Power System Protection Lecture 2 Annotated
Power System Protection Lecture 2 Annotated
Lecture 2
Dr. Fattahi
Importance of Analyzing Symmetrical and Asymmetrical Components
Operator "a":
Dr. Fattahi
Symmetrical Components of a Three-Phase Fault
Dr. Fattahi
Symmetrical Components of a Three-Phase Fault
Note: Note:
Dr. Fattahi
Power System Fault
Conversion Between Phase and Symmetrical Example: The currents in a 3-phase unbalanced
Component Domains: system are:
The symmetrical components ( 0 , 1 , 2 ) can be
obtained from phase currents ( 0 , 1 , 2 ) using the 0 = (12 + 96); 1 = (12 912); 2 = ( 15 + 910)
following equation*s: A The phase sequence in abc. Calculate the zero,
1 positive and negative sequence components of the
0 = ( 0 + 1 + 2) currents.
3
1
1 ( 0 + 0 1 + 02 2 )
=
3
1 2
2 = ( 0 + 0 1 + 0 2)
3
The symmetrical components ( 0 , 1 , 2 ) can be
obtained from phase currents ( 0 , 1 , 2 ) using the
following matrix equation*s:
2 3 21 1 1 37 26 0 37
6 07 6
6 7 6 2 0 77 66 1 77
6 17 = 61 0
6 2 75 61 02 75 64 2 75
4 4 0
Where 0 = 4 9120 is the phase shift factor.
Dr. Fattahi
Power System Fault
Example: The sequence voltages in the A (red) Example: The zero and positive sequence
phase are as under: components of red phase are as under,
+0 = 100+; +1 = (200 9100)+; +2 = 100+. Find +00 = (05 90866) V; +10 = 2\0°V If the phase
the phase voltages +0 , +1 and +2 voltage +0 = 3\0°+, find the negative sequence
component of red phase and the phase voltages +1
and +2 . the currents.
Dr. Fattahi
Classification of Shunt Faults
Dr. Fattahi
Example of Phasor Diagram
Consider a fault occurring close to the distant end of a transmission line. Examining the phasor
diagram reveals that the voltage at the relay’s position during the fault is of lesser magnitude
compared to its value prior to the fault, and it is also lagging behind its pre-fault value. To maintain
clarity, the diagram displays only the voltage of phase a.
Dr. Fattahi
Voltages at the relay location during various faults
Dr. Fattahi