horizontal (with vertical pad) 0.122 to 0.152
Spherical 0.061 to 0.107
Vertical or horizontal (with horizontal pad) 0.055 to 0.107
At atmospheric pressure 0.107
At 2100 kPa 0.101
At 4100 kPa 0.091
At 6200 kPa 0.082
At 10300 kPa 0.064
Wet steam 0.076
Most vapours under vacuum 0.061
Salt and caustic evaporators 0.046
INDEX
NOMENCLATURE INDEX
http://en.citizendium.org/wiki/Vapor-liquid_separator
http://petrowiki.org/Separator_sizing
http://www.cheresources.com/invision/topic/11856-selecting-vertical-separator-ld-ratio/
Petroleum and Gas Field Processing - Hussein K. Abdel-Aal, Mohamed Aggour, M. A. Fahim
http://books.google.com.qa/books?id=BZOPlA-SmMUC&pg=PA97&lpg=PA97&dq=%22three+phase
%22+separator+L/D+ratio+%22GPSA
%22&source=bl&ots=u979BoWCxd&sig=p13fCbqS52y7bE3eGRDtfj7nGq0&hl=en&sa=X&ei=s9dMVJHiHKvcy
http://www.cheresources.com/invision/topic/17158-three-phase-separator-design-suggestion-needed/
wO4tIK4BQ&redir_esc=y#v=onepage&q=%22three%20phase%22%20separator%20L%2FD%20ratio
http://en.citizendium.org/wiki/Vapor-liquid_separator
http://www.chemicalforums.com/index.php?topic=8913.0
http://www.chemicalforums.com/index.php?topic=9252.0
http://www.cheresources.com/invision/topic/41-sizing-a-flash-tank-or-vapor-liquid-separator/
http://www.eng-tips.com/faqs.cfm?fid=1153
http://process-designs.com/
http://www.razifar.com/cariboost_files/
Design_20Two_20Phase_20Separators_20Within_20the_20Right_20Limits.pdf
http://en.wikipedia.org/wiki/Souders%E2%80%93Brown_equation
http://books.google.com.qa/books?id=lpA83iVcaGYC&pg=PA159&lpg=PA159&dq=Kh+
%3D+1.25+Kv+separator&source=bl&ots=fV8ewKHkag&sig=q70X8-
xfxPnk9MBMHgaEFwLhIhU&hl=en&sa=X&ei=M-NVVPepM4XWPfaLgYAI&redir_esc=y#v=onepage&q=Kh
IPS-E-PR-880, 1997
%20%3D%201.25%20Kv%20separator&f=false
16 in x 5 ft
16 in x 7½ ft
16 in x 10 ft
20 in x 5 ft
20 in x 7½ ft
20 in x 10 ft
24 in x 5 ft
24 in x 7½ ft
24 in x 10 ft
30 in x 5 ft
30 in x 7½ ft
30 in x 10 ft
36 in x 5 ft
36 in x 7½ ft
36 in x 10 ft
36 in x 15 ft
42 in x 7½ ft
42 in x 10 ft
42 in x 15 ft
48 in x 7½ ft
48 in x 10 ft
48 in x 15 ft
54 in x 7½ ft
54 in x 10 ft
54 in x 15 ft
60 in x 7½ ft
60 in x 10 ft
60 in x 15 ft
INDEX
Two Phase (Gas - Oil) Vertical separator: As per API 12J
INPUT PARAMETERS
Qg 25 mmscfd Gas rate
Qo 3000 bbl/d Oil rate SCHEMATIC
γ 0.70 Gas specific gravity
Retention time,
Ag,min 4.03 ft2 Minimum gas flow area Oil Gravities
minutes (Typical)
Step 3:
NOTES
1. The maximum allowable superficial velocity calculated from the above factors is for separators normally having a wire mesh mist extractor.
This rate should allow all liquid droplets larger than 10 microns to settle out of gas.
