Solar Drive EM15 SP User Manual

The document provides information about an EM15-SP series solar inverter user manual. It includes safety precautions, product information, installation instructions, operation instructions, function code descriptions, troubleshooting tips, and a Modbus communication protocol appendix.

Uploaded by

Rinaldy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
40 views

Solar Drive EM15 SP User Manual

The document provides information about an EM15-SP series solar inverter user manual. It includes safety precautions, product information, installation instructions, operation instructions, function code descriptions, troubleshooting tips, and a Modbus communication protocol appendix.

Uploaded by

Rinaldy
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 41

EMHEATER

User Manual

EM15-SP Series Solar Inverter

China EM Technology Limited


EM15-SP User Manual Preface

Preface
Thank you for purchasing the EM15 series solar inverter developed by China EM Technology Limited.

Features:
 MPPT algorithm of fast tracking of maximum power point of PV cells, efficiency >99%.
 Solar battery working point voltage can be manually or automatically MPPT tracking.
 All weather automatic operation,can also be manually or automatically,
 Realize”sunrise work and sunset sleep”.
 35 kinds protection function. including auto detecting short circuit after power on.
 Auto sleep function/pump dry protect/low frequency protection/over load protection and etc.
 Full protections:overload,over current, overvoltage,under voltage,short circuit, dry pumping etc.
 Output frequency range: V/F(0~3000hz); vector control(0~300HZ).
 Overload capacity:60s with 150% of rated current,3s with 180% of rated current.
 Speed accuracy:±0.5%(SVC);±0.02%(VC).
 Pulse setting input:0Khz~100Khz.
 Remote control, support RS232/RS485 protocol, terminal control, analog control.

Before unpacking, please check carefully:


1. Whether the nameplate model of solar inverter are consistent with your order ratings. The box contains the solar
inverter, user manual.
2. Whether the solar inverter is damaged during transportation. If you find any omission or damage, please contact
us or your local supplier immediately.
First-time Use
For the users who use this product for the first time, read the manual carefully. If in doubt concerning some
functions or performances, contact the technical support personnel to ensure correct use.
Due to the continuous improvement of solar inverter, this document will be updated without prior notice.

EM15-SP series solar inverter complies with the following international standards. All products have passed the CE
certification.
IEC/EN61800-5-1: 2003 Variable speed electric drive system safety requirements;
IEC/EN61800-3: 2004 Variable speed electric drive system, Part 3: The Electro Magnetic Compatibility (EMC)
Standards of Product and its specific testing methods.

Version:V1.0.0
Contents EM15-SP User Manual

Contents
1. Safety Information and Precautions......................................................................................................................... 1
1.1 Safety Information ......................................................................................................................................... 1
2. Product Information ................................................................................................................................................. 3
2.1 Designation Rules .......................................................................................................................................... 3
2.2 EM15-SP series.............................................................................................................................................. 3
2.3 Product appearance and installation dimension ............................................................................................. 4
2.3.1 Product appearance ............................................................................................................................. 4
2.3.2 EM15-SP solar inverter appearance and installing dimension(mm) ................................................... 4
2.3.3 Appearance and installation dimension of external keypad (keypad tray).......................................... 5
3.Installation of Frequency Inverter............................................................................................................................. 6
3.1 Installation environment ................................................................................................................................ 6
3.2 Installation direction and space...................................................................................................................... 6
3.3 Sketch and Description of Main Circuit Terminals........................................................................................ 7
3.3.1 Function and description of Main Circuit Terminals .......................................................................... 7
3.4 Control Circuit and Main Circuit Terminals Description .............................................................................. 8
3.4.1 Control Circuit and Main Circuit Wiring ............................................................................................ 8
3.4.2 Control Circuit Terminal Layout......................................................................................................... 9
3.4.3 Description of control circuit terminals .............................................................................................. 9
3.4 Collection Diagram For Different Motor..................................................................................................... 10
3.5. 1 The wiring of water-level automatic control .....................................................................................11
4 Operation and display ............................................................................................................................................. 13
4.1 Instruction of operation and display ............................................................................................................ 13
4.2 Function Code Table .................................................................................................................................... 14
5. Description of Function Codes .............................................................................................................................. 19
F0: Basic Function Parameters Group ............................................................................................................... 19
F1 Motor Parameter ........................................................................................................................................... 22
F4 Input Terminals ............................................................................................................................................. 23
F9 Faults and protection parameters .................................................................................................................. 24
FE Solar water pump control parameters .......................................................................................................... 25
FP User password parameters ............................................................................................................................ 28
6. Fault Diagnosis and Solution ................................................................................................................................. 29
6.1 Fault Alarm and Countermeasures ............................................................................................................... 29
Appendix I. Modbus communication protocol .......................................................................................................... 31
I. About Protocol................................................................................................................................................ 31
II. Application Methods ..................................................................................................................................... 31
III. Bus structure ................................................................................................................................................ 31
EM15-SP User Manual 1. Safety Information and Precautions

1. Safety Information and Precautions

In this manual, the notices are graded based on the degree of danger:

Danger: Indicates that failure to comply with the notice will result in severe personal injury or even death.

Warning: Indicates that failure to comply with the notice will result in personal injury or property damage.
Read this manual carefully so that you have a thorough understanding. Installation, commissioning or maintenance
may be performed in conjunction with this chapter. EMHEATER will assume no liability or responsibility for any
injury or loss caused by improper operation.
1.1 Safety Information

Danger
 Do not use damaged or missing components solar inverter. Failure to comply will result in personal injury.
 Please use the electric motor with upper B insulation class. Failure to comply will result in personal injury.
 Install the solar inverter on incombustible objects such as metal, and keep it away from combustible materials.
Failure to comply may result in a fire.
 Wiring must be performed only by qualified personnel under instructions described in this manual. Failure to
comply may result in unexpected accidents.
 A circuit breaker must be used to isolate the power supply and the solar inverter. Failure to comply may result
in a fire.
 Ensure that the power supply is cut off before wiring. Failure to comply may result in electric shock.
 Connect the solar inverter to ground properly by standard. Failure to comply may result in electric shock.
 Cover the solar inverter properly before power-on to prevent electric shock.
 Do not open the solar inverter’s cover after power-on to prevent from electric shock.
 Do not touch the solar inverter with wet hand and its peripheral circuit to prevent from electric shock.
 Do not touch the terminals of the solar inverter (including the control terminals). Failure to comply may result
in electric shock.
 Do not touch the U, V, W terminal or motor connecting terminals when solar inverter automatically does
safety testing for the external high-voltage electrical circuit. Failure to comply may result in electric shock.
 Do not go close to the equipment when selected the restart function. Failure to comply may result in personal
injury.
 Do not touch the fan or the discharging resistor to check the temperature. Failure to comply will result in
personal injury.
 Signal detection must be performed only by qualified personal during operation

1
1. Safety Information and Precautions EM15-SP User Manual

Warning:
 When two solar inverters are laid in the same cabinet, arrange the installation positions properly to ensure the
enough cooling effect.
 Do not drop wire residue or screw into the solar inverter. Failure to comply will result in damage to the solar
inverter.
 Never connect the power supply cables to the output terminals (U, V, W) of the solar inverter. Failure to
comply will result in damage to the solar inverter.
 Make sure that all the connecting wires comply with the requirement of EMC and the safety standard in the
region. Use wire sizes recommended in the manual. Failure to comply may result in accidents.
 Never connect the braking resistor between the DC bus terminals (P+) and (P-). Failure to comply may result
in a fire.
 Do not perform the voltage resistance test on any part of the solar inverter because such test has been done in
the factory. Failure to comply will result in accidents.
 All peripheral devices must be connected properly under the instructions described in this manual. Failure to
comply will result in accidents.
 Note the danger during the rotary running of motor when check the parameters. Failure to comply will result
in accidents.
 Do not change the factory default settings of the solar inverter. Failure to comply will result in damage to the
solar inverter.
 Avoid objects falling into the solar inverter when it is running. Failure to comply will result in damage to solar
inverter.
 Do not start/stop the solar inverter by turning the contactor ON/OFF. Failure to comply will result in damage
to the solar inverter.

2
EM15-SP User Manual 2. Product Information

2. Product Information

2.1 Designation Rules

EM15 - SP 1 - 015

Product Series Product Type Output Voltage Adaption Motor


EMHEATER SP: Solar Pump 1S: DC 310 / AC 1PH 220V In 5d5: 5.5KW
Solar Inverter AC 1PH 220V Output 015: 15KW
1: DC 310 / AC 1PH 220V In
AC 3PH 220V Output
3: DC 540V/AC 3PH 380V In
AC 3PH 380V Output

Diagram 2-1 Designation rules

2.2 EM15-SP series


Table 2-1EM15-SP Models and technical datas
EM15-SP1[S]
d75 1d5 2d2 004 5d5 7d5 011 015 018 022 030 037 045
Description
DC input (+, -)
Rated power/KW 0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45
Min. DC voltage/V 120
Max.DC voltage/V 400
Recommended MPPT
250~400
range /V
AC output(U, V, W)
Output current/A 3.8 5.1 9 13 25 32 45 60 75 91 112 150 176
EM15-SP3 d75 1d5 2d2 004 5d5 7d5 011 015 018 022 030 037 045
Description 055 075 090 110 132 160 200 220 250 280 315 355 400
DC input (+, -)
0.75 1.5 2.2 4 5.5 7.5 11 15 18.5 22 30 37 45
Rated power/KW
55 75 90 110 132 160 200 220 250 280 315 355 400
Min. DC voltage/V 280
Max.DC voltage/V 750
Recommended MPPT
350~750
range /V
AC output(U, V, W)
2.1 3.8 5.1 9 13 17 25 32 37 45 60 75 91
Output current
112 150 176 210 253 304 377 426 465 520 585 650 725
Output frequency 0~50/60Hz
Power factor >0.99
Communication mode RS485 communication
Protection class IP20
Ambient temperature -10℃~ +40℃(ambient temperation at 40℃~50℃,please keep derated use)
Storage temperature -20℃~ +60℃
Humidity Smaller than 95%RH, non-condensation
Cooling Forced Air cooling
Altitude Lower than 1000 m
Humidity Less than 95%RH, without condensing
Vibration Less than 5.9 m/s2 (0.6 g)

