Topic Assignment1
Topic Assignment1
Abstract-- This paper proposes an LLC resonant converter automatic voltage equalization [12-13]. However, the
with parallel-series transformer connection and voltage transformer volume is not yet much reduced, since only
doubler rectifier (PSVD LLC),i.e. LLC circuit structure in half of the turns-ratio is reduced.
which the transformers are parallel-series connected and the The proposed circuit combines the advantages of these
secondary side is voltage doubler rectifier. The parallel-series two methods proposed above. The transformer turns ratio
connection can reduce the turns ratio of the transformer. And is a quarter of the one in the traditional LLC circuit,
the use of the characteristics of the voltage doubler rectifier effectively reducing the size of the transformer. The
circuit improves the efficiency of the system, especially in the copper loss of the primary side of the transformer is
application of high frequency, low input voltage and high reduced and the loss of the voltage equalization resistance
output voltage. This paper introduces the structure and
is eliminated. The efficiency improvement effect is
working modes of the proposed circuit and analyzes the
principle of how this circuit improves efficiency. A 1000W especially noticeable in the case of high operating
prototype of the proposed circuit is established to verify the frequency and high output voltage operating conditions.
effectiveness of the scheme.
II. THE CIRCUIT CONFIGURATION AND BASIC OPERATION
Index Terms-- improve efficiency; PSVD LLC; voltage PRINCIPLE OF THE PROPOSED CONVERTER
doubler rectifier;
I. INTRODUCTION
Nowadays, power electronic converters are
increasingly moving toward high frequency and high-
power density. Because of the unique advantages of the
LLC circuit, i.e. the ZVS of the primary side switches and
the ZCS of the secondary side rectifier diodes, LLC
converters are gradually becoming one of the most widely
used DC/DC converter topology [1-4]. Therefore, more Fig.1 Circuit configuration of the proposed converter
and more investigations focus on the LLC circuits and
there are many optimization designs to improve its
performance. The improvements include control methods
and circuit topology [5-8].
Considering that LLC circuit can achieve ZVS and have
high efficiency, it is better to choose LLC circuit for boost
conversion. In applications with low input voltage and
high output voltage, the transformer’s secondary side turns
ratio is much larger than the primary side, which makes it Fig.2 LLC converter with parallel-series connected transformers and
difficult to reduce the volume of the transformers. In order full bridge rectifier circuit (PSFB LLC)
to reduce the turns ratio of the transformer, an LLC Fig.1 shows the configuration of the PSVD LLC. The
resonant converter with two transformers parallel-series circuit includes switching network, resonator and sub-side
connected is proposed [9-11]. This method not only rectifier circuit. The switching network of the PSVD
reduces the voltage stress on the secondary side of the consists of switches S1-S4. Dds1-Dds4 are parasitic diodes of
transformer, but also reduces the copper loss of the the S1-S4, and COSS1-COSS4 are the output capacitance of the
transformers’ primary side. However, although this switches. The resonant tank consists of a resonant inductor
method reduces the transformers’ turns ratio, utilizing two Lr, a resonant capacitor Cr and two magnetizing inductors
transformers instead of one transformer does not Lm1 and Lm2. Parallel-series connecting transformers T1 and
significantly reduce the transformer’s volume. In addition, T2 have the same turns ratio n=n1=n2. The output rectifier
the voltage doubler rectifier circuit is also used to replace composed of two diodes D1 and D2, two electrolytic
the full bridge rectifier circuit in the traditional LLC capacitors C1 and C2, and load RO. Cj1 and Cj2 are the
circuit. This circuit can reduce the volume of the parasitic capacitances of D1 and D2. C1 and C2 are used to
transformer, in addition, the equalizing resistor is not
store the energy from the primary side to the secondary
needed, because the output capacitor can achieve
ⓒ2019 KIPE 14
side. The capacitance of C1 and C2 are equal and two the same, i.e. the switches conduction losses Pson and
capacitors C1 and C2 split the output voltage equally. The switching losses Poff of S1-S4 are the same. The secondary
T1 and T2 are parallel connected on the primary side,so side of the PSVD adopts a voltage doubler rectification
the voltage on the secondary side of the transformer can be structure, which reduces the number of turns of the
balanced automatically. T1 and T2 are series connected on secondary side of the transformer by half, i.e. n1=
the secondary side and they will have the same secondary n2=0.5n3=0.5n4=n. In addition, considering that the
side current. And this can ensure that the primary currents number of secondary diodes in the PSVD is half that of the
PSFB LLC circuit. In order to reduce the variation, two
of the transformers are the same. Thus, the
diodes connected in parallel are used in the PSVD to
automatic current sharing can be achieved on the primary
ensure the number of the secondary diodes are the same as
side. The voltage doubler rectifier circuit increases the the PSFB LLC circuit. Therefore, each diode on the
secondary output voltage of the transformer by twice secondary side of the PSVD passes the same current as the
through C1 and C2. This will help to reduce the transformer PSFB LLC circuit, and the diode conduction losses Pdon of
turns ratio and the secondary side voltage stress. the two circuits are the same.
