0% found this document useful (0 votes)
53 views

Ordering Code Details

1. This document provides information for ordering an Overcurrent Protection 7SJ80 device, including available configurations for measuring inputs, binary inputs/outputs, auxiliary voltage, construction, regional settings, communication ports, and measuring/fault recording options. 2. The device comes in various housing options with different numbers of measuring inputs, binary inputs, outputs, and status contacts. It can be ordered for surface or flush mounting. 3. Regional defaults, languages, and fronts can be specified. Communication ports include serial and Ethernet options.

Uploaded by

Juned Hamzavi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views

Ordering Code Details

1. This document provides information for ordering an Overcurrent Protection 7SJ80 device, including available configurations for measuring inputs, binary inputs/outputs, auxiliary voltage, construction, regional settings, communication ports, and measuring/fault recording options. 2. The device comes in various housing options with different numbers of measuring inputs, binary inputs, outputs, and status contacts. It can be ordered for surface or flush mounting. 3. Regional defaults, languages, and fronts can be specified. Communication ports include serial and Ethernet options.

Uploaded by

Juned Hamzavi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Overcurrent Protection 7SJ80

Selection and ordering data

Product description Order No. Short code


12345 6 7 8 9 10 11 12 13 14 15 16 17 18 19

1 Overcurrent Protection 7SJ80 V4.70 7SJ80 - - +

Measuring inputs, binary inputs and outputs


Housing 1/6 19"; 4 x I, 3 BI, 5 BO (2 Changeover/Form C), 1 Live status contact 1
2 Housing 1/6 19"; 4 x I, 7 BI, 8 BO (2 Changeover/Form C), 1 Live status contact
Housing 1/6 19"; 4 x I, 3 x U, 3 BI, 5 BO (2 Changeover/Form C), 1 Live status contact
2
3
Housing 1/6 19"; 4 x I, 3 x U, 7 BI, 8 BO (2 Changeover/Form C), 1 Live status contact 4 see
Housing 1/6 19"; 4 x I, 11 BI, 5 BO (2 Changeover/Form C), 1 Live status contact 7 next
Housing 1/6 19"; 4 x I, 3 x U, 11 BI, 5 BO (2 Changeover/Form C), 1 Live status contact 8 page

3 Measuring inputs, default settings


Iph = 1A / 5A, Ie =1A / 5A 1
Iph = 1A / 5A, Iee (sensitive) = 0,001 to 1,6A / 0,005 to 8A 2

Auxiliary voltage
DC 24 V / 48 V
4 DC 60 V / 110 V / 125 V / 220 V / 250 V, AC 115 V, AC 230 V
1
5

Construction
Surface-mounting case, screw-type terminal B
Flush-mounting case, screw-type terminal E
5 Region specific default and language settings
Region DE, IEC, language German (language changeable), standard front A
Region World, IEC/ANSI, language Englisch (language changeable), standard front B
Region US, ANSI, language US-English (language changeable), US front C
6 Region FR, IEC/ANSI, language French (language changeable), standard front
Region World, IEC/ANSI, language Spanish (language changeable), standard front
D
E
Region World, IEC/ANSI, language Italian (language changeable), standard front F
Region RUS, IEC/ANSI, language Russian (language changeable), standard front G
Region CHN, IEC/ANSI, language Chinese (language not changeable), Chinese front K
7 Port B (at bottom of device, rear)
No port 0
IEC60870-5-103 or DIGSI4/Modem, electrical RS232 1
IEC60870-5-103 or DIGSI4/Modem, electrical RS485 2

8 IEC60870-5-103 or DIGSI4/Modem, optical 820nm, ST connector


PROFIBUS DP Slave, electrical RS485
3
9 L 0 A
PROFIBUS DP Slave, optical, double ring, ST connector 9 L 0 B
MODBUS, electrical RS485 9 L 0 D
MODBUS, optical 820nm, ST connector 9 L 0 E
DNP 3.0, electrical RS485 9 L 0 G
9 DNP 3.0, optical 820nm, ST connector
IEC 60870-5-103, redundant, electrical RS485, RJ45 connector
9 L 0 H
9 L 0 P
IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector 9 L 0 R
IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 0 S
DNP3 TCP + IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector 9 L 2 R
DNP3 TCP + IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 2 S
PROFINET + IEC 61850, 100Mbit Ethernet, electrical, double, RJ45 connector 9 L 3 R
PROFINET + IEC 61850, 100Mbit Ethernet, optical, double, LC connector 9 L 3 S