2. Additional resource for K factor from GPSA Engineering Data Book:
Pressure, barg K factor, m/s Adjustment of K factor for pressure
0 0.11 Pressure, psig % of Design value
7 0.11 Atm. 100
21 0.10 150 90
42 0.09 300 85
63 0.08 600 80
105 0.07 1150 75
GPSA Notes:
1. K = 0.107 at a gauge pressure of 7 bar. Subtract 0.003 for every 7 bar above a gauge pressure of 7 bar.
2. For glycol or amine solutions, multiply above K values by 0.6 - 0.8.
3. Typically use one-half of the above K values for approximate sizing of vertical separators without mesh pads.
4. For compressor suction scrubbers and expander inlet separators, multiply K by 0.7 - 0.8.
3. Additional resource for retention times from gas Conditioning and Processing, Volume 2.
Natural gas-oil 1 to 3 minutes
Lean oil surge tanks 10 to 15 minutes
Fractionation feed surge tanks 8 to 15 minutes
Refrigerant surge tanks 4 to 7 minutes
Refrigerant econonomizers 2 to 3 minutes
4. As per GPSA, typical vertical H/D ratios are normally in the 2 to 4 range.
Two Phase (Gas - Oil) Horizontal Separator: As per API 12J
INPUT PARAMETERS SCHEMATIC
Qg 25 mmscfd Gas rate
Qo 3000 bbl/d Oil rate
γ 0.70 Gas specific gravity
Retention time,
Ag,min 2.42 ft2 Minimum gas flow area Oil Gravities
minutes (Typical)
Step 3:
NOTES
1. The maximum allowable superficial velocity calculated from the above factors is for separators normally having a wire mesh mist extractor. This
rate should allow all liquid droplets larger than 10 microns to settle out of gas.
2. Additional resource for K factor from GPSA Engineering Data Book:
Pressure, barg K factor, m/s Adjustment of K factor for pressure
0 0.11 Pressure, psig % of Design value
7 0.11 Atm. 100
21 0.10 150 90
42 0.09 300 85
63 0.08 600 80
105 0.07 1150 75
GPSA Notes:
1. K = 0.107 at a gauge pressure of 7 bar. Subtract 0.003 for every 7 bar above a gauge pressure of 7 bar.
2. For glycol or amine solutions, multiply above K values by 0.6 - 0.8.
3. For compressor suction scrubbers and expander inlet separators, multiply K by 0.7 - 0.8.
3. Additional resource for retention times from gas Conditioning and Processing, Volume2.
Natural gas-oil 1 to 3 minutes
Lean oil surge tanks 10 to 15 minutes
Fractionation feed surge tanks 8 to 15 minutes
Refrigerant surge tanks 4 to 7 minutes
Refrigerant econonomizers 2 to 3 minutes
4. As per GPSA, typical horizontal L/D ratios are normally in the 2.5 to 5 range.
INDEX
INDEX
Three Phase (Gas - Oil - Water) Horizontal Separator: As per API 12J
INPUT PARAMETERS
Qg 8 mmscfd Gas rate SCHEMATIC
Qo 8000 bbl/d Oil rate
Qw 3000 bbl/d Water rate
γ 0.70 Gas specific gravity
Retention time,
Ag,min 1.92 ft2 Minimum gas flow area Oil Gravities
minutes (Typical)
NOTES
1. The maximum allowable superficial velocity calculated from the above factors is for separators normally having a wire mesh mist extractor.
This rate should allow all liquid droplets larger than 10 microns to settle out of gas.
2. Additional resource for K factor from GPSA Engineering Data Book:
Pressure, barg K factor, m/s Adjustment of K factor for pressure
0 0.11 Pressure, psig % of Design value
7 0.11 Atm. 100
21 0.10 150 90
42 0.09 300 85
63 0.08 600 80
105 0.07 1150 75
GPSA Notes:
1. K = 0.107 at a gauge pressure of 7 bar. Subtract 0.003 for every 7 bar above a gauge pressure of 7 bar.
2. For glycol or amine solutions, multiply above K values by 0.6 - 0.8
3. Typically use one-half of the above K values for approximate sizing of vertical separators without mesh pads
4. For compressor suction scrubbers and expander inlet separators, multiply K by 0.7 - 0.8
3. Additional resource for retention times from gas Conditioning and Processing, Volume2.
Natural gas-oil 1 to 3 minutes
Lean oil surge tanks 10 to 15 minutes
Fractionation feed surge tanks 8 to 15 minutes
Refrigerant surge tanks 4 to 7 minutes
Refrigerant econonomizers 2 to 3 minutes
4. As per GPSA, typical horizontal H/D ratios are normally in the 2 to 4 range.
INDEX
Three Phase (Gas - Oil) Horizontal Separator: As per API 12J
INPUT PARAMETERS
Qg 8 mmscfd Gas rate SCHEMATIC
Qo 8000 bbl/d Oil rate
Qw 3000 bbl/d Water rate
γ 0.70 Gas specific gravity
Step 3:
NOTES
1. The maximum allowable superficial velocity calculated from the above factors is for separators normally having a wire mesh mist extractor.
This rate should allow all liquid droplets larger than 10 microns to settle out of gas.
2. Additional resource for K factor from GPSA Engineering Data Book:
Pressure, barg K factor, m/s Adjustment of K factor for pressure
0 0.11 Pressure, psig % of Design value
7 0.11 Atm. 100
21 0.10 150 90
42 0.09 300 85
63 0.08 600 80
105 0.07 1150 75
GPSA Notes:
1. K = 0.107 at a gauge pressure of 7 bar. Subtract 0.003 for every 7 bar above a gauge pressure of 7 bar.
2. For glycol or amine solutions, multiply above K values by 0.6 - 0.8
3. For compressor suction scrubbers and expander inlet separators, multiply K by 0.7 - 0.8
3. Additional resource for retention times from gas Conditioning and Processing, Volume2.
Natural gas-oil 1 to 3 minutes
Lean oil surge tanks 10 to 15 minutes
Fractionation feed surge tanks 8 to 15 minutes
Refrigerant surge tanks 4 to 7 minutes
Refrigerant econonomizers 2 to 3 minutes
4. As per GPSA, typical horizontal L/D ratios are normally in the 2.5 to 5 range.
INDEX
Two Phase (Gas - Oil) Vertical Separator: As per "Petroleum and Gas Field Proce
Hussein K. Abdel-Aal, Mohamed Aggour, M. A. Fahim"
INPUT PARAMETERS
Qg 15 mmscfd Gas rate
Qo 3000 bbl/d Oil rate
CALCULATIONS EQUATIONS
Step 1: Determine gas and oil properties
ρg 3.7 lb/ft3 Gas operating density
ρo 53.0 lb/ft3 Oil operating density
Step 2: Determine Cd
Cd 1.13 Assume Drag coefficient
u 0.41 ft/s Settling velocity of oil droplet
Re 56 Reynolds no.
Cd 1.16
Click me
Use goal seek to get error zero, by changing
Error 0.00 asssumed Cd
D, in H, in Ls, ft SR
30 85.7 13.5 5.4
36 59.5 11.3 3.8
42 43.7 10.5 3.0
48 33.5 10.1 2.5
54 26.4 10.0 2.2 TABLE 2 (Ref. API 12J)
