Intelidrive Lite
Intelidrive Lite
InteliDrive Lite
Modular Engine Controller
ID-Lite
USER GUIDE
!! Warnings !!
Remote control
InteliDrive-Lite controller can be remotely controlled. In case of the work on the engine check, that
nobody can remotely start the engine.
To be sure:
Disconnect remote control via RS232 line
Disconnect input REM START/STOP
or
Disconnect output STARTER
Because of large variety of InteliDrive-Lite parameters settings, it is not possible to describe any
combination. Some of InteliDrive-Lite functions are subject of changes depend on SW version.
The data in this manual only describes the product and are not warranty of performance or
characteristic.
Text
PAGE (Capital letters in the frame) buttons on the front panel
Break Return (Italic) set points
Engine protections (Bold) Set point group
REMOTE START/STOP (Capital letters) binary inputs and outputs
Note:
ComAp believes that all information provided herein is correct and reliable and reserves the right to
update at any time. ComAp does not assume any responsibility for its use unless otherwise expressly
undertaken.
Note:
SW and HW must be compatible (e.g. ID-Lite firmware and ID-Lite HW) otherwise the function will be
disabled. If wrong software is downloaded the message HARDWARE INCOMPATIBLE appears on
controller screen. In this case use Boot load (jumper) programming – close Boot jumper and follow
instructions in LiteEdit, download correct software.
Controller supports WebSupervisor system. This system enables gen-set and drive fleet and assets
management as well as pure monitoring. Visit www.comap.cz for more details about WebSupervisor.
Software package
ID-Lite-2.0 is distributed as ID-Lite-2.0.iwe package. It is compatible with the LiteEdit-4.5 (or - 4.5.1)
PC software – use installation package LiteEdit 4.5 r1 Installation Suite from ComAp web.
No setpoints, No history screens are visible when User interface = User (use Enter+Page, Enter,
Enter).
Hints:
No plug-in module can be configured in “ID-Lite-s-2.0.AIL “ reduced screen version of ail archive.
To insert the module, please follow the instructions for IL-NT RS232 module, procedure is analogous.
You must open the cover first (use screwdriver to open) and then insert the module into slot. Once you
have inserted it, the module will snap under plastic teeth. It is supposed to be installed permanently.
Should you need to remove it, the safest way is to remove whole back cover and than remove module
manually.
Boot jumper
RS485 Terminator jumper
Hint:
Use the shielded USB A-B cable with this module! Recommended is ComAp cable – Order code:
“USB-LINK CABLE 1.8M”.
0 VBat
GND
+Ubat
Prop valves
AOUT 1
AOUT 2
AOUT 3
AOUT 4
BIN 7
BIN 8
BIN 9
BIN 10
Binary inputs
IL-NT AIO
IL-NT AIO is optional plug-in card with additional four Analog inputs and one Analog output. Use
LiteEdit to configure Inputs and Output.
I
AI4
U
AI3
R
AI2
R AI1
0VBATT 0VBATT
+24VBATT +24VBATT
1 2 3 4 5 6 7 8 9 10
IL-NT 0V +VBatt AOUT1 AOUT2 AOUT3 AOUT4 AOUT5 AOUT6 AOUT7 AOUT8
AOUT8
IL-NT IO1 0V +VBatt AOUT1 AOUT2 AOUT3 AOUT4 BIN7 BIN8 BIN9 BIN10
IL-NT BIO8 BIO1 BIO2 BIO3 BIO4 BIO5 BIO6 BIO7 BIO8 0V 0V
IL-NT AIO AIN1 AIN2 AIN3 AIN4 n.c. n.c. I out U out PWM n.c.
out
Hint:
The module requires configuration settings before usage. See IB-Lite-1.x Reference Guide.
Hint:
GPRS and CSD services has to be provided by your GSM/GPRS operator for successful operation.
Hint:
GPRS and CSD connection is not suitable for firmware update process, kindly used wired connection
instead like RS232, USB, RS485 or ethernet via IB-Lite!
InpChar
Necessary condition: Regulator: LAI SpeedReq = OFF and controller MAN mode.
Necessary condition: Regulator: LAI SpeedReq = OFF and controller MAN mode.
PI loop and Hysteresis comparator functions can be used for Engine Load Limitation or for any other
control function.
2
LoadSwitch 0/1
AIN CMPH
LBO
Up Limit
Down Limit
AIN
RPM Pick-up RPM
1
J1939 0-5V/20mA
ENGINE ECU PI
CAN Percent Load LoadLimit
Up Limit AnOut
or RPM
L Request1 Dn Limit
Engine load L Request2 Bias
Hydr. L Req Ramp
Valve
LBI L Request2
LBI L Reg Disable
Proportional
On / Off
Description: CMPH (Comparator with Hysteresis) detect the RPM decrease below the Down limit,
activates the Binary output Load switch that reduces (slow down feeder) the load. There are expected
corresponding droop characteristics on the engine.
Speed switch
Purpose: Switch on/off some device depends on RPM level.
General comparator
Purpose: Switch on/off some device depends on analog value – e.g. temperature.
Description: The engine load (e.g. feeder speed) is reduced when actual “Percentual load” (coming
from ECU) is over the Load limit: LoadRequest1 (or LoadRequest2) setpoint. Load can be
continuously reduced by Analog output or switched between two levels by Binary output to keep the
Engine load on or below the limit.
Description: 1-PI (can be used 3-PI as well) detect the difference between actual and requested value
and changes the output to keep the controlled value on the limit.
Function requires plug-in module with Analog output.
AOUT
Input Analog input: CU: AI1, AI2, AI3
AIO: AI1, AI2, AI3, AI4
Function 1-PI
Binary input: L Request 2 (optional)
Binary input: L Reg Disable (optional)
Function 3-PI
Binary input: Request 2 (optional)
Binary input: Reg Disable (optional)
Output Analog output: Load Limit (plug-in module)
Analog output: ByRPMCtrlAout (plug-in module)
Setpoints Load limit: Load Input = Load
Load Bias
Load Request 1
Load Request 2
Load ReqRamp
Load UpLimit
Load DownLimit
Load Gain
Load Integral
Regulator: Reg Input
Reg Bias
Request
Request 2
Reg Gain
Reg Integral
Functions 3 = PI loop and 4 = Comparator with Hysteresis (CMPH) are available. The function setup is
done by corresponding setpoints in Regulator group.
The 3-PI function output is Speed request transmitted via J1939 or Analog output. Both functions can
use controller or plug-in IL-NT-AIO module Analog inputs.
In table below see different operation conditions.
InpChar
Following example changes the RPM between two levels based on pressure.
LBO Function:
Speed Switch Regulator Comparator output
Take care if the Speed request in AUT mode is not limited by Engine params: Speed ramp.
