RE 615 61850eng 756475 ENq
RE 615 61850eng 756475 ENq
615 series
IEC 61850 Engineering Guide
Document ID: 1MRS756475
Issued: 2021-12-21
Revision: Q
Product version: 5.0 FP1
This document and parts thereof must not be reproduced or copied without written permission from
ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized
purpose.
The software or hardware described in this document is furnished under a license and may be used,
copied, or disclosed only in accordance with the terms of such license.
Trademarks
ABB and Relion are registered trademarks of the ABB Group. All other brand or product names
mentioned in this document may be trademarks or registered trademarks of their respective holders.
Warranty
Please inquire about the terms of warranty from your nearest ABB representative.
www.abb.com/relion
Disclaimer
The data, examples and diagrams in this manual are included solely for the concept or product
description and are not to be deemed as a statement of guaranteed properties. All persons responsible
for applying the equipment addressed in this manual must satisfy themselves that each intended
application is suitable and acceptable, including that any applicable safety or other operational
requirements are complied with. In particular, any risks in applications where a system failure and/or
product failure would create a risk for harm to property or persons (including but not limited to
personal injuries or death) shall be the sole responsibility of the person or entity applying the
equipment, and those so responsible are hereby requested to ensure that all measures are taken to
exclude or mitigate such risks.
This product has been designed to be connected and communicate data and information via a network
interface which should be connected to a secure network. It is the sole responsibility of the person
or entity responsible for network administration to ensure a secure connection to the network and
to take the necessary measures (such as, but not limited to, installation of firewalls, application of
authentication measures, encryption of data, installation of anti virus programs, etc.) to protect the
product and the network, its system and interface included, against any kind of security breaches,
unauthorized access, interference, intrusion, leakage and/or theft of data or information. ABB is not
liable for any such damages and/or losses.
This document has been carefully checked by ABB but deviations cannot be completely ruled out. In
case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than
under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or
damage resulting from the use of this manual or the application of the equipment.
Conformity
UK legislations:
• Electromagnetic Compatibility Regulations 2016
• Electrical Equipment (Safety) Regulations 2016
• The Restriction of the Use of Certain Hazardous Substances in Electrical and Electronic Equipment
Regulations 2012
These conformities are the result of tests conducted by the third-party testing in accordance with
the product standard EN / BS EN 60255-26 for the EMC directive / regulation, and with the product
standards EN / BS EN 60255-1 and EN / BS EN 60255-27 for the low voltage directive / safety regulation.
The product is designed in accordance with the international standards of the IEC 60255 series.
Safety information
Dangerous voltages can occur on the connectors, even though the auxiliary voltage has been
disconnected.
When the plug-in unit has been detached from the case, do not touch the inside of the case.
The relay case internals may contain high voltage potential and touching these may cause
personal injury.
The protection relay contains components which are sensitive to electrostatic discharge.
Unnecessary touching of electronic components must therefore be avoided.
Whenever changes are made in the protection relay, measures should be taken to avoid
inadvertent tripping.
Contents
Contents
1 Introduction..............................................................................................11
1.1 This manual............................................................................................................................................. 11
1.2 Intended audience................................................................................................................................. 11
1.3 Product documentation....................................................................................................................... 12
1.3.1 Product documentation set................................................................................................ 12
1.3.2 Document revision history...................................................................................................13
1.3.3 Related documentation........................................................................................................13
1.4 Symbols and conventions.................................................................................................................... 13
1.4.1 Symbols................................................................................................................................... 14
1.4.2 Document conventions........................................................................................................ 14
3 PCM600 tool............................................................................................. 17
3.1 Connectivity packages......................................................................................................................... 18
3.2 PCM600 and relay connectivity package version............................................................................18
5 GOOSE.......................................................................................................25
5.1 Horizontal communication..................................................................................................................25
5.1.1 Configuring horizontal communication........................................................................... 25
5.2 GOOSE publishing properties.............................................................................................................25
5.3 Configuring GOOSE with IEC 61850 Configuration tool............................................................... 26
5.3.1 Defining IEDs and starting IEC 61850 Configuration tool............................................ 26
5.3.2 Configuring a GOOSE publisher with IEC 61850 Configuration tool.......................... 27
5.3.3 Configuring a GOOSE subscriber with IEC 61850 Configuration tool........................37
5.4 Configuring GOOSE with IET600....................................................................................................... 39
5.4.1 Defining devices and exporting the SCD file for IET600 ..............................................39
5.4.2 Creating an empty project with IET600 ...........................................................................41
8 615 series
IEC 61850 Engineering Guide
Contents
615 series 9
IEC 61850 Engineering Guide
Contents
9 Glossary.................................................................................................. 110
10 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Introduction
1 Introduction
615 series 11
IEC 61850 Engineering Guide
Introduction 1MRS756475 Q
Figure 1: The intended use of documents during the product life cycle
12 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Introduction
Download the latest documents from the ABB Web site http://
www.abb.com/relion.
Product series- and product-specific manuals can be downloaded from the ABB
Web site www.abb.com/substationautomation.
615 series 13
IEC 61850 Engineering Guide
Introduction 1MRS756475 Q
1.4.1 Symbols
The caution icon indicates important information or warning related
to the concept discussed in the text. It might indicate the presence
of a hazard which could result in corruption of software or damage to
equipment or property.
The information icon alerts the reader of important facts and conditions.
The tip icon indicates advice on, for example, how to design your project
or how to use a certain function.
14 615 series
IEC 61850 Engineering Guide
1MRS756475 Q IEC 61850 overview
The IEC 61850 standard specifies an expandable object-oriented data model and
wide set of protocol services for substation automation (standard parts 7-x). The
standard does not specify any protection or control functions, but specifies how
the functions expose their information to a communication network.
615 series 15
IEC 61850 Engineering Guide
IEC 61850 overview 1MRS756475 Q
MMS
Real-time
communication
3 TCP
IP
Ethernet link layer
Ethernet physical layer with priority tagging (100 Mbit/s)
1 Abstract communication services 3 ISO/OSI stack
interface (ACSI)
2 Stack interface
Figure 3: Communication stacks and mapping used in IEC 61850
16 615 series
IEC 61850 Engineering Guide
1MRS756475 Q PCM600 tool
3 PCM600 tool
Protection and Control IED Manager PCM600 offers all the necessary functionality
to work throughout all stages of the protection relay life cycle.
• Planning
• Engineering
• Commissioning
• Operation and disturbance handling
• Functional analysis
The whole substation configuration can be controlled and different tasks and
functions can be performed with the individual tool components. PCM600 can
operate with many different topologies, depending on the customer needs.
PCM600 is used to conduct complete engineering and configuration activities
needed for the bay level protection relays.
Connectivity Packages are separate software packages that provide type and
version information to PCM600. Further Connectivity Packages assist the tool with
communications.
PCM600 uses IEC 61850 over Ethernet to communicate with bay devices. This
communication allows PCM600 to configure and monitor the devices. In addition
to IEC 61850 the devices have optional communications protocols and hardware
to connect to station engineering tools. PCM600 provides the ability to export the
configuration of the devices or an entire substation in a standard file format which
enables station engineering in separate IEC 61850 System Configuration tools.
A PC with PCM600 can be connected to any 615 series protection relay within a
station by using the Ethernet connection. The connection can also be used for
service and maintenance purposes. In addition, the connection is used to handle
disturbance records from the protection relays.
The modern-day protection relays are designed using the concept of the IEC 61850
standard. This is primarily in regards to how functions within the protection relay
are modelled and how the protection relay is represented in the substation. See
the IEC 61850 parameter list for the list of logical nodes available in the protection
relay and observe how they follow the structure and rules as defined in part 7 of the
standard.
The engineering of the used communication protocols is a separate task and an
addition to the engineering of protection and control functions.
PCM600 can be used for different purposes throughout the protection relay life
cycle. A set of special tools is available for different applications.
The applications can be organized into groups.
• Relay engineering
• Communication engineering
• Record management
• Device monitoring and diagnostic
615 series 17
IEC 61850 Engineering Guide
PCM600 tool 1MRS756475 Q
18 615 series
IEC 61850 Engineering Guide
1MRS756475 Q 615 series data model
615 series 19
IEC 61850 Engineering Guide
615 series data model 1MRS756475 Q
All generic functionality, such as modelling of physical inputs and outputs as well as
the alarming LED functionality, resides under logical device LD0. A full description
of the protection relay's data model is available in the parameter list.
During system engineering in the system configuration tool, do not
delete or rename logical devices, logical nodes, data objects or data
attributes in the IEC 61850 data model.
20 615 series
IEC 61850 Engineering Guide
1MRS756475 Q 615 series data model
Each protection relay can communicate to five separate clients to receive events,
read or write data (an active PCM600 connection is considered to be a client).
The protection relay can report data in either buffered or unbuffered mode and
execute direct or select-before-operate control sequences according to the control
commands sent by the client.
The protection relays are also capable of horizontal or peer-to-peer communication.
They can be programmed to publish (send) information to and subscribe (receive)
information from other devices according to IEC 61850-8-1 and IEC 61850-9-2 LE.
IEC 61850 standard Edition 2 increased several identification string lengths which
affect communication engineering and interoperability. The table lists identification
length values to be considered especially with third party tools. ABB tools generally
check the length values.
Table 2: Number of control block data sets and size of data sets
615 series 21
IEC 61850 Engineering Guide
615 series data model 1MRS756475 Q
22 615 series
IEC 61850 Engineering Guide
1MRS756475 Q 615 series data model
The protection relay does not support defining data on data attribute
level for data sets used for vertical reporting. Only data object level is
allowed.
615 series 23
IEC 61850 Engineering Guide
615 series data model 1MRS756475 Q
GOOSE communication has its own diagnostic counters. See Chapter 5.7.4
Diagnostic counters for information on diagnostic counters used in GOOSE
communication.
24 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
5 GOOSE
615 series 25
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
subnetwork in a GOOSE message. The GOOSE control block links the data set and
its attributes to actual data.
26 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
The IED can send single binary, double binary, integer and floating point
data values with a quality attribute. A quality attribute is used at the
receiver side to check data validity.
615 series 27
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
5.3.2.1 Creating a GOOSE data set with IEC 61850 Configuration tool
The sending data set is defined with the GOOSE control block. With the IEDs of
this product series, the sending GOOSE data set can have a maximum of 20 data
attributes to minimize the message-handling load in the receiving and sending
IEDs.
All data sets must be configured under the logical node LLN0 and must be provided
with names unique within the IED. The IEDs allow a maximum of four GOOSE
control blocks, which effectively limits the IED to four data sets for GOOSE, as there
is a one-to-one correspondence between the GOOSE control blocks and GOOSE
data sets. Typically, it is sufficient to define a single data set and control block
for an application. However, it is recommended to use a separate data set and
corresponding control block for analog values.
1. Select the target IED in the Plant Structure view.
2. Select GOOSE Communication in the drop-down box on the toolbar.
28 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
4. To add a new data set, right-click the area containing the data set names and
select New.
5. Define the LN where the data set is to be placed (accept preselected “ LD0/
LLN0”) and give the data set a unique name.
615 series 29
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
The received GOOSE data set can contain signals on the data attribute or data
object level. Data object level GOOSE entries can only be received of the following
CDC types: SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Other CDC types
can be connected to application only when dataset is defined in attribute level.
Defining GOOSE data set entries with IEC 61850 Configuration tool
1. Select the Data Sets tab.
30 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
3. In the Data Set Entry window, select the data attribute or data object present
in the data set.
• Click Append selected to add the data to the end of the data set. To add a
data object level entry, select it from the FC section. To add a data attribute
level entry, select it from the DA section
• Click Insert selected to add the data above the selected row in the data set
entries list.
• To remove a data from the data set, select the data in the data set entries
pane and click Remove selected.
615 series 31
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
32 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
3. To add a new GOOSE control block, right-click the area containing the existing
GOOSE control blocks and select New.
4. Browse to LLN0 under LD0 to define where the GOOSE control block is to be
placed.
615 series 33
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
34 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
6. In the Data set drop-down list, select the previously created data set to link
with the GCB.
Data set entries in a data set linked to the GCB can be modified from
the GOOSE control block tab by selecting Data Set details in the
shortcut menu.
7. Edit the properties and addresses of the created GOOSE control block.
Edit at least MAC Address and APP ID.
615 series 35
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
36 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
With the IEDs of this product series, only t(max) is configurable, not
t(min).
The multicast MAC address is usually unique, and APP-ID must be unique.
615 series 37
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
1 Subscriber 1 3 Publisher
2 Subscriber 2
Figure 15: GCB client editor showing the senders and receivers
In the Data Sets tab and the GOOSE Controls tab, the
Clients column shows all the configured IEDs. For the IED
without data sets and GCBs, however, there is no check
box in the grid matrix since the IED publishes the GOOSE
control block to the network.
In the Data Sets tab, the clients are mapped
automatically to the corresponding data sets based on
38 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
PCM600
Export Import
SCD
Create
file
ABB
IET600
devices
Configure GOOSE
Third party publisher and
device Export
subscriber
ICD
file Import Export
SCD file
Import
Third party
PCM600
device
Configure
GOOSE Configure
inputs
615 series 39
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
5.4.1 Defining devices and exporting the SCD file for IET600
Use PCM600 to define the substation and the devices. Before starting the system
engineering, configure the device in PCM600.
For more information, see PCM600 documentation.
4. Click Export.
40 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
615 series 41
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
42 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
The protection relay can send single binary, double binary, integer and
floating point data values with a quality attribute. A quality attribute is
used at the receiver side to check data validity.
615 series 43
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
4. To add a new data set, right-click the area containing the data set names and
select Insert new row the shortcut menu.
5. Define the LN where the data set is to be placed (accept preselected “ LD0/
LLN0”) and give the data set a unique name.
After creating the GOOSE data sets, define the data attributes for the data sets.
If quality data attributes are added to a data set, they must be located
after the status value of the corresponding data object.
The received GOOSE data set can contain signals on the data attribute or data
object level. Data object level GOOSE entries can only be received of the following
CDC types: SPS, SPC, ACD, ACT, DPS, DPC, INC, INS, ENC and ENS. Other CDC types
can be connected to application only when dataset is defined in attribute level.
44 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
• Click Insert > to add the data attribute above the selected row in the data
set entries list.
A maximum of 80 data attributes can be added in total to the IED's GOOSE data
sets. Recommendation is to divide the attribute amount to 20 per GOOSE data
set for maximum performance in sender/receiver.
Data set entries for vertical reporting are selected using the data
object level, and entries for GOOSE using the data attribute or data
object level.
After defining the data entries for the data sets, configure the GOOSE control block
properties.
615 series 45
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
3. To add a new GOOSE control block, right-click the area containing the existing
GOOSE control blocks and select Insert new row.
4. Browse to LLN0 under LD0 to define where the GOOSE control block is to be
placed.
5. Give a unique name to the GOOSE control block.
46 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
6. In the Attached Dataset drop-down list, select the previously created data set.
7. Edit the GOOSE control block properties and addresses. Edit at least MAC
Address and APP-ID.
To set the visibility of the GoCB columns, click the upper-left icon of
the table and select or clear the check boxes in the Field Chooser
dialog.
615 series 47
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
48 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
The multicast MAC address is usually unique, and APP-ID must be unique.
615 series 49
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
50 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
3. Go to the Project Explorer view and select the Plant Structure tab.
4. Right-click the project and select Import.
615 series 51
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
6. In the SCL Import Options dialog box under IED Types, select Don't import
IEDs of unknown type if the GOOSE configuration does not include thirdparty
devices.
7. Click Import.
For more information, see PCM600 documentation.
52 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
615 series 53
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
6. In Signal Matrix in the GOOSE sheet, map the GOOSE publisher data into the
corresponding GOOSERCV function block.
The columns in the GOOSE sheet represent publisher data and the rows
represent the possible subscriber input point.
The GOOSE receiver block output VALID defines the validity for the
received data. The value is based on the received quality attribute
value or communication status. This validity information can be used
in the application to build the validity logic in addition to the GOOSE
default supervision information.
During the protection relay start-up phase, the protection relay
keeps the value of the output VALID as “1” until the communication
is activated. After the communication is activated, the value
of the output VALID is updated by the value received via the
communication.
If the data type does not match with the GOOSERCV function block,
the attribute cell is red.
In Signal Matrix, the received GOOSE data can be directly connected to the
relay application. The GOOSE inputs are shown on the Binary or Analog Inputs
sheets and they can be connected to the application receiver function blocks.
The columns represent publisher data and the rows represent the possible
subscriber input points.
If the data type, for example timestamp, is not supported by the relay
application, the attribute column is red. The quality attribute is automatically
incorporated in the application with the status value, and it is not seen in Signal
Matrix.
7. Save the changes made in Signal Matrix.
8. Write to the IED.
54 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
When the protection relay uses IEC 61850 Edition 2, the Test quality bit is active in
the sender if the relay is set to test mode. When the relay uses IEC 61850 Edition 1,
the Test field in GOOSE message is also set when in test mode.
When the GOOSE sender is in test mode and the GOOSE receiver is not, in Edition 1
mode the GOOSE receiver freezes to its previous valid state, and in Edition 2 mode
the data value is defaulted and the quality set to invalid.
The Test bit is active in the sender if the protection relay is set to test mode.
See the technical manual for more information on the test mode.
The GOOSE frame is also not accepted if ConfRev deviates from the one in the
configuration. These error situations can be observed in the GSELPRT1 diagnostic
counters.
The default GOOSE input value is “0” for all the data types. The functionality is
analogous to physically wired galvanic Normally Open (NO) contacts where the
disconnected signal gives value “0” of FALSE to relay application. The application
must be designed to withstand the default value. This value is used when the
subscribed GOOSE data is not valid, or it is not received from the network and the
peer device is considered to be in a time-out state.
If a peer device sends the data including the quality attribute, the receiver device
input object is not updated according to the received status value if the data quality
is bad, questionable or blocked. The default value is also used in this case.
615 series 55
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
56 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
615 series 57
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
TRUE
Receiver Timeout
Counter +1
Needs TRUE Needs
Commissioning Commissioning
Counter +1 ?
FALSE
TRUE Configuration
Configuration Revision
Revision
Mismatch Counter +1
Mismatch?
FALSE
FALSE
Target Data Value Is
Defaulted and Quality Set
To Invalid. Alarm Is Set
To TRUE
TRUE State or Sequence
Number Not As
Expected?
State or Sequence FALSE
Number Error Counter
+1
TRUE
Same State Number As
Previous Message?
FALSE
TRUE
IEC 61850 Edition 2?
FALSE
Test Diagnostic
Counter +1
TRUE
Device In Test
Mode?
FALSE
58 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
FALSE
Value is followed by
quality attribute?
TRUE
TRUE
FALSE
TRUE
Bad quality=
Target data value is TRUE INVALID | RESERVED |QUESTIONABLE |
defaulted and quality set Quality is bad? OVERFLOW | OUT-OF-RANGE | BAD-
to invalid. REFERENCE | OSCILLATORY | FAILURE
| INCONSISTENT | INACCURATE
FALSE
TRUE
TRUE
Operator blocked? Old data?
FALSE FALSE
FALSE
Figure 37: Receiving GOOSE data with quality in the protection relays
615 series 59
IEC 61850 Engineering Guide
GOOSE 1MRS756475 Q
Force value
GOOSERCV_BIN
60 615 series
IEC 61850 Engineering Guide
1MRS756475 Q GOOSE
Tests
Function tests
Current protection
PHPTUC1 [3I<(1),37(1)]
Reset
Activate START
Deactive START
Activate OPERATE
Deactive OPERATE
615 series 61
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
62 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
Use correct Ethernet connectors in the IED with HSR. IEDs with HSR
support have three Ethernet connectors and redundant Ethernet ports
are marked as LAN A and LAN B. The third Ethernet port without any LAN
A or LAN B marking is an interlink port which is used as a redundancy box
connector. However, RED615 with HSR/PRP support does not implement
an interlink port.
Primary Secondary
IEEE 1588 v2 IEEE 1588 v2
master clock master clock
(optional)
IEC 61850
HSR
SMV traffic
Backup 1588
master clock
Figure 40: Recommended HSR reference topology with SMV and IEEE 1588 v2
The maximum number of IEDs supported in the HSR ring is 30. This is to
keep the ring delay as small as possible for horizontal applications.
The IED interlink port does not support IEEE 1588 v2 slave devices.
615 series 63
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
The IED interlink port does not support IEEE 1588 v2 slave devices.
Primary Secondary
IEEE 1588 v2 IEEE 1588 v2
master clock master clock
(optional)
IEC 61850
Managed
PRP Managed
Ethernet switch Ethernet switch
SMV traffic
Backup
IEEE 1588 v2
master clock
Figure 41: Recommended PRP reference topology with SMV and IEEE 1588 v2
64 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
• It is recommended to use IEEE 1588 v2 devices with the same clock mode (one-
step or two-step) within one network. Ethernet switches performing one-step to
two-step conversions should be avoided due to additional inaccuracy.
• One SMV publisher generates around 5 Mbit/s traffic to the network. This is
about 5 % of bandwidth in PRP and 10 % in HSR when the bandwidth of the used
network is 100 Mb/s.
615 series 65
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
The default data set for SMV sending is fixed and should not be
modified.
Due to the high time accuracy requirement of SMV the used time synchronization
method must be IEEE 1588 v2. PTP priorities of IEDs and other IEEE 1588 v2
devices in the network need to be configured properly (smaller value means highest
priority) for best master clock algorithm in 1588. External accurate master clocks
must be set with highest priority and if the IED is selected as backup, master clock
priorities should be set accordingly in all IEDs.
Some network routers can block 1588 traffic. Check that all devices using
1588 time synchronization utilize the same master clock.
SMV data set and SVCB should not be manually added or removed with other tools.
66 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
The SMV sender and the possible SMV receiver IEDs become visible.
3. Edit the properties and addresses of the sampled value control block.
615 series 67
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
68 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
615 series 69
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
2. In the IED Capabilities tab, check the Override for Client Service
SampledValues box to adjust the IED615 option to support sampled values
services.
3. Edit the properties and addresses of the sampled value control block.
70 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
615 series 71
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
SMVRCV ULTVTR1
UL1 UL1 ALARM ULTVTR1_ALARM
UL2 UL2 WARNING ULTVTR1_WARNING
UL3 UL3
Uo MINCB_OPEN
O:146|T:2,5|I:1 O:147|T:2,5|I:1
RESTVTR1
Uo ALARM RESTVTR1_ALARM
WARNING RESTVTR1_WARNING
O:148|T:2,5|I:1
Figure 51: Receiving all phase voltages and residual voltage using SMV
Synchrocheck function requires and uses only single analog phase voltage (UL1)
connected to ULTVTR2.
SMVRCV ULTVTR2
UL1 UL1 ALARM ULTVTR2_ALARM
UL2 MINCB_OPEN WARNING ULTVTR2_WARNING
UL3 O:147|T:2,5|I:2
Uo
O:146|T:2,5|I:1
Figure 52: Receiving line voltage for synchrocheck functionality using SMV
72 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
Figure 53: Application Configuration tool logic example for the SMV applications
The receiver activates the TxTR WARNING and ALARM outputs if any of the quality
bits, except for the derived bit, is activated. When the receiver is in the test mode,
it accepts SMV frames with test bit without activating the TxTR WARNING and ALARM
outputs.
The TxTR WARNING in the receiver is activated if the synchronization accuracy of the
sender or the receiver is worse than 4 µs. The output is held on for 10 seconds after
the synchronization accuracy returns within limits.
The TxTR ALARM in the receiver is activated if the synchronization accuracy of the
sender or the receiver is unknown, worse than 8 ms in 50 Hz mode and 6,7 ms in 60
Hz mode or two or more consecutive frames are lost. The output is held on for 10
seconds after the synchronization accuracy returns within limits.
Quality of received SMV is available as outputs in SMV measurement function block
and not propagated directly to protection function blocks along with the SMV
measurement values. To handle situations where SMV is not available, its quality
is not good or there is an issue with time synchronization, the WARNING and ALARM
outputs of SMV measurement function blocks must be connected to application,
for example to block directional protection.
615 series 73
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
Modify only MAC address, VLAN ID and sampled value ID to keep the 9-2
LE compliancy. Leave the others as default.
74 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
-
8.000 8.
000
-
8.000 8.
000
-
8.000 8.
000
TxTR ALARM activates when two or more consecutive SMV frames are lost or late.
A single loss of frame is corrected with a zero-order hold scheme. The effect on
protection is considered negligible in this case and it does not activate the TxTR
WARNING or ALARM outputs.
615 series 75
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
Number Maximum signal Internal Store Queue Addition Theoretical max sum Recommended max
of hops processing delay switch and latency al of delays (µs) delay setting (ms)
in (µs) 1 latency forward (µs) 2, 3 tolerance
network (µs) 2 latency 4
50Hz 60Hz (µs) 2 50Hz 60Hz 50Hz 60Hz
50 2 0.23 0.94
3 1.48 2.19
5 2.73 3.44
6 3.98 4.69
7 5.23 5.94
60 2 0.18 0.78
3 1.22 1.82
4 2.26 2.86
5 3.3 3.91
6 4.35 4.95
1 Signal processing delay of SMV sender, REF615 5.0 FP1 5.1.20 used as example. Depends on
merging unit used.
2 Latencies are totals over the number of hops and they are calculated for 100 Mbit full-duplex
Ethernet network.
3 Queue latency calculated when the port has started to send a full-sized frame (1500 bytes)
before the SMV frame and the switch has been configured to prioritize SMV
4 Additional tolerance in case of long wires or disturbance in network.
5 Average values, variation is ±0.1 ms
76 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
Time
The time parameters are found via menu path Configuration > Time.
In IEEE 1588 v2, the PTP domain is a logical grouping of clocks that synchronize to
each other using the protocol but that are not necessarily synchronized to clocks in
another domain.
PTP priority 1 and PTP priority 2 are used in the execution of the best master clock
algorithm in which lower values take precedence. Priority 1 is the first one used to
decide the clock master.
615 series 77
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
Description Value
Sync source IEEE 1588 master
IEEE 1588 slave
Sync status Up
Down
Sync accuracy 0...26 bits
Bits Accuracy
21 0.5 µs
20 1 µs
19 2 µs
18 4 µs
17 8 µs
11 0.5 ms
10 1 ms
9 2 ms
8 4 ms
7 8 ms
1 0.5 s
0 1s
Description Value
Grandmaster Identity
Grandmaster time src Atomic clock
GPS
Terrestrial radio
Table continues on the next page
78 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
Description Value
PTP
NTP
Hand set
Other
Internal oscil.
Grandmaster accuracy
Within a domain, grandmaster is the clock that is the ultimate source of time for
clock synchronization using the PTP protocol.
Grandmaster identity indicates the identity of the master clock.
Grandmaster time src indicates the source of time used by the grandmaster clock.
Grandmaster accuracy indicates the accuracy of the grandmaster clock.
Description Value
SMV synch accuracy No sync
Local clock
Global clock
Local synch accuracy
Max Dev Sync Acc
SMV synch accuracy value ”No sync” indicates that the SMV is either not in use or
it does not use IEEE 1588 v2. The clock synchronization is locally synchronized to
the grandmaster clock with parameter value “Local clock” and to the GPS clock with
parameter value “Global clock”.
Local synch accuracy indicates the time synchronization accuracy in microseconds.
Max Dev Sync Acc indicates the maximum clock deviation in situation where clock
accuracy was over 4 µs.
615 series 79
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
Parameter Value 5
Delay Mechanism P2P
VLAN priority mandatory (default=4)
Ethertype 0x88f7
Announce period 1s
Sync period 1s
Pdelay period 1s
PTP mode transparent
5 Some devices use the standard notation format 2x[s] of IEEE 1588 v2 intervals. The values in this
table are in [s] format.
80 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Process bus and IEEE 1588 time
synchronization
615 series 81
IEC 61850 Engineering Guide
Process bus and IEEE 1588 time 1MRS756475 Q
synchronization
82 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
7.1.1 Adding new IEC 61850 clients for IEC 61850 Configuration
tool
Adding a new IEC 61850 client to a PCM600 project is a two-step operation. First, a
new generic IEC 61850 IED object must be created under the plant structure and the
relevant client ICD or CID file must be imported to the generic IEC 61850 IED.
1. Right-click a bay node in the project plant structure, point to New, then point to
Generic IEC61850 IEC and select IEC61850 IED.
615 series 83
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
4. Select a valid Client SCL file (ICD or CID) and click Open in the file selection
dialog box.
5. In the SCL Import Options dialog box, select Ignore PCM Object Type and then
click Import.
84 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
The newly added client should be present in the Clients column along with other
clients in both the Data Set tab and the Report Controls tab.
9 10
615 series 85
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
When the engineering mode is enabled, SCD files from external IEC
61850 engineering tools cannot be imported into PCM600.
86 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
615 series 87
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
5. Right-click the area containing the data set names and select New to add a new
data set.
6. In the Create New Data Set dialog box, define the LN where to place the data
set (accept preselected “LD0/LLN0”) and give the data set a unique name.
88 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
After creating the GOOSE data sets, define the data set entries (data attributes or
data objects) for the data sets.
615 series 89
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
3. In the data set entry window, select the data attribute to be contained in the
data set.
• Click Append selected to add the data attribute to the end of the data set.
• Click Insert selected to add the data attribute above the selected row in the
data set entries list.
• To remove a data attribute from the data set, select the data attribute in the
data set entries pane and click Removed selected.
Reporting datasets can include status and measurement type of data. Also
configuration and setting values can be added to datasets in case required.
Data set entries for vertical reporting are selected using
the data object level, and entries for GOOSE using the
data attribute or data object level.
The default data set for SMV sending is fixed and may not
be modified.
90 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
4. Browse to LLN0 under LD0 to define where to place the report control block.
5. Give a unique name to the report control block.
615 series 91
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
6. In the drop-down list, select the previously created data set to link with the
RCB.
7. Edit the properties and options of the created report control block.
92 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
Data set entries in a data set linked to the GCB can be modified from the
RCB Control Block tab by selecting the Data Set Details in the shortcut
menu.
615 series 93
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
PCM600
1. In the Plant Structure, click the IED node which is RCB server.
2. Click Report Controls tab.
The rows of the Report Controls window show RCBs configured for the IED.
The columns of the Report Controls window show the RCB clients configured in
the PCM600.
3. To add or remove clients for a report control block, click the check-box in the
grid, corresponding to the client and RCB.
Five clients at the maximum can be connected to a RCB.
1 2
94 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
PCM600
615 series 95
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
IET600
96 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
IET600
615 series 97
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
IET600
4. Type the name of the client IED as it is in the file to be imported. Click OK.
98 615 series
IEC 61850 Engineering Guide
1MRS756475 Q Engineering of event reporting with
IET600
6. In the file selection dialog box, select any valid SCL file that is SCD, ICD, CID or
IID, and click Open.
IET600 automatically matches IEDs with the same name in IET600 and in the
file.
7. Click OK to import the IED from the file.
615 series 99
IEC 61850 Engineering Guide
Engineering of event reporting with 1MRS756475 Q
IET600
3. In the Subnetworks grid, select the bus from the Subnetwork list to attach the
IEC 61850 client to the bus.
An alternative way is to drag the client in the Communication tab to the correct
subnetwork.
Figure 73: Defining bus connection properties for IEC 61850 clients
4. Repeat the steps to attach all five default clients in the project to the bus.
By default, the IEDs' bus connections are ready-made when the configuration work
is started and need not to be set separately. After the client bus connections are
created, the event clients appear in the RCB Clients tab.
1 2 3 4 5
1 Menu on the top of the user 4 Editors for detailed design and
interface engineering of the substation, IEDs
2 Navigation pane for context- and IEC 61850 communication
oriented navigation and filtering 5 Logging and messaging (output)
the various editors panel
3 Properties pane for detailed
properties of the selected element
in the navigation pane
Figure 74: IET600 user interface
Choose upper or lower level in the structure to see the data of single,
many or all IEDs at the same time in the editor pane.
2. Select or clear the check boxes from the Field Chooser dialog box.
1 2 3
Data set entries for vertical reporting are selected using the data object
level, and entries for GOOSE using the data attribute or data object level.
Deleting an RCB does not remove it from IET600. Instead, its status is
set to “Deleted” and it is not exported to SCL files. Removing a data set
automatically puts the related RCB to the “Deleted” state.
1. Configure the default clients which are used by the rule-based RCB generation
to automatically configure RCB clients.
Use buttons on the RCB client editor.
9 Glossary
615 series Series of numerical protection and control relays for protection and su-
pervision applications of utility substations, and industrial switchgear
and equipment
ACSI Abstract communication service interface
APDU Application protocol data unit
APPID Application identifier
CID Configured IED description
COM600S Substation Management Unit. An all-in-one communication gateway, au-
tomation platform and user interface solution for utility and industrial
distribution substations.
COMTRADE Common format for transient data exchange for power systems. Defined
by the IEEE Standard.
Connectivity A collection of software and information related to a specific protection
package and control IED, providing system products and tools to connect and
interact with the IED
CT Current transformer
CTRL Control logical device
Data attribute Defines the name, format, range of possible values and representation of
values while being communicated
Data set The content basis for reporting and logging containing references to the
data and data attribute values
DR Disturbance recorder
EMC Electromagnetic compatibility
Ethernet A standard for connecting a family of frame-based computer networking
technologies into a LAN
FC Functional constraint
FTP File transfer protocol
GCB 1. GOOSE control block 2. Generator circuit breaker
GoCB GOOSE control block
GoID GOOSE control block-specific identifier
GOOSE Generic Object-Oriented Substation Event
GPS Global Positioning System
HMI Human-machine interface
HSR High-availability seamless redundancy
ICD IED capability description
IEC International Electrotechnical Commission
IEC 61850 International standard for substation communication and modeling
IEC 61850-8-1 A communication protocol based on the IEC 61850 standard series
Table continues on the next page
IEC 61850-9-2 A communication protocol based on the IEC 61850 standard series
IEC 61850-9-2 LE Lite Edition of IEC 61850-9-2 offering process bus interface
IED Intelligent electronic device
IET600 Integrated Engineering Toolbox
IID Instantiated IED description
LD0 Logical device zero (0)
LE Light Edition
LED Light-emitting diode
LHMI Local human-machine interface
LLN0 Logical node zero (0)
LN Logical node
MAC Media access control
MicroSCADA Substation automation system
MMS 1. Manufacturing message specification 2. Metering management system
Modbus A serial communication protocol developed by the Modicon company in
1979. Originally used for communication in PLCs and RTU devices.
Multicast ad- An identifier for a group of hosts that have joined a multicast group
dress
NTP Network time protocol
P2P peer-to-peer
PCM600 Protection and Control IED Manager
PRP Parallel redundancy protocol
PTP Precision Time Protocol
RCB Report control block
SCADA Supervision, control and data acquisition
SCD Substation configuration description
SCL XML-based substation description configuration language defined by IEC
61850
SMV Sampled measured values
ST Connector type for glass fiber cable
SVCB Sampled value control block
TAL Time allowed to live
TCP/IP Transmission Control Protocol/Internet Protocol
VLAN Virtual LAN
VT Voltage transformer
XML Extensible markup language
www.abb.com/mediumvoltage
www.abb.com/relion
www.abb.com/substationautomation
1MRS756475 Q