HZ7411 Circuit Breaker Analyzer-User Manual
HZ7411 Circuit Breaker Analyzer-User Manual
Thank you for choosing HZ 7411 Circuit Breaker Dynamic Charac ter is tic
Tester.
We hope that this inst rum ent can mak e your work eas ier and more
enjoyable, so that you can get the feeling of office aut omat ion in the test
Bef ore us ing the inst rument , please read this manual, and oper at e and
maint ain the inst rum ent ac cording to the manual to pr olong its service lif e.
"Just a light pr ess, the test will be completed aut omat ically" is the
If you ar e sat isfied with this inst rum ent, please tell your colleagues;
if you ar e not satisf ied with this inst rum ent, please call (0312) 6775656 to
tell you to ser ve you at all times- Baoding Huazheng Elect ric Manufact uring
Co. , Lt d. , our company will def initely make you satisf ied !
Contents
II.Performance.....................................................................................................................3
III.Term definitions..............................................................................................................3
IV.Panel layout.................................................................................................................... 5
VI.Data query.................................................................................................................... 13
VII.Other settings..............................................................................................................14
VIII.Field connection........................................................................................................ 14
X.Packing List................................................................................................................. 20
1
I.Product technical parameters
1.1 Use environment
Input power:220V±10%,50Hz±10%
Atmospheric pressure:86~106kpa
Temperature::-10~40℃
Humidity:≦80%RH
Insulation resistance:>2MΩ
Dielectric strength: the power supply withstands the power frequency of the
1.3.1 Time
When the range is selected from 250-4000ms, the resolution is 0.1ms and the
error is 0.1ms ± 1 word; when the range is 10000-20000ms, the resolution is 1ms
1.3.2 Speed
1.3.3 Current
The range is 20A, the resolution is 0.01A, and the error is 1% ± 0.1A.
The range is 50-2000Ω, the resolution is 0.1Ω, and the error is% 1 ± 1Ω.
1.3.7 Stroke
Switch type Range(mm) Resolution(mm) Error
Vacuum circuit 50
breaker
SF6 circuit breaker 300 0.1 1%±1 word
Less oil circuit 1000
breaker
Table 1
2
II.Performance
2.1 Time
The machine can measure the natural parting and closing time of 12 metal
fractures, the same period time, the same period time, the same period time, the
gold short time, the no flow time, the closing spring time of the process of closing -
parting, dividing - parting and dividing - dividing; Some models can measure the
This tester can record and measure the closing bounce time, the number of
bounces, the bounce process, and the bounce waveform of each fracture.
This tester can record and calculate the rigid points, rigidity, maximum speed,
average speed, total travel, opening distance, over travel, rebound amplitude,
This tester can record the opening / closing current value and current waveform of
the opening / closing coil, and provides DC5 ~ 270V 20A digital circuit breaker
operation power supply, automatically completes the low voltage operation test of
the circuit breaker, and measures the open circuit. The operating voltage of the
device.
Some models of this machine can measure 6-way closing resistance value
III.Term definitions
♦ Opening / closing time: When the opening / closing coil is powered on as the
timing starting point, the time to the opening / closing of the moving and static
contacts.
♦ In the same period: Among the same phase, the difference between the
3
♦ Phase-to-phase synchronization: The difference between the maximum and
♦ Average speed: During the opening (closing) process, remove the front and back
of the moving contact by 10%, take the middle 80%, the ratio of the travel of the
♦ Maximum speed: During the opening (closing) process, after the moving contact
measurement unit every 10ms until the moving contact movement stops, and
several speed unit values are obtained. The speed value is the maximum speed
of opening (closing).
