BACnet Protocol Implementation Conformance Statement (PICS)

Date: Jan 31, 2019


Vendor Name: LG Electronics
Product Name: AC Smart BACnet
Product Model Number: PACS5A000
Application Software Version: 1.0 Firmware Revision: 1.50.4 BACnet Revision: 12
Product Description: This gateway converts between BACnet/IP or Modbus TCP protocol and RS-485
LGAP (LG Aircon protocol) allowing third party control and monitoring of the LG A/C system. It has a
built in web server that does not require any additional software.

BACnet Standardized Device Profile (Annex L):


BACnet Operator Workstation (B-OWS)
BACnet Building Controller (B-BC)
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
BACnet Smart Senor (B-SS)
BACnet Actuator (B-SA)

BACnet Interoperability Building Blocks Supported (BIBBs)


Data Sharing BIBBs
Bibb Type Supported BACnet Service Initiate Execute
DS-RP-B Data Sharing-Read Property-B ReadProperty -

DS-RPM-B Data Sharing-ReadPropertyMultiple-B ReadPropertyMultiple -

DS-WP-B Data Sharing-WriteProperty-B WriteProperty -

DS-WPM-B Data Sharing-WritePropertyMultiple-B WritePropertyMultiple -

SubscribeCOV -

DS-COV-B Data Sharing-COV-B ConfirmedCOVNotification -

UnconfirmedCOVNotification -

Device Management BIBBs


Bibb Type Supported BACnet Service Initiate Execute
Device Management-Dynamic Device, Who-Is
DM-DDB-B
Binding-B I-Am - -
Device Management-Dynamic Object, Who-Has -
DM-DOB-B
Binding-B I-Have -
Device Management- -
DM-DCC-B DeviceCommunicationControl
DeviceCommunicationControl-B
Device Management- -
DM-TS-B TimeSynchronization
TimeSynchronization-B
Segmentation Capability:
Segmented requests supported Window Size - 1
Segmented responses supported Window Size - 64

Standard Object Types Supported:


Dynamically Dynamically Writable
Object-Type Optional Properties Supported
Creatable Deletable Properties
Description, Reliability, Min_Pres_Value,
Analog Input No No N/A
Max_Pres_Value, Resolution, COV_Increment
Description, Reliability, Priority_Array,
Analog Value No No Present_Value
Relinquish_Default, COV_Increment
Description, Reliability, Inactive_Text,
Binary Input No No N/A
Active_Text
Description, Inactive_Text, Active_Text,
Binary Output No No Present_Value
Priority_Array, Relinquish_Default
Description, Inactive_Text, Active_Text,
Binary Value No No Present_Value
Priority_Array, Relinquish_Default
Location, Description, UTC_Offset,
Profile_name, Daylight_Saving_Status,
APDU_Segment_Timeout,
Device No No N/A
Active_COV_Subscriptions,
Max_Segments_Accepted, Local_Date,
Local_Time
Multi-State Input No No Description, State_Text N/A
Multi-State
No No Description, State_Text Present_Value
Output

Data Link Layer Options:

BACnet IP, (Annex J)


BACnet IP, (Annex J), Foreign Device
ISO 8802-3, Ethernet (Clause 7)
ANSI/ATA 878.1, 2.5 Mb. ARCNET (Clause 8)
ANSI/ATA 878.1, RS-485 ARCNET (Clause 8), baud rate(s)
MS/TP Master (Clause 9), baud rate(s):
MS/TP Slave (Clause 9), baud rate(s):
Point-to-Point, EIA 232 (Clause 10), baud rate(s):
Point-to-Point, modem, (Clause 10), baud rate(s):
LonTalk, (Clause), medium:
Other:

Device Address Binding:


Is static device binding supported? (This is currently necessary for two-way communication with MS/TP slaves and
certain devices)
Yes No

Networking Options:
Router, Clause 6 - List all routing configurations, e.g., ARCNET-Ethernet, Ethernet-MS/TP, etc.
Annex H, BACnet Tunneling Router over IP
BACnet/IP Broadcast Management Device (BBMD)

Does the BBMD support registrations by foreign devices?


Yes No

Character Sets Supported:


Indicating support for multiple character sets does not imply that they can all be supported simultaneously.
ISO 10646 (UTF-8) IBM™ /Microsoft, DBCS ISO 8859-1
ISO 10646 (UCS-2) ISO 10646 (UCS-4) JIS C 6226

If this product is a communication gateway, describe the types of non-BACnet equipment/network(s) that the
gateway supports:
This gateway converts between BACnet IP or Modbus TCP protocol and RS-485 LGAP (LG Aircon protocol) allowing
third party control and monitoring of the LG A/C system.