SpeedRequest =
Configured Not AI SpeedRequest
at least one LBI SpeedSel1
configured
LBI SpeedSel2
LBI SpeedSel3
Opened
SpeedRequest =
constant
SpeedRequest starts at
SpeedRequest =
ECU SpeedAdj
stay on the last value
SpeedRequest = and go Up/Down by
or
BI SpeedSel1 or BI Speed Ramp within
value is changed by
BI SpeedSel2 or MinSpeedLim - SpeedRequest =
LBI SpeedUp/Down
BI SpeedSel3 MaxSpeedLim ECU SpeedAdj
SpeedRequest =
go Up/Down by
BI Speed Ramp within
MinSpeedLim MaxSpeedLim
MAN mode
START – starts the engine.
STOP – stops the engine.
Hint:
The engine can run without load unlimited time.
The controller does not automatically stop the running engine in MAN mode.
The controller does not start the engine when binary input REM START/STOP is closed.
Start-stop sequence
MODE = MAN (Engine start/stop request is given by pressing buttons START and STOP )
MODE = AUT (Engine start/stop request is given by binary input REM START/STOP)
The start-up sequence can be interrupted in any time by coming stop request
Fuel solenoid is switched on with time advance of 1s fixed before starter motor is switched on.
Hint:
Threshold level for D+ input is 80% supply voltage; activation delay is 1s (to override short firings
during cranking – for example in cold conditions).
AUT mode
The controller does not respond to START, STOP buttons. Engine start/stop request is given by
binary input REM START/STOP.
PI loop and Hysteresis comparator functions can be used both for Engine Load Limitation or any other
control function.
AUT mode
Engine starts and runs all the time when the LBI Rem start/stop is closed. Running Timer is activated
after Rem s/s is opened. To stop the engine the Rem start/stop has to be opened or controller
Order codes
Order code
Above described ID-Lite set in the box ID-Lite
Separate Fixing clips (brackets) Clamps set for ID-Lite
Separate set of (female) connectors can be ordered TermSet IL-NT
Cutout
for InteliDrive-Lite
112 x 172 mm
(4.4 x 6,8“)
Plug-in
110 (4,3")
25 (1,0")
126 (5,0")
RS 232 module
80 (3,1")
4,3 (0,17")
186 (7,3")
Modem or PC
Interface
RS-232C
+24 V
BINARY OUTPUTS
DIESEL / GAS ENGINE
ECU
Hint:
It is possible to start Volvo and Scania engines via CAN bus. See Engines started via CAN bus.
Modem or PC
Interface
RS232
+24 V
BINARY OUTPUTS
IGS-PTM
CAN
DIESEL / GAS ENGINE
Power supply
To ensure proper function:
Use min. power supply cable of 1.5mm2
Maximum continuous DC power supply voltage is 36VDC. Maximum allowable power supply voltage
is 39VDC. The ID-Lite’s power supply terminals are protected against large pulse power disturbances.
When there is a potential risk of the controller being subjected to conditions outside its capabilities, an
outside protection devise should be used.
Hint:
The InteliDrive-Lite controller should be grounded properly in order to protect against lighting strikes!!
The maximum allowable current through the controller’s negative terminal is 4A (this is dependent on
binary output load).
For the connections with 12VDC power supply, the InteliDrive-Lite includes internal capacitors that
allow the controller to continue operation during cranking if the battery voltage dip occurs. If the
voltage before dip is 12V, after 150ms the voltage recovers to 7 V, the controller continues operating.
During this voltage dip the controller screen backlight can turn off and on but the controller keeps
operating.
It is possible to further support the controller by connecting the external capacitor or I-LBA module.
Connecting the external capacitor Connecting I-LBA – Low Battery Adaptor module
Relays Relays
controller controller
T2A D T2A
+ + + +
I-LBA
+
- - - -
C
- + - +
12VDC Battery 12VDC Battery
The capacitor size depends on required time. It shall The I-LBA module ensures min. 350ms voltage dip
be approximately thousands of microFarads. under following conditions:
The capacitor size should be RS232 and other plug-in module is connected.
5 000 microFarad to withstand 150ms voltage dip Voltage before dip is 12V and after 350ms the
under following conditions: voltage recovers to min. allowed voltage 5V,
Voltage before dip is 12V, after 150ms the voltage The I-LBA enables controller operation from 5VDC
recovers to min. allowed voltage, i.e. 8V (for 10 to 30 sec).
The wiring resistance from battery should be up to
0.1 Ohm for I-LBA proper function.
+ -
B a tte ry HUGE
LOADS
STARTER
Fuse
K1 K1 K2
K2
controller
T1A
+
-
DC relays
- +
24VDC Battery
Grounding
To ensure proper function:
Use as short as possible cable to the grounding point on the switchboard
2
Use cable min. 2,5mm
The “-“ terminal of the battery has to be properly grounded
MAGNETIC
PICK-UP
iL Signal b
D C
Signal
GAC
Speed Control Unit
ESD 5500
+ -
Power
Supply
- Power
+
Supply
+ -
Battery
Be aware of interference signal from Speed governor when one speed pick-up is used.
If engine will not start:
- Check ground connection from pick-up to controllers, eventually disconnect ground connection
to one of them
- Galvanic separate ID-Lite RPM input using ComAp separation transformer RPM-ISO (1:1)
- Use separate pick-up for Speed governor and InteliDrive-Lite
Analog inputs
Three analog inputs are available on the ID-Lite
Configuration
Each analog input can be configured by LiteEdit software following way.
LiteEdit Possibility
Type Not used Analog input isn’t used
Alarm
Name … text Up to 14 ASCII characters
Config Analog Analog measuring in specified range.
Binary: open/close - threshold 750 Ω.
Three-state: open/close - threshold 750 Ω,
Failure <10 Ω or > 2400 Ω
Alarm Over Overstep. Sensor fail does not activate protection.
properties Over+Fls Overstep and Sensor fail activates protection.
Under Under step. Sensor fail does not activate protection.
Under+Fls Under step and Sensor fail activates protection.
Sensor - Sensor name … text
Points Resolution Number of decimal points
Dimension bar,%,°C, …
Contact NC Valid only for binary and three-state inputs
type NO Valid only for binary and three-state inputs
COM
AI1 – binary input
AI1
AI2
AI3
AI2 – three state input
AI3 – analog resistive input
2x
470
Analog inputs are designed for resistive sensors with resistance in range of 0Ω to 2,4kΩ.
To ensure a proper function use shielded cables, especially for length over >3m.
As binary input
Open, close state are detected, threshold level is 750 Ω.
Binary inputs
4k7
ID-Lite
+ -
Power
Supply
+ -
Battery
LOAD
ID-Lite
+ -
Power
Supply
+ -
Battery
Connection rules
CAN bus line must be connected in series, from one unit to the next (no star, no cable stubs, no
branches) both ends must by the 120-ohm (internal or external) resistor terminated. Maximal CAN bus
length is up to 200 meters.