Port A (at bottom of device, in front)

10 No port
With Ethernet interface (DIGSI, I/O-Unit connection, not IEC61850), RJ45 connector
0
6

Measuring/Fault Recording
With fault recording 1
With fault recording, average values, min/max values 3
You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec
4/18 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 2
Overcurrent Protection 7SJ80
Selection and ordering data

ANSI No. Product description Order No. Short code


Bestell-Nr.
12345 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Overcurrent Protection 7SJ80 V4.70 7SJ80 - - +
1
Basic version F A 3)

50/51 Time-overcurrent protection, phase I>, I>>, I>>>, Ip


50N/51N
50N(s)/51N(s)1)
Time overcurrent protection, ground IE>, IE>>, IE>>>, IEp
Sensitive ground fault protection IEE>, IEE>>, IEEp
2
Intermittent ground fault protection
87N2) High impedance REF
49 Overload protection
74TC Trip circuit supervision
50BF Circuit-breaker failure protection
46 Negative-sequence system overcurrent protection
37
86
Undercurrent monitoring
Lockout 3
Parameter changeover
Monitoring functions
Control of circuit breaker
Flexible protection functions (current parameters)
Inrush restraint

Basic functionality + Directional sensitive ground fault, voltage and frequency protection F B 4)
4
51V Voltage dependent inverse-time overcurrent protection
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1) Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
64/59N
27/59
Displacement voltage
Under/Overvoltage 5
81U/O Under/Overfrequency, f<, f>
47 Phase rotation
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change

Basic functionality + Directional phase & ground overcurrent,


directional sensitive ground fault, voltage and frequency protection
F C 4)
6
51V Voltage dependent inverse-time overcurrent protection
67 Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
67N Directional time-overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
67Ns1)
64/59N
27/59
Sensitive ground-fault protection, IEE>, IEE>>, IEEp
Displacement voltage
Under/Overvoltage
7
81U/O Under/Overfrequency, f<, f>
47 Phase rotation
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change

Basic functionality + Directional phase & ground overcurrent, directional sensitive ground F F 4)
8
fault, voltage and frequency protection + Undervoltage controlled reactive power protection
+ Directional intermittent ground fault protection
51V Voltage dependent inverse-time overcurrent protection
67 Directional overcurrent protection, phase, I>, I>>, I>>>, Ip
67N
67Ns1)
Directional overcurrent protection, ground, IE>, IE>>, IE>>>, IEp
Directional sensitive ground fault protection, IEE>, IEE>>, IEEp
9
67Ns2) Directional intermittent ground fault protection
64/59N Displacement voltage
27/59 Under/Overvoltage
81U/O Under/Overfrequency, f<, f>
Undervoltage controlled reactive power protection, Q>/V<
47 Phase rotation
Flexible protection functions (current and voltage parameters)): Protective function for voltage, see
27R/32/55/59R/81R power, power factor, rate-of-frequency change, rate-of-voltage change next
page

10
1) Depending on the ground current input the function will be either sensitive (IEE) or non-sensitive (IE)
2) Function only available with sensitive ground current input (Position 7=2)
3) Only if position 6 = 1, 2 or 7
4) Only if position 6 = 3, 4 or 8

SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 2 4/19


Overcurrent Protection 7SJ80
Selection and ordering data

ANSI No. Product description Order No. Bestell-Nr.


Short code
12345 6 7 8 9 10 11 12 13 14 15 16 17 18 19

1 Overcurrent Protection 7SJ80 V4.70 7SJ80 - - +

Basic functionality + Directional phase overcurrent, voltage and frequency protection + F Q 5)


synchrocheck

2 51V
67
Voltage dependent inverse-time overcurrent protection
Directional time-overcurrent protection, phase, I>, I>>, I>>>, Ip
27/59 Under/Overvoltage (phase-to-phase)
81U/O Under/Overfrequency, f< ,f>
47 Phase rotation
25 Synchrocheck
Flexible protection functions (current and voltage parameters)): Protective function for voltage,
27R/59R/81R rate-of-frequency change, rate-of-voltage change

3
Automatic Reclosing (AR), Fault Locator (FL)
Without 0
79 With automatic reclosure function 1

4 21FL
79/FL
With FL
With automatic reclosure function and FL
2
3

10

You will find a detailed overview of the technical data (extract of the manual) under: http://www.siemens.com/siprotec

5) Only with position 6 = 3 or 4 and position 16 = 0 or 1

4/20 SIPROTEC Compact · SIEMENS SIP 3.01 · Edition 2