Security Issues of Power System Interconnection
Security Issues of Power System Interconnection
Abstract--Voltage stability, transient stability and dynamic disturbance. The system is said to be stable in transient state if
stability studies are three approaches to power system security the rotor angle separation between any two machines tends to
studies. keep in a certain range after the disturbance. On the other
For evaluation of the synchronous interconnection of the African hand, the system is transient unstable if the rotor angles keep
regional power pools interconnection, security issues should be
running away. Figure 1 illustrates the stable and unstable cases
taken care of before any economic analysis is done. Power system
security studies have been used in industries only in time of during a transient period for a four-machine system. Figure1
planning. This paper will address a futural real time security (a) is stable case because the difference between any two rotor
system in operation of deregulated power pools. angles is within a certain range though the rotors are speeding
up. Figure 1(b) shows generators separated in two groups and
Keywords-- Dynamic stability, power system margin, power their rotor angles continue to drift apart. Therefore, (b) is
system operation, real-time, security, transient stability, voltage unstable case.
stability
III. DYNAMIC STABILITY
I. INTRODUCTION OF STABILITY
Dynamic stability is the ability of a power system to return
S tability is categorized as synchronous or angular stability
and voltage stability depending on the quantities in which
one is interested. Synchronous stability is focused on rotor
to its initial state or reach another steady state nearby after a
small disturbance. Dynamic stability of a system can be
understood by looking at the damping of the system
angles or frequencies of generators and voltage stability is oscillation, which can be triggered by either an unexpected
focused on bus voltages. Depending on the time-period one is disturbance, or a regular operation of the power system. The
observing, stability can be categorized as transient stability oscillation should die out in several seconds after the
and dynamic stability. The observed time-period for transient disturbance for a strong system, Figure 2(a). If the oscillation
stability is about a couple of swings after the disturbance. That is decaying slowly, Figure 2(b), then the system has bad
of dynamic stability is normally 1 to 6 seconds after the dynamic characteristics. If the system has a lasting oscillation,
disturbance. However, if necessary, the simulation time can be Figure 2(c), or even diverging oscillation, Figure 2(d), the
longer than 10 seconds. Table 1 summarizes different system is dynamically unstable. The poor damping of the
categories of stability. oscillation signals a narrow stability margin of the power
system. With this small margin, the system operators must be
Table 1 Categories of power system stability very careful when they are executing the system operations
Transient Dynamic because the operation criteria might not apply. The same
Stability Stability operation might drive the system to an unstable area though it
Synchronous Observe Observe dynamic was good yesterday.
Stability transient response (1~6 In a power system, it may be stable during transient period
response (1~2 Seconds after but unstable during dynamic period, as shown in Figure 3.
Swings after disturbance) of
disturbance) of generators
generators Rotor Angle
1
2
4 (c)
Time
(a) Unstable
Figure 1 Rotor angle behavior during a transient
Both of two generators speed up after the fault and one would
say that the system is transient stable from the first swing of
rotor angles. After the first swing, the rotor angles begin a
divergent oscillation, which is unstable. One of the
phenomena of dynamic stability problems is the oscillation.
The frequency of the oscillation is between 0.2 and 10 Hz.
Thus, this oscillation is called low frequency oscillation since (d)
its frequency is low compared to system frequency. Figure 2 Oscillations
Rotor Angle
Dynamic
unstable
(a)
Transient
stable
Yes (1) No
Operator
Takes Action
?
Plan B(2)
Rem edy
Status B
Sy stem Data Evaluate System Status A
Calculate System Intelligent Relay s Plan A(2)
Status Based on
OM Monitoring Rem edy
OM
Status C
Plan C(2)
P-V Curve Rem edy
Display
(1)
Operator Takes No
Action
?
Yes
Note: (1) Preventive actions include Re-dispatch, Shedding interruptible loads, Shedding weak bus loads, etc.
(2) Plans A, B, C remedies
VII. BIOGRAPHY