Tips - Liebert Intellislot Web Cards
Tips - Liebert Intellislot Web Cards
i
9.0 SUPPORT INFORMATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9.1 View Web Card Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
9.2 Events and Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
APPENDIX A - FIRMWARE UPDATES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
FIGURES
Figure A1 Null connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A10
TABLES
Table 1 Liebert IntelliSlot card communication protocols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Table 2 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Table 3 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Table 4 Configuration interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 5 Guide to configuration details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Table 6 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Table 7 System information identifiers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Table 8 Network Settings menu guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Table 9 Boot/IP settings range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Table 10 Domain Name Server settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Table 11 Management protocol ranges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Table 12 SNMP communications menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Table 13 Web server settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Table 14 Time Server parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Table 15 Factory default passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 16 Username and password guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Table 17 Factory default passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Table 18 Messaging menu guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Table 19 E-mail configuration guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Table 20 SMS configuration guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Table 21 E-mail and SMS message guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Table 22 Factory default MAC addresses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Table 23 Control operations parameters—functions vary by Liebert unit . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Table A1 Overview of the upgrade process . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Table A2 Estimated Time for downloads. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A1
Table A3 Communication settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A2
Table A4 Firmware update settings - TFTP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A6
Table A5 Firmware update settings - Web . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A8
ii
IMPORTANT SAFETY INSTRUCTIONS
! WARNING
Only a qualified service professional should install these products. Liebert recommends
having an Emerson Network Power Liebert Services representative perform the installation
in large UPSs. Contact Liebert Services at 1-800-LIEBERT (1-800-543-2378).
! WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications.
Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected
from the electrical source.
Check the circuits with a voltmeter before beginning installation.
1
Introduction
1.0 INTRODUCTION
The Liebert® IntelliSlot® Web Card family delivers enhanced communications and control to Liebert
AC Power and Precision Cooling systems.
Liebert IntelliSlot Web cards bring SNMP, Telnet and Web-management capability to many models
of Liebert power and cooling equipment. The cards employ an Ethernet network to monitor and
manage a wide range of operating parameters, alarms and notifications.
Liebert IntelliSlot Card Part Number SNMP HTTP HTTPS Modbus E-mail SMS Telnet
Liebert IntelliSlot Web Card IS-WEBCARD ✔ ✔ ✔ — ✔ ✔ ✔
Liebert IntelliSlot Web Card-LB IS-WEBLB ✔ ✔ ✔ — ✔ ✔ ✔
Liebert IntelliSlot Web Card-LBDS IS-WEBLBDS ✔ ✔ — — — — ✔
Liebert IntelliSlot Web/485 Card
IS-WEB485ADPT ✔ ✔ — ✔ — — ✔
With Adapter
Liebert IntelliSlot Web cards support both 10Mbit and 100Mbit communication speeds and either
half or full duplex.
NOTE
See online demonstrations of Web cards installed in Liebert equipment at:
http://demos.liebert.com
2
Introduction
NOTE
Change the username and password today to prevent unauthorized access.
3
Installation
2.0 INSTALLATION
! WARNING
Only a qualified service professional should install these products. Liebert recommends
having a Liebert Services representative perform the installation in large UPSs. Contact
Liebert Services at 1-800-LIEBERT (1-800-543-2378).
NOTE
When installing the card in a Liebert NX™,
configure the communication port of NX to
2400 baud. See the NX user manual for
details.
4
Installation
! WARNING
Risk of electric shock. Can cause equipment damage, injury or death.
Service and maintenance work must be performed only by properly trained and qualified
personnel and in accordance with applicable regulations and manufacturers’ specifications.
Opening or removing the covers to any equipment may expose personnel to lethal voltages
within the unit even when it is apparently not operating and the input wiring is disconnected
from the electrical source.
Check the circuits with a voltmeter before beginning installation.
Follow these steps to install a Liebert IntelliSlot Web/485 Card With Adapter (P/N IS-WEB485ADPT).
• Locate the adapter mounting location in your Liebert equipment.
• Secure the Liebert IntelliSlot Web/485 Card With Adapter with the supplied screws.
• Connect the equipment's communication cable to the TB1 terminal block or P1 on the card (see
the user manual for the Liebert power or cooling unit for details).
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal block; Pin 1 is at the far
left, and Pin 2 is the middle pin.
P1
TB3 (P1: +) (P2: -)
(P3: NC) P1 is on left
end of terminal block.
Network Port for NMS
and Web Access
5
Configuration Overview
Each configuration section provides instructions using the Terminal Emulation (Serial or TCP/IP
Connection) / Telnet Interface, along with a brief description of how to access the same function
through the Web Interface.