3
2. Product Information EM15-SP User Manual

2.3 Product appearance and installation dimension


2.3.1 Product appearance

Diagram 2-2 Product appearance (With potentiometer)

2.3.2 EM15-SP solar inverter appearance and installing dimension(mm)

Diagram 2-3 Appearance and installation dimension of EM15 series (Plastic housing structure)
Matching inverter Appearance and installing dimension (Unit: mm)
Voltege Power Range W W1 H H1 D d
1PH 220V 0.75~2.2kW
3PH 220V 0.75~2.2kW 120 108 205 195 166 Φ4.5
3PH 380V 4~5.5kW
3PH 220V 4~5.5kW
162 148 250 238 191 Φ5.5
3PH 380V 7.5~11kW
3PH 220V 7.5~11kW
223 207 323 307 207 Φ5.5
3PH 380V 15~22kW

4
EM15-SP User Manual 2. Product Information

Diagram 2-4 Appearance and installation dimension of EM15 series (Metal housing structure)

Matching inverter Appearance and installing dimension (Unit: mm)


Voltege Power Range W W1 H H1 D d
3PH 220V 15~18.5kW
300 220 540 500 240 Φ7
3PH 380V 30~37kW
3PH 220V 22kW
340 260 580 540 270 Φ10
3PH 380V 45~55kW
3PH 220V 37~45KW
410 260 610 575 280 Φ12
3PH 380V 75~90kW
3PH 380V 110~132kW 460 320 710 690 335 Φ12
3PH 380V 160~220kW 535 360 885 830 370 Φ12
3PH 380V 250~315kW 650 360 1040 985 415 Φ12
3PH 380V 355~400kW 815 600 1350 1250 445 Φ12

2.3.3 Appearance and installation dimension of external keypad (keypad tray)

Diagram 2-5 Appearance and installation dimension of external keypad (keypad tray)

5
3. Installation of Frequency Inverter EM15-SP User Manual

3.Installation of Frequency Inverter

3.1 Installation environment


1. The place with indoor vents or ventilation devices.
2. The environment temperature shall be -10℃~40℃. If the temperature is over 40℃but less than 50℃,
better to take down the cover of frequency inverter or open the front door of cabinet to facilitate heat
dissipation.
3. Try to avoid high temperature and wet place; the humidity shall be less than 90% without frost deposit.
4. Avoid direct sunlight.
5. Keep away from flammable, explosive and corrosive gas and liquid.
6. No dust, floating fiber and metal particles.
7. Install on the place without strongly vibration. And the vibration should be not over 0.6G, Especially
pay attention to far away from the punching machine, etc.
8. Keep away from electromagnetic interference source.

3.2 Installation direction and space


In order to not affect the service life of frequency inverter and reduce its performance, note for its
installation direction and space and correctly fasten it.

Diagram3-1 Ventilating duct installation dimension diagram of frequency inverter

Installation dimension
Power class
A B
≤7.5kW ≥ 20mm ≥ 100mm
11kW - 30kW ≥ 50mm ≥ 200mm
≥ 37kW ≥ 50mm ≥ 300mm

Please install the frequency inverter vertically, to send out the heat upward, and pay attention to direction of
frequency inverter to avoid inversion.
If there are several units of frequency inverter installed, please install them side by side, do not to install up
and down.

6
EM15-SP User Manual 3. Installation of Frequency Inverter

3.3 Sketch and Description of Main Circuit Terminals


3.3.1 Function and description of Main Circuit Terminals
Single phase 220V output:EM15-SP1S-d75 ~ EM15-SP1S-011
Three phase 220V output:EM15-SP1-d75~EM15-SP1-011
Three phase 380V output:EM15-SP3-d75~EM15-SP3-022

Three phase 380V output:EM15-SP3-030~EM15-SP3-090

Three phase 380V output:EM15-SP3-110~EM15-SP3-400

Terminal symbol Function description


L,N or R,T DC power input terminals
P+,PB Braking resistor connectin
P,P+ External DC reactor connecting terminals,shorted by bronze before delivery
P+,P- DC power input terminals;External brake unit DC output terminal

or E/PE Grounding terminal


U,V,W Three-phase AC power output terminals

7
3. Installation of Frequency Inverter EM15-SP User Manual

3.4 Control Circuit and Main Circuit Terminals Description


3.4.1 Control Circuit and Main Circuit Wiring

Diagram3-2 EM15-SP control circuit and main circuit wiring

8
EM15-SP User Manual 3. Installation of Frequency Inverter

3.4.2 Control Circuit Terminal Layout

Diagram3-3 EM15-SP control circuit terminal sketch diagram

3.4.3 Description of control circuit terminals


Terminal Terminal
Type Terminal function description
Symbol Name
Provide +10V power supply to external unit. Maximum output
External current:10Ma
+10V-GND +10V power
supply Generally, it provides power supply to external potentiometer
with resistance range of 1 kΩ~5kΩ
External Provide +24 V power supply to external unit. Generally, it
Power
Supply +24V-COM +24V power provides power supply to DI/DO terminals and external
supply sensors.Maximum output current: 200 mA
External
power supply
PLC It connect with +24V default
input
terminals
Analog input
AI1-GND
1
1. Input range: DC 0V~10V/ 0mA~20mA(decided by jumper
Analog Analog input AI1/AI2 on the control board); AI3: DC -10V~+10V
AI2-GND
input 2 2. Impedance: 22 kΩ (voltage input), 500 Ω (current input)
Analog input
AI3-GND
3
DI1-COM Digital input 1
1. Optical coupling isolation, compatible with dual polarity
DI2-COM Digital input 2
input
DI3-COM Digital input 3
Digital 2.Input Impedance: 2.4 kΩ
input DI4-COM Digital input 4
3. Voltage range for level input: 9V~30 V
DI5-COM Digital input 5
High Speed
HDI-COM Maximum input frequency: 100 kHz
Pulse Input
Analog output Voltage or current output is decided by jumper AO1/AO2.
AO1-GND
1
Output voltage range: 0V~10 V
Analog Analog output
AO2-GND Output current range: 0mA~20 mA
2
output
Constrained by function code b4-00 "FMP terminal output
FMP- COM High Speed mode selection" as the high-speed pulse output, the highest
Pulse Output frequency is 100kHz; when use as an open collector output,

9
3. Installation of Frequency Inverter EM15-SP User Manual

Terminal Terminal
Type Terminal function description
Symbol Name
specifications is the same as DO.
TA1-TB1
NC terminal
Relay TA2-TB2 Contact driving capacity: 250 VAC, 3 A, COSø= 0.4
output TA1-TC1 DC 30 V, 1 A
NO terminal
TA2-TC2
PG card interface PG cards: Open-collector, differential are selectable options.
Auxiliary
interface Communications expansion Reversed
External keypad interface Connected to an external keypad
COM grounding PE selection ,default connection.
PE-COM In the case of interference, connecting PE to COM can improve
anti-interference
GND grounding PE selection ,default connection.
PE-GND In the case of interference, connecting PE to COM can improve
anti-interference.
AI1 output selection.
Jumper AI1 Voltage or Current output, voltage output by default.
AI2 output selection.
AI2 Voltage or Current output, current output by default.
AO1/AO2 output selection.
AO1/AO2 Voltage or Current output, voltage output by default.
485 communication resistor selection, default connection ON.
458 In the case of interference, anti-interference can be improved.

3.4 Collection Diagram For Different Motor

Photovoltaic cell
Note: For the EM15-SP1S series,
U and V as single Phase 220V
output terminal.
EM15-SP

+ - U V W

Water Tank

Water Pipe

C o n t r o l Te r m i n a l
COM DI1 DI2

Pump

Diagram3-4 220V three phase installed without water level sensor (PV Input)

10
EM15-SP User Manual 3. Installation of Frequency Inverter

Photovoltaic cell

EM15-SP
Water Tank
+ - U V W

Water Pipe

C o n t r o l Te r m i n a l
COM DI1 DI2 DI4 DI5

Pump

Diagram3-5 Diagram of 3phsae inverter connection method (PV Input)


3.5. 1 The wiring of water-level automatic control
The wiring for floater water-level switch connected by cable
The common port, which using floate water-level switch connected by cable, is fed to the terminal “COM”
of EM15-SP. And then, connected to DI1.
DI1 DI1
EM15-SP EM15-SP
COM
Inverter COM
Inverter

High water-level

Low water-level

Diagram3-6 Diagram of Low water level and high water level


Remarks:
When the actual water-level in the wells is higher than the horizontal line of high water-level, DI1 will be
connected to the “COM” as well as controller automatically will start the pump. On the contrary, if the
actual water-level is lower than the horizontal line of low water-level, DI1 will be disconnected from

11
3. Installation of Frequency Inverter EM15-SP User Manual

“COM” as well as controller automatically stop the pump to prevent anhydrous idling.
The wiring for floater water-level switch mounted on a side
The floater water-level switch mounted on a side is the normally open contact to output and its common
wire is connected to the terminal COM of EM15-SP inverter. At the same time, the low level-water wire is
connected to terminal DI4 and the high water-level wire is connected the terminal DI5.
High water-level

EM15-SP EM15-SP
DI5 COM DI5 COM
Detector switch of Detector switch of
high water-level high water-level

EM15-SP EM15-SP
DI4 COM DI4 COM
Detector switch of Detector switch of
low water-level low water-level

Low water-level

Diagram3-7 Diagram of Low water level and high water level

Remarks:
When the actual water-level in the reservoir is lower than horizontal line of low water-level, DI4 and DI5
will be disconnected from the COM as well as controller automatically strat the pum. On the contrary, if the
actual water-level is higher than the horizontal line of high water-level, DI4 and DI5 will be connected to
COM as well as controller automatically stop the pump to prevent water overflow.
Notice:
1. If only use one detection signal of water-level in the reservoir, DI4 and DI5 must be connected together
by conductor.

12
EM15-SP User Manual 4. Operation and Display

4 Operation and display

4.1 Instruction of operation and display

Diagram 4-1 Operating panel


No. Name Function
The 5-digit LED display is able to display the set frequency, output frequency, monitoring
LED display area
data and fault codes.
Hz Frequency unit
A Current unit
V Voltage unit
STOP/ OFF indicates that the frequency inverter is in the stop state and ON indicates
RUN that the frequency inverter is in the running state.
FWD/REV It is Forward/Reversal indicator, ON indicates forward rotation.
Unit / Status It indicates whether the frequency inverter is operated by operation keypad,
Indicator area LOCAL terminals or remoter (communication). OFF indicates keypad operation
/REMOTE control state; ON indicates terminals operation control state; Blinking
indicates remote operation control state.
Tunning/ Torque Control/Fault indicator
TRIP When the indicator is ON, it indicates torque control mode. When the
/ALARM indicator is blinking slowly, it indicates the auto-tuning state. When the
indicator is blinking quickly, it indicates the fault state.
Frequency, data or function code increase or decrease; the encoder knob has the
Encoder knob
confirmation key function
Programming key: Enter or exit menu level I.
Confirmation key: Enter the menu interfaces level by level, and confirm the
parameter setting.
Multi-function key: Perform function switchover according to the setting of
b9-01
Shift key: Select the displayed parameters in turn in the stop or running
state, and select the digit to be modified when modifying parameters.
Operation key area
Increment key: Increase data or function code.

Decrement key: Decrease data or function code.

Running key: Start the frequency inverter in the keypad control mode.
Stop/Reset key: Stop the frequency inverter when it is in the running state and
perform the reset operation when it is in the fault state. The functions of this
key are restricted by b9-00.
13
4. Operation and Display EM15-SP User Manual

4.2 Function Code Table


If FP-00 set to a non-zero number, parameter protection is enabled. You must write in correct user password to
enter the menu.
To cancel the password protection function, enter with password and set FP-00 to 0。
The parameter menu under the user-defined parameter mode can directly enter without password.
A is frequency inverter system parameter. Group “F” is basic function parameters .Group “U” is monitoring
function parameters.
Code Name Description Default
F0: Basic function parameters
1: G type(Constant torque load models ) Model
F0-00 G/P type selection
2: P type(Fan, water pump load models ) dependent
0: Keypad control (LED off)
F0-02 Command source selection 1: Terminal control (LED on) 0
2: Communication control (LED blinking)
0: Digital setting (Preset frequencyF0-08, UP/DOWN
modifiable, no-record after power off)
1: Digital setting (Preset frequencyF0-08 , UP/DOWN
Main frequency source X modifiable, record after power off)
F0-03 4
selection 2: AI1
3: AI2
4: Keypad potentiometer
9: Communication setting
F0-08 Preset frequency 0.00Hz~maximum frequency(F0-10) 50.00Hz
0: Forward;FWD/REV lights off;
F0-09 Rotation direction 0
1: Reverse;FWD/REV lights on;
F0-10 Maximum frequency 50.00Hz~500.00Hz 50.00Hz
0: Set by(F0-12)
1: AI1
Source of frequency
F0-11 2: AI2 0
upper limit
3: AI3
5: Communication setting
F0-12 Frequency upper limit Frequency lower limit(F0-14)~maximum frequency(F0-10) 50.00Hz
F0-13 Frequency upper limit offset 0.00Hz~maximum frequencyF0-10 0.00Hz
F0-14 Frequency lower limit 0.00Hz~frequency upper limit(F0-12) 0.00Hz
Model
F0-15 Carrier frequency 0.5kHz~16.0kHz
dependent
Carrier frequency adjustment 0: No
F0-16 1
with temperature 1: Yes
0.00s~650.00s(F0-19=2)
Model
F0-17 Acceleration time 1 0.0s~6500.0s(F0-19=1)
dependent
0s~65000s(F0-19=0)
0.00s~650.00s(F0-19=2)
Model
F0-18 Deceleration time 1 0.0s~6500.0s(F0-19=1)
dependent
0s~65000s(F0-19=0)
0: 1s
Acceleration/Deceleration
F0-19 1: 0.1s 1
time unit
2: 0.01s
Record of digital setting 0: not record
F0-23 0
frequency of power failure 1: record
0: Maximum frequency (F0-10)
Acceleration/Deceleration time
F0-25 1: Set frequency 0
base frequency
2: 100Hz
Base frequency for UP/ DOWN 0: Running frequency
F0-26 0
modification during running 1: Setting frequency
Binding command source to Unit's digit: Binding keypad command to following frequency
F0-27 0000
frequency source source.
14
EM15-SP User Manual 4. Operation and Display

Code Name Description Default


0: No binding
1: Frequency source by digital setting
2: AI1
3: AI2
4: Keypad potentiometer
9: Communication setting
Ten's digit:: Binding terminal command to frequency source.
Hundred's digit: Binding communication command to frequency
source.
F0-28 Serial communication protocol 0: MODBUS-RTU protocol 0
F1: Motor parameter
0: General asynchronous motor
F1-00 Motor type selection 0
1: Variable frequency asynchronous motor
Model
F1-01 Rated motor power 0.1kW~1000.0kW
dependent
Model
F1-02 Rated motor voltage 1V~2000V
dependent
0.01A~655.35A(Frequency inverter power≤55kW) Model
F1-03 Rated motor current dependent
0.1A~6553.5A(Frequency inverter power >55kW)
Model
F1-04 Rated motor frequency 0.01Hz~maximum frequency
dependent
Model
F1-05 Rated motor rotational speed 1rpm~65535rpm
dependent
F4: input terminals parameters
F4-00 DI function selection 0: No function 01
F4-01 DI2 function selection 1: Forward RUN (FWD) or running command 09
F4-02 DI3 function selection 2: Reverse RUN (REV) or the direction of FED/REV 53
F4-03 DI4 function selection 4: Forward JOG(FJOG) 51
F4-04 DI5 function selection 5: Reverse JOG(RJOG) 52
8: Free stop
9: Fault reset(RESET)
10: Run pause
11: Normally open(NO) input of external fault
33: Narmally closed (NC) input of external fault
36: External STOP terminal 1
F4-05 DI6 function selection 02
44: User-defined fault 1
47: Emergercy stop
48: External STOP terminal 2
51: Full-water detection 1
52: Full-water detection 2
53: MPPT stop/ Photovoltaic control stop
F4-13 AI curve1 Min. input Value 00.00V~F4-15 00.00V
Corresponding setting of AI
F4-14 -100.0%~+100.0% 000.0%
curve1 Min.input
F4-15 AI curve1 input maximum value F4-13~+10.00V 10.00V
Corresponding setting of AI
F4-16 -100.0%~+100.0% 100.0%
curve1 input maximum value
F4-17 AI1 input filter time 0.00s~10.00s 00.10s
F4-18 AI curve 2 Min. input Value 0.00V~F4-20 00.00V
Corresponding of AI curve 2
F4-19 -100.0%~+100.0% 000.0%
Min. input Value
F4-20 AI curve2 input maximum value F4-18~+10.00V 10.00V
Corresponding of AI curve2
F4-21 -100.0%~+100.0% 100.0%
input maximum value
F4-22 AI2 filter time 0.00s~10.00s 00.10s
F4-35 DI1delay time 0.0s~3600.0s 0.0s
F4-36 DI2 delay time 0.0s~3600.0s 0.0s
F4-37 DI3 delay time 0.0s~3600.0s 0.0s

15
4. Operation and Display EM15-SP User Manual

Code Name Description Default


F9: Fault and Protection parameters
F9-09 Fault auto reset times 0~20 20
Relay action selection during 0: Not act
F9-10 0
fault auto reset 1: Act
F9-11 Time interval of fault auto reset 0.1s~100.0s 5.0s
Unit's digit: Input phase loss protection
Input phase loss
Ten's digit: Contactor energizing protection
F9-12 protection/contactor energizing 00
0: Disabled
protection selection 1: Enabled
0: Disabled
F9-13 Output phase loss protection 0
1: Enabled
0: No fault
2: Over current during acceleration
3: Decelerated current during acceleration
4: Over current at constant speed
5: Overvoltage during acceleration
6: Decelerated voltage during deceleration
7: Overvoltage at constant speed
9: Less voltage fault
10: Frequency inverter overload
11: Motor overload
12: Power input phase loss
13: Power output phase loss
14: IGBT Module overheat
F9-14 Fault types 00
15: External equipment fault
16: Communication fault
18: Current detection fault
21: EEPROM read- write fault
22: Frequency inverter hardware fault
23: Short circuit to ground
26: Accumulative running time reached
27: User-defined fault 1
28: User-defined fault 2
29: Accumulative power-on time reached
40: Fast current limit fault
43: Motor over-speed
55: Load distribution slave failure
F9-37 Frequency of fault - -
F9-38 Current of fault - -
F9-39 DC Bus voltage of fault - -
F9-40 Input terminals status of fault - -
F9-41 Output terminal status of fault - -
Frequency inverter status of
F9-42 - -
fault
F9-43 Power-on time of fault - -
F9-44 Running time of fault - -
FE: parameters for solar water pump control
0: Disabled
FE-00 PV inverter Selection 1
1: Enabled
0: Manual setting
FE-01 Vmpp voltage Selection 1
1: MPPT Automatic algorithm tracking
Vmpp voltage manual
FE-02 0-1000.0V 500.0V
Reference value
0: General three phase ac motor
FE-03 Motor Selection 1: Single phase motor with capacitor 0
2: Single phase motor without capacitor
FE-04 CVT proportional gain 1 0.0%-999.9% 100.0%
16
EM15-SP User Manual 4. Operation and Display

Code Name Description Default


FE-05 CVT Integral gain1 0.0%-999.9% 100.0%
FE-06 Reserved -- --
FE-07 Reserved -- --
FE-08 Reserved -- --
FE-09 Reserved -- --
FE-10 Mppt search upper limit voltage 0-1000.0V 750.0V
FE-11 Mppt search lower limit voltage 0-1000.0V 300.0V
FE-12 MPPT search gain 0%-500% 100%
FE-13 MPPT search time interval 0.0-10.0s 1.0sec
FE-14 Reserved 0 0
FE-15 Reserved 0 0
FE-16 Dormancy voltage 0.0-1000.0V 300.0V
FE-17 Dormancy wake-up voltage 0.0-1000.0V 350.0V
FE-18 Dormancy wake-up time 0-30000sec 60sec
detection frequency of low
FE-19 0.00Hz~300.00Hz 10.00Hz
frequency protection
Detection time of low frequency
FE-20 0-30000s 10sec
protection
low frequency protection
FE-21 0-30000s 60sec
automatic recovery time
detection current of dry
FE-22 0.0-999.9A 0.0A
pumping protection
detection time of dry pumping
FE-23 0-30000s 10sec
protection
automatic recovery time of dry
FE-24 0-30000s 60sec
pumping protection
detection current of overcurrent
FE-25 0.0-999.9A 0.0A
protection
detection time of overcurrent
FE-26 0-30000s 10sec
protection
over current protection
FE-27 0 -30000s 60sec
automatic recovery time
FE-28 Min. power protection value 0.00kw - 650.00kw 0.00kw
Detection time of Min. power
FE-29 0 - 30000s 0sec
protection
Min. power protection
FE-30 0 - 30000s 0sec
automatic recovery time
0: terminal
FE-31 Full water detection mode 1: AI1 0
2: AI2
Analog full-water detection
FE-32 0-100.0% 25.0%
Thresholds
detection time of full-water
FE-33 0-30000s 10sec
protection
FE-34 exit time of full-water protection 0-30000s 60sec
analog sensor damaged
FE-35 0-100.0% 0.0%
Thresholds
FE-36 PV DC correction coefficient 0.0-200.0% 100.00%
FE-37 PV DC correction offset -100.00A-100.00A 0.00A
FE-38 power curve point 0 0.0kw-999.9kw 0.5kw
FE-39 power curve point 1 0.0kw-999.9kw 1.0kw
FE-40 power curve point 2 0.0kw-999.9kw 1.5kw
FE-41 power curve point 3 0.0kw-999.9kw 2.0kw
FE-42 power curve point 4 0.0kw-999.9kw 2.5kw
FE-43 flow curve point 0 0.0-999.9m^3/h 0.0 m^3/h
FE-44 flow curve point 1 0.0-999.9m^3/h 5.0 m^3/h
FE-45 flow curve point 2 0.0-999.9m^3/h 10.0m^3/h
FE-46 flow curve point 3 0.0-999.9m^3/h 15.0m^3/h
FE-47 flow curve point 4 0.0-999.9m^3/h 20.0m^3/h

17
4. Operation and Display EM15-SP User Manual

Code Name Description Default


FP: Parameters for User password
FP-00 User password 0 ~ 65535 00000
0: No operation
1: Restore default settings except motor parameters and
accumulation record.
FP-01 Restore default settings 0
02: Clear records
04: Back up present user parameters
501: Restore user backup parameters
Unit’s digit: U group display selection
0: Not displayed
Function parameter group 1: Display
FP-02 01
display selection Ten’s digit: A Show Select
0: Not displayed
1: Display
0: modifiable
FP-04 Parameter modification property 0
1: Not modifiable
U0: Monitoring parameters
U0-00 Running frequency(Hz) -- 0.01Hz
U0-01 Setting frequency(Hz) -- 0.01Hz
U0-02 PV voltage(V) -- 0.1V
U0-03 Output voltage(V) -- 1V
U0-04 Output current(A) -- 0.01A
U0-05 PV power (KW) -- 0.1KW
U0-06 PV current(A) -- 0.01A
U0-07 DI input status -- 1
U0-08 DO output status -- 1
U0-09 AI1 -- 0.01V
U0-10 AI2 -- 0.01V
U0-11 KAI -- 0.01V
U0-12 PVopen circuit voltage -- 0.1V
U0-13 Pump flow speed -- 0.1m^3/hr
U0-14 Daily flow -- 0.1m^3
Cumulative flow(low water
U0-15 -- 0.1m^3
level)
Cumulative flow (high water
U0-16 -- 0.1Km^3
level)
U0-17 Daily generated electricity -- 0.1kwh
Cumulative electricity
U0-18 -- 0.1kwh
consumption(low water level)
Cumulative electricity
U0-19 -- 1Mwh
consumption(high water level)
Ar: Parameters for Alarm
Ar.01 Dormancy 81
Ar.02 Low frequency protection 82
Dry pumping rotection
Ar.03 83
/underload
Ar.04 Overcurrent protection 84
A4.05 Min.power protection 85
A4.06 Full-water protection 86
A4.07 Analog sensor fault 87

18
EM15-SP User Manual 5. Description of Function Code

5. Description of Function Codes

F0: Basic Function Parameters Group


1: G type(Constant torque load models ) Model
F0-00 G/P type selection
2: P type(Fan, water pump load models ) dependent
This parameter is used to display the delivered model and cannot be modified.
1: Applicable to constant torque general load with rated parameters specified.
2: Applicable to variable torque load (fan and pump) with rated parameters specified.

0: Keypad control (LED off)


F0-02 Command source selection 1: Terminal control (LED on) 0
2: Communication control (LED blinking)
It is used to determine the input channel of the frequency inverter control commands, such as run, stop, forward
rotation, reverse rotation and jog operation. You can input the commands in the following three channels:
0: Keypad control ("LOCAL/REMOT" indicator off)
Commands are given by pressing keys “RUN” and “STOP/RESET” on the operation panel.
1: Terminal control ("LOCAL/REMOT" indicator on)
Commands are given by means of multifunctional input terminals with functions such as FWD, REV, JOGF, and
JOGR.
2: Communication control ("LOCAL/REMOT" indicator blinking)
Commands are given from host computer. For more details please refer to the appendix of communication protocol.
0: Digital setting(Preset frequencyF0-08 , UP/DOWNUP/DOWN
modifiable, no-record after power off)
1: Digital setting (Preset frequencyF0-08,UP/DOWNUP/DOWN
Main frequency source modifiable, record after power off)
F0-03 4
X selection 2: AI1
3: AI2
4: Keypad potentiometer
9: Communication setting
It is used to select the setting channel of the main frequency. You can set the main frequency in the following 10
channels:
0: Digital setting (not record at power failure)
The initial value of the set frequency is the value of F0-08 (Preset frequency). You can change the set frequency by
pressing ▲ and ▼ on the operation panel (or using the UP/DOWN function of input terminals).
When the Frequency inverter is powered on again after power failure,the set frequency reverts to the value of F0-08
(record digital setting frequency )
1: Digital setting (record at power failure)
The initial value of the set frequency is the value of F0-08(Preset frequency). You can change the set frequency by
pressing keys ▲ and ▼ on the operation panel (or using the UP/DOWN functions of input terminals).
When the frequency inverter is powered on again after power failure, the setting frequency is the value memorized
at the moment of the last power failure.
Note that F0-23 (record digital setting frequency of power failure) F0-23 determines whether the set frequency is
memorized or cleared when the frequency inverter stops.It is related to stopping rather than power failure.
2: AI1
3: AI2
The frequency is set by analog input. The EM15 control board provides two analog input (AI) terminals (AI1, AI2).
Including:
AI1: 0V~10 V voltage input or 0mA ~ 20mA current input, determined by jumper JP2 on the control card;
19
5. Description of Function Code EM15-SP User Manual

AI2: 0V~10 V voltage input or 0mA ~ 20mA current input, determined by jumper JP3 on the control card;
The corresponding relationship curve between the input voltage of AI1, AI2 and the target frequency can be
user-defined.
EM15-SP provides 5 corresponding curves, 3 groups curves are linear relation (2 point correspondence), 2 curves are
arbitrary curve of 4 points corresponding relationship,User can set by F4-13 ~ F4-27 function code and A6 group
function code. F4-33 is used to set the AI1~AI2 two analog input. When AI is used as the frequency setting source,
the corresponding value 100% of the voltage/current input corresponds to the value of F0-10 (Maximum frequency).
4: Keypad potentiometer
9: Communication setting
The frequency is set by communication mode.

F0-08 Preset frequency 0.00Hz~ maximum frequency(F0-10) 50.00Hz


If the frequency source is digital setting he value of this parameter is the initial frequency of the frequency inverter
(digital setting).

0: Forward direction
F0-09 Rotation direction 0
1: Reverse direction
You can change the rotation direction of the motor just by modifying this parameter without changing the motor
wiring. Modifying this parameter is equivalent to exchanging any two phase of the motor's U, V, W wires.
Note:
The motor will restore original running direction after parameter initialization. Do not use this function in
applications where changing the rotating direction of the motor is prohibited after system commissioning is
complete.

F0-10 Maximum frequency 50.00Hz~500.00Hz 50.00Hz


When the frequency source is AI, pulse setting (HDI), or Multi-segment speed, the 100% of input corresponds to the
value of this parameter.

0: Set byF0-12
1: AI1
F0-11 Source of frequency upper limit 2: AI2 0
3: Keypad potentiometer
5: Communication setting
It is used to set the source of the frequency upper limit, including digital setting(F0-12),AI, pulse setting or
communication setting.

F0-12 Frequency upper limit Frequency lower limit(F0-14)~maximum frequency(F0-10) 50.00Hz


Setting Frequency upper limit.

F0-13 Frequency upper limit offset 0.00Hz~maximum frequency(F0-10) 0.00Hz


If the source of the frequency upper limit is analog input, set F0-13 as the offset value,the final frequency upper
limit is obtained by adding the offset in this parameter to the frequency upper limit set in F0-11

F0-14 Frequency lower limit 0.00Hz~frequency upper limit (F0-12) 0.00Hz


If the frequency command is lower than the value of this parameter set by F0-14, the frequency inverter can stop, r
run at the frequency lower limit, or run at zero speed.The result can be determined byF8-14(setting frequency lower
than frequency lower limit running mode).
20
EM15-SP User Manual 5. Description of Function Code

0.00s~650.00s(F0-19=2)
Model
F0-17 Acceleration time 1 0.0s~6500.0s(F0-19=1)
dependent
0s~65000s(F0-19=0)
0.00s~650.00s(F0-19=2)
Model
F0-18 Deceleration time 1 0.0s~6500.0s(F0-19=1)
dependent
0s~65000s(F0-19=0)
Acceleration time indicates the time required by the frequency inverter to accelerate from 0 Hz to "Acceleration /
Deceleration base frequency"(F0-25 ) that is, t1 in Diagram 6-1.
Deceleration time indicates the time required by the frequency inverter to decelerate from "Acceleration /
Deceleration base frequency" (F0-25 ),to 0 Hz, that is, t2 in Diagram 5-1.

Diagram 5-1 Acceleration/Deceleration time

0: 1s
Acceleration/Deceleration time
F0-19 1: 0.1s 1
unit
2: 0.01s
To satisfy requirements of different applications ,the EM15 provides three acceleration/ deceleration time units,
1s, 0.1s and 0.01s.
Note: Modifying this parameter will make the decimal places of all frequency-related parameters change and
corresponding frequency values change. Pay attention for this in on-site application.

Record of digital setting 0: not record


F0-23 0
frequency of power failure 1:record
This parameter is valid only when the frequency source is digital setting.
If F0-23 is set to 0, the digital setting frequency value restore to the value of F0-08(Preset frequency)after the
frequency inverter stops. The modification by using keys ▲ and ▼ or the terminal UP/DOWN function is cleared to
zero.
If F0-23 is set to 1, the digital setting frequency value “Reserved”is the set frequency at the moment when the
frequency inverter stops. The modification by using keys ▲ and ▼ or the terminal UP/ DOWN function remains is
record and valid.

0: Maximum frequency(F0-10)
Acceleration/Deceleration time
F0-25 1: Set frequenc 0
base frequency
2: 100Hz

21
5. Description of Function Code EM15-SP User Manual

The acceleration/deceleration time indicates the time for the frequency inverter to increase from 0 Hz to the
frequency set in F0-25,figure 6-1 is the acceleration/deceleration time diagram.
If this parameter is set to 1, the acceleration/deceleration time is related to the set frequency. If the set frequency
changes frequently, the motor's acceleration/deceleration also changes.
Pay attention for this in on-site application.

Base frequency for UP/ DOWN 0: Running frequency


F0-26 0
modification during running 1: Setting frequency
This parameter is valid only when the frequency source is digital setting.
It is used to set the base frequency to be modified by using keys ▲ and ▼ or the terminal UP/DOWN function.If the
running frequency and setting frequency are different, there will be a large difference between the frequency
inverter's performance during the acceleration/ deceleration process.

Unit's digit: Binding keypad command to following frequency


source.
0: No binding
1: Frequency source by digital settin
2: AI1
Binding command source to
F0-27 3: AI2 0000
frequency source
4: AI3
9: Communication setting
Ten's digit: Binding terminal command to frequency source.
Hundred's digit: Binding communication command to frequency
source.
It is used to bind the three running command sources with the nine frequency sources, facilitating to implement
synchronous switchover.
For details on the frequency sources, see the description of F0-03 (Main frequency source X selection).Different
running command sources can be bound to the same frequency source.
If a command source has bound to a frequency source, this frequency source set in ,F0-03~F0-07no longer takes
effect when this command source is effective.

F0-28 Serial communication protocol 0: Protocol MODBUS-RTU 0


The use of EM15-SP serial port communication protocol MODBUS.

F1 Motor Parameter
0: General asynchronous motor
F1-00 Motor type selection 0
1: Variable frequency asynchronous motor
Model
F1-01 Rated motor power 0.1kW~1000.0kW
dependent
Model
F1-02 Rated motor voltage 1V~2000V
dependent
0.01A~655.35A(Frequency inverter power≤55kW) Model
F1-03 Rated motor current
0.1A~6553.5A(Frequency inverter power >55kW) dependent
Model
F1-04 Rated motor frequency 0.01Hz~maximum frequency
dependent
Model
F1-05 Rated motor rotational speed 1rpm~65535rpm
dependent
Set the parameters according to the motor nameplate no matter whether V/F control or vector control is adopted.
To achieve better V/F or vector control performance, motor auto-tuning is required. The motor auto-tuning
accuracy depends on the correct setting of motor nameplate parameters.

22
EM15-SP User Manual 5. Description of Function Code

F4 Input Terminals
The EM15 provides six digital input (DI) terminals (HDI can be used for high-speed pulse input) and two analog
input (AI) terminals. The optional extension card provides another six DI terminals (DI7 to DI12) and one AI
terminal (AI3).

F4-00 DI1 function selection 1: Forward RUN (FWD) Standard


F4-01 DI2 function selection 9 Standard
F4-02 DI3 function selection 53 Standard
F4-03 DI4 function selection 51 Standard
F4-04 DI5 function selection 52 Standard
F4-05 DI6 function selection 2 Standard

The following table lists the functions available for the DI terminals.
Value Function Description
0 No function Set 0 for reserved terminals to avoid malfunction.
Forward RUN (FWD) or running
1
command The terminal is used to control forward or reverse running of the
Reverse RUN (REV) or the direction frequency inverter.
2
of FED/REV
4 Forward JOG (FJOG) FJOG for the JOG forward running, RJOG for the JOG reverse
5 Reverse JOG (RJOG) running.
8 Free stop
9 Fault reset (RESET)
10 RUN pause
Normally open (NO) input of external
11
fault
Normally closed (NC) input of external
33
fault
36 External STOP terminal 1
44 User-defined fault 1
47 Emergency stop
48 External STOP terminal 2
51 Full-water detection 1 Two probes any access, from the water-full position to maintain a
52 Full-water detection 2 certain height difference in the installation
53 MPPT stop/ Photovoltaic control stop Into the common speed mode

F4-13 AI curve1 Min.input 0.00V ~ F4-15 0.00V


Corresponding setting of AI curve1
F4-14 -100.00% ~ 100.0% 0.0%
Min.input
F4-15 AI curve1 input maximum value F4-13 ~ 10.00V 10.00V
Corresponding setting of AI curve1
F4-16 -100.00% ~ 100.0% 100.0%
input maximum value
F4-17 AI1 filter time 0.00s ~ 10.00s 0.10s
These parameters are used to define the relationship between the analog input voltage and the corresponding setting
value.
When analog input voltage is larger than setting” Max. input” (F4-15), Analog voltage should be calculated as ”
Max. input”. The same, When analog input voltage is smaller than setting” Min. input” (F4-13), Analog voltage
should be calculated as ” Min. input” F4-34.
When the analog input is current input, 1 mA current corresponds to 0.5 Volts.
(AI1 filter time) is used to set the software filter time of AI1. If the analog input is liable to interference, increase
23
5. Description of Function Code EM15-SP User Manual

the value of this parameter to stabilize the detected analog input. However, increase of the AI filter time will slow
down the response of analog detection. Set this parameter properly based on actual conditions.
In different applications, 100% of analog input corresponds to different nominal values. For details, refer to the
description of different applications.
Following tables for reference:

Diagram 5-2 The relationship between analog given and setting value

F4-35 DI1 delay time 0.0s ~ 3600.0s 0.0s


F4-36 DI2 delay time 0.0s ~ 3600.0s 0.0s
F4-37 DI3 delay time 0.0s ~ 3600.0s 0.0s
For setting DI changing status, Inverter’s delay for this actives.
Only DI1、DI2、DI3 has delay time functions

F9 Faults and protection parameters


F9-09 Fault auto reset times 0~20 20
It is used to set the times of fault auto resets if this function is used. After the value is exceeded, the frequency
inverter will remain in the fault state.

Do action selection during 0: Not act


F9-10 0
fault auto reset 1: Act
It is used to decide whether DO acts during the fault auto reset if the fault auto reset function is used.

Time interval of fault auto


F9-11 0.1s ~ 100.0s 5.0s
reset
is used to set the waiting time from the frequency inverter alarm to fault auto reset.

Input phase loss Unit's digit: Input phase loss protection


protection/contactor Ten's digit: Contactor energizing protection
F9-12 00
energizing protection 0: Disabled
selection 1: Enabled
It is used to determine whether to perform input phase loss or contactor energizing protection.

0: Disabled
F9-13 Output phase loss protection 0
1: Enabled

24
EM15-SP User Manual 5. Description of Function Code

It is used to determine whether to perform output phase loss protection.

F9-14 Fault type 0 ~ 99 00


It is used to record the types of the most recent three faults of the frequency inverter. 0 indicates no fault.

F9-37 Frequency of fault It displays the frequency when the latest fault occurs.
F9-38 Current of fault It displays the current when the latest fault occurs.
F9-39 DC Bus voltage of fault It displays the DC bus voltage when the latest fault occurs.
It displays the status of all DI terminals when the latest fault occurs. The
sequence is as follows:
Input terminals status of BIT9 BIT8 BIT7 BIT6 BIT5 BIT4 BIT3 BIT2 BIT1 BIT0
F9-40
fault DI0 DI9 DI8 DI7 HDI DI5 DI4 DI3 DI2 DI1
If a DI is ON, the setting is 1. If the DI is OFF, the setting is 0. The value
is the equivalent decimal number converted from the DI status.
It displays the status of all output terminals when the latest fault occurs.
The sequence is as follows:
BIT4 BIT3 BIT2 BIT1 BIT0
Output terminal status of
F9-41 DO2 DO1 REL REL FMP
fault
If an output terminal is ON, the setting is 1. If the output terminal is
OFF, the setting is 0. The value is the equivalent decimal number
converted from the DI statuses.
Frequency inverter status
F9-42 Reserved
of fault
F9-43 Power-on time of fault It displays the present power-on time when the latest fault occurs.
F9-44 Running time of latest fault It displays the present running time when the latest fault occurs.

FE Solar water pump control parameters


0: Disabled
FE-00 PV inverter selection 1
1: Enabled
If set to 0, inverter will be working as normal frequency inverter.

Vmpp voltage reference 0: Manual


FE-01 1
selection 1: MPPT Automatic algorithm tracking
Vmpp voltage manual setting
FE-02 0 - 1000.0V 500.0V
value
It is for setting solar panels working point voltage Vmpp. Solar water pump’s working theory as below: Vmpp is
selected between FE-01 MPPT running result and FE-02, then output running frequency by CVT controller.

0: General three phase ac motor


FE-03 Motor Selection 1: Single phase motor with capacitor --
2: Single phase motor without capacitor
0: General three phase ac motor
1: Single phase motor with capacitor
2: Single phase motor without capacitor

25
5. Description of Function Code EM15-SP User Manual

PE-10~PE-13 PE-01
PE-04~PE-08
MPPT f ref
Vmpp CVT
Controller
PE-02

V pn

Diagram 5-3 Photovoltaic water pump control schematic


FE-04 CVT proportional gain 1 0.0% - 999.9% 100.0%
FE-05 CVT Integral gain1 0.0% - 999.9% 100.0%
It is CVT controller’s PI parameters,it should be switchover in two groups according to solar cells Vpn voltage ,
switchover point is FE-08V; switchover point FE-08 default as 0.0V. It is for enable the first group parameters,
switchover theory as below diagram:

KP/KI

K2

K1

PE-08 PE-08+50V Vpn

Diagarm 5-4 Switch the schematic


CVT controller is the core parts for solar water pump control, if any unbalance output frequency, please close
MPPT(select manual reference Vmpp ), then adjust proportional gain or Integral gain till frequency is stable; after
that, open MPPT search again;

FE-10 Mppt search upper limit voltage 0 - 1000.0V 750.0V


FE-11 Mppt search lower limit voltage 0 - 1000.0V 300.0V
FE-12 MPPT search gain 0% - 500% 100%
FE-13 MPPT search time interval 0.0 - 10.0sec 1.0sec
FE-10/FE-11set MPPT search Vmpp’s upper or limit value,FE-12 set search gain, FE-13 set search time interval,If
open MPPT, frequency fluctuation is very large, decrease search gain and increase search time interval to improve
its stability.

0: terminal
FE-31 Full-water detection mode 1: AI1 0
2: AI2
Analog full-water detection
FE-32 0 - 100.0% 25.0%
Thresholds
26
EM15-SP User Manual 5. Description of Function Code

detection time of full-water


FE-33 0 - 30000sec 10sec
protection
exit time of full-water
FE-34 0 - 30000sec 60sec
protection
analog sensor damaged
FE-35 0 - 100.0% 0.0%
Thresholds
FE-31 is for Full-water detection mode.
If set to 0, set any terminals(default DI4/DI5)function code to 51/52,two terminals enabled in same time could
activate Full-water protection and two terminals disabled in same time could activate exit Full-water protection.
One of the terminals enabled, remains its status without any change.
FE-33/FE-34 for detection time of full-water protection and exit time of full-water protection;
FE-35 for analog sensor damaged Thresholds,if FE-31 set to analog detection, and analog feedback is larger than
the setting detectionThreshold value of FE-35. Judge it as analog sensor faults. Display A.Prb, and stop running;
FE-31 set to 0, close sensor faults detection.

FE-36 PV DC correction coefficient 0.0 - 200.0% 100.00%


FE-37 PV DC correction offset -100.00A - 100.00A 0.00A
As software estimating solar cells’ DC current value, this parameters will correction this estimation value, U0-06
displays correction current, correction formula is U0-06 =(estimation value * FE-36)+ FE-37 ;

FE-38 power curve point 0 0.0kw - 999.9kw 0.5kw


FE-39 power curve point 1 0.0kw - 999.9kw 1.0kw
FE-40 power curve point 2 0.0kw - 999.9kw 1.5kw
FE-41 power curve point 3 0.0kw - 999.9kw 2.0kw
FE-42 power curve point 4 0.0kw - 999.9kw 2.5kw
FE-43 flow curve point 0 0.0 - 999.9m^3/h 0.0 m^3/h
FE-44 flow curve point 1 0.0 - 999.9m^3/h 5.0 m^3/h
FE-45 flow curve point 2 0.0 - 999.9m^3/h 10.0m^3/h
FE-46 flow curve point 3 0.0 - 999.9m^3/h 15.0m^3/h
FE-47 flow curve point 4 0.0 - 999.9m^3/h 20.0m^3/h
According output power(U0-05) calculate output flow speed(U0-13), User reference(P-Q curve), input to FE-38~
FE-47, software automatically calculate U0-13;Generally, P-Q curve as below:

P[KW ]

Q[m3 / h]
Diagram 5-5 P-Q curve

27
5. Description of Function Code EM15-SP User Manual

FP User password parameters


FP-00 User password 0 ~ 65535 0
If it is set to any non-zero number, the password protection function is enabled. After a password has been set and
taken effect, you must enter the correct password in order to enter the menu. If the entered password is incorrect
you cannot view or modify parameters.
If FP-00 is set to 00000, the previously set user password is cleared, and the password protection function is
disabled.

0: No operation
1: Restore default settings except motor parameters and
accumulation record.
FP-01 restore default settings 2: Clear records 0
4: Back up present user parameters
501: Restore user backup parameters
1. Restore default settings except motor parameters
If FP-01 is set to 1, most function codes are restored to the default settings except motor parameters, frequency
command resolution (F0-22, fault records, accumulative running time (F7-09), accumulative power-on time (F7-13)
and accumulative power consumption (F7-14).
2. Clear records
If FP-01 is set to 2, the fault records, accumulative power-on time (F7-13), accumulative running time (F7-09), and
accumulative power consumption (F7-14) are cleared.
4. Back up present user parameters
the present parameter settings are backed up, helping you to restore the setting if incorrect parameter setting is
performed.
501. Restore user backup parameters
If FP-01 is set to 4, the previous backup user parameters are restored.

Parameter modification 0: Modifiable


FP-04 0
property 1: Not modifiable
It is used to set whether the parameters are modifiable to avoid mal-function. If it is set to 0, all parameters are
modifiable. If it is set to 1, all parameters can only be viewed.

28
EM15-SP User Manual 6. Fault Diagnosis and solution

6. Fault Diagnosis and Solution

6.1 Fault Alarm and Countermeasures


EM15-SP inverter has 35 types of warning information and protection function. In case of abnormal fault,
the protection function will be invoked, the inverter will stop output, and the faulty relay contact of the
inverter will start, and the fault code will be displayed on the display panel of the inverter. Before
consulting the service department, the user can perform self-check according to the prompts of this chapter,
analyze the fault cause and find out t solution. If the fault is caused by the reasons as described in the dotted
frame, please consult the agents of inverter or our company directly. Among the 35 types of warning
information, Err22 is hardware over current or over voltage signal. In most cases, the hardware over
voltage fault will cause Err22 alarm.
Table 7-1 Common faults and solution of the frequency inverter
Fault Code Err01 Fault Type Inverter unit protection
1: The output circuit is grounded or short circuited. 1: Eliminate external faults.
2: The connecting cable of the motor is too long. 2: Install a reactor or an output filter.
3: The IGBT overheat. 3: Check the air filter and the cooling fan.
4: The internal connections become loose. 4: Connect all cables properly.
5: The main control board is faulty. 5: Ask for technical support
6: The drive board is faulty. 6: Ask for technical support
7: The inverter IGBT is faulty. 7: Ask for technical support
Fault Code Err02/Err04 Fault Type Over current during acceleration/ at constant speed
1: The output circuit is grounded or short circuited. 1: Eliminate external faults.
2: Motor auto-tuning is not performed. 2: Perform the motor auto- tuning.
3: The acceleration time is too short. 3: Increase the acceleration time.
4: Manual torque boost or V/F curve is not appropriate. 4: Adjust the manual torque boost or V/F curve.
5: The voltage is too low. 5: Adjust the voltage to normal range.
6: The startup operation is performed on the rotating 6: Select rotational speed tracking restart or start the
motor. motor after it stops.
7: A sudden load is added during acceleration. 7: Remove the added load.
8: The frequency inverter model is of too small power 8: Select a frequency inverter of higher power class.
class.
Fault Code Err03 Fault Type Over current during deceleration
1: The output circuit is grounded or short circuited. 1: Eliminate external faults.
2: Motor auto-tuning is not performed. 2: Perform the motor auto-tuning.
3: The deceleration time is too short. 3: Increase the deceleration time.
4: The voltage is too low. 4: Adjust the voltage to normal range.
5: A sudden load is added during deceleration. 5: Remove the added load.
6: The braking unit and braking resistor are not 6: Install the braking unit and braking resistor.
installed.
Fault Code Err05/ Err06 Fault Type Overvoltage during acceleration/deceleration
1: The input voltage is too high. 1: Adjust the voltage to normal range.
2: An external force drives the motor during 2: Cancel the external force or install a braking resistor.
acceleration.
3: The acceleration/deceleration time is too short. 3: Increase the acceleration/deceleration time.
4: The braking unit and braking resistor are not 4: Install the braking unit and braking resistor.
installed.
Fault Code Err07 Fault Type Overvoltage at constant speed
1: The input voltage is too high. 1: Adjust the voltage to normal range.
2: An external force drives the motor during 2: Cancel the external force or install the braking
deceleration. resistor.
Fault Code Err08 Fault Type Control power supply fault
The input voltage is not within the allowable range. Adjust the input voltage to the allowable range.
29
6. Fault Diagnosis and solution EM15-SP User Manual

Fault Code Err09 Fault Type Low voltage


1: Instantaneous power failure occurs on the input 1: Reset the fault.
power supply.
2: The frequency inverter's input voltage is not within 2: Adjust the voltage to normal range.
the allowable range.
3: The DC bus voltage is abnormal. 3: Ask for technical support
4: The rectifier bridge and buffer resistor are faulty. 4: Ask for technical support
5: The drive board is faulty. 5: Ask for technical support
6: The main control board is faulty. 6: Ask for technical support
Fault Code Err10 Fault Type Frequency inverter overload
1: The load is too heavy or locked- rotor occurs on the 1: Reduce the load and check the motor and mechanical
motor. condition.
2: The frequency inverter model is of too small power 2: Select a frequency inverter of higher power class.
class.
Fault Code Err12 Fault Type Power input phase loss
1: The three-phase power input is abnormal. 1: Eliminate external faults.
2: The drive board is faulty. 2: Ask for technical support.
3: The lightningproof board is faulty. 3: Ask for technical support.
4: The main control board is faulty. 4: Ask for technical support.
Fault Code Err13 Fault Type Power output phase loss
1: The cable connecting the frequency inverter and the 1: Eliminate external faults.
motor is faulty. 2: Check whether the motor three phase winding is
2: The frequency inverter's three-phase outputs are normal.
unbalanced when the motor is running.
3: The drive board is faulty. 3: Ask for technical support.
4: The IGBT module is faulty. 4: Ask for technical support.
Fault Code Err14 Fault Type IGBT Module overheat
1: The ambient temperature is too high. 1: Lower the ambient temperature.
2: The air filter is blocked. 2: Clean the air filter.
3: The fan is damaged. 3: Replace the damaged fan.
4: The thermally sensitive resistor of the IGBT module 4: Replace the damaged thermally sensitive resistor.
is damaged.
5: The inverter IGBT module is damaged. 5: Replace the inverter module.
Fault Code Err15 Fault Type External equipment fault
1: External fault signal is input via DI. 1: Reset the operation.
2: External fault signal is input via virtual I/O. 2: Reset the operation.
Fault Code Err16 Fault Type Communication fault
1: The host computer is in abnormal state. 1: Check the cabling of host computer.
2: The communication cable is faulty. 2: Check the communication cabling.
3: The communication extension card is set improperly. 3: Set the communication extension card correctly.
4: The communication parameters in group bA are set 4: Set the communication parameters properly.
improperly.
Fault Code Err18 Fault Type Current detection fault
1: The HALL device is faulty. 1: Replace the faulty HALL device.
2: The drive board is faulty. 2: Replace the faulty drive board.
Fault Code Err22 Fault Type Frequency inverter hardware fault
1: Overvoltage exists. 1: Handle based on over voltage.
2: Over current exists. 2: Handle based on over current.

30
Appendix I. Modbus communication protocol

EM15series of inverter provides RS485 communication interface, and adopts MODBUS communication protocol.
User can carry out centralized monitoring through PC/PLC to get operating requirements. And user can set the
running command, modify or read the function codes, the working state or fault information of frequency inverter
by Modbus communication protocol.

I. About Protocol
This serial communication protocol defines the transmission information and use format in the series
communication and it includes master-polling (or broadcasting) format, master coding method and the content
includes function code of action, transferring data and error checking. The response of slave is the same structure,
and it includes action confirmation, returning the data and error checking etc. If slave takes place the error while it
is receiving the information or cannot finish the action demanded by master, it will send one fault signal to master
as a response.

II. Application Methods


The frequency inverter will be connected into a “Single-master Multi-slave” PC/PLC control net with RS485 bus as
the communication slave.

III. Bus structure


1) Hardware interface.
The “485+” and “485-“terminals on frequency inverter are the communication interfaces of Modbus
2) Topological mode
It is a “Single-master Multi-slave” system. In this network, every communication machine has a unique slave
address. One of them is as “master” (usually PC host machine, PLC and HMI, etc.), actively sends out the
communication, to read or write the parameters of slave. Other machines will be used as slave and response to the
inquiry/command from master. At one time only one machine can send the data and other machines are in the
receiving status. The setup range of slave address is 0 to 247. Zero refers to broadcast communication address. The
address of slave must is exclusive in the network.
3) Transmission mode
There provide asynchronous series and half-duplex transmission mode. In the series asynchronous communication,
the data is sent out frame by frame in the form of message. According to the Modbus-RTU protocol, when the free
time of no transmission in communication data lines is more than the transmission time of 3.5byte, it indicates that
a new start of communication frame.

EM15 series inverter has built-in the Modbus-RTU communication protocol, and is applicable to response the slave
“Inquiry/command” or doing the action according to the master’s “Inquiry / Command” and response to the data.

Here, master is personnel computer (PC), industrial machine or programmable logical controller (PLC), and the
slave is inverter. Master not only visits some slave, but also sends the broadcast information to all the slaves. For
the single master “Inquiry/Command”, all of slaves will return a signal that is a response; for the broadcast
6. Fault Diagnosis and solution EM15-SP User Manual

information provided by master, slave needs not feedback a response to master machine.

Communication data structure


Modbus protocol communication data format of EM15 series inverter is shown as following. The inverter only
support the reading and writing of Word type parameters, the corresponding reading operation command is “0x03”,
the writing operation command is “0x06”. The writing and reading operation of byte or bit is not supported.
>3.5Byte 1Byte 1Byte 2Byte 2Byte 2Byte

Number
Target Read the Function code CRC
Master reads Free
address
of
correction and
station command Free
command frame (Start frame) function
address (0x03) (H……L) L……H
code(n)

Calculate CRC
correction

In theory, the host computer can continuously read several function codes once (that is, the maximum value of “n”
is 12), but note that not to jump across the last function code in this function group to avoid the wrong reply.
>3.5Byte 1Byte 1Byte 1Byte (2n)Byte 2Byte

Target Read the Number Function code CRC


Slave reads Free
address correction and
station command of Data Free
response frame (Start frame)
address (0x03) type(2n) (H……L) L……H

Calculate CRC
correction

>3.5Byte 1Byte 1Byte 2Byte 2Byte 2Byte

Target Write the Function code Function code CRC


Master writes Free
station command address parameter correction and Free
command frame (Start frame)
address (0x06) (H……L) (H……L) L……H

Calculate CRC
correction

>3.5Byte 1Byte 1Byte 2Byte 2Byte 2Byte

Target Write the Function code Function code CRC


Slave writes Free
station command address parameter correction and Free
response frame (Start frame)
address (0x06) (H……L) (H……L) L……H

Calculate CRC
correction

If the wrong communication frame was detected by the salve or other reasons caused the failure of reading and
writing, the wrong frame will be replied.