tested, the switch model is different, and each manufacturer defines different
rigid opening and closing speeds. This tester includes various different
10ms after opening before Certain oil switches and SF6 circuit
1
closing breakers
4
36mm before closing,
8 LW6 type SF6 circuit breaker
72mm after opening
Table 2
If none of the above definitions meet the current speed definition of the short
circuit being tested, the user can select the "Custom" option in the parameter
setting interface-speed definition option, enter and save a speed definition that
conforms to the rules. Alternatively, you can also choose a closer speed definition
to measure, and then manually cut out the required rigid opening / closing speed
IV.Panel layout
Figure 1
5
② switch socket
test
⑦ A1B1C1N
⑧ A2B2C2N
12 channels on / off time measurement channel
⑨ A3B3C3N
⑩ A4B4C4N
⑬ Grounding post
⑭ printer
⑮ LCD screen
screen. After booting, the LCD screen enters the home menu interface after
playing the boot animation. There are 6 function area buttons on the homepage,
6
Figure 2
The data measurement interface is divided into upper, middle, and lower 3
areas (see Figure 3). The upper display area of the screen displays the current
closing and opening status of the 12-way fracture in real time. The opening and
closing of the fracture is displayed in red and the opening is displayed in green.
The middle part of the screen is the test mode selection area, providing a
total of 8 test modes, which are "Auto Test", "Open Test", "Close Test", "Manual
Open and Close", "Open and Close Test", and "Open and Close Test". "," Open
and close, "and" low-voltage test. " In the automatic test mode, the instrument
automatically selects the opening test or the closing test according to the current
port status (the opening test is performed when 1 of the 12-way break is closed).
In the low-voltage test mode, the instrument automatically judges whether the low
trip or low trip occurs according to the current status of each fracture (the low trip
is performed when one of the 12 fractures is closed). The user can select the
corresponding test mode according to the test requirements and the current
fracture state. After clicking the mode button, it will automatically jump to the
7
Figure 3
At the bottom of the screen is a page-turning button area, which has three
buttons: "Back to Home", "Parameter Setting" and "Motor Energy Storage". Click
After clicking the "Parameter Setting" or "Test Mode" button, the screen jumps
When the selected test mode is one of "Auto test", "Open test", "Close test",
"Open and close test", "Close and open test" and "Open and close", the page
8
Figure 4
The operation interface is also divided into three areas: the fracture status
display area in the upper part, the parameter setting area in the middle part, and
the page turning button area in the lower part. The functions of the upper and
lower areas are similar to the mode selection interface and will not be described
again. It mainly introduces the selection and setting of each parameter in the
combined resistance contact and metal contact mode. The default is metal
contact.
♦ Trigger mode: The trigger mode is divided into two working modes: internal
trigger and external trigger. The internal trigger mode is to use the internal DC
power of the instrument to drive the on / off coil of the device under test. In the
external trigger mode, the internal DC source of the instrument does not
work, but the on / off coil of the device under test is driven by the on-site
power. The external voltage action signal is used as the timing starting point. This
parameter can only be selected in "Auto test", "Open test" and "Close test" modes,
♦ Speed definition: This parameter is used to define the calculation rules of rigid
9
opening / closing speed to meet the different requirements of different switch
manufacturers and models. This machine has built-in 10 common speed definition
modes and a custom mode that can be saved in case of power failure. If the
above method still can't find a satisfactory speed definition, you can first select the
"10ms before closing" mode, measure the "time-travel characteristic curve", and
speed value.
♦ Output voltage: Set the output operating voltage value according to the needs of
the field (it is invalid to set this item in external trigger mode).
♦ Sensor: The sensor needs to set three parameters: type, quantity and position.
Types include displacement and angle; the number defaults to 1 (some models
♦ Switch stroke: Enter the total stroke value of the switch when using the angle
sensor; enter the marked stroke value of the sensor when using the angle sensor.
♦ Test time: The total test time is the time of the internal DC power output voltage.
This time should meet a. When doing a single opening and closing test, it should
meet the inherent opening and closing time of the device under test; b. When
doing a re-closing test, it should meet the inherent opening and closing time that is
greater than the multiple actions of the device under test Sum of time.
♦ Reclosing time: This item needs to be set during reclosing test. The reclosing
and closing time is counted as T closing and closing, and the reclosing and closing
time is counted as T closing and closing. T opening and closing is the period of
time from powering on the opening coil to powering on the closing coil. T closing is
the period of time from powering on the closing coil to powering on the opening
coil.
Open—Topen-close—Close—Tclose-open—Open
When you select the "close-to-open" test mode in the mode selection interface,
the "General Mode" and "Special Mode" options will pop up on the right. The
10
above-mentioned reclosing time can optionally be performed in the normal mode.
If special mode is selected, the time parameters Topen-close and Tclose-open will be
automatically set to 0ms and cannot be changed. Because the working mode at
this time is that when any one of the 12 groups of ports detects a closing signal
during the closing process, it immediately stops the closing command and opens
Figure 5
After setting the test parameters, click the "Start Test" button to perform the
test. After the test is completed, enter the data interface (see Figure 6). The
parameters shown in the figure are the parameters before the test. Enter the
corresponding interface by selecting the button in the upper right corner of the
figure. For example, the "test data" interface contains all the test result data, and
the "graphic analysis" contains the dynamic graphics and current and
displacement curves of each port. In the “Storage and Print” interface, operations
such as transferring to a USB flash drive, printing data, and deleting data can be
performed.
11
Figure 6
Select the "Manual Open / Close" test mode, the screen will switch to the
"Start Test" interface in this mode, press the "Input Voltage" button and enter the
corresponding voltage value and confirm, and select "Close" according to the
Figure 7
12
Figure 8
If you select the “Open / Close Low Jump” test mode, the screen will switch
to the “Start Test” interface in this mode, and set the “Control Pulse Width” (that is,
the coil power-on time), “Initial Voltage”, and “Step Voltage” in this order. ", Select"
Single "or" Continuous "mode for boost operation. The use of this function is that
VI.Data query
Click the "Data Query" button to enter the historical data viewing interface.
This item is divided into four parts: "test record", "test data", "graphic analysis" and
"storage printing", which are basically the same as the interface after the test is
completed.
The "test record" contains the test result number, time, test product
/ closing time, rigid opening / closing speed, maximum speed, average speed,
opening distance, overtravel, total stroke, coil current, coil resistance, and phase
The "graphic analysis" includes the 12-way fracture bounce curve, the
13
displacement curve of the test fracture, and the coil current curve. And by
selecting specific t1 and t2 values, the average speed in the specified motion
In the initial state, the background of the value display areas of t1 and t2 are
white. Clicking on any one of the white areas will change the background color
(the background color of t1 becomes pink and the background color of t2 becomes
light green) and the same color light will be displayed Ruler. At this time, click the
color change area again to manually enter the time (less than or equal to the test
duration value) or click anywhere on the display area of the bounce curve and
displacement curve, and then move the cursor ruler to select the specified time
scale. During input or movement, t1 / t2, S1 / S2, I1 / I2, will dynamically display
the time, displacement value and coil current value of the cursor ruler, △t and △S
will dynamically display the time and displacement difference of the selected
position ,V is the average speed in the time interval between t1 and t2. The
"Stored print" can optionally print test data or data or graphics in graphic
analysis, and can save the current data to a USB storage device, so that the data
VII.Other settings
The “brightness adjustment” and “time calibration” in the main interface can
be operated according to the interface prompts, and will not be repeated here. The
“system settings” are the factory parameters of the instrument, which cannot be
VIII.Field connection
8.1 Ground and port connections
14
the protective ground of the instrument to the field ground before performing
other wiring and operations. After the test, turn off the power of the instrument,
remove the other wires, and finally remove the ground wire. This machine's
fracture line is a four-core sheathed wire with four colors: yellow, green, red, and
black, which correspond to ABC and the public end, respectively. The connection
conductors (red is the closing conductor, green is the opening conductor, and
15
black is the power common terminal) and 3-core sheathed wires are used as
instrument, disconnect the control power in the switch control box under test
(usually disconnect the fuse connected to the control power in the control box and
the control bus), but the power supply of the switch mechanism cannot be cut ,
And then wire as shown below. The instrument can only provide DC current
internally. Use the instrument's internal power supply to “internal trigger”. If the
method.
When using an external field power supply for the opening and closing control, the
"internal power supply" is not wired. When the switch is single-tested, two wires
“externally triggered” are connected to both ends of the brake coil; when the
switch is single-tested, the two wires “externally triggered” are connected to both
ends of the open-circuit coil. When operating with an external power supply, use
the "external trigger" method. External trigger mode can be tested regardless of
Select the appropriate sensor according to the measured switch. For some
16
imported and joint-venture switches, the linear drive part is enclosed inside the
switch body. When the switch manufacturer leaves the factory for speed tests, the
switches are tested on the switch opening and closing indicators or rotary shafts.
In this case, angle sensors are used. The axis of the rotation sensor should be
kept concentric with the axis of the switch as much as possible, otherwise the
rotation of the sensor will be hindered, and the burr of the measured curve will be
very heavy, which will affect the accuracy of the test data.
If you need to measure the stroke of the switch very accurately, you need a
linear sensor. There are three types of linear sensors: 50mm, 200mm and 300mm.
50mm linear sensor is used to measure the travel speed of vacuum switch;
200mm, 300mm is used to measure the SF6 switch travel and speed These two
an example, as shown below. When installing the linear resistance sensor, ensure
that the sensor's moving axis can move in a straight line, and fix the sensor with a
magnetic universal bracket. The method is similar for SF6 switch and oil switch.
17
IX.On-site common problems
9.1 On-site closing and opening control wiring is incorrect or there is a
Find the control wiring diagram of the on-site control cabinet and ask relevant
professionals to find the closing and opening coils and switch auxiliary contacts
respectively. Refer to Appendix II of this manual for control wiring diagrams and
instructions for rewiring. Check the control circuit to ensure that the circuit is
unblocked.
9.2 The instrument prompts "Power supply current output exceeds limit,
wrong control wiring, which causes the short-circuit protection function to start,
and the instrument "closes and opens the control power" has no output. Shut
down at this time, and check the wiring again according to the first item above.
b. The instrument may not be driven normally due to the excessive coil load on
site.
① For the switch of the electromagnetic mechanism, the driving current required
by the switch closing coil is large (up to 100A or several hundred amps), and the
18
result, the load is too large and the instrument cannot be driven normally.
Generally, the closing control line is connected to the closing contactor coil in
front of the closing coil, and the switch contactor is controlled by the instrument.
The contactor is used to drive the switch closing coil to make the switch act.
② For the switch of hydraulic and spring mechanism, the default is “excessive
load” when the output current of the instrument is greater than 6A. Please take a
look or use a multimeter to measure the resistance of the closing coil to confirm
that the closing coil current is large. Then please check the wiring carefully,
make sure that the closing output is not short-circuited, and then restart after
power off.
This kind of situation may be caused by the burnout of the power supply
insurance of the instrument and the loss of power supply to the entire instrument.
At this time, the replacement insurance can be replaced. Or the internal power
supply of the instrument has failed. At this time, external triggering can be used for
measurement. After the test is completed, notify the company to return to the
19
X.Packing List
NO. Name Quantity
Black 1
Red 1
3 Test line
Green 1
Yellow 1
5 Ground cable 1
6 Power line 1
7 Angle sensor 1
8 Line sensor 1
Connector 3
Test line 1
9
Converter 1
Black 4
Alligator Red 1
10
clips Green 1
Yellow 1
Black 1
Red 1
11 Small clip
Green 1
Yellow 1
12 Print paper 1
20
13 Fuse pipe 1
21