For CAN data cables details see chapter Technical data – Communication interface. CAN cable
shielding connect to ID-Lite COM terminal.
ID-Lite contains internal fix 120-ohm resistor and must be located on the CAN bus end.
It is possible to connect only one IGL-RA15 to ID-Lite.
Use button in LiteEdit (3.0 or higher) configuration window to activate CAN (J1939) interface.
Analog outputs
Optional plug in card IL-NT AOU8 provides eight Pulse-With-Modulation (PWM) outputs. These are
intended to drive VDO style analog gauges. This is to provide visual indication of typically ECU values
without installing additional sensors on the engine. PWM signal emulates sensor which would be
typically mounted on the engine.
Any value from controller may be configured to the outputs. Use LiteEdit PC SW to configure
corresponding sensor/gauge curve and value selection.
Modem or PC
Interface
RS232
0V
+12 V
BINARY OUTPUTS
+12VBAT
0 VBAT
AOUT 1
AOUT 2
AOUT 3
AOUT 4
AOUT 5
AOUT 6
AOUT 7
AOUT 8
Hint:
Import latest ECU list – ECU list-4.9.iwe for up to date engine ECU specification.
Select the proper esl file in LiteEdit-Options-ESL files – typically Allspeed.esl.
More information about ECU list packages, configuration and wiring recommendations can be found in
Comap Electronic Engines Support manual.
The ID-Lite controller always sends either speed request = 0 % or the IDLE command via J1939 in
controller IDLE state. In the MAN mode the IDLE operation can be controlled by Nominal/Idle binary
input.
Loss of communication causes shutdown of the running engine. On the contrary, the ECU can be
switched off at quiescent engine that means not-communicating ECU is in that moment normal
situation. All values from ECU shall show ####, but no alarm is displayed. The output ECU CommOK
follows the real situation that means it is not active anytime when the ECU does not communicate.
The output ECU PwrRelay closes at the beginning of prestart and opens if the engine shall be
stopped.
The engine is started via standard contact output or via CAN bus (for Volvo and Scania engines). For
other engines J1939 is used for monitoring only.
Cummins MODBUS
When “Cummins-Modbus” option is selected, following values are read from Modbus Register Data
(for QSX15,QSK45, QSK60):
Value name Short name Dimension Type Frame name
Red Shutdown Lamp Red Lamp - BIN 10005
Yellow Warning Lamp Yellow Lamp - BIN 10006
Hint:
ID-Lite controller doesn’t support J1587 diagnostic line on Volvo engines. This can cause in some
cases a J1939 alarm message FC:000608 due to missing J1587 bus. Contact your Volvo distributor to
update ECU firmware.
For Scania Fault codes (FC) are displayed. Following messages are available for particular groups of
Fault codes:
Faultcode Diagnostic code Faultcode Diagnostic code
0x1000 Overspeed 0x6702 AlternatorChrg
0x1100 EngSpdSensor1 0x6A00 ExhaustBrkAct
0x1200 EngSpdSensor2 0xB000 OilPressProt
0x2000 WtrTempSensor 0xB100 CoolantLevProt
0x2100 ChrgAirTmpSens 0xB200 OverheatCoolWt
0x2200 ChrgAirPrsSens 0xB300 EmergencyStop
0x2300 OilTempSensor 0xB501 CoolantLevel
0x2400 OilPressSensor 0xC000 PDEInjctorCyl1
0x2600 SensorSupply1 0xC100 PDEInjctorCyl2
0x2700 SensorSupply2 0xC200 PDEInjctorCyl3
0x2800 ExtrAnalogInp 0xC300 PDEInjctorCyl4
0x3200 BatteryVoltage 0xC400 PDEInjctorCyl5
0x3300 CAN msg not ok 0xC500 PDEInjctorCyl6
0x3403 CAN version 0xC600 PDEInjctorCyl7
0x4300 HWWatchdog 0xC700 PDEInjctorCyl8
0x6200 FanActuator 0xE200 OverheatProt
0x6400 WasteGateAct 0xE600 CoordEmergStop
0x6600 StarterActuatr
Analog inputs
Reading of mentioned values from ECU enables to use analog inputs of the unit for other purposes,
e.g. measuring, displaying and alarm activation related to various quantities. The configuration thus
allows using three analog inputs on the central unit and four analog inputs on plug-in module if
connected.
If the engine without ECU is controlled by ID-Lite, the first analog input is permanently configured to
Oil pressure, other analog inputs remain freely configurable.
Modem or PC
Interface
RS232
0V
NOT USED
SPRINKLER
D+
REMOTE OFF
+24 V
EMERGENCY STOP
ACCESS LOCK
REMOTE S/S
BINARY OUTPUTS
BINARY
ALARM
INPUTS READY TO LOAD
PRESTART
1 2 3 4 5 6 7 8 9 10
10 -pin EMS B1
DIESEL/GAS ENGINE
connector
ECU
GND
+24 V DC
FUEL LEVEL
JOHN DEERE
ID-Lite binary output description John Deere 21 pin Deutsch connector
Start output D
Fuel output G (switched ECU power),J (ignition)
CUMMINS ISB/ISBE
ID-Lite binary output description Cummins ISB OEM Harness connector B
Start output connects directly to engine starter solenoid
Fuel output 39
Alarm
If the input is closed (or opened) selected alarm is activated.
Binary Alarm configuration items
Name 14 characters ASCII string
Contact type NC Normally closed
NO Normally opened
Alarm type Warning
Shut down
Alarm active All the time
Engine running only
Rem start/stop
External request for engine run. AUT mode only.
Emergency stop
If the input is opened, shut down is immediately activated. Input is inverted (normally closed) in default
configuration.
Hint:
In case of controller hardware or software fail, safe stop of the engine doesn’t have to be ensured. To
back-up the Emergency stop function it is recommended to connect separate circuit for disconnection
of Fuel solenoid and Starter signals.
Sprinkler
If the input is closed all alarms are disabled except the binary input EMERGENCY STOP and "engine
overspeed protection".
Hint:
Warning SprinklActive is indicated in the Alarm list if sprinkler mode active to inform the operator that
the engine is not protected.
Access lock
If the input is closed, no setpoints can be adjusted from controller front panel and engine mode (OFF-
MAN-AUT) cannot be changed.
Hint:
Access lock does not protect setpoints and mode changing from LiteEdit. To avoid unqualified
changes the selected setpoints can be password protected.
Remote OFF
If closed, InteliDrive-Lite is switched to OFF mode (there are three modes OFF-MAN-AUT). When
opens controller is switched back to previous mode.
Hint:
This binary input should be connected to schedule timer switch, to avoid start of engine.
Remote MAN
If the input is active, MAN mode is forced to the controller independently on the position of the MODE
selector.