The four working modes of the PSVD are shown in
Fig.3. And the Fig.4 shows the key waveform of the
proposed circuit.
Mode 1 (t0 - t1): At time t0, power switches S1 and S3 are
turned on in the case of zero voltage (ZVS). The rectifier
diode D1 is conducted. C1 is charged in this mode.
Mode 2 (t1 – t2): At time t1, D1 is turned off in the case
of zero current (ZCS). The energy is no longer transferred
from the input side to the output side. On the primary side,
the resonance occurs between Lr, Cr, Lm1 and Lm2.
Mode 3 (t2 – t3): S1 and S3 are turned off at t2 time. COSS1
and COSS3 is charged, while COSS2 and COSS4 is discharged
until Vds1 and Vds3 rises to Vin, and theVds2 and Vds4
drops to zero. D2 is conducted and the C2 is charged.
Mode 4 (t3 – t4): The parasitic diodes Dds2 and Dds4 is
naturally turned on at t3 time. Thus, S2, S4 can be turned on
in the case of zero voltage (ZVS) at t4 time.
The operation modes of the PSVD during the t5-t8 time
are similar to the Mode 1-Mode 4, so the detailed working
modes are not repeated.
15
to reduce the magnetic loss by reducing the volume of the losses of the two circuits include Pcoreloss, Peqloss, Poff, Pson
transformer. However, when the output voltage gain is and Pdon. The Poff, Pson and Pdon of the two circuits are same.
high, the number of turns on the secondary side of the Therefore, the Poff, Pson and Pdon are only needed to
transformer will be large. This will lead to a large Pcoreloss. calculate in the PSVD circuit, and these losses in the PSFB
Compared with the traditional LLC circuit and the PSFB circuit are the same.
LLC circuit, the PSVD has the smaller turns ratio, and will
A. Magnetic component loss calculation for two circuits
have a smaller volume of the transformer.
In addition to reducing the Pcoreloss, another The flux density change ∆B is set to 0.2T, in order to
characteristic of the PSVD is that the equalizing resistors minimize the number of turns of the transformer and
are not needed. In order to meet the withstand voltage control variables. According to the loss diagram, at a
requirements and reduce the volume of the Co as much as switching frequency of 200kHz, the core loss of 0.2T flux
possible at the same time. When outputting a high voltage, density corresponds to a core loss of 0.0009W/mm3. So,
the PSFB LLC circuit requires two capacitors in series as the transformer magnetic losses of the proposed circuit and
the output capacitor. Therefore, the voltage equalization the PSFB circuit are
resistors are needed for the PSFB LLC. However, in the −4
Pcoreloss . PSVD = 2 ⋅ 9 ⋅ 10 ⋅ 6549W = 11.79W (1)
PSVD, the two output capacitors can achieve self-voltage −4
equalization [13], so, the equalizing resistors are not Pcoreloss . PSFB = 2 ⋅ 9 ⋅ 10 ⋅ 12010W = 21.618W (2)
needed. Thus, there is no loss of the equalizing resistors It can be seen from the above two equations that the
(Peqloss) in the proposed circuit. proposed circuit reduces the magnetic loss by nearly half,
which can improve the circuit efficiency.
The copper loss of the magnetic component can be
ignored, for the DC resistance of the resonant inductor and
the transformer are very small.
3
The volume of the resonant inductor is 2815 mm . So,
the magnetic loss of resonant inductor can be expressed as
follows
16
Comparing to the above losses, it can be found that the
V + I off Rds
T3 = Tg ⋅ ln gs Pcoreloss of the transformer is dominant in all losses. And
(11)
Vgs there is also a relatively large loss in the equalizing resistor.
Since the Pcoreloss can be regarded as a constant, the total
Poff .total = 4 Poff = 4 ⋅ 0.5Vds I off (T2 + T3 ) f s = 0.05W (12)
main loss expression of the two circuit can be expressed as
where Ioff is the turn off instantaneous current, Tg is the turn follows.
off time constant, T2 is the voltage transmission time, T3 is Theoretical main loss expression of the proposed circuit:
the current transmission time. Pmain.total . PSVD = Pcoreloss . PSVD + Pon + Pdiode.on (21)
So, the total switching loss Poff.total is only 0.2W. And it
2
can be ignored. P P
Pmain .total . PSVD = 15.45 + 0.079π 2 o + 0.5π o (22)
D. The conduction loss of the switches V
o Vo
(14) Po Po Vo
2
(24)
Pmain . total . PSFB = 25.3 + 0.079π 2 + 0.5π +
2n1π Io Vo Vo 71200
I r.rms = (15) The approximate efficiency graph is shown in Fig.4.