60 21.4 10.1 2.0 Oil Gravities
66 17.7 10.3 1.9 Above 35 oAPI
72 14.9 10.6 1.8 20 to 30 oAPI
78 12.7 10.9 1.7 10 to 20 oAPI
84 10.9 11.2 1.6
90 9.5 11.6 1.6
NOTES
1. As per GPSA, typical vertical H/D ratios are normally in the 2 to 4 range.
INDEX
m and Gas Field Processing -
M. A. Fahim"
SCHEMATIC
EQUATIONS
TABLE 2 (Ref. API 12J)
Retention time,
Oil Gravities
minutes (Typical)
Above 35 oAPI 1
20 to 30 oAPI 1 to 2
10 to 20 oAPI 2 to 4
le 1)
INDEX
Two Phase (Gas - Oil) Horizontal Separator: As per "Petroleum and Gas Field Processing -
Hussein K. Abdel-Aal, Mohamed Aggour, M. A. Fahim"
INPUT PARAMETERS
Qg 15 mmscfd Gas rate SCHEMATIC
Qo 3000 bbl/d Oil rate
CALCULATIONS EQUATIONS
Step 1: Determine gas and oil properties
ρg 3.7 lb/ft3 Gas operating density
ρo 53.0 lb/ft3 Oil operating density
Step 2: Determine Cd
Cd 1.2 Assume Drag coefficient
u 0.40 ft/s Settling velocity of oil droplet
Re 55 Reynolds no.
Cd 1.19
Click
Click me
me
Use goal seek to get error zero, by changing
Error 0.00 asssumed Cd
SR = 12 ls
Ls, ft Governing (oil or
D, in Lg, ft (gas) Lo, ft Ls, ft (oil) case gas)/D
Liquid
6 13.85 14.35 357.00 476.0 Capacity 952.00
Liquid
12 6.93 7.93 89.25 119.0 Capacity 119.00
Liquid TABLE 2 (Ref. API 12J)
24 3.46 5.46 22.31 29.8 Capacity 14.88
Liquid Retention time,
Oil Gravities
30 2.77 5.27 14.28 19.0 Capacity 7.62 minutes (Typical)
Liquid Above 35 oAPI 1
36 2.31 5.31 9.92 12.4 Capacity 4.14
Liquid 20 to 30 oAPI 1 to 2
42 1.98 5.48 7.29 9.8 Capacity 2.80
Liquid 10 to 20 oAPI 2 to 4
48 1.73 5.73 5.58 8.1 Capacity 2.02
Liquid
54 1.54 6.04 4.41 6.9 Capacity 1.53
Gas
60 1.39 6.39 3.57 6.1 capacity 1.28
Gas
66 1.26 6.76 2.95 5.5 capacity 1.23
Gas
72 1.15 7.15 2.48 5.0 capacity 1.19
NOTES
1. As per GPSA, typical horizontal L/D ratios are normally in the 2.5 to 5 range.
INPUT PARAMETERS
Qg 8 mmscfd Gas rate SCHEMATIC
Qo 8000 bbl/d Oil rate
Qw 3000 bbl/d Water rate
ρ'o 27.6 API
o Oil density
CALCULATIONS EQUATIONS
Step 1: Determine gas and oil properties
ρg 0.89 lb/ft3 Gas operating density
ρo 55.5 lb/ft3 Oil operating density
Step 2: Determine Cd
Cd 2.07 Assume Drag coefficient
u 0.65 ft/s Settling velocity of oil droplet
Re 22 Reynolds no.
Cd 2.09
Error Use goal seek to get error zero, by changing
0.00 Click me
asssumed Cd
NOTES
1. As per GPSA, typical vertical H/D ratios are normally in the 2 to 4 range.
INDEX
Three Phase (Gas - Oil - Water) Horizontal Separator: As per "Petroleum and Gas Field Processing - Hussein
K. Abdel-Aal, Mohamed Aggour, M. A. Fahim"
INPUT PARAMETERS
Qg 8 mmscfd Gas rate SCHEMATIC
Qo 8000 bbl/d Oil rate
Qw 3000 bbl/d Water rate
ρ'o 27.5 API
o
Oil density
γo 0.89 Oil specific gravity
CALCULATIONS EQUATIONS
Step 1: Determine gas and oil properties
ρg 0.89 lb/ft3 Gas operating density
ρo 55.5 lb/ft 3
Oil operating density
Step 2: Determine Cd
Cd 2.07 Assume Drag coefficient
u 0.65 ft/s Settling velocity of oil droplet
Re 22 Reynolds no.
Cd 2.09
Error 0.00 Click me Use goal seek to get error zero, by changing asssumed C d
NOTES
1. As per GPSA, typical horizontal L/D ratios are normally in the 2.5 to 5 range.
INDEX
sing - Hussein
3 to 5
5 to 10
10 to 20
20 to 30