0% found this document useful (0 votes)
24 views

NLCC - ST CL

1. The document provides calculations for the reactions at joints of columns for a dryer offgas cleaning system main structure. 2. Loads considered include dead load, equipment load, live load, wind load, and seismic load. 3. Reaction forces are calculated at each of 4 points (P1, P2, P3, P4) in the X, Y, and Z directions for each load case. The largest reaction forces occur at the base of the structure (P1 and P2).

Uploaded by

Anh Ky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
24 views

NLCC - ST CL

1. The document provides calculations for the reactions at joints of columns for a dryer offgas cleaning system main structure. 2. Loads considered include dead load, equipment load, live load, wind load, and seismic load. 3. Reaction forces are calculated at each of 4 points (P1, P2, P3, P4) in the X, Y, and Z directions for each load case. The largest reaction forces occur at the base of the structure (P1 and P2).

Uploaded by

Anh Ky
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

PROJECT CODE : 719002

Calculation Sheet for DOCUMENT NO. : CAL-1-004-C-0001


Dryer Offgas Cleaning System
DATE : 05/09/2023
- Main Structure
REV :1
COLUMN REACTIONS - STAIR COLUMN
I. INPUT DATA
1. Building Description
Length LF = 36.3 m
Width L= 27.224 m
Height of column H= 18.566 m
Roof Slope i= 0 %
Building type Open Buildings
2. Design Load
Dead Load See calculation sheet
Live Load See calculation sheet
Equipment Load See calculation sheet
Wind load See calculation sheet
Wind Speed 40.00 m/s Exposure C
Seismic Load See calculation sheet
3. Application Codes
The Loads and Deflection Limits MBMA-2012
Structural Steel Design AISC/LRFD 360-10
* Reaction Force of Windload is at 50years, 3s.
II. JOINT REACTIONS
Elv +0.400

1. Sign Convention
Z

X
I Section U Section
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-004-C-0001
Dryer Offgas Cleaning System
DATE : 05/09/2023
- Main Structure
REV :1
COLUMN REACTIONS - STAIR COLUMN
2. Reactions
Horizontal Horizontal Vertical Moment Moment Moment
Joint OutputCase
Reaction Hx Reaction Hy Reaction Vz Mx My Mz
Text Text KN KN KN KN-m KN-m KN-m
Point-P1 Dead Load (D+SD) -0.1 0.3 88.9 0.0 0.0 0.0
Point-P1 Equipment Load (E) -0.1 0.2 153.7 0.0 0.0 0.0
Point-P1 Live Load 1 (L1) 0.0 0.1 20.3 0.0 0.0 0.0
Point-P1 Live Load 2 (L2) 0.0 0.1 3.8 0.0 0.0 0.0
Point-P1 Live Load 3 (L3) 0.0 0.1 7.2 0.0 0.0 0.0
Point-P1 Wind Load X+ direction (WX(+)) -4.3 0.0 -6.2 0.0 0.0 0.0
Point-P1 Wind Load X- direction (WX(-)) 4.2 0.0 6.1 0.0 0.0 0.0
Point-P1 Wind Load Y+ direction (WY(+)) 0.3 -3.4 -241.6 0.0 0.0 0.0
Point-P1 Wind Load Y- direction (WY(-)) -0.3 3.4 241.6 0.0 0.0 0.0
Point-P1 Seismic Load X+ direction (SX(+)) -31.7 0.2 -75.2 0.0 0.0 0.0
Point-P1 Seismic Load X- direction (SX(-)) 31.7 -0.2 75.2 0.0 0.0 0.0
Point-P1 Seismic Load Y+ direction (SY(+)) -0.1 -26.1 -2576.4 0.0 0.0 0.0
Point-P1 Seismic Load Y- direction (SY(-)) 0.1 26.1 2576.4 0.0 0.0 0.0
Point-P2 Dead Load (D+SD) -0.1 0.3 91.3 0.0 0.0 0.0
Point-P2 Equipment Load (E) -0.1 0.2 147.6 0.0 0.0 0.0
Point-P2 Live Load 1 (L1) 0.0 0.1 22.5 0.0 0.0 0.0
Point-P2 Live Load 2 (L2) 0.0 0.1 3.5 0.0 0.0 0.0
Point-P2 Live Load 3 (L3) 0.0 0.1 6.6 0.0 0.0 0.0
Point-P2 Wind Load X+ direction (WX(+)) -4.4 0.1 12.3 0.0 0.0 0.0
Point-P2 Wind Load X- direction (WX(-)) 4.3 -0.1 -12.1 0.0 0.0 0.0
Point-P2 Wind Load Y+ direction (WY(+)) 0.4 -3.6 -251.9 0.0 0.0 0.0
Point-P2 Wind Load Y- direction (WY(-)) -0.4 3.6 251.9 0.0 0.0 0.0
Point-P2 Seismic Load X+ direction (SX(+)) -32.9 0.6 153.2 0.0 0.0 0.0
Point-P2 Seismic Load X- direction (SX(-)) 32.9 -0.6 -153.2 0.0 0.0 0.0
Point-P2 Seismic Load Y+ direction (SY(+)) -0.2 -26.6 -2590.1 0.0 0.0 0.0
Point-P2 Seismic Load Y- direction (SY(-)) 0.2 26.6 2590.1 0.0 0.0 0.0
Point-P3 Dead Load (D+SD) 0.0 0.0 2.2 0.0 0.0 0.0
Point-P3 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P3 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Wind Load X+ direction (WX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Wind Load X- direction (WX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Wind Load Y+ direction (WY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Wind Load Y- direction (WY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P3 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Dead Load (D+SD) 0.0 0.0 2.2 0.0 0.0 0.0
Point-P4 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P4 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Wind Load X+ direction (WX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Wind Load X- direction (WX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Wind Load Y+ direction (WY(+)) 0.0 0.0 0.2 0.0 0.0 0.0
Point-P4 Wind Load Y- direction (WY(-)) 0.0 0.0 -0.2 0.0 0.0 0.0
Point-P4 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P4 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Dead Load (D+SD) 0.0 0.0 1.7 0.0 0.0 0.0
Point-P12 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P12 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Wind Load X+ direction (WX(+)) 0.0 0.0 -0.1 0.0 0.0 0.0
Point-P12 Wind Load X- direction (WX(-)) 0.0 0.0 0.1 0.0 0.0 0.0
Point-P12 Wind Load Y+ direction (WY(+)) 0.0 0.0 0.5 0.0 0.0 0.0
Point-P12 Wind Load Y- direction (WY(-)) 0.0 0.0 -0.5 0.0 0.0 0.0
Point-P12 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P12 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-004-C-0001
Dryer Offgas Cleaning System
DATE : 05/09/2023
- Main Structure
REV :1
COLUMN REACTIONS - STAIR COLUMN
Point-P12 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Dead Load (D+SD) 0.0 0.0 1.7 0.0 0.0 0.0
Point-P13 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P13 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Wind Load X+ direction (WX(+)) 0.0 0.0 -0.1 0.0 0.0 0.0
Point-P13 Wind Load X- direction (WX(-)) 0.0 0.0 0.1 0.0 0.0 0.0
Point-P13 Wind Load Y+ direction (WY(+)) 0.0 0.0 -0.4 0.0 0.0 0.0
Point-P13 Wind Load Y- direction (WY(-)) 0.0 0.0 0.4 0.0 0.0 0.0
Point-P13 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P13 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Dead Load (D+SD) 0.0 0.0 1.7 0.0 0.0 0.0
Point-P52 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P52 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Wind Load X+ direction (WX(+)) 0.0 0.0 -0.1 0.0 0.0 0.0
Point-P52 Wind Load X- direction (WX(-)) 0.0 0.0 0.1 0.0 0.0 0.0
Point-P52 Wind Load Y+ direction (WY(+)) 0.0 0.0 -0.2 0.0 0.0 0.0
Point-P52 Wind Load Y- direction (WY(-)) 0.0 0.0 0.2 0.0 0.0 0.0
Point-P52 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P52 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Dead Load (D+SD) 0.0 0.0 1.7 0.0 0.0 0.0
Point-P53 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P53 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Wind Load X+ direction (WX(+)) 0.0 0.0 -0.1 0.0 0.0 0.0
Point-P53 Wind Load X- direction (WX(-)) 0.0 0.0 0.1 0.0 0.0 0.0
Point-P53 Wind Load Y+ direction (WY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Wind Load Y- direction (WY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P53 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Dead Load (D+SD) 0.0 0.0 2.2 0.0 0.0 0.0
Point-P61 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P61 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Wind Load X+ direction (WX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Wind Load X- direction (WX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Wind Load Y+ direction (WY(+)) 0.0 0.0 -0.7 0.0 0.0 0.0
Point-P61 Wind Load Y- direction (WY(-)) 0.0 0.0 0.7 0.0 0.0 0.0
Point-P61 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P61 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Dead Load (D+SD) 0.0 0.0 2.2 0.0 0.0 0.0
Point-P62 Equipment Load (E) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Live Load 1 (L1) 0.0 0.0 2.5 0.0 0.0 0.0
Point-P62 Live Load 2 (L2) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Live Load 3 (L3) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Wind Load X+ direction (WX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Wind Load X- direction (WX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Wind Load Y+ direction (WY(+)) 0.0 0.0 -0.1 0.0 0.0 0.0
Point-P62 Wind Load Y- direction (WY(-)) 0.0 0.0 0.1 0.0 0.0 0.0
Point-P62 Seismic Load X+ direction (SX(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Seismic Load X- direction (SX(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Seismic Load Y+ direction (SY(+)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P62 Seismic Load Y- direction (SY(-)) 0.0 0.0 0.0 0.0 0.0 0.0
Point-P63 Dead Load (D+SD) -0.1 -0.1 86.4 0.0 0.0 0.0
Point-P63 Equipment Load (E) -0.1 -0.4 145.3 0.0 0.0 0.0
Point-P63 Live Load 1 (L1) 0.0 -0.1 18.1 0.0 0.0 0.0
PROJECT CODE : 719002
Calculation Sheet for DOCUMENT NO. : CAL-1-004-C-0001
Dryer Offgas Cleaning System
DATE : 05/09/2023
- Main Structure
REV :1
COLUMN REACTIONS - STAIR COLUMN
Point-P63 Live Load 2 (L2) 0.0 0.0 1.6 0.0 0.0 0.0
Point-P63 Live Load 3 (L3) 0.1 -0.1 5.1 0.0 0.0 0.0
Point-P63 Wind Load X+ direction (WX(+)) -5.2 0.0 -8.6 0.0 0.0 0.0
Point-P63 Wind Load X- direction (WX(-)) 5.1 0.0 8.5 0.0 0.0 0.0
Point-P63 Wind Load Y+ direction (WY(+)) -0.2 -3.2 249.5 0.0 0.0 0.0
Point-P63 Wind Load Y- direction (WY(-)) 0.2 3.2 -249.5 0.0 0.0 0.0
Point-P63 Seismic Load X+ direction (SX(+)) -40.7 -0.2 -101.5 0.0 0.0 0.0
Point-P63 Seismic Load X- direction (SX(-)) 40.7 0.2 101.5 0.0 0.0 0.0
Point-P63 Seismic Load Y+ direction (SY(+)) 0.3 -24.5 2636.5 0.0 0.0 0.0
Point-P63 Seismic Load Y- direction (SY(-)) -0.3 24.5 -2636.5 0.0 0.0 0.0
Point-P64 Dead Load (D+SD) -0.1 -0.1 88.8 0.0 0.0 0.0
Point-P64 Equipment Load (E) -0.1 -0.4 139.8 0.0 0.0 0.0
Point-P64 Live Load 1 (L1) 0.0 -0.1 21.1 0.0 0.0 0.0
Point-P64 Live Load 2 (L2) 0.0 0.0 1.6 0.0 0.0 0.0
Point-P64 Live Load 3 (L3) 0.1 -0.1 4.6 0.0 0.0 0.0
Point-P64 Wind Load X+ direction (WX(+)) -5.3 0.1 7.2 0.0 0.0 0.0
Point-P64 Wind Load X- direction (WX(-)) 5.3 -0.1 -7.2 0.0 0.0 0.0
Point-P64 Wind Load Y+ direction (WY(+)) -0.2 -3.4 259.7 0.0 0.0 0.0
Point-P64 Wind Load Y- direction (WY(-)) 0.2 3.4 -259.7 0.0 0.0 0.0
Point-P64 Seismic Load X+ direction (SX(+)) -42.1 0.8 99.2 0.0 0.0 0.0
Point-P64 Seismic Load X- direction (SX(-)) 42.1 -0.8 -99.2 0.0 0.0 0.0
Point-P64 Seismic Load Y+ direction (SY(+)) 0.4 -24.9 2651.0 0.0 0.0 0.0
Point-P64 Seismic Load Y- direction (SY(-)) -0.4 24.9 -2651.0 0.0 0.0 0.0