Remote AUT
If the input is active, AUT mode is forced to the controller independently on the position of the MODE
selector. If another of „remote“ inputs is active, then the REMOTE AUT input has the lowest priority.
RemControlLock
If the input is active, setpoints writing or command sending from the external terminal is disabled.
Emergency manual
If the input is activated the controller behaves like when switched to OFF mode and opens all binary
outputs. There is one exception – STOP SOLENOID doesn’t activate on this transition.
Detection of "running" engine and subsequent alarm message "Sd Stop fail" is blocked.
The controller shows “Emerg Man” state and the engine can not be started.
After the input is open again, the controller recovers to previous state and behaves according to the
actual situation.
Function is active in any controller mode.
StartButton
Binary input has the same function as Start button on the ID-Lite front panel. It is active in MAN mode
only.
StopButton
Binary input has the same function as Stop button on the ID-Lite front panel. It is active in MAN mode
only.
FaultResButton
Binary input has the same function as Fault reset button on the ID-Lite front panel.
Nominal/Idle
Input works in MAN mode only switching between Idle-Running state. Active Nominal/Idle input
activates binary output Idle/Nominal and sends Speed request = Engine params: Idle speed and/or
active (binary) IDLE command to the ECU (e.g. to Volvo EMS).
Active input opens the binary output Ready to Load during the engine “Running” state. Ready to Load
can be closed back (if other conditions are fulfilled – see the Ready to Load binary output description)
if Nominal/Idle opens.
Speed Up
If the input is active, the Speed Request may increase the engine speed value. The Speed Request
value may also depend on the conditions which are described in the chapter below.
Speed Down
If the input is active, the Speed Request may decrease the engine speed value. The Speed Request
value may also depend on the conditions which are described in the chapter below.
SpeedUp/Down binary inputs are active only when Regulator: LAI SpdSelect = OFF.
Speed Sel 1
If the input is active, the Speed request = Engine params: BI Speed Sel 1 setpoint. The function is
affected by Engine params: RetToSpeedAdj.
RetToSpeed
Speed Sel 2
If the input is active, the Engine params: BI Speed Sel 2 setpoint may give the engine speed value
for Speed request to an ECU engine. The Speed Request value may also depend on the conditions
which are described in the chapter below.
Speed Sel 3
If the input is active, the Engine params: BI Speed Sel 3 setpoint may give the engine speed value
for Speed request to an ECU engine. The Speed Request value may also depend on the conditions
which are described in the chapter below.
Hint:
Engine params: RetToSpeedAdj = DISABLED … Speed request is set by BI Speed Sel1, ..2, ..3
edge (button press). i.e. input can be opened and Speed request stay constant.
Engine params: RetToSpeedAdj = ENABLED … Speed request is set by BI Speed Sel1, ..2, ..3 level
(switch) i.e. when input is opened Speed request go back to Engine params: ECU SpeedAdj level.
SpeedSel1, ..2, ..3 binary inputs are active only when Regulator: LAI SpdSelect = OFF.
When more binary inputs are active at the same time, e.g. all binary inputs: ‘Speed Sel1’, ‘Speed
Sel2’, ‘Speed Sel3’ then requested speed is given by Engine params: BI Speed Sel 1 (lowest index)
setpoint.
Lang selection
Switch display texts between two languages.
Load Request2
Active input switches the Load limit request to Load limit: LoadRequest2 setpoint.
LoadReg Disable
Active input disables the Load limit PI loop and switches analog output to constant Load limit: Load
bias.
RegRequest2
Active input switches the … by RPM loop request to Regulator: Request2 setpoint.
R Reg Disable
Active input disables the …by RPM PI loop and switches analog output to constant Regulator: Reg
bias.
Clear DayCons
Active input executes counter reset of DayCons statistical value.
Clear TripCons
Active input executes counter reset of TripCons statistical value.
Fuel solenoid
Closed output opens the fuel solenoid and enables the engine start.
The output opens if:
• EMERGENCY STOP comes or
• Cooled engine is stopped or
• in pause between repeated starts
Stop solenoid
The closed output energizes stop solenoid to stop the engine.
The output is active at least for Stop time, if the stop lasts longer; it stays active until all symptoms say
the engine is stopped.
The engine is stopped if:
RPM < 2 and
Oil pressure < Engine params: StartingPoil.
Hint:
The engine can be started anytime, if all symptoms say the engine is steady regardless of the fact the
Stop solenoid can still be active (in that case it is deactivated before cranking).
Stop Pulse
Output is active for 1 second after Stop solenoid output activation. This signal is sent to ECU in case
of engine stop request.
Ignition
The output closes after reaching value of CrankRPM, fixed 30RPM. Opens after stopping of the
engine or in pause during repeated start.
Prestart
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During repeated crank attempts the output is closed too.
The output could be used for pre-glow, pre-heat or prelubrication.
Preglow
The output closes prior to the engine start and opens when Starting RPM speed is reached. During
repeated crank attempts the output is closed too.
The output could be used for pre-glow or pre-heat.
Cooling pump
The output closes when engine starts and opens Engine params: AfterCool time after stop of the
engine.
Idle/Nominal
The output either follows the Nominal/Idle binary input in MAN mode or follows the engine state in
AUT mode:
The output Idle/Nominal closes after the timer Idle time elapses. The Idle time counter starts to
countdown when Start speed reached. The Underspeed protection is not evaluated during idle period.
A Start fail protection occurs if the RPM drop below 2RPM during idle state.
Air valves
Output closes together with Prestart and opens after the engine is stopped.
Alarm
The output closes if:
• any warning or shutdown comes up or
• the engine malfunctions
The output opens if
• FAULT RESET is pressed
The output closes again if a new fault comes up.
Horn
The output closes if:
• any warning or shutdown comes up or
• the engine malfunctions
The output opens if:
• FAULT RESET is pressed or
• HORN RESET is pressed or
• Max time of HORN is exceeded (Horn timeout)
The output closes again if a new fault comes up.
Wrn AnImAIO1..4
Output closes if the AIO: AI1..4 warning alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Sd AnImAIO1..4
Output closes if the AIO: AI1..4 shutdown alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Ready
The output is closed if following conditions are fulfilled:
• Engine is not running and
• No Shut down or Slow stop alarm is active
• Controller is not in OFF mode
Ready to load
The output is closed if engine is running and no alarm is active - it is possible to close load. The output
opens when Wrn underspeed protection is active and during cooling state.
Running
Output closes if the engine is in Running state.
Cooling
The output closes when engine is in Cooling state.
Fault Reset
One second pulse as echo for panel Fault reset button.
Stop failed
Output closes when the engine has to be stopped, but speed or oil pressure is detected. This
protection goes active 60s after stop command.
Overspeed
Output closes if the engine over speed alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Underspeed
Output closes if the engine “Wrn Underspeed” or “Sd Underspeed” alarm activates i.e. when RPM is
below the Engine Protect: Underspeed or Engine params: Starting RPM limit.