32
>3.5Byte 1Byte 1Byte 1Byte 2Byte

Slave reads and Target Read the CRC


response error Free
station command Error type correction and Free
(Start frame)
frame address (0x83) L……H

Calculate CRC Error types:


correction 01-Command code error
>3.5Byte 1Byte 1Byte 1Byte 2Byte 02-Address error
03-Data error
04-Command cannot to process
Slave writes and Target Write the CRC
Free
response error station command Error type correction and Free
(Start frame)
frame address (0x86) L……H

Calculate CRC
correction

RTU frame format


Frame start (START) More than the 3.5- character time
Slave address(ADR) Communication address:1 to 247(0: broadcast address)
03: Read slave parameters
Command code(CMD)
06: Write slave parameters
It indicates the external parameter address of frequency inverter in
Function code address(H) hexadecimal format;
There are functional code or non-functional code (such as running state
parameter/ running command parameters) type parameters, for details see the
Function code address(L) address definition.
During the transmission, high bit is put in the front, and low bit is at the back.
It indicates the number of function code ready by the frame. If it is “1”, then it
Number of function code(H)
indicates that it reads one function code. During the transmission, high bit is
put in the front, and low bit is at the back.
Number of function code(L) Only one function code can be modified at one time without the field.
Data(L) It indicates the replying data or the data waiting to write-in. During the
Data(H) transmission, high bit is put in the front, and low bit is at the back.
END 3.5- character time
CRC Checking
In RTU mode, messages include an error-checking field that is based on a CRC method. The CRC field checks the
contents of the entire message. The CRC field is two bytes, containing a16-bit binary value. The CRC value is
calculated by the transmitting device, which appends the CRC to the message. The receiving device recalculates a
CRC during receipt of the message, and compares the calculated value to the actual value it received in the CRC
field.
If the two values are not equal, that means transmission is error
The CRC is started by 0xFFFF.Then a process begins of applying successive eight-bit bytes of the message to the
current contents of the register. Only the eight bits of data in each character are used for generating the CRC. Start
and stop bits, and the parity bit, do not apply to the CRC. During generation of the CRC, each eight-bit character is
exclusive ORed with the register contents. Then the result is shifted in the direction of the least significant bit
(LSB), with a zero filled into the most significant bit (MSB) position. The LSB is extracted and examined. If the
LSB was a 1, the register is then exclusive ORed with a preset, fixed value. If the LSB was a 0, no exclusive OR
takes place. This process is repeated until eight shifts have been performed. After the last (eighth) shift, the next
eight-bit byte is exclusive ORed with the register's current value, and the process repeats for eight more shifts as
described above. The final contents of the register, after all the bytes of the message have been applied, is the CRC
value.
6. Fault Diagnosis and solution EM15-SP User Manual

When the CRC is appended to the message, the low-order byte is appended first, followed by the high-order byte.
unsigned int crc_chk_value(unsigned char *data_value,unsigned char length
{
unsigned int crc_value=0xFFFF;
int i;
while(length--)
{
crc_value^=*data_value++;
for(i=0;i<8;i++)
{
if(crc_value&0x0001)
{
crc_value=(crc_value>>1)^0xa001;
}
else
{
crc_value=crc_value>>1;
}
}
}
return(crc_value);
}
Definition of communication parameter address
Read and write function-code parameters (Some functional code is not changed, only for the manufacturer use.)
The group number and mark of function code is the parameter address for indicating the rules.
High level bytes: F0~FF(Group F), A0~AF(GroupA), 70-7F(Group U)
Low level bytes: 00 ~ FF
For example: F3-12, address indicates to 0xF30C.
Note: Group U: Only for reading parameter, cannot be changed parameters.
Some parameters cannot be changed during operation, some parameters regardless of what kind of state the inverter
in, the parameters cannot be changed. Change the function code parameters, pay attention to the scope of the
parameters, units, and relative instructions.

Inquiry address When


Function code group Communication inquiry address
Communication modifies RAM
F0~FE 0xF000~ 0xFEFF 0x0000~ 0x0EFF
A0~FC 0xA000~0xACFF 0x4000~0x4CFF
U0 0x7000~ 0x70FF
Besides, due to EEPROM be frequently stored, it will reduce the lifetime of EEPROM. In the communication mode,
and some function codes don’t have to be stored as long as change the RAM value.

Stop/start parameter
Parameter Parameter
Parameter description Parameter description
address address
Communication set value(-10000 ~ PID setting
1000H 1010H
10000)(Decimal)
1001H Running frequency 1011H PID feedback
1002H DC Bus voltage 1012H PLC process
1003H Output voltage 1013H Pulse input frequency, unit: 0.01KHz
1004H Output current 1014H Feedback speed, unit:0.1Hz
1005H Output power 1015H Remaining running time

34
1006H Output torque 1016H Voltage before AI1correction
1007H Running speed 1017H Voltage before AI2correction
1008H DI input terminal 1018H Voltage before AI3correction
1009H DO output terminal 1019H Linear speed
100AH AI1 voltage 101AH Present power-on time
100BH AI2 voltage 101BH Present running time
100CH AI3 voltage 101CH Pulse input frequency, unit:1Hz
100DH Counting value input 101DH Communication setting value
100EH Length value input 101EH Actual feedback speed
100FH Load speed 101FH Main frequency X display
1020H Auxiliary frequency Y display
Note: Communication setting value is the percentage of relative value, 10000 corresponds to 100%, -10000
correspond to -100.00%.

Control command input frequency inverter: (write in only)


Command word address Command function
0001: Forward running
0002: Reverse running
0003: Forward jog
2000H 0004: Reverse jog
0005: Free stop
0006:Decelarating stop
0007: Fault reset

Read inverter status: (read only)


Command word address Command function
0001: Forward running
3000H 0002: Reverse running
0003: Stop

Parameter locking password collation: (If the feedback is the 8888H, it indicates the password collation passed)
Password address Contents of input password
1F00H *****

Digital output terminal control: (write in only)


Address Of locking password command Contents of locking password command
BIT0: DO1 output control
BIT1: DO2 output control
BIT2: Relay 1 output control
BIT3: Relay 2 output control
BIT4: FMR output control
2001H
BIT5: VDO1
BIT6: VDO2
BIT7: VDO3
BIT8: VDO4
BIT9: VDO5
6. Fault Diagnosis and solution EM15-SP User Manual

Analog output AO1 control: (write in only)


Command word address Command function
2002H 0~7FFF indicates 0%~100%

Analog output AO2 control: (write in only)


Command word address Command function
2003H 0~7FFF indicates 0%~100%

Pulse output control: (write in only)


Command word address Command function
2004H 0~7FFF indicates 0%~100%

Inverter fault description:


Inverter fault
Inverter fault information
description
0000: No fault 0015: EEPROM read-write in fault
0001: Reserved 0016: Frequency inverter hardware fault
0002: acceleration over current 0017: Short circuit to ground fault
0003: deceleration over current 0018: Reversed
0004: Constant speed over current 0019: Reversed
0005: acceleration over voltage 001A: Accumulative running time reached
0006: deceleration over voltage 001B: User-defined fault 1
0007:Constant speed over voltage 001C: User-defined fault 2
0008: Buffer resistor fault 001D: Accumulative power-on time reached
0009: less voltage fault 001E: Off load
8000H 000A:Frequency inverter overload 001F: PID lost during running
000B: Motor overload 0028: fast current limit fault
000C: Input phase failure 0029: Motor switchover fault during
000D: Output phase failure running
000E: IGBT overheat 002A: Too large speed deviation
000F: External equipment fault 002B: Motor over-speed
0010: Communication fault 002D: Motor overheat
0011: Contactor fault 005A: Encode lines setting fault
0012: Current detection fault 005B: Not connect to the encoder
0013: Motor auto-tuning fault 005C: Initial location fault
0014: Encoder/PG fault 005E: Speed feedback fault

Group Fd Communication parameters


Code Parameter Name Setting Range Default
Unit's digit: Modbus baud ratio.
0: 300 BPS 5: 9600 BPS
1: 600 BPS 6: 19200 BPS
Fd-00 Baud ratio setting 5
2: 1200 BPS 7: 38400 BPS
3: 2400 BPS 8: 57600 BPS
4: 4800 BPS 9: 115200 BPS
This parameter is used to set the data transfer rate from host computer and the frequency inverter. Please note that
baud ratio of the host computer and the inverter should be consistent. Otherwise, the communication is impossible.
The higher the baud ratio is, the faster the communication is.

Code Parameter Name Setting Range Default


0: No check, data format <8,N,2>
Fd-01 Modbus Data format 0
1: Even parity check, data format<8,E,1>

36
Code Parameter Name Setting Range Default
2: Odd Parity check, data format<8,O,1>
3: No check, data format <8,N,1>
The host computer and frequency inverter setup data format must be consistent, otherwise, communication is
impossible.

Code Parameter Name Setting Range Default


Fd-02 Broadcast address 0~247 (0: Broadcast address) 1
When the local address is set to 0, that is, broadcast address, it can realize the broadcast function of host computer.

Code Parameter Name Setting Range Default


Fd-03 Modbus response time 0~20 ms 2 ms
Response delay time: it refers to the interval time from the inverter finishes receiving data to sending data to the
host machine. If the response time is less than the system processing time, then the response delay time is based on
the time delay of the system processing time. If the response delay time is more than the system processing time,
after the system processes the data, it should be delayed to wait until the response delay time is reached, then
sending data back to host machine.

Code Parameter Name Setting Range Default


Communication 0.0s:invalid
Fd-04 0.0s
timeout 0.1s~60.0s
When the function is set to 0.0s, the communication interface timeout parameter is invalid.
When the function code is set to time value, if the interval time between the communication and the next
communication is beyond the communication timeout, the system will report communication failure error (Err16).
At normal circumstances, it will be set as invalid. If in the continuous communication system, set this parameter,
you can monitor the communication status.

Code Parameter Name Setting Range Default


Modbus protocol data Unit's digit: Modbus protocol.
Fd-05 transmission format 0: Non-standard Modbus protocol 1
selection 1: Standard Modbus protocol
Fd-05=1: Select standard Modbus protocol.
Fd-05=0: When reading the command, the slave machine return is one byte more than the standard Modbus
protocol’s, for details, refer to communication data structure of this protocol.

Code Parameter Name Setting Range Default


Communication
0: 0.01A
Fd-06 reading current 0
1: 0.1A
resolution
It is used to confirm the unit of current value when the communication reads the output current.