2
2 100
2 nπP
Pon = 2 I r . rms Rds = 4 Rds 1 o = 1.5W (16) 95
Vo
EFFICIENCY(%)
I sec. peak 75
I sec. rms = (17) 100 200 300 400 500 600 700 800 900 1000
2 POWER(W)
Fig.5 Comparison of the efficiency of the two circuits.
I sec. rms I sec. peak
I diode. rms = = (18)
2 2 2 In different temperatures have different magnetic loss
curves, and the efficiency curve of this graph is estimated
Vdiode.on = 0.1I diode. rms + 0.7 (19)
based on the magnetic loss at 60ºC, so it will deviate from
Po
2
Po the experimental. It can be seen from Fig.5 that the PSVD
Pdiode.on = 0.025π V + 0.5π V = 3.28W
2
(20) has an improvement in efficiency. And as the power level
o o decreases, the efficiency increases more obviously. As
where Isec.rms is the secondary side current effective value, shown in Fig.6, with the output voltage increase and the
Idiode.rms is the current effective value of the diode, Vdiode.on power level decreases, the efficiency of the PSVD is
is the conduction voltage of the diode significantly higher than that of the PSFB LLC circuit.
17
output is 600V, the rated power is 1000W and the full
resonant frequency is 200kHz. In addition, some key
parameters of the two prototype circuits are provided in the
table II. In addition, the total volume of the transformers in
the proposed circuit is 13098 mm3, and the volume of the
transformer in the circuit with only one transformer is
17300 mm3. It is clearly that the size of the transformers is
reduced.
REFERENCES
[1] A. K. S. Bhat, “Analysis and design of a modified series
resonant converter,” IEEE Trans. Power Electron vol. 8, no.
Fig.8 Arm midpoint voltage and the resonant current of primary side at 4, pp. 423-430, Oct. 1993.
full load [2] B. -. Lin and J. -. Chen, “Analysis of a new ZVS converter
with output voltage doubler,” 2009 4th IEEE Conference on
Industrial Electronics and Applications, Xi'an, 2009, pp.
2026-2031.
[3] H. Xu, Z. Yin, Y. Zhao and Y. Huang, “Accurate Design of
High-Efficiency LLC Resonant Converter with Wide
Output Voltage,” IEEE Access, vol. 5, pp. 26653-26665,
2017.
[4] Nor Azura, S. Iqbal, Soib Taib, “LLC resonant DC-DC
converter for high voltage applications,” Energy Conversion
(CENCON) 2014 IEEE Conference on, pp. 90-95, 2014.
18
[5] Z. Hu, Y. Liu and P. C. Sen, “Bang-Bang Charge Control
for LLC Resonant Converters,” IEEE Trans. Power
Electron, vol. 30, no. 2, pp. 1093-1108, Feb. 2015.
[6] W. Sun, Y. Xing, H. Wu and J. Ding, “Modified High-
Efficiency LLC Converters with Two Split Resonant
Branches for Wide Input-Voltage Range Applications,”
IEEE Trans. Power Electron, vol. 33, no. 9, pp. 7867-7879,
Sept. 2018.
[7] Z. Fang, J. Wang, S. Duan, K. Liu and T. Cai, “Control of
an LLC Resonant Converter Using Load Feedback
Linearization,” IEEE Trans. Power Electron, vol. 33, no. 1,
pp. 887-898, Jan. 2018.
[8] H. Ma, Q. Liu and Y. Wang, “Discrete pulse frequency
modulation control with sliding-mode implementation on
LLC resonant DC/DC converter via input-output
linearization,” IET Power Electron, vol. 7, no. 5, pp. 1033-
1043, May 2014.
[9] B. Lin and H. Shih, “ZVS Converter With Parallel
Connection in Primary Side and Series Connection in
Secondary Side,” IEEE Trans. Power Electron, vol. 58, no.
4, pp. 1251-1258, April 2011.
[10] B. Lin and J. Dong, “ZVS Resonant Converter with
Parallel–Series Transformer Connection,” IEEE Trans. Ind.
Electron, vol. 58, no. 7, pp. 2972-2979, July 2011.
[11] H. Zhou, L.-F. Ma, T.-F. Wang, and Z.-S. Wang, “Full-
bridge LLC resonant converter with parallel-series
connected transformers,” Power Electron., vol. 50, no. 4, pp,
54-56, Apr. 2016
[12] B. R. Lin and S. F. Wu, “Analysis of a resonant converter
with two transformers and voltage doubler rectifier,” IET
Power Electron, vol. 4, no. 4, pp. 400-406, April 2011.
[13] Yilei Gu, Lijun Hang, Zhengyu Lu, Zhaoming Qian and
Dehong Xu, “Voltage doubler application in isolated
resonant converters,” in Proc. IEEE IECON, Nov. 2005, pp.
1184–1188.
[14] S. Maniktala, Switching Power Supplies A to Z. Newnes,
London-UK, Jun. 22, 2006, ch. 5, ISBN: 0750679700.
19