The output opens, if
• “Wrn Underspeed” alarm is not active
• “Sd Underspeed” alarm is not active and
• FAULT RESET is pressed
Start failed
Output closes after the engine start-up fails.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Battery flat
Output closes when InteliDrive-Lite performs reset during start procedure (probably due to weak
battery).
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
V batt failed
Output closes when battery over/under voltage warning appears.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Sd Oil Press
Output closes if the oil pressure shutdown alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Sd Engine Temp
Output closes if the water temperature shutdown alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Sd FuelLevel
Output closes if the Fuel level shutdown alarm activates.
Wrn FuelLevel
Output closes if the Fuel level warning alarm activates.
Common Wrn
Output closes when any warning alarm appears.
The output opens, if
• No warning alarm is active and
• FAULT RESET is pressed
Common Sd
Output closes when any shut-down alarm appears.
The output opens, if
• No sd alarm is active and
• FAULT RESET is pressed
Common Fls
Output closes when any sensor fail alarm appears.
The output opens, if
• No warning alarm is active and
• FAULT RESET is pressed
OFF mode
The output is closed, if OFF mode is selected.
MAN mode
The output is closed, if MAN mode is selected.
AUT mode
The output is closed, if AUT mode is selected.
ChrgAlternFail
Output closes if engine is running and D+ input not energized.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
Hint:
Threshold level for D+ input is 80% supply voltage.
ServiceTime
Output closes if the ServiceTime alarm activates.
The output opens, if
• alarm is not active and
• FAULT RESET is pressed
ECU PwrRelay
The output closes at the beginning of prestart and opens if the engine shall be stopped.
ECU YellowLamp
The output copies warning information from ECU.
ECU RedLamp
The output copies shutdown information from ECU.
CtrlHeartBeat
Output signalizes watchdog reset. In a healthy state it blinks at 500ms : 500ms rate. When watchdog
reset occurs, it stops blinking.
ECU CommError
The output is an inversion of binary output ECU CommOK, i.e. the output is closed when ECU is not
communicating and all values from ECU show #####.
BI1..10 – stat
In case the assigned binary input is configured to any control function, the output propagates the state
of the input. BI1..6 are assigned for CU: BI1..6, BI7..10 are assigned for BI7..BI10 of IL-NT IO1
optional card.
Timer1
Output activates when Timer1 is active. Simultaneously the engine is started when is in AUT mode.
Timer2
Output activates when Timer2 is active
Glow plugs
The output closes prior to the engine start (Prestart) and opens when Starting RPM speed is reached.
During repeated crank attempts the output is opened.
Conveyor
Binary output of Conveyor function. See Binary input Conveyor.
LoadSwitch
Binary output from Load switch comparator – see Load limit setpoint group.
SpeedSwitch
Binary output from Speed switch comparator – see Regulator setpoint group.
Analog inputs
Three analog inputs are designed for resistive sensors only.
Oil press
Oil pressure analog input. Default VDO sensor in range 0 to 10.0 bars.
Water temp
Water temperature analog input. Default VDO sensor in range 0 to 100 °C.
Fuel level
Fuel level analog input. Default VDO sensor 0-180R = 0-100%
Hint:
For further information about analog inputs’ configuration see Analog inputs.
Use LiteEdit 3.0 to enable/disable J1939 interface and to configure ID-Lite analog inputs.
Hint:
RPM reading is automatically switched to pickup measuring (depends on Basic setting: Gear teeth
value) if J1939 fails.
ChangePassword
Use ↑ or ↓ keys to set and ENTER key to change the password.
Hint:
At first the Password has to be entered before the new Password can be changed.
Basic settings
Engine name
User defined name, used for engine – ID-Lite identification at remote phone or mobile connection.
Engine name is max 14 characters long and have to be entered using LiteEdit (3.0 or higher) software.
GearTeethBI3 [-]
The second RPM (RPM-BI3 value) can be measured in limited frequency range 1 to 50Hz on Binary
input 3. The RPM-BI3 value indicates RPM calculated from BI3 frequency and Basic settings:
GearTeeth3 setpoint.
The RPM-BI3 value =0 below 1 Hz and =### over 50 Hz.
Configure BI Type = Not used and change the name according the function for RPM-BI3 measuring.
Hint:
The RPM-BI3 measuring is switched off when Basic setting: GearTeethBI3 = 0. In this case BI3
operates as standard Binary input.
Step: 1
Range: 0 – 10
DispBaklightTO [min]
Timeout after which the display backlight is switched off.
Step: 1 min
Range: 0 – 60 min
Default value: 0 … means that the display lights all the time
Comms Settings
Contr. addr (1 .. 32) [-]
Controller identification number. It is possible to set controller address different from the default value
(1) so that more ID-Lite controllers can be interconnected (via RS485) and accessed e.g. from
Modbus terminal.
Hint:
When opening connection to the controller it's address has to correspond with the setting in PC tool.
From LiteEdit it is only possible to connect to controllers with address 1.
Hint:
For details on communication speed and other technical parameters please see chapter Technical
Data.
For detail description see chapter Modbus protocol.
Hint:
For details on communication speed and other technical parameters please see chapter Technical
Data.
For detail description of communication possibilities see actual Inteli Communication Guide xxx.pdf -
chapter Modbus protocol and others.
ModemIniString
If your modem needs some additional initialization AT commands (i.e. because of national telephony
network differences), it can be entered here. Otherwise leave this setpoint blank.
IBLite IP Addr
IP address of IB-Lite module
IBLite NetMask
IB-Lite network mask
IBLite GateIP
IP address of gateway for IB-Lite
ComAp Port
Port for ComAp communication over IB-Lite or IL-NT-GPRS module
APN Name
Name of APN access point for GPRS network.
Hint:
This information shall provide the your GSM/GPRS operator.
APN UserName
User name for APN access point.
Hint:
This information shall provide the your GSM/GPRS operator.
APN UserPass
User password for APN access point.
Hint:
This information shall provide the your GSM/GPRS operator.
AirGate IP
IP address of AirGate server.
SMTP UserName
User name or name of e-mail account for verification of email sender on SMTP server. If parameter
left empty, no verification is expected. Works for IB-Lite only.
SMTP Server IP
IP address of SMTP server. Works for IB-Lite only.
Contr MailBox
E-mail address used as “Sender” of alarm e-mails from IB-Lite.
Hint:
If SMTP server requires verification of sender, e-mail address has to be registered to SMTP server
and setpoints “SMTP UserName” and “SMTP UserPass” has to be set to correct values.
Time Zone
List of time zones used for time reference.
DNS IP Address
IP address of Domain Name Server.
Engine params
Starting RPM [RPM]
“Firing” speed when ID-Lite controller stops cranking (starter goes OFF).
Sd Underspeed protection is activated when RPM drops back below the Starting RPM for more than 5
second the engine starting procedure.
Limit is ignored when Gear teeth = 0 i.e. in engine operation without speed pickup (running state is
indicated from D+ or Starting POil.
Step: 1 RPM
Range: 5 – 1500 RPM
Function with shorter period (Prestart time or Preglow time) starts later to finish both in the same time
– when Starting RPM speed is reached.
Step: 1s
Range: 0 – 600 s
MinSpeedLim [RPM]
The setpoint presets the minimum engine speed in the “Running” operation mode. Also see other
conditions in the chapter below.
Step: 1 RPM
Default: 1200 RPM
Range: Starting RPM – MaxSpeedLim
MaxSpeedLim [RPM]
The setpoint presets the maximum engine speed in the “Running” operation mode. Also see other
conditions in the chapter below.
Step: 1 RPM
Default: 2700 RPM
Range: MinSpeedLim – 4000 RPM
Hint:
When none of the binary inputs: ‘Speed Sel 1’, ‘Speed Sel 2’ and ‘Speed Sel 3’, ‘Speed Up’ and
‘Speed Down’ has not been configured then engine speed is given by the ‘Engine params: ECU
SpeedAdj‘ setpoint.
p
d ar
ee e p
the 0,6 sec constant 5RPM/s not depend on Engine params:
Sp in
g
En
SpeedRamp setting. This enables fine setting of Engine speed to
specific like 1500 RPM value.
5RPM/s
0,6s Time
Step: 1 RPM/s
Default: 100 RPM
Range: MaxSpeedLim
Binary Inputs:
Speed Up Engine params:
MinSpeedLim
Speed Down MaxSpeedLim
Engine params:
Speed Sel 2 Engine params: BI Speed ramp ECU
Speed request
BI Speed Sel 2
0%ofSpeedReq [RPM]
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
Step: 1 RPM
Default: 0 RPM
Range: 0 – 3000 RPM
100%ofSpeedReq [RPM]
Limit for Speed Request transformation from RPM to % range for ECU engines using % format.
Step: 1 RPM
Default: 2000 RPM
Range: 0 – 4000 RPM
InpChar
Request 1 [-]
Regulator requested value.
Step: 1
Range: -10000 – +10000
Default: 0
Request 2 [-]
Regulator requested value when LBI Request2 is active.
Step: 1
Range: -10000 – +10000
Default: 0
2
LoadSwitch 0/1
AIN CMPH
LBO
Up Limit
Down Limit
AIN
RPM Pick-up RPM
1
J1939 0-5V/20mA
ENGINE ECU PI
CAN Percent Load LoadLimit
Up Limit AnOut
or RPM
L Request1 Dn Limit
Engine load L Request2 Bias
Hydr. L Req Ramp
Valve
LBI L Request2
LBI L Reg Disable
Proportional
On / Off
LoadRequest1 [-]
Regulator requested value.
Step: 1
Range: -10000 – +10000
Default: 100
LoadReqRamp [ 1/s ]
Ramp when switching between LoadRequest1 and LoadRequest2.
Step: 1/s
Range: 1 – +10000/s
Default: 100
LoadUpLimit [-]
Load limit regulator PI output upper limit.
LoadDnLimit [-]
Load limit regulator PI output low limit.
Step: 1
Range: 0 – 10000
Default: 9900
Load CMP On
Limit to open LBO LoadSwitch
Step: 1
Range: -10000 – +10000
Engine protect
Eng prot del [s]
During the start of the engine, some engine protections have to be blocked (e.g. Oil pressure).
The protections are unblocked after the Protection del time. The time starts after reaching Start RPM.
Step: 1s
Range: 0 – 300 s
Overspeed [%]
Limit for engine Sd overspeed protection.
Step: 1% of nominal RPM
Range: 50 – 150%
Underspeed [%]
The limit for Warning Underspeed protection. Active protection is indicated as “Wrn underspeed” in
Alarm list. Under speed Warning protection is inactive 5 second after RPM is over Engine params:
Starting RPM and during the Idle time.
The “Ready to load” output is deactivated when Wrn underspeed protection is active and needs the
Fault reset for activation after RPM is over Underspeed limit.
Step: 1% of nominal RPM
Range: Starting RPM – 100%
d
ee
rsp
M
de
RP
Un
rn
W
e ed
Engine protect: Underspeed sp
r
de
Warning level Un
Sd
Engine params: Starting RPM
Shut-down level
5s
AnlInp2 level1 []
Warning limit level for ANALOG INPUT 2
Step: 1 °C
Range: -100 – 10000
AnlInp2 level2 []
Shutdown limit level for ANALOG INPUT 2
Step: 1 °C
Range: -100 – 10000
AnlInp3 level1 []
Warning limit level for ANALOG INPUT 3
Step: 1%
Range: -100 – 10000
AnlInp3 level2 []
Shutdown limit level for ANALOG INPUT 3
Step: 1%
Range: -100 – 10000
NextServTime [h]
Counting down when engine running. Service time alarm appears if reaches zero.
Step: 1h
Range: 0 – 65535h
GearBoxRatio [-]
There are two new protections related to RPM-BI3 where function of Engine protect: RPMdiff Sd,
RPMdiff Wrn limits depends on setting of GearBoxRatio:
Hint:
The RPM-BI3 measuring and corresponding protections are switched off when Basic setting:
GearTeethBI3 = 0. In this case BI3 operates as standard Binary input.
RPMdiff Sd [-]
RPM-BI3 Sd underspeed protection limit or Sd difference limit between RPM-BI3 and RPM transferred
via GearBoxRatio. See description in GearBoxRatio setpoint.
Message: Sd RPMdiff
Step: 1
Range: 1 – 1000
Date/Time
Time stamp per [min]
Time interval for periodic history records.
Step: 1 min
Range: 0 – 200min
Time [HHMMSS]
Actual time.
Date [DDMMYYYY]
Actual date.
AutoRun: Engine automatically starts and stops in AUT mode according the Timer1 setting.
AutoRegCMP: start and stop engine in AUT mode according the LBO Speed switch - see Regulator:
Reg CMP setpoints. The comparator function (output) works opposite when Regulator: Reg CMP On
< Reg CMP Off. The Date/Time: .. repeat, ..ON time, ..Duration settings are not important in this case.
AutoBatt: engine starts when actual Battery voltage < Engine protect: Batt undervolt + Batt volt
del and stays running for Date/Time: Timer1 Duration. Function operates in AUT mode.
Timer1..2 repeat
[NONE/MONDAY/TUESDAY/WEDNESDAY/THURSDAY/WEDNESDAY/FRI
DAY/SATURDAY/SUNDAY/MON-FRI/MON-SAT/MON-SUN/SAT-SUN]
Defines TIMER1 activation. Binary output TIMER1 is internally linked with Rem Start/Stop binary input.
Refer to binary inputs for details.