NOTE
The Terminal Emulation and Telnet interfaces present the same menus and choices.
6
Configuration Overview
5. When the message at right appears in the HyperTerminal window, RTCS v2.96.00 Telnet server
press the Enter key. Service Port Manager Active
6. In the Main Menu, enter the number that corresponds to your choice. <Esc> Ends Session
Refer to 3.1 - Guide to Configuration for details on each function. Main Menu
----------
7. After making changes, return to the Main Menu and choose Exit and 1: System Information
2: IP Network Settings
Save to reboot the Web card and put your changes into effect (see 3: Messaging
3.6 - Saving Changes and Reinitializing the Web Card). 4: Factory Settings
5: Firmware Updates
7
Configuration Overview
NOTE
For security, change the default username and password (see 5.7 - Change Username /
Password).
6. In the Main Menu, enter the number that corresponds to your choice. Main Menu
Refer to 3.1 - Guide to Configuration for details on each function. ----------
1: System Information
7. After making changes, return to the Main Menu and choose Exit and 2: IP Network Settings
3: Messaging
Save to reboot the Web card and put your changes into effect (see 4: Factory Settings
3.6 - Saving Changes and Reinitializing the Web Card). 5: Firmware Updates
8
Configuration Overview
sensitive):
a. Login (username—default is Liebert) Login: Liebert
Password: ********
b. Password (default is Liebert)
NOTE
For security, change the default username and password (see 5.7 - Change Username /
Password).
4. In the Main Menu, enter the number that corresponds to your choice. Main Menu
Refer to 3.1 - Guide to Configuration for details on each function. ----------
1: System Information
5. After making changes, return to the Main Menu and choose Exit and 2: IP Network Settings
3: Messaging
Save to reboot the Web card and put your changes into effect (see 4: Factory Settings
5: Firmware Updates
3.6 - Saving Changes and Reinitializing the Web Card).
q: Quit and abort changes
x: Exit and save
9
Configuration Overview
Web Interface
• After making each change, click the Save button. A reminder
appears each time you make a change (shown at right).
• Without leaving the Configure tab window (below left), click
Reinitialize in the left panel, then click the Reinitialize button
at right to reboot the Web card and put your changes into effect.
First click
Reinitialize
at left
Then click
Reinitialize
button
• A message window appears, shown above right, and remains until the card is reinitialized.
10
System Information
Web Interface
To access System Information through the Web interface:
• Click on the Configure tab, then Agent Info in the left panel and finally Edit in the right panel.
After making changes, click Save.
Configure tab
Agent
Info
Edit
11
Network Settings
12
Network Settings
Web Interface
To access Boot/IP Settings through the Web interface:
• Click on the Configure tab, then Network Settings in the left panel and finally Edit beneath
the table of parameters and descriptions. After making changes, click Save.
Configure tab
Network
Settings
Edit
13
Network Settings
14
Network Settings
Web Interface
To access the DNS menu through the Web interface:
• Click on the Configure tab, then Network Settings in the left panel and finally Edit beneath
the table of parameters and descriptions. After making changes, click Save.
Configure
tab
Network
Settings Obtain
Click Edit address
to change automatically
settings
Specify
address
Options for
how long
card retains
resolved
addresses
SNMP Agent Enable or disable SNMP for remote management. Enable SNMP Agent? [y/n] ?>
15
Network Settings
Web Interface
To access Management Protocol settings through the Web interface:
• Click on the Configure tab, then Management Protocol in the left panel and finally Edit in
the right panel. After making changes, click Save.
Configure
tab
Management
Protocol
Click on Edit
to enable any
options List sets
frequency of
Heartbeat
Traps
16
Network Settings
Display/Modify Communities
View devices that have permission to access the Web card, identified by IP address or hostname, read/
write permission and community string. Up to 20 devices may be configured for access.
Communities - Example
-------------------------
1: 10.0.0.5 write public1
2: 10.0.0.6 write public1
17
Network Settings
Edit a device (see example at right to enter all parameters in one line): Example
• Enter e to edit an entry, then press Enter. e 2 10.0.0.7 read public2
• Type the Entry Number, then press Enter. (then press Enter)
• Enter the new IP address or hostname, then press Enter.
• Enter 1 for read or 2 for write access for this device, then press Enter.
• Enter the new community string, then press Enter.
Delete a device (see example at right to enter parameters in one line): Example
• Enter d, then press Enter. No confirmation message will appear. d2
• Type the Entry Number, then press Enter. (then press Enter)
NOTE
Avoid the following setting—it permits access by any host and may pose a security risk:
• IP address = 0.0.0.0
• Access = write
• Community = public
18
Network Settings
Web Interface
To access Web Server settings through the Web interface:
• Click on the Configure tab, then Web in the left panel and finally Edit in the right panel. After
making changes, click Save.
Configure tab
Web Edit
19
Network Settings
Click on
View
Certificate
• Click the View Certificate button. This opens the Certificate window.
Certificate
Path tab
View
Certificate
• In the Certificate window, above left, click the Certificate Path tab.
• In the Certificate Path tab, above right, click on Allegro Root CA, then on View Certificate.
20
Network Settings
• In the Certificate window, click the Install Certificate button, as shown below.
Install
Certificate
Automatically
select...
• Click on Automatically select the certificate store based on the type of certificate, then
click Next.
• The final Wizard window appears with a message that the process is complete. Click Finish.
• A confirmation box appears with a message that the import was successful. Click OK.
21
Network Settings
Continue to
this website
• Click on Continue to this website (not recommended) to open a connection to the Web card.
Certificate
Error
View
Certificates
• Click the Certificate Error box next to the address bar, shown above left.
• In the window that pops up, shown above right, click the View Certificates link. This opens the
Certificate window.
Certificate
Path tab
View
Certificate
• In the Certificate window, above left, click the Certificate Path tab.
• In the Certificate Path tab, above right, click on Allegro Root CA, then on View Certificate.
22
Network Settings
• In the Certificate window, click the Install Certificate button, as shown below.
Install
Certificate
Automatically
select...
• Click on Automatically select the certificate store based on the type of certificate, then
click Next.
• The final Wizard window appears with a message that the process is complete. Click Finish.
• A confirmation box appears with a message that the import was successful. Click OK.
23
Network Settings
Web Interface
To access Telnet settings through the Web interface:
• Click on the Configure tab, then Telnet in the left panel and finally Edit in the right panel.
After making changes, click Save.
Configure tab
Edit
Telnet
24
Network Settings
Web Interface
To access Time (SNTP) settings through the Web interface:
Click on the Configure tab, then Network Settings in the left panel and finally Edit in the right
panel. After making changes, click Save.
Configure
tab
Time
Server
list
Click on Edit
to choose Time
options Servers
must be
entered
manually
Time zones
available
from list
25
Network Settings
Web Interface
To access usernames and passwords through the Web interface:
• Click on the Configure tab, then Users in the left panel and finally Edit in the right panel. After
making changes, click Save.
Configure tab
Edit
Users
26
Network Settings
2. Enter y to reset the Administrator and General User usernames and passwords to the default
settings.
NOTE
This feature is not available through the Web interface
27
Messaging
6.0 MESSAGING
The Messaging menu is used to set up e-mail and text message notifications Messaging Menu
from the Web card. ---------------
1: Email 'disabled'
2: SMS 'disabled'
Terminal Emulation (Serial or TCP/IP Connection) / Telnet 3: Email Configuration
4: SMS Configuration
To access these options:
<ESC>: Cancel menu level
1. Choose Messaging from the Main Menu. Please select a key ?>
2. Select an option, then use the following guide to make changes.
Table 18 Messaging menu guide
Menu item Refer to:
E-Mail Configuration page 29
SMS Configuration page 30
Customize Messages (E-Mail and SMS) page 32
Web Interface
To access Messaging settings through the Web interface:
• Click on the Configure tab, then Messaging in the left panel and finally Edit in the right panel.
After making changes, click Save.
Configure tab
Edit
Messaging
28
Messaging
29
Messaging
Web Interface
To access E-Mail Configuration through the Web interface:
• Click on the Configure tab, then Email in the left panel and finally Edit in the right panel.
After making changes, click Save.
Configure tab
Email
Edit
30
Messaging
Web Interface
To access SMS Configuration through the Web interface:
• Click on the Configure tab, then SMS in the left panel and finally Edit in the right panel. After
making changes, click Save.
Configure tab
Edit
SMS
31
Messaging
32
Messaging
Web Interface
To access Customize Message settings through the Web interface:
• Click on the Configure tab, then Customize Messages in the left panel and finally Edit in the
right panel. Choose the items to include in each type of message in the Email and SMS columns.
• After making changes, click Save.
Configure tab
Edit
Customize
Message
33
Factory Settings
2. Enter y (yes) at the prompt to confirm your choice. To cancel, enter n (no).
3. A message appears until the process is complete.
Resetting card to factory defaults...
Web Interface
To restore the factory default settings through the Web interface:
• Click on the Configure tab, then Factory Defaults in the left panel and finally Reset to Fac-
tory Defaults in the right panel.
