Ds-En 2502352 Iki-50 1FR2

The IKI-50_1F R2 is a universal feeder control unit for intelligent distribution network stations. It offers distribution network operators high transparency and cost-effectiveness through fault detection algorithms and the ability to remotely control switches. The unit can detect various fault types, measure voltages, currents, and powers, and has communication capabilities. It is maintenance-free and suitable for panel mounting.

Uploaded by

saul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
252 views9 pages

Ds-En 2502352 Iki-50 1FR2

The IKI-50_1F R2 is a universal feeder control unit for intelligent distribution network stations. It offers distribution network operators high transparency and cost-effectiveness through fault detection algorithms and the ability to remotely control switches. The unit can detect various fault types, measure voltages, currents, and powers, and has communication capabilities. It is maintenance-free and suitable for panel mounting.

Uploaded by

saul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

IKI-50_1F R2

Universal Feeder Control Units for Intelligent Distribution Network Stations

The universal Feeder Control Unit IKI-50_1F R2 is


the appropriate solution for intelligent distribution
network stations and offers distribution network
operators a high level of transparency and cost-
effectiveness. The IKI-50_1F R2 includes all
algorithms for selective fault detection. It is
suitable for all neutral point treatments. Switching
commands for load switch control can be fed to the
IKI-50_1F R2 via communication bus and executed
field-related with 1.5-pole switching safety.

Properties

Fault detection
• directional short-circuit detection
• directional earth fault detection, directional static earth fault detection (wattmetric
method), directional transient earth fault detection (wiper method), earth fault detection
via pulse locating
• suitable for all neutral point treatments
• no summing transformer required

fault early detection


• fault early detection by detection of transient disturbances
• partial discharge trend detection together with CAPDIS-S2_55 (R5)

load flow measurement


• voltages, Currents, powers, frequencies, cos-phi, . ..
• Momentary and average values
• Limit value monitoring

Remote control and network automation


• selective control of up to two motors
• extensive logic functions freely programmable with PC software KriesConfig

IKI- 50_F1 R2 is maintenance-free


• no battery
• unlimited data retention
• error indication in case of power failure over 6 hours

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 1/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

precise voltage measurement with precision dividers


• optional voltage measurement with precision dividers, z. E.g. resistive sensors
• two voltage inputs: 1x capacitive, 1x resistive
• patented method for voltage calibration via a reference measurement from another feeder
.

Technical Data
Device data

Article number 2502352


Product designation IKI-50_1F R2
Number of feeders 1
Parameterization software KriesConfig
Configuration Via software Kries-Config (download at kries.com), Via
HMI and display (limited)

Operating elements and display

Front display LC-Display and LEDs


Direction keys Operation via four direction keys
Red LED (1) Error event detected | internal energy storage empty
Yellow LED (2) Slave Test | Primary Test | Device Warnings
Dreen LED (3) Status message device state
Buffer of power supply Capacitor (6h)

Dimensions and installation instructions

Case height x width x depth 49 x 96 x 108 mm


Cutout height x width 45 x 92 mm
Norm cutout dimensions DIN IEC 61554:2002-08
Installation type Panel mounting
Sheet thickness 1.5 ... 2.5 mm

Operating conditions

Operating temperature -25°C ... 55°C


Storage temperature -25°C ... 70°C
Humidity max. 95 % relative humidity at 40° C
Protection class IP54 (Front)

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 2/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Fault detection and failure forecast

Fault detection Individually selectable, any combinations possible


Star point types Short-term low-ohmic terminated neutral, Low-ohmic
terminated neutral, Inductive terminated neutral,
Isolated neutral
Short circuit detection I>> 
Directional short-circuit detection I>> 
Threshold current short-circuit detection I>> 100 A ... 1,000 A (adjustable in steps)
Threshold time short-circuit detection I>> 40 ms ... 1,600 ms (adjustable in steps)
Earth short-circuit detection Ie>> 
Directional earth short-circuit detection Ie>> 
Threshold current earth short-circuit detection Ie>> 40 A ... 1,000 A (adjustable in steps)
Threshold time earth short-circuit detection Ie>> 40 ms ... 1,600 ms (adjustable in steps)
Directional static earth fault detection Ie>; 
Threshold current static earth fault detection Ie> 2 A ... 30 A (adjustable in steps)
Directional transient earth fault detection Ie> 
Threshold current transient earth fault detection 3I0 1 A ... 1,000 A (freely adjustable)
Threshold voltage transient earth fault detection 3U0 1 kV ... 300 kV (freely adjustable)
Earth fault detection via pulse locating 
Pulse length of pulse locating symmetrical / asymmetrical
Transient fault detection IIe> 
TE trend monitoring • in conjunction with CAPDIS-S2_55 (R5)
• Indication on the display, transmission via Modbus-
RTU
• Partial discharge trend via frequency distribution;
integration over 24h, trend over 72h
Fault reset Auto, Manually on the device, After time (1 h ... 8 h,
configurable)
Event log The last 20 fault events are stored with event number,
date, time, name of the triggering fault detection,
fault direction, phase and fault current value.
Earth fault transient detection 
Directional earth short-circuit detection 
Interfaces and communication

USB interface Mini-USB


Modbus-RTU 
Modbus-RTU Slave 
Modbus transmission rates [kBd] 9600, 19200, 38400, 57600, 115200
Slave test 
Kries-Energietechnik GmbH & Co. KG
Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 3/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Interfaces and communication

Digital Inputs 6
Potential-free digital inputs 4
Digital Outputs 4
Digital outputs for 1.5 pole switching 2
Connection cable cross section Max. 2,5 mm
Switching capacity relay AC: max. 62,5 VA max. 2A; max. 250 VAC
DC: max. 2A @ 40 VDC
Relay outputs 6
Voltage inputs 2 (1x LRM/CAPDIS, 1x precision 3.25V)
Current transformer 3

Measurement values and functions

Voltage measurement 
Measuring range voltage Capacitive (Input F1), Precision divider with an output
signal of 3.25 V/sqrt(3) in nominal operation (input
UF2)
Phase-to-ground voltages 
Phase to phase voltages 
Measuring range voltage 0.02 kV ... 92 kV | Start of voltage measuring range:
2% of Un
Precision voltage measurement Yes
Accuracy voltage measurement Input UF1 (capacitive): 3 % of measurement value
after on-site calibration
Input UF2 (resistive): 0.5 % of measurement value
Cross calibration 
Current measurement 
Measuring range current 0.5 A ... 1,158 A (with current transformer IKI-LUM)
Zero-sequence current 
Accuracy current measurement 3 % of measurement value, optionally 1% of
measurement value
Conductor currents 
Active power 
Reactive power 
Apparent power 
Rotary field detection 
Frequency measurement 
Mean value determination 
Min-max value determination 
Kries-Energietechnik GmbH & Co. KG
Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 4/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Measurement values and functions

Phase position 
Phase shift cos-phi 
Limit value monitoring Voltage, current, frequency, reactive power and
voltage
Logic functions programmable A total of 32 logic rules can be programmed.

Power supply

Auxiliary power supply 24...230 VAC/DC (jeweils 15 %)


Power consumption 2W
Insulation voltage 2 kV, 1 min
CT-supplied -
Display buffer for fault indication Unlimited data retention (independent of auxiliary
power and buffer power);
Error display after power failure (depending on
adjustable follow-up time):
• with overrun time 12 seconds: 6 hours
• with run-on time 60 seconds: 4.5 hours

Compatible current transformers


Article number Product designation

2512106_H001 IKI-LUM_d92 Split-Core Transducer with cable tie (set) | Ø 92mm


2512106_H003 IKI-LUM_d92 Split-Core Transducer for C-Cone-Bushings (set) | Ø 92mm
2512106_H004 IKI-LUM_d92 Split-Core Transducer for SIEMENS-Bushings (set) | Ø 92mm

Connecting cables CTs


Article number Product designation

3503118_S Connecting cable set | pluggable | Length = 3,0m


3503135_S Connecting cable set | pluggable | Length = 5,0m
3503135_S999 Connecting cable set | pluggable | Lengths on request

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 5/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Accessories
Article number Product designation

2500484 Y-cable IKI to CAPDIS | 0.4 m | 2 x system plug


2500486_H002 Y-Cable IKI to CAPDIS | 0.4 m | Sx blade plug to system plug, decoupled
2500487 Y-cable IKI to CAPDIS | 0.4 m | 2 x Sx blade plug to system plug
2500484_S999 Y-cable CAPDIS to IKI; Lengths and connector combinations on request

Comparison of products
IKI-50_1F R2 IKI-50_1F R2e
2502352 2502461
Level of digitalisation 2 1
Short circuit detection
I>>  
Directional short-circuit
detection I>>  
Earth short-circuit
detection Ie>>  
Directional earth short-
circuit detection Ie>>  
Earth fault transient
detection  
Pulsation detection
 
Directional static earth
fault detection Ie>;  
Slave test
 
Relay outputs 6 4
Modbus-RTU
 
Modbus-RTU Slave
 
CT-supplied - -
Auxiliary power supply 24...230 VAC/DC (jeweils 15 %) 24...230 VAC/DC (jeweils 15 %)
Buffer of power supply Capacitor (6h) Capacitor (6h)
USB interface Mini-USB Mini-USB
Digital Inputs 6 4
Digital Outputs 4 4
Digital IOs configurable Yes Yes
Switching functions Switching of up to two load switches
--
feeder control unit 1.5-pole switching
Digital outputs for 1.5
2
pole switching
Voltage inputs 2 (1x LRM/CAPDIS, 1x precision 3.25V) 1 (LRM/CAPDIS)

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 6/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

IKI-50_1F R2 IKI-50_1F R2e


2502352 2502461
Voltage measurement
 
Precision voltage mea-
Yes
surement
Capacitive (Input F1), Precision divider with an out-
Measuring range volt-
put signal of 3.25 V/sqrt(3) in nominal operation
age
(input UF2)
Cross calibration
 -
Current measurement
 
Logic functions pro-
A total of 32 logic rules can be programmed. A total of 32 logic rules can be programmed.
grammable
Balanced core CT
- -
optional
IKI-LUM_d92 Split-Core Transducer with cable tie IKI-LUM_d92 Split-Core Transducer with cable tie
(set) | Ø 92mm (2512106_H001) (set) | Ø 92mm (2512106_H001)
IKI-LUM_d92 Split-Core Transducer for C-Cone- IKI-LUM_d92 Split-Core Transducer for C-Cone-
Compatible CTs
Bushings (set) | Ø 92mm (2512106_H003) Bushings (set) | Ø 92mm (2512106_H003)
IKI-LUM_d92 Split-Core Transducer for SIE- IKI-LUM_d92 Split-Core Transducer for SIE-
MENS-Bushings (set) | Ø 92mm (2512106_H004) MENS-Bushings (set) | Ø 92mm (2512106_H004)

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 7/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Wiring diagram

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 8/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations

Notes on the use of precision dividers

Precision dividers
Resistive or capacitive precision dividers with high accuracy can be connected to the voltage
input UF2. These precision dividers are connected via shielded coaxial cables. Kries offers the
following components for this purpose, please inquire separately:
• shielded coaxial cables in different lengths
• ohmic voltage dividers of type OAS for right-angle connectors with C-cones, symmetrical or
asymmetrical
• ohmic voltage dividers of type OKE for air-insulated switchgears
• capacitive precision dividers for asymmetrical right-angle connectors with shortened C-
cone (on request)

Cross calibration
Via a procedure patented by Kries, the exact voltage signal of the precision dividers can be
determined from a feeder (e. e.g., the transformer feeder) can be used as the reference
voltage for the other feeders. In the IKI-50_1F R2, an automated cross-calibration procedure
is integrated for this purpose, with which this adjustment can be carried out manually or at
specified time intervals. This makes it possible to realize a high degree of accuracy in voltage
measurement for the entire distribution network station.

Kries-Energietechnik GmbH & Co. KG


Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 9/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.