1. The document provides specifications for the CASB383AU wall sounder beacon, including operating voltages, current draw, temperature range, sound output levels and tones. 2. Installation instructions are given for mounting the base and making electrical connections to ensure IP66 integrity. 3. Assembly details show how to attach the sounder to the base and ensure cables do not stress the PCB. Dimensions of the product are also provided.

Uploaded by

Yuri Oliveira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
25 views

Installation CASB383

1. The document provides specifications for the CASB383AU wall sounder beacon, including operating voltages, current draw, temperature range, sound output levels and tones. 2. Installation instructions are given for mounting the base and making electrical connections to ensure IP66 integrity. 3. Assembly details show how to attach the sounder to the base and ensure cables do not stress the PCB. Dimensions of the product are also provided.

Uploaded by

Yuri Oliveira
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Technical Data PR211-179-595-01 Effective November 2017

CASB383AU wall sounder beacon


specification
Supply Voltage 18 ~ 32 Vdc Cooper Fire
Cable Size / type 0.5 ~ 2.5mm/ FIRETUF, FP200 or MICC Wheatley Hall Road
Doncaster
Standby current < 450 uA
South Yorkshire
Operating temperature -10 to +55 degrees C (95%RH)
DN2 4NB
Sound output @ +/-3dB Low volume : 92dB @ <6.5mA
(set by panel) Tel: 01302 321 541
Medium volume : 97dB @ <7.5mA
www.cooper-ls.com
High volume : 100dB @ <8.5mA
Tones Continuous 984Hz
Bell Tone
Order codes
(set by panel)
Pulsed Sweep ISO8201 3x500ms CASB383AU Addressable Wall Sounder/Beacon
800-970Hz ½ Sec Gap CASB383AU/WP Addressable Wall Sounder/Beacon
Pulsed 984 / 0Hz pulse 1Hz IP66
Beacon

Installation details
Wall Sounder/Beacon
1. Mounting base 2. Connection details

Earth

Earth

OUT
(i) Drill required holes for cable gland fixing

IN
(ii) Drill out the required fixing holes
E - + E - +
(iii) Fix to mounting suface using two suitable screws

LOOP
Cooper Fire Systems
LOOP

OUT
IN

Analogue Addressable
Drill position for Panel
rear cable entry
WARNING: Do NOT use high voltage testers if ANY equipment is
connected to the system.
Earth screen must be continuous along entire length of loop.

3. Sounder assembly
(i) Clip sounder onto base
50

50

60 (ii) Ensure cables do not put stress on the PCB

Drill position Holes


for glands Guides

Key

Dimensions To Un-Lock use key provided


106

105 91

25-9816-B
Technical Data PR211-179-595-01
Effective November 2017

Wall Sounder/Beacon IP66


1. Mounting base 3. Sounder assembly
(i) D
 rill required holes for cable gland fixing (top or bottom) and (i) Location ribs must align on base and sounder
ensure cables are correctly sealed for IP66 integrity. (ii) Ensure cables do not put stress on the PCB
(ii) Fix to mounting surface using four suitable screws (iii) Bolt sounder onto base
Drill positions
for glands RIB
97
Use these four
62
holes to ensure
IP66 integrity
75
50

50

Dimensions

2. Connection details
Earth

Earth

OUT
IN

E - + E - +

110
LOOP

Cooper Fire Systems


LOOP

OUT
IN

Analogue Addressable
Panel

110 100
WARNING
Do NOT use high voltage testers when beacons or control panel are
connected to the system.

Earth screen of cable to be continuous between sounders.

Eaton
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu

© 2017 Eaton Eaton is a registered trademark.


All Rights Reserved
Publication No. PR211-179-595-01 / XXX All other trademarks are property
November 2017 of their respective owners.