The document describes ACV's stainless steel Tank-in-Tank technology for water heaters. The Tank-in-Tank design features an inner stainless steel tank enclosed within an outer tank that is heated by a boiler. This allows for rapid heating of domestic water while reducing energy losses. The inner tank's corrugated design also helps prevent limescale buildup and makes maintenance unnecessary.

Uploaded by

ted
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views

Guide: Product

The document describes ACV's stainless steel Tank-in-Tank technology for water heaters. The Tank-in-Tank design features an inner stainless steel tank enclosed within an outer tank that is heated by a boiler. This allows for rapid heating of domestic water while reducing energy losses. The inner tank's corrugated design also helps prevent limescale buildup and makes maintenance unnecessary.

Uploaded by

ted
Copyright
© © All Rights Reserved
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 49

2004

Product
Guide

Stainless Steel Tank-in-Tank Technology


Downloaded from www.Manualslib.com manuals search engine
Distributor/Agent

The Facts about Tank-in-Tank

Like all good ideas, the ACV Tank-in-Tank concept is as simple as it’s It also provides a uniform temperature throughout the volume of the
effective and like all good ideas that work really well, it’s also stood tank. Since the inner tank can move freely, it can expand and contract
the test of time. under changes in pressure and prevent limescale forming on the
surface.
The Tank-in-Tank is a DHW tank entirely immersed within an outer
tank which contains the primary fluid, with the inner tank itself being This simple and highly effective design allows specifiers and installers
a stainless steel heat exchanger. The corrugated wall of the inner to benefit from the cost advantages of ACV’s high volume production
tank forms a large heat exchange surface that can heat the domestic while taking comfort from the fact that the system they are
water in a very short time. specifying or installing is the best there is.

Stainless steel inner tank Combined boilers and water heaters


Specially designed stainless steel hot water Tank-in-Tank doesn’t stop at hot water storage
cylinder enclosed within an outer tank which is tanks – the design is also found throughout
heated by the boiler. Stainless steel, coupled our HeatMaster and Delta ranges of combined
with the know-how of ACV, gives the domestic boiler and water heaters. These are high
hot water tank exceptional resistance to performance, direct fired hot water storage
aggressive water conditions. heaters, which have indirect heat transfer due
to the Tank-in-Tank construction. They have
one very major advantage over other direct
fired water heaters - because they heat the
Large heating surface area DHW with a primary circuit, this primary water
The inner tank acts as a large thermal store and can be used to provide central heating as well.
is the heart of the Tank-in-Tank system. It is
totally immersed in the primary hot water and
with a large heating surface area (typically 1.5
Anti-legionellae
to 2.5 times greater than that of a standard coil)
Natural turbulence across the concave base
it can heat a large quantity of domestic hot
keeps particles in suspension, preventing
water in an exceptionally short time. Thanks to
formation of sediment and - aided by high
this rapid heating capacity, the volume of water
store temperatures - helps to avoid growth of
stored can be reduced, and energy loss kept to
legionellae bacteria.
a minimum.

Self-descaling Maintenance-free
The tank is free to expand and contract as a Thanks to their stainless steel tank, the ACV
result of the variations in pressure which occur range of Tank-in-Tank products require no
with every draw-off. The corrugations amplify anode protection and the self-descaling
these movements and prevent the formation of feature eliminates the need for regular
lime scale on the surface of the exchanger, descaling. A primary coil is not required and
which retains its high performance throughout there is no need to worry about
its service life. Just one of the unique contamination, leaking and sludging caused by
advantages of ACV Tank-in-Tank systems. cracked linings.
20031031

ACV UK Ltd
St David's Business Park, Dalgety Bay, Fife, KY11 9PF
Tel: +44 (0)1383 820100 Fax: +44 (0)1383 820180
Email: [email protected] www.acv-uk.com

ACV accepts no responsibility whatsoever for any inaccuracy in transcribing or printing the present document. ACV reserves the right to change the technical specifications and components of its products without prior notice.