Timer1..2 ON time
Day time when Timer 1..2 output activates.
Timer1..2Duration
Duration of Timer 1..2 output.
Step: 1 min
Range: 1 – 1440 s
Sensor spec
Calibr AI1, AI2, AI3 […]
Calibrating constant to adjust the measured value of ID-Lite analog inputs. Physical dimension of
calibrating constant is corresponding to Analog input.
Step: 1
Range: -1000 – +1000
Hint:
Calibration constants have to be adjusted when measured value is near the alarm level.
AIO module
AnlInAIO1..4 lev1 []
The level for AIO ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
AnlInAIO1..4 lev2 []
The level for AIO ANALOG INPUT 1..4 alarm detection.
Step: 1
Range: -100 - +10000
Hint:
Plug-in analog inputs protection alarms can be configured following way
Configuration Protection
Under Protection is activated only when measured value is under measured level.
Over Protection is activated only when measured value is over measured level.
Under+fls Level 2 protection is activated by sensor fail as well.
Over+fls Level 2 protection is activated by sensor fail as well.
SMS/E-Mail
Remote alarm messaging
If a GSM modem and/or Internet bridge is connected to the controller, the controller can send SMS
messages and/or emails in the moment when a new alarm appears in the Alarm list. The message will
contain a copy of the Alarm list.
To enable this function, you should select with setpoints Yel Alarm Msg and Red Alarm Msg, which
levels of alarms shall be announced (red/yellow/both) and also enter valid GSM phone number and/or
e-mail address to the setpoints TelNo/Addr Ch1 and TelNo/Addr Ch2. It is possible to put either a
GSM number or e-mail to both setpoints.
NOTE:
An internet module must be available for sending of e-mails. Similarly, a GSM modem is necessary for
sending of SMS.
Hint:
There are 5 attempts for any active call (SMS/E-Mail). Timeout for connection is 90 sec and after 120
sec controller starts the next attempt. During the time the IL-NT is trying to send an active call type,
incoming calls are blocked.
Hint
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
Hint
The target address (GSM phone number or e-mail address) must be set correctly to the setpoint(s)
TelNo/Addr Ch1 resp. TelNo/Addr Ch2.
TelNo/Addr Ch1, 2
Enter either a valid GSM phone number or e-mail address to this setpoint, where the alarm messages
shall be sent. Type of active call is considered from the value of this parameter. If it consist „@“ it is
supposed to be e-mail address and active e-mail is sent. If the value is number, without „@“, it is
supposed to be the telephone number and active SMS is sent.
Hint:
For GSM numbers use either national format (i.e. like number you will dial if you want to make a local
call) or full international format with "+" character followed by international prefix in the begin.
This setpoint can be modified from PC only!
7
9
10
8
11
12
1. MODE→ Cyclic forward selection the engine operation mode (OFF -> MAN -> AUT )
2. ←MODE Cyclic backward selection the engine operation mode (AUT -> MAN ->OFF )
3. HORN RESET Deactivates the HORN
4. FAULT RESET Acknowledges faults and alarms
5. START Start of the engine
6. STOP Stop of the engine
7. GREEN LED Engine running
8. RED LED Engine fail
9. PAGE Cyclic selection of the display mode(MEASUREMENT->ADJUSTEMENT)
10. ↑ Select the set point, select the screen or increase set point value
11. ↓ Select the set point, select the screen or decrease set point value
12. ENTER Confirm set point value
Serial number, Password decode and Diagnostic data are available on User interface screen
Init screens
Customer Logo screen
This is a first screen which is dedicated for information provided by customers such as contact
numbers, service technician contact and customer message for end users of gen-set. Configuration of
this screen is only done by LiteEdit PC software.
Details on recognition of configured electronic engine are in chapter Identifying configured ECU.
Language screen
ID-Lite controller offers configurable language support. On this screen is possible to switch between
languages configured in controller.
Other way to change language is by binary input Lang Selection.
USER interface is simple menu displaying just measurement, alarm and init screens.
ENGINEER interface allow changing the settings of controller, reviewing the history, measurement
and alarms. This mode is default.
Description
* Wrn Water temp Active not accepted alarm
Wrn Water temp Active accepted alarm
* Wrn Water temp Inactive not accepted alarm
Inactive accepted alarm
Press FAULT RESET accepts all alarms. Non-active alarms immediately disappear from the list.
Active alarm list appears on the screen when a new alarm comes up and Main MEASUREMENT
screen is active.
Hint:
Alarm list does not activate when you are reviewing the values or setpoints.
Second alarm list for ECU alarms is also available. It is displayed one screen above the standard
alarm list on the controller display or under the standard alarm list in Control window of LiteEdit. If an
alarm appears in this alarm list, it is signalized in the standard alarm list and by exclamation mark on
the main measure screen.
Control from the front panel:
5 4
ECU State
ECU YellowLamp
ECU RedLamp
WaitToStart
Hint:
This screen is shown/hidden depending on whether the ECU is configured or not.
ECU Values
Oil pressure Bar or psi
Water temp °C or °F
PercLoadAtCS % (Percentual load at current speed.)
Boost pressure Bar or psi
ManifoldTemp °C or °F
Fuel rate L/h or gph
Hint:
This screen is shown/hidden depending on whether the ECU is configured or not.
NextServTime
Hint:
Invisible in ID-Lite-s-2.0.ail configuration file.
Running time is measured in complete minutes, displayed in complete hours. Values are stored in
nonvolatile memory.
ECU AlarmList
Diagnostic messages are read from ECU and displayed in this second alarm list. For Standard J1939
engines SPN (Suspect Parameter Number), FMI (Failure Mode Identifier) and OC (Occurrence
Counter) are shown together with verbal description if available.
Following image shows displaying of ECU alarms in the second alarm list. The additional information
for the row selected by cursor is on the last row (SPN, OC and FMI codes).
If the verbal description of alarm is not available, the SPN (decimal and hexadecimal) is displayed.
EngOilPress WRN
BoostPress FLS
EngOilTemp FLS
629(275h) FLS
Controller#1
EngCoolTemp WRN
_____________________
SPN:110 OC:7 FMI:3
Hint:
For FMI = 0 and 1, WRN is displayed. For other FMI codes, FLS is displayed.
Alarm list
Displays active or inactive alarms configured on ID-Lite Binary or analog outputs.
ID-Lite controller automatically switches to the Alarm list screen when any new Alarm appears, but
from Main measure screen only.
Warning (WRN)
When warning comes up, only alarm outputs and common warning output are closed.
Possible warnings:
See List of possible events
100%
Sensor fail
0%
mA
Information on binary
Protection
Events specification output available (See Description
type
list of Binary outputs)
Wrn Oil Press WRN YES Oil pressure is smaller than Wrn Oil
press setpoint.
Sd Oil Press SD YES Oil pressure is smaller than Sd Oil
press setpoint.
