Ds-En 2502352 Iki-50 1FR2
Ds-En 2502352 Iki-50 1FR2
Properties
Fault detection
• directional short-circuit detection
• directional earth fault detection, directional static earth fault detection (wattmetric
method), directional transient earth fault detection (wiper method), earth fault detection
via pulse locating
• suitable for all neutral point treatments
• no summing transformer required
Technical Data
Device data
Operating conditions
Digital Inputs 6
Potential-free digital inputs 4
Digital Outputs 4
Digital outputs for 1.5 pole switching 2
Connection cable cross section Max. 2,5 mm
Switching capacity relay AC: max. 62,5 VA max. 2A; max. 250 VAC
DC: max. 2A @ 40 VDC
Relay outputs 6
Voltage inputs 2 (1x LRM/CAPDIS, 1x precision 3.25V)
Current transformer 3
Voltage measurement
Measuring range voltage Capacitive (Input F1), Precision divider with an output
signal of 3.25 V/sqrt(3) in nominal operation (input
UF2)
Phase-to-ground voltages
Phase to phase voltages
Measuring range voltage 0.02 kV ... 92 kV | Start of voltage measuring range:
2% of Un
Precision voltage measurement Yes
Accuracy voltage measurement Input UF1 (capacitive): 3 % of measurement value
after on-site calibration
Input UF2 (resistive): 0.5 % of measurement value
Cross calibration
Current measurement
Measuring range current 0.5 A ... 1,158 A (with current transformer IKI-LUM)
Zero-sequence current
Accuracy current measurement 3 % of measurement value, optionally 1% of
measurement value
Conductor currents
Active power
Reactive power
Apparent power
Rotary field detection
Frequency measurement
Mean value determination
Min-max value determination
Kries-Energietechnik GmbH & Co. KG
Sandwiesenstr. 19 | D-71334 Waiblingen 06.11.23
kries.com | [email protected] | +49 7151 96932 0 Page 4/9
© Kries-Energietechnik GmbH & Co. KG | Subject to modifications.
IKI-50_1F R2
Universal Feeder Control Units for Intelligent Distribution Network Stations
Phase position
Phase shift cos-phi
Limit value monitoring Voltage, current, frequency, reactive power and
voltage
Logic functions programmable A total of 32 logic rules can be programmed.
Power supply
Accessories
Article number Product designation
Comparison of products
IKI-50_1F R2 IKI-50_1F R2e
2502352 2502461
Level of digitalisation 2 1
Short circuit detection
I>>
Directional short-circuit
detection I>>
Earth short-circuit
detection Ie>>
Directional earth short-
circuit detection Ie>>
Earth fault transient
detection
Pulsation detection
Directional static earth
fault detection Ie>;
Slave test
Relay outputs 6 4
Modbus-RTU
Modbus-RTU Slave
CT-supplied - -
Auxiliary power supply 24...230 VAC/DC (jeweils 15 %) 24...230 VAC/DC (jeweils 15 %)
Buffer of power supply Capacitor (6h) Capacitor (6h)
USB interface Mini-USB Mini-USB
Digital Inputs 6 4
Digital Outputs 4 4
Digital IOs configurable Yes Yes
Switching functions Switching of up to two load switches
--
feeder control unit 1.5-pole switching
Digital outputs for 1.5
2
pole switching
Voltage inputs 2 (1x LRM/CAPDIS, 1x precision 3.25V) 1 (LRM/CAPDIS)
Wiring diagram
Precision dividers
Resistive or capacitive precision dividers with high accuracy can be connected to the voltage
input UF2. These precision dividers are connected via shielded coaxial cables. Kries offers the
following components for this purpose, please inquire separately:
• shielded coaxial cables in different lengths
• ohmic voltage dividers of type OAS for right-angle connectors with C-cones, symmetrical or
asymmetrical
• ohmic voltage dividers of type OKE for air-insulated switchgears
• capacitive precision dividers for asymmetrical right-angle connectors with shortened C-
cone (on request)
Cross calibration
Via a procedure patented by Kries, the exact voltage signal of the precision dividers can be
determined from a feeder (e. e.g., the transformer feeder) can be used as the reference
voltage for the other feeders. In the IKI-50_1F R2, an automated cross-calibration procedure
is integrated for this purpose, with which this adjustment can be carried out manually or at
specified time intervals. This makes it possible to realize a high degree of accuracy in voltage
measurement for the entire distribution network station.