Configure tab
Reset
to Factory
Defaults
Factory
Defaults
34
Factory Settings
35
Monitor and Control Functions - Web Only
Agent
Information
Device
Status
Monitor
Categories
Click to view in
right panel
• The top portion of the left panel displays information that appears on all pages:
• Agent Information - name, contact, location and description of the Liebert unit (as defined
in 4.0 - System Information)
• Device Status - current status of the Liebert unit and whether any alarms are active (if so,
the most recent alarm is listed)
• Monitor Categories appear at bottom left, organized with folder icons and showing the avail-
able Monitoring functions.
• Click on a category to view parametric data in the right panel. The example above shows a
graphic representation of the current state of a Liebert UPS. Other categories show data in table
format. The information will vary according to the type of Liebert unit.
NOTE
If any alarms are currently active, they are listed below the graphic in the opening window.
Click on the Active Alarms category to view more details about any alarms that are active.
36
Monitor and Control Functions - Web Only
Control tab
Control
Operations
Click to view in
right panel
• Control Operations categories appear at bottom left, organized with folder icons and showing
the available Control functions. Clicking on a category changes the view in the right panel. The
example above shows the summary page.
The following guide is a partial list of Control operations—these vary by the type of Liebert unit.
Table 23 Control operations parameters—functions vary by Liebert unit
Command Description
Abort Commands Prevent any pending commands from being completed.
Alarm Silence / Alarms Temporarily silence an audible alarm that is active. Reset or acknowledge alarms
Output / System Turn the Liebert unit On or Off; reboot the unit.
Statistics Reset statistics—for example, battery or power statistics
Tests Initiate diagnostic tests on the Liebert unit.
Setpoints Change setpoints for the Liebert unit.
• To perform an operation, click on a Control Operations category at left, then click on the appropri-
ate button in the right panel. The example below shows control operations for two Liebert units.
Liebert
GXT2U
example
Output
Liebert
DS
example
Setpoints
37
Monitor and Control Functions - Web Only
Links
Agent Event Log at the top of the page includes two links, (.txt) and (.csv). The Txt link will download
the entire event history in unformatted text. The CSV link will download the entire event history in
comma-separated format, which can then be imported into an application such as Microsoft Excel®.
Scroll through
Event Log Event Log tab
38
Support Information
Web Interface
To view Web card information through the Web interface:
• Click on the Support tab, then Summary in the left panel. The Web card information appears in
the right panel.
Support tab
Listing in
right panel
Summary
39
Support Information
• Choose Display Events to view a list of supported events for Display Events (Example)
the Liebert unit, as shown in the example at right. -----------------
AlarmOnBypass,1.3.6.1.2.1.33.
These events may vary according to the Liebert unit where the 1.6.3.9
lgpAgentDeviceCommunicationLost,
card is installed. 1.3.6.1.4.1.476.1.42.2.3.0.1
Hit any key to continue...
• Choose Display Parameters to view a list of supported param-
eters for the Liebert unit, as in the example at right. Display Parameters (Example)
----------------------
These parameters vary according to the Liebert unit where the sysDescr,1.3.6.1.2.1.1.1.0
sysObjectID,1.3.6.1.2.1.1.2.0
card is installed. Hit any key to continue...
Web Interface
To view events and parameters through the Web interface:
• Click on the Support tab, then Events (or Parameters) in the left panel. The events or parame-
ters are listed in the right panel. The example below shows a list of Events.
Support tab
Listing in
right panel
Events (or
Parameters)
40
Introduction
A1
Connect to the Card - Terminal Emulation, Telnet or Web Interface
A2
Preparing to Update Liebert IntelliSlot Firmware
Configure and
Support Tabs
A3
Preparing to Update Liebert IntelliSlot Firmware
A.3.2 Determine the Liebert IntelliSlot Card Type and Firmware Version
Each type of Liebert IntelliSlot card uses different firmware. Attempting to upgrade a card with the
firmware for another type of card will fail and may damage the card.
To determine the type of card in your Liebert equipment:
Web Interface
To view Web card information using a Web browser:
1. Open a connection to the Liebert IntelliSlot card (if needed, see instructions in A.2.4 - Open the
Web Interface).
2. Click on the Support tab, then Summary in the left panel. The Liebert IntelliSlot card model,
part number and firmware version appear in the right panel.
Support tab
A4
Updating the Firmware - HTTP (Web) Method
Browse
Web
Connect To Filename
Update Firmware
5. Click on the Browse button to locate the upgrade file. This is the file with the extension “.bin”
downloaded in A.3.3 - Download the Firmware Upgrade File to the Computer. Then click
Open to return to the update screen.
6. When ready to begin the update, click the Update Firmware button.
A screen will appear, showing the firmware update progress.
NOTE
Do not refresh your browser or open another browser window. Wait until the firmware update
has been completed before opening other applications or using the computer for other tasks.
7. A message appears indicating whether the update was successful.
After the firmware update is completed, the card will reinitialize and you may return to the Liebert
IntelliSlot card’s Web interface.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card
Type and Firmware Version).
A5
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
6. After making changes, press the Escape key twice to return to the Main Menu.
7. Choose Exit and Save to save your changes and reboot the card.
A6
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
14. A message appears, as shown at right, The firmware on this card is currently being updated.
This operation may take 6 or more minutes depending
showing the progress by percent on network traffic and other factors. The card will be
complete. rebooted upon successful completion of the process OR
control will be returned to this terminal session upon
15. When the progress screen shows 100% failure so another firmware update attempt can be made.
complete, the card will be rebooted. Firmware update in process... Percent Complete(0%)
Press Enter when this is finished.
16. Press the Escape key to return to the Main Menu
Main Menu, then choose Exit and ----------
1: System Information
Save. 2: IP Network Settings
3: Messaging
The upgrade is now complete. 4: Factory Settings
5: Firmware Updates
Check the new firmware version if you q: Quit and abort changes
x: Exit and save
wish (see A.3.2 - Determine the Liebert Please select a key ?>
IntelliSlot Card Type and Firmware
Version).
A.5.2 TFTP Method - Web Interface
To update the Liebert IntelliSlot card firmware using the TFTP method with a Web interface:
Edit
TFTP
A7
Updating the Firmware - TFTP (HyperTerminal, Telnet, Web) Method
6. After making changes, click Save, then click Reinitialize in the left panel to reboot the card.
Configure
tab
Save
TFTP
Reinitialize
Update
Firmware
A8
Updating the Firmware - Xmodem (Serial) Method
11. During the update, the window displays a progress bar, as shown below left.
NOTE
Do not close the Web browser during this process or the update will abort.
After the firmware update is completed, the card will reinitialize automatically. A reboot mes-
sage, as shown below right, remains until the rebooting is finished.
Progress
of update
When the rebooting is complete, the Web browser window returns to the default opening view. The
upgrade is now complete.
Check the new firmware version if you wish (see A.3.2 - Determine the Liebert IntelliSlot Card
Type and Firmware Version).
A9
Updating the Firmware - Xmodem (Serial) Method
115200 bps
Configure
button
A10
Updating the Firmware - Xmodem (Serial) Method
A11
Updating the Firmware - Xmodem (Serial) Method
9600 bps
Configure
button
29. Choose Exit and Save from the Main Menu to reboot the card. Main Menu
When rebooting is complete, the upgrade is finished. ----------
1: System Information
2: IP Network Settings
Check the new firmware version if you wish (see A.3.2 - Determine 3: Messaging
the Liebert IntelliSlot Card Type and Firmware Version). 4: Factory Settings
5: Firmware Updates
A12
Updating the Firmware - Xmodem (Serial) Method
Notes
A13
Updating the Firmware - Xmodem (Serial) Method
A14
Ensuring The High Availability
Of Mission-Critical Data And Applications.
Emerson Network Power, the global leader in enabling business-critical Technical Support / Service
continuity, ensures network resiliency and adaptability through Web Site
a family of technologies—including Liebert power and cooling www.liebert.com
technologies—that protect and support business-critical systems. Monitoring
800-222-5877
Liebert solutions employ an adaptive architecture that responds
[email protected]
to changes in criticality, density and capacity. Enterprises benefit Outside the US: 614-841-6755
from greater IT system availability, operational flexibility and Single-Phase UPS
reduced capital equipment and operating costs. 800-222-5877
[email protected]
Outside the US: 614-841-6755
Three-Phase UPS
800-543-2378
[email protected]
Environmental Systems
800-543-2778
Outside the United States
614-888-0246
Locations
United States
1050 Dearborn Drive
P.O. Box 29186
Columbus, OH 43229
Europe
Via Leonardo Da Vinci 8
Zona Industriale Tognana
35028 Piove Di Sacco (PD) Italy
+39 049 9719 111
While every precaution has been taken to ensure the accuracy
and completeness of this literature, Liebert Corporation assumes no
Fax: +39 049 5841 257
responsibility and disclaims all liability for damages resulting from use of Asia
this information or for any errors or omissions. 7/F, Dah Sing Financial Centre
© 2008 Liebert Corporation 108 Gloucester Road, Wanchai
All rights reserved throughout the world. Specifications subject to change
without notice. Hong Kong