Wrn Engine Temp WRN YES Water temperature is greater than
Wrn Water temp setpoint.
Sd Engine Temp SD YES Water temperature is greater than Sd
Water temp setpoint.
Wrn Fuel Level WRN YES Fuel level is smaller than Wrn Fuel
Level setpoint.
Sd Fuel Level SD YES Fuel level is smaller than Sd Fuel
Level setpoint.
Ubat WRN YES Battery voltage is out of limits given by
Batt overvolt and Batt undervolt
setpoints.
Wrn AIO WRN YES Warning alarm configurable on the
input of plug-in.
Sd AIO SD YES Shutdown alarm configurable on the
input of plug-in.
Binary input Configurable YES Configurable Warning/Shutdown
alarms on the inputs of ID-Lite.
Battery flat SD YES If the controller switches off during
starting sequence due to bad battery
condition it doesn’t try to start again
and activates this protection.
Start failed SD YES Engine start failed.
ParamFail NONE NO Wrong checksum of parameters.
Happens typically after downloading
new firmware or changing of the
parameter. The controller stays in
INIT mode. Check all parameters,
History file
InteliDrive-Lite stores a record of each important event into the history file. The history file seats 117
records. When the history file is full, the oldest records are removed.
Hint:
To force history download in LiteEdit (direct, modem or Internet) open History window and select
History | Read history command.
Record structure
Abbreviation Historical value
Num Number of historical event
Reason Event specification
Date Date of historical event in format DD/MM/YY
Time Time of historical event in format HH:MM:SS
RPM Engine speed
UBat Battery voltage
OilP ID-Lite Analog input 1 value ( default Oil pressure)
EngT ID-Lite Analog input 2 value ( default Water temperature)
FLvl ID-Lite Analog input 3 value ( default Fuel level)
AIM1 Plug-in Analog input 1 value
AIM2 Plug-in Analog input 2 value
Hint:
Make sure the grounding system on controller and PC – COM port (negative of the PC DC supply) are
identical – before the first direct connection. There must not be any voltage between these two points
otherwise the internal reversible fuse in controller burns out. The simple solution is to assure, that the
PC supply 240/20V is ground free (GND terminal is not connected).
PC CONTROLLER
2 - RxD 2 - RxD
RS232
RS232
0 VDC
- +
Battery
RS232, USB or RS485 interface can be used for direct cable connection to a PC. The setpoint COM1
Mode or COM2 Mode (according to the interface used) must be set to DIRECT position for this kind of
connection.
SMS commands
Examples
Value reading #1:0 r8276 #1 … controller address
0 … access code
r8276 … read value number 8276
… response #Gen-set name: 100
Setpoint setting #1:0 p1234,r8276,w8276 110,r8276 #1 … controller address
0 … access code
p1234 … password
r8276 … read value of 8276
w8276 110 … write 110 to 8276
r8276 … read value of 8276
… response #Gen-set name:ok,100,ok,110
Engine control #1:0 p1234,c1 #1 … controller address
0 … access code
p1234 … password
c1 … engine start (c2=stop)
… response #Gen-set name:ok Command was accepted
Language translator
Default archive contains English and Chinese languages. To change default Chinese (Unicode) to any
Latin language use Remove and Add buttons in LiteEdit – Translator-Language window.
Language support
ID-LITE firmware version 1.6 and above supports following language code pages:
Modbus protocol
Select the ID-Lite serial ports function in the Basic settings: COM1 mode or COM2 mode = MODEM.
Use LiteEdit: Controller - Generate Cfg image (Modbus registers) command to get registers list.
The complete description of Modbus communication protocol can be found in Modbus Protocol
Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are
available from web site at http://www.modicon.com/openmbus/ .
Hint:
Download the actual controller Modbus registers list from controller or from (ail) archive - use
“Controller-Generate Cfg image” command from LiteEdit software.
Internet connection
ID-Lite controllers can be monitored from LiteEdit over the Internet via internal IB-Lite plug-in
module.
AirGate connection
ID-Lite controllers can be monitored from LiteEdit or WebSupervisor system via AirGate. AirGate
technology is for easy plug’n’play communication over Internet. GPRS and IB-Lite plug-in cards
are suitable for this system. It overcomes problems with fixed and public IP address necessity,
with firewalls and difficult communication settings.
Hint:
It is strongly recommended to use the same type of modem on the both sides (ID-Lite and PC) of
connection.
Allowed supply voltage drop-out: 100ms from min. 10V return to min. 8V
Battery voltage measurement tolerance 2 % at 24V
Hint:
For the supply voltage less than 7V the backlight of the display is switched off.
Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all.
Operating conditions
Operating temperature ID-Lite -20..+70oC
Operating temperature ID-Lite LT# -40..+70oC
Storage temperature -30..+80oC
Protection front panel IP65
Humidity 95% without condensation
Standard conformity
Low Voltage Directive EN 61010-1:95 +A1:97
Electromagnetic Compatibility EN 50081-1:94, EN 50081-2:96
EN 50082-1:99, EN 50082-2:97
Vibration 5 - 25 Hz, ±1,6mm
25 - 100 Hz, a = 4 g
Shocks a = 200 m/s2
Technical data
ID-Lite Standard Order code:ID-Lite-xxxxx
LT
o o o o
Operating temperature -20 C..+70 C -40 C..+70 C
Storage temperature -30 oC..+80oC -30 C..+80oC
o
Analog inputs
Not electrically separated
Number of inputs 3
Resolution 10 bits
Jumper selectable range V, Ohm (default), mA
Maximal resistance range 2500 Ω
Maximal voltage range 2.5 V
Current range 0 – 20 mA
Input impedance 180 Ω for mA measuring
Input impedance > 100 kΩ for V measuring
Resistance measurement tolerance ± 2 % ± 2 Ω out of measured value
D+ function
Max. D+ output current 300 mA
Guaranteed level for signal Charging OK 80% of supply voltage
Maximal distance 5m
Maximum Speed Up to 57.6 kBd (DIRECT), 38.4kBd Analog modem,
9.6 kBd digital modem, 57.6 kBd (MODBUS)
GSM/GPRS modem
Quad Band 850/900/1800/1900 MHz
GPRS multi-slot class 10
CSD up to 14.4 kbps
TCP/IP communication over GPRS
Voltage supply 8-36V DC
Inputs:
Maximal resistance range: 2400 Ohm
Maximal voltage range: 4V
Current range: 0-20 mA
Input impedance (current): 180 Ohm for mA measuring
Input impedance (voltage): >68 kOhm for V measuring
Outputs:
Voltage measurement tolerance: ± 1,5% +- 10mV
Current measurement tolerance: ± 2% +- 0,1mA
Operating conditions
Operating temperature -20..+70oC
Storage temperature -40..+80oC
Protection front panel IP65
Horn output
Maximum current 1A
Maximum switching voltage 36 VDC