Schneider Electric - Sepam-Serie-20 - 59646
Schneider Electric - Sepam-Serie-20 - 59646
Specifications
To be discontinued
notification_critical_stroke To be end-of-service on: 31-Dec-2030
notification_critical_stroke
Main
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Module Type Input/output module
Complementary
Input/Output Type 10 inputs + 4 outputs 24...250 V at DC
19-Dec-2023 1
Output Type Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity:
0.005 kA cos φ > 0.3 making capacity: < 15 A for 200 ms
Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity:
0.008 kA resistive making capacity: < 15 A for 200 ms
Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R <
40 ms making capacity: < 15 A for 200 ms
Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.0005 kA L/R <
20 ms making capacity: < 15 A for 200 ms
Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.0007 kA
resistive making capacity: < 15 A for 200 ms
Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.0001 kA L/R <
40 ms making capacity: < 15 A for 200 ms
Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.0002 kA L/R <
20 ms making capacity: < 15 A for 200 ms
Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.0003 kA
resistive making capacity: < 15 A for 200 ms
Control relay: 24 V DC continuous current: 8 A breaking capacity: 0.004 kA L/R < 40
ms making capacity: < 15 A for 200 ms
Control relay: 24 V DC continuous current: 8 A breaking capacity: 0.006 kA L/R < 20
ms making capacity: < 15 A for 200 ms
Control relay: 24 V DC continuous current: 8 A breaking capacity: 0.008 kA resistive
making capacity: < 15 A for 200 ms
Control relay: 250 V DC continuous current: 8 A breaking capacity: 0.0002 kA
resistive making capacity: < 15 A for 200 ms
Control relay: 48 V DC continuous current: 8 A breaking capacity: 0.001 kA L/R < 40
ms making capacity: < 15 A for 200 ms
Control relay: 48 V DC continuous current: 8 A breaking capacity: 0.002 kA L/R < 20
ms making capacity: < 15 A for 200 ms
Control relay: 48 V DC continuous current: 8 A breaking capacity: 0.004 kA resistive
making capacity: < 15 A for 200 ms
Indication relay: 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking
capacity: 0.001 kA cos φ > 0.3 making capacity: < 15 A for 200 ms
Indication relay: 127 V DC continuous current: 2 A breaking capacity: 0.0005 kA L/R
< 20 ms making capacity: < 15 A for 200 ms
Indication relay: 127 V DC continuous current: 2 A breaking capacity: 0.0006 kA
resistive making capacity: < 15 A for 200 ms
Indication relay: 220 V DC continuous current: 2 A breaking capacity: 0.00015 kA L/R
< 20 ms making capacity: < 15 A for 200 ms
Indication relay: 220 V DC continuous current: 2 A breaking capacity: 0.0003 kA
resistive making capacity: < 15 A for 200 ms
Indication relay: 24 V DC continuous current: 2 A breaking capacity: 0.002 kA L/R <
20 ms making capacity: < 15 A for 200 ms
Indication relay: 24 V DC continuous current: 2 A breaking capacity: 0.002 kA
resistive making capacity: < 15 A for 200 ms
Indication relay: 250 V DC continuous current: 2 A breaking capacity: 0.0002 kA
resistive making capacity: < 15 A for 200 ms
Indication relay: 48 V DC continuous current: 2 A breaking capacity: 0.001 kA L/R <
20 ms making capacity: < 15 A for 200 ms
Indication relay: 48 V DC continuous current: 2 A breaking capacity: 0.001 kA
resistive making capacity: < 15 A for 200 ms
Environment
2 19-Dec-2023
Electromagnetic Compatibility 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV
MC and MD, conforming to ANSI C37.90.1
1 MHz damped oscillating wave: (immunity tests-conducted disturbances), III, 2.5 kV
MC, 1 kV MD, conforming to IEC 60255-22-1
100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV
MC, 1 kV MD, conforming to IEC 61000-4-12
Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
Conducted disturbance emission: (emission tests), B, conforming to EN 55022
Disturbing field emission: (emission tests), conforming to IEC 60255-25
Disturbing field emission: (emission tests), A, conforming to EN 55022
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV
contact, conforming to ANSI C37.90.3
Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV
contact, conforming to IEC 60255-22-2
Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz,
conforming to ANSI C37.90.1
Fast transient bursts: (immunity tests-conducted disturbances), A or B, 4kV, 2.5 kHz/
2 kV, 5 kHz, conforming to IEC 60255-22-4
Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz,
conforming to IEC 61000-4-4
Immunity to conducted RF disturbances: (immunity tests-conducted disturbances),
10 V, conforming to IEC 60255-22-6
Immunity to magnetic fields at network frequency: (immunity tests-radiated
disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8
Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...
1 GHz, conforming to IEC 60255-22-3
Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...
1 GHz, conforming to ANSI C37.90.2 (1995)
Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80
MHz...2 GHz, conforming to IEC 61000-4-3
Surges: (immunity tests-conducted disturbances), III, 2 kV MC, 1 kV MD, conforming
to IEC 61000-4-5
Voltage interruptions: (immunity tests-conducted disturbances), 100 %, 10 ms,
conforming to IEC 60255-11
Climatic Withstand Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm
H2S, 0.2 ppm S02, 0.02 ppm NO2, 0.01 ppm Cl2 conforming to IEC 60068-2-60
Continuous exposure to damp heat (in operation) : Ca: 10 days, 93 % RH, 40 °C
(104 °F) conforming to IEC 60068-2-3
Continuous exposure to damp heat (in storage) : Ca: 56 days, 93 % RH, 40 °C (104
°F) conforming to IEC 60068-2-3
Exposure to cold (in operation) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
Exposure to cold (in storage) : Ab: - 25 °C (- 13 °F) conforming to IEC 60068-2-1
Exposure to dry heat (in operation) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
Exposure to dry heat (in storage) : Bb: 70 °C (158 °F) conforming to IEC 60068-2-2
Influence of corrosion/gaz test 2 (in operation) : C: 21 days, 75 % RH, 25 °C (- 13
°F), 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
Salt mist (in operation) : Kb/2 conforming to IEC 60068-2-52
Temperature variation with specified variation rate (in operation) : Nb: - 25 °C to 70
°C (- 13 °F to 158 °F) 5 °C/min (41 °F/min) conforming to IEC 60068-2-14
Packing Units
Unit Type Of Package 1 PCE
19-Dec-2023 3
Number Of Units In Package 3 72
4 19-Dec-2023
Sustainability
Green PremiumTM label is Schneider Electric’s commitment to delivering products with best-in-
class environmental performance. Green Premium promises compliance with the latest regulations,
transparency on environmental impacts, as well as circular and low-CO2 products.
Guide to assessing product sustainability is a white paper that clarifies global eco-label
standards and how to interpret environmental declarations.
Learn more about Green Premium arrow2_right
Guide to assess a product’s sustainability arrow2_right
Transparency RoHS/REACh
Well-being performance
Mercury Free
19-Dec-2023 5