Downloaded from www.Manualslib.com manuals search engine


Products

Hot Water

rgy
Tanks

rag r

Ene
Sto Wate

He trict
g
e

atin
lti-
ar

e
Dis
t

Pag
Mu
Sol
Ho
SmartLine • 3

HR • 5

Jumbo • 7

HRS / HRE • 9

HR FB / ACCU • • 11

SVM • 13
ter oiler
r
ate

Boilers and
g

e
nal
din

Flu
He
B

g
Flu ventio
Water Heaters
and bined

sin
tan

ung

ed

den
ic
or S
Wa

anc
ll H

c tr
Com

e
Con
e
LPG

Con

Pag
s
Flo

Bal
Ele
Wa

Oil
Ga

Delta Performance • • • • • • 15

Delta Performance FV / MV • • • • • • 17

HeatMaster® 30 • • • • • 19

HeatMaster® 60 • • • • • • • 21

HeatMaster® 70-100 • • • • • • • 23

HeatMaster® 150-200 • • • • • • 25

HeatMaster® 71-101 • • • • • • 27

HeatMaster® 201 • • • • • 29

E-Tech S • • • 31

ETS • • 33

TER • • 35

Prestige 24-32 • • • • • 37

Prestige 47-64-85 • • • • • 39

Compact N • • • • • 41

Compact A • • • • • 43
Products

Compact S • • • • • 45

Concentric Flue Systems • 47


4
2

Downloaded from www.Manualslib.com manuals search engine


Hot Water Storage Tanks

SmartLine 2 3 4 5 2 3 4 5
Range 1 1
6 6
14 14
7 7

8 8

13 13

9 12 9

12 10 10

11 11

SL SLE

1. Control thermostat, high 8. 50mm polyurethane


limit thermostat and wiring insulation
connection 9. Shock-proof, thick
2. Domestic cold water inlet polypropylene outer casing
3. DHW recirculation or 10. Primary water return
temperature and pressure connection
relief valve connection 11. Rigid PVC base
4. Primary air vent 12. Steel outer tank
5. Domestic hot water outlet 13. Thermostat pocket
6. Stainless steel inner tank 14. Rigid PVC top cover
7. Primary water flow 15. Immersion heater
connection connection (SLE only)

Product Description Unvented Hot Water


All SmartLine tanks can be used as unvented hot
water tanks by the addition of a Mains Pressure
• Utilises ACV Tank-in-Tank technology for fast heat up and rapid recovery
SystemPak, containing the following
• Two different models available : SLE and SL components :

• SLE includes 3kW immersion heater, located in the bottom of tank in the
primary water
• Combined pressure
• 6 models of 130, 160, 210, and 240 litres (SLE), 320 and 420 litres (SL) reducing valve and strainer
• High quality 50mm polyurethane insulation • Cold water inlet check
valve
• Low heat loss (only 8.6°C over 24 hours for the SLE240)
• Cold water expansion relief
• Hard-wearing polypropylene finish
valve
• Stainless steel construction - no need for sacrifical anodes
• Expansion vessel
SmartLine

• Vented or unvented use, with mains pressure SystemPak available


• Temperature and pressure
• Large heating surface area means reduced boiler cycling relief valve

• Domestic or commercial use • Tundish


5
3

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

A C A C

B B
Front Left Side Front Right Side

SLE 130 - 240 SL 320 - 420

Maximum Operating Pressure Factory Test Pressure Maximum Operating


Primary: 3 bar - SLE Primary: 4.5 bar - SLE Temperature
4 bar - SL 6.0 bar - SL 90°C
Secondary: 10 bar Secondary: 13 bar

SLE SLE SLE SLE SL SL


130 160 210 240 320 420
Code 06604801 06604901 06605001 06605101 06604001 06606801
Total capacity L 130 161 203 242 318 413
Primary capacity L 55 62 77 78 55 55
Heating surface area m2 1.03 1.26 1.54 1.94 2.65 3.24
Primary pressure drop mbar 17 22 37 45 90 95
Primary flow rate L/h 2100 2600 3500 4200 6200 6400
Maximum useable input from boiler kW 23 31 39 53 73 88.5
Primary connections (female BSP) Ø 1" 1" 1" 1" 11/2" 11/2"
Hot water connections (male BSP) Ø 1" 1" 1" 1" 11/2" 11/2"
Immersion heater connection (female BSP) Ø 11/2" 11/2" 11/2" 11/2" n/a n/a
Dimensions A mm 960 1160 1435 1680 1550 1975
B mm 555 555 555 555 660 660
C mm 525 725 997 1244 1030 1455
Weight empty Kg 55 65 75 87 141 167
Weight full Kg 185 226 278 329 459 580

Domestic Hot Water Performances

SLE SLE SLE SLE SL SL


130 160 210 240 320 420
Peak flow 40°C L/10’ 236 321 406 547 922 1195
Peak flow 45°C L/10’ 202 275 348 469 790 1012
Peak flow 60°C L/10’ 117 161 209 272 504 620
Peak flow 1st hour 40°C L/60’ 784 1063 1349 1820 2666 3151
Peak flow 1st hour 45°C L/60’ 672 911 1156 1560 2285 2608
Peak flow 1st hour 60°C L/60’ 384 549 689 913 1368 1513
Continuous flow 40°C L/h 658 890 1132 1527 2093 2536
Continuous flow 45°C L/h 564 763 970 1309 1794 2058
SmartLine

Continuous flow 60°C L/h 320 465 576 769 1037 1153
Initial heat up time from 10 to 85°C min 22 22 20 20 23 24

6
4
Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of
10°C, without the use of a thermostatic mixing valve on the domestic hot water outlet.

Downloaded from www.Manualslib.com manuals search engine


Hot Water Storage Tanks

14 1 2 3 4
HR601
13
5

12

11
6
10

9 7

1. Domestic cold water inlet 7. Thermostat pocket


2. DHW recirculation or 8. Primary water return
temperature and connection
pressure relief valve 9. Rigid polyurethane foam
connection insulation
3. Primary air vent 10. Steel outer tank
4. Domestic hot water 11. Stainless steel inner tank
outlet 12. Stove enamelled metal
5. Primary water flow casing
connection 13. Thermometer
6. Thermometer pocket 14. Control thermostat

Product Description

• Tank-in-Tank floor standing indirect hot water storage tank


• Stainless steel construction - no need for sacrifical anodes
• High efficiency - fast heat up and rapid recovery
• Fully insulated with rigid polyurethane foam insulation
• Stove enamelled casing complete with control panel
• One model providing 606 litres total capacity
• Can be used in battery formation for high output installations
• Vented or unvented use, with mains pressure SystemPak available
• Large heating surface area means reduced boiler cycling
HR 601

7
5

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 5 bar
Secondary: 10 bar
Factory Test Pressure
Primary: 7.5 bar
Secondary: 13 bar
Maximum Operating Temperature
90°C
Top

Front Right Hand Side

HR 601 Domestic Hot Water Performances


Code 06204401
Total capacity L 606
Primary capacity L 161 HR 601
Heating surface area m2 3.58
Peak flow 40°C L/10’ 1345
Primary pressure drop mbar 92
Peak flow 45°C L/10’ 1153
Primary flow rate L/h 7200
Peak flow 60°C L/10’ 706
Max. absorbed boiler output kW 88
Peak flow 1st hour 40°C L/60’ 3437
Primary connections (female BSP) Ø 2"
Peak flow 1st hour 45°C L/60’ 2946
Hot water connections (male BSP) Ø 11/2"
Peak flow 1st hour 60°C L/60’ 1733
Weight empty Kg 240
Continuous flow 40°C L/h 2511
Weight full Kg 846
Continuous flow 45°C L/h 2152
Continuous flow 60°C L/h 1232

Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of 10°C,
without the use of a thermostatic mixing valve on the domestic hot water outlet.

Project Reference
Wrexham Maelor Hospital, North Wales
Four HR601's installed in battery formation providing 2824 litres of hot water at 60°C in 10 minutes and a continuous
output of 4928 litres per hour for the new extension to this general hospital in North Wales.

HR 601

Downloaded from www.Manualslib.com manuals search engine


Hot Water Storage Tanks

6 14 12 7
Jumbo
13

9 5

8 11

1 10

3 4

1. Stainless steel inner tank 8. Control thermostat


2. Steel outer tank 9. Thermometer
3. 120 mm thick mineral wool 10. Thermostat pocket
insulation 11. Thermometer pocket
4. Primary water return 12. Primary air vent
connection 13. Metal casing
5. Primary water flow 14. DHW recirculation or
connection temperature and pressure
6. Domestic cold water inlet relief valve connection
7. Domestic hot water outlet

Product Description

• Tank-in-Tank floor standing indirect hot water storage tank

• Stainless steel construction - no need for sacrifical anodes

• High performance - fast heat up and rapid recovery

• Fully insulated with mineral wool

• Stove enamelled steel casing, supplied separately to enable the


tank to pass through standard 800mm doorways
• Two sizes - 800 and 1000 litres

• Can be used in battery formation for high output installations


Jumbo

• Vented or unvented use, with mains pressure SystemPak available

• Large heating surface area means reduced boiler cycling

9
7

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Top

Front Right hand side

Maximum Operating Pressure Factory Test Pressure Maximum Operating Temperature


Primary: 5 bar Primary: 7.5 bar 90°C
Secondary: 10 bar Secondary: 13 bar

JUMBO JUMBO
800 1000
Code 06253901 06254001
Total capacity L 800 1000
Primary capacity L 125 160
Heating surface area m2 4.56 5.5
Primary Pressure drop mbar 96 101
Primary flow rate L/h 7500 7800
Maximum useable input from boiler kW 100 112
Primary connections (female BSP) Ø 2" 2"
Hot water connections (male BSP) Ø 2" 2"
Dimensions A mm 1915 2315
B mm 1020 1020
C mm 340 340
D mm 1250 1650
E mm 1020 1020
Weight empty Kg 360 380
Weight full Kg 1160 1380

Domestic Hot Water Performances

JUMBO JUMBO
800 1000
Peak flow 40°C L/10’ 1881 2265
Peak flow 45°C L/10’ 1612 1941
Peak flow 60°C L/10’ 961 1145
Peak flow 1st hour 40°C L/60’ 4270 4940
Peak flow 1st hour 45°C L/60’ 3660 4234
Peak flow 1st hour 60°C L/60’ 2124 2438
Continuous flow 40°C L/h 2868 3210
Jumbo

Continuous flow 45°C L/h 2458 2751


Continuous flow 60°C L/h 1395 1552

10
8
Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of
10°C, without the use of a thermostatic mixing valve on the domestic hot water outlet.

Downloaded from www.Manualslib.com manuals search engine


Hot Water Storage Tanks

13
HRS / HRE 12
13 1
12
1

2 2
11 11
3 3

10
4 4
9 10
5 5
10

9 6 9 6

8 8

7 7

HR S2 HRE

1. Removable top cover 9. Coil connection (HRS)


2. Control panel or auxiliary connection
3. Stainless steel tank (HRE)
4. Polyurethane foam 10. Coil connection (HRS)
insulation or auxiliary connection
5. Front panel (HRE)
6. Stainless steel coil heat 11. DHW recirculation or
exchanger (HRS) or temperature and
connection for pressure relief valve
immersion heater (HRE) connection
7. Steel base 12. Cold water connection
8. Drain connection 13. Hot water connection

Product Description

• Stainless steel construction (including coils)


• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
• Control panel including thermostat and thermometer
• Vented or unvented use, with mains pressure SystemPak available
HRS
• Indirect hot water storage tank with single high recovery coil (HRS1) or double coils (HRS2)
• Ideal for very high primary pressures or for use with a solar collector
• Available in four sizes - 275 and 467 litres (HRS1) or 269 and 461 litres (HRS2)
HRS / HRE

HRE
• Direct hot water storage tank
• Ideal as a buffer store for plate heat exchangers and heat recovery units
9
• Supplied with two 11/2” female BSP connections to allow immersion heaters to be added
• Available in two sizes - 281 and 473 litres

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

HR S1 HR S2 HRE

Maximum Operating Pressure Maximum Operating Temperature


Primary: 20 bar (HRS) 90°C
Secondary: 10 bar

HRS1 HRS1 HRS2 HRS2 HRE HRE


301 501 301 501 301 501
Code 06234201 06234401 06234301 06234501 07234601 07234701
Tank capacity L 275 467 269 461 281 473
Coil capacity L 5 5 10 10 n/a n/a
Coil pressure drop mbar 96 96 192 192 n/a n/a
Primary flow rate L/h 2000 2000 4000 4000 n/a n/a
Heating surface area m2 0.94 0.94 1.88 1.88 n/a n/a
Coil connections (male BSP) Ø 1" 1" 1" 1" n/a n/a
Auxiliary connections (male BSP) Ø n/a n/a n/a n/a 1" 1"
Hot water connections (male BSP) Ø 1" 1" 1" 1" 11/2" 11/2"
Immersion heater connection (female BSP) Ø n/a n/a n/a n/a 11/2" 11/2"
Maximum length of immersion heater mm n/a n/a n/a n/a 450 550
Dimensions height mm 1860 2020 1860 2020 1860 2020
width mm 680 750 680 750 680 750
depth mm 680 750 680 750 680 750
Weight Empty Kg 94 123 102 131 89 119
Weight Full Kg 374 595 381 602 370 592

Domestic Hot Water Performances

HRS1 HRS1 HRS2 HRS2 HRE HRE


301 501 301 501 301 501
Peak flow 40°C L/10’ 869 1485 869 1485 n/a n/a
Peak flow 45°C L/10’ 745 1273 745 1273 n/a n/a
Peak flow 60°C L/10’ 430 899 430 899 n/a n/a
Peak flow 1st hour 40°C L/60’ 1713 2329 2554 3170 n/a n/a
Peak flow 1st hour 45°C L/60’ 1468 1996 2189 2717 n/a n/a
Peak flow 1st hour 60°C L/60’ 776 847 1263 1732 n/a n/a
HRS / HRE

Continuous flow 40°C L/h 1012 1012 2022 2022 n/a n/a
Continuous flow 45°C L/h 867 867 1733 1733 n/a n/a
Continuous flow 60°C L/h 500 500 1000 1000 n/a n/a

10
Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of
10°C, without the use of a thermostatic mixing valve on the domestic hot water outlet.

Downloaded from www.Manualslib.com manuals search engine


Solar / Multi-Energy Tanks
6 7

HR FB / ACCU 6 15 7

4
9 13
1 4
2
2 11 5
3 8
3
9
12 5

14 10
9

10
8

HR FB ACCU
1. Stainless steel inner tank 10. Coil heat exchanger
2. Steel outer tank 11. Secondary thermostat pocket
3. Insulation :
- Rigid polyurethane foam (HR FB) 12. Primary thermostat pocket
HR FB - Mineral wool (Accu Tank)
13. Auxiliary primary water flow
4. Primary water flow connection for alternative heating
connection source (Accu Tank only)
5. Primary water return 14. Auxiliary primary water return
connection connection for alternative heating
6. Domestic cold water inlet source (Accu Tank only)
ACCU 7. Domestic hot water outlet
15. DHW recirculation or
8. Drain connection temperature and pressure relief
9. Immersion heater connection valve connection (Accu Tank only)

Product Description

• Multi-Energy floor standing Tank-in-Tank hot water tanks


• Ideal as a thermal store for solar collectors, heat pumps, heat recovery from refrigeration
plant and many other energy sources
• Stainless steel construction - no need for sacrificial anodes
• Fully insulated with rigid polyurethane (HR FB) or mineral wool (Accu Tank)
• Includes control panel with thermostat and thermometer
• Optional high recovery copper coil heat exchanger
• Immersion heater connection
HR FB / ACCU

• Vented or unvented use, with mains pressure SystemPak available


• HR FB available in two slimline models of 360 and 450 litres with factory fitted casing
• Accu Tank available in two models of 618 and 809 litres, with casing supplied separately
13
11 to enable the tank to pass through standard 800mm doorways

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Multi-Energy Options


Primary: 3 bar A Primary thermal store
Secondary: 10 bar B Stainless steel DHW tank
Coil: 13 bar C Heat source from solid
fuel boilers or heat pumps
Factory Test Pressure
D Coil heat exchanger
Primary: 4.5 bar
E Immersion heater
Secondary: 13 bar
F Heat source from solar
Coil: 20 bar
panels or heat recovery
Maximum Operating Temperature from refrigerator
90°C G Heat source from boiler

HR FB HR FB ACCU B ACCU B
300 450 600 800
Code 06254201 06603202 06240201 06240401
Tank
Total capacity L 360 450 618 809
Primary capacity L 189 261 434 625
Heating surface area m2 1.99 2.58 2.16 2.16
Primary pressure drop mbar 90 75 60 60
Primary flow rate L/h 5400 5700 n/a n/a
Maximum usable input from boiler kW 63 63 38 38
Primary connections (female BSP) Ø 1” 2” 11/4” 11/4”
DHW connections (male BSP) Ø 1” 11/2” 1” 1”
Immersion heater connection Ø 11/2” 11/2” 11/2” 11/2”
Dimensions height mm 1900 1860 1730 2030
width mm 680 750 1020 1020
depth mm 680 750 1020 1020
Weight empty Kg 190 212 251 280
Weight full Kg 550 662 869 1089
Coil
Surface area m2 2.6 2.6 2.6 2.6
Primary connection (male BSP) Ø 3/ ” 3/ ” 3/ ” 3/ ”
4 4 4 4
Flange diameter mm 190 190 190 190
Length mm 610 610 610 610
Pressure drop mbar 160 160 160 160
Primary flow rate L/h 700 700 700 700
Rated output kW 13.12 13.12 13.12 13.12

Domestic Hot Water Performances

HR FB HR FB ACCU B ACCU B
300 450 600 800
Peak flow 40°C L/10’ 427 455 280 303
Peak flow 45°C L/10’ 366 390 240 260
Peak flow 60°C L/10’ 220 270 144 182
Peak flow 1st hour 40°C L/60’ 1930 2474 1094 1211
Peak flow 1st hour 45°C L/60’ 1654 2120 938 1034
HR FB/ACCU

Peak flow 1st hour 60°C L/60’ 562 726


Continuous flow 40°C L/h 1804 1940 1089 1089
Continuous flow 45°C L/h 1546 1662 933 933
Continuous flow 60°C L/h 653 653
14
12
Note: The above performances are based on a primary flow temperature of 85°C and a domestic cold water inlet of
10°C, without the use of a thermostatic mixing valve on the domestic hot water outlet. If the boiler is heated using
the immersion heater, domestic hot water output depends on the heating element fitted.

Downloaded from www.Manualslib.com manuals search engine


District Heating Tanks

5 3 1 6

SVM
7

10

11

12

2 4

1. Primary (district heating) 7. Rigid polyurethane


circuit flow connection foam insulation
2. Primary (district heating) 8. Outer primary
circuit return connection (district heating) tank
3. Intermediary (central heating) 9. Intermediary
circuit flow connection (central heating) tank
4. Intermediary (central heating) 10. Stainless steel DHW
circuit return connection inner tank
5. Domestic cold water inlet 11. Thermostat pocket
6. Domestic hot water outlet 12. Stove enamelled casing

Product Description Unvented Hot Water


Mains Pressure SystemPaks are available for use
with all SVM models, containing the following
• SVM TripleTank system providing central heating and hot water : all components :
the proven advantages of ACV Tank-in-Tank technology with an
additional tank fed by a district heating main • Combined pressure reducing
• Ideal for high-rise apartment blocks and dwellings fed from a central valve and strainer
boiler plant or district heating main
• Temperature and pressure relief
• Three concentric tanks wrapped around each other : valve
- Stainless steel inner tank for domestic hot water • Cold water expansion relief valve
(maximum operating pressure 10 bar)
• Failsafe hot water blending valve
- Intermediary tank containing the central heating circuit,
provides heat transfer to the radiators at low pressure • Cold water inlet check valve
- Outer tank contains the district heating water, operating at up • Tundish
to 6 bar with low pressure drop across the tank
• Expansion vessel
• Compact and very easy to install, with proven reliability and minimal
SVM

maintenance : efficient, economic, quiet and safe


• High quality polyurethane insulation
Heating Sealed
• Stove enamelled casing complete with control panel containing System Kits are also
13 thermostats available.
• Available in 3 models : 115, 140 and 180

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications
Maximum Operating Pressure Factory Test Pressure Maximum Operating Temperature
District Heating 6 bar District Heating 9 bar 90°C
Primary 3 bar Primary 4.5 bar
Secondary 10 bar Secondary 13 bar

SVM SVM SVM


115 140 180
Code 06223901 06221801 06224101
Total capacity L 149 182 208
Primary (district heating) capacity L 26 30 33
Intermediary (central heating) capacity L 17 20 22
DHW capacity L 106 132 153
Primary heating surface area m2 1.67 1.99 2.23
Typical output to central heating kW 15.7 17.4 20.5
DHW heating surface area m2 1.4 1.71 2.0
Primary connections (female BSP) Ø 3/ ” 3/ ” 3/ ”
4 4 4
Intermediary connections (male BSP) Ø 3/ ” 3/ ” 3/ ”
4 4 4
DHW connections (male BSP) Ø 3/ ” 3/ ” 3/ ”
4 4 4
Dimensions height mm 1450 1700 1880
width mm 475 475 475
depth mm 500 500 500
Weight empty Kg 110 130 148
Weight full Kg 259 312 356

Project References
Langdon Hills, Basildon, Essex.
This refurbishment of the heating and hot water systems for Basildon District Council of a 1960’s housing estate
utilised the existing district heating mains infrastructure together with a selection of 278 SVM TripleTanks.
The design was undertaken by G K Salter & Associates of Swanley, Kent. The installation was carried out by
Interserve FM Ltd.

Hillside Towers, Sheffield.


These apartment blocks were the first in the UK to make use of the superior characteristics of the ACV SVM
TripleTanks in District Heating. This Sheffield City Council financed refurbishment involved the total renovation of
seven 1960’s-built blocks of flats, which involved the installation of 336 SVM 115 TripleTanks. The design was
undertaken by DBS Architects of Sheffield and installed by local contractor Bumford Heating Ltd of Barnsley.
SVM

16
14

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

Delta 17 13
4
Performance 7
14
15

16 12

18

1
2
3
5
6
7

10 8
9
19
11

1. Stainless steel inner tank 11. Primary drain connection


2. Primary heating circuit 12. Top primary water flow and
3. Rigid polyurethane foam return connections
insulation 13. Flue connection
4. Stove enamelled metal casing 14. Control panel
5. Flue pipes 15. Domestic hot water outlet
6. Stainless steel flue turbulators 16. Domestic cold water inlet
7. Control thermostat pocket 17. Lower limit thermostat and
8. Alternative primary water thermometer pocket
return connection 18. Manual reset high limit
9. Combustion chamber thermostat
10. Combustion chamber plate 19. Oil or gas burner

Product Description
• High performance low-cost combined boiler and
water heater
• Stainless steel Tank-in-Tank design Simplicity Itself
• Choice of burner: The Delta Performance features an exceptionally easy to use
- Low-NOx premix gas or LPG (BG2000-S) control panel with no complex electronics, allowing the end-user
to have full control over their system. It is also easy to install, with
- Pressure jet natural gas or LPG (Riello) a simple plug and socket wiring connection.
- Pressure jet 28 sec or 35 sec oil (Riello)
• Anti-Legionellae : hot water stored at consistently
high temperature
• Fully insulated with rigid polyurethane foam
Delta Performance

• Stove enamelled casing


• Control panel including thermostats, thermometer,
indicators and on/off switch
• 22 to 62 kW output (oil) or 22 to 49 kW (gas)
• Can be used in battery formation for high
output installations
17
15 • Vented or unvented use, with mains pressure
SystemPaks available
• Primary heating sealed system kits also available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications
Maximum Operating Pressure
Primary: 3 bar
Secondary: 10 bar
Factory Test Pressure
Primary: 4.5 bar
Secondary: 13 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz

25 35 45 55

Code 04600001 04600101 04600201 04604301


Fuel Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options type Riello oil - Riello pressure jet natural gas/LPG - BG2000-S natural gas/LPG
Input – Riello burners kW 25-33 33-45 42-61 50-69
Input – BG2000-S burner kW 25 35 45 55
Output – Riello burners kW 22-29 29-40 38-54 45-62
Output – BG2000-S burner kW 22.45 31.35 40.5 49
Primary capacity L 83 104 70 82
Total capacity L 157 178 132 151
Heating surface area m2 1.59 1.59 1.99 2.46
Flue circuit pressure drop mbar 0.02-0.09 0.08-0.09 0.01-0.08 0.02-0.05
DHW connection (male BSP) Ø 3/ ” 3/ ” 3/ ” 3/ ”
4 4 4 4
Primary connection (female BSP) Ø 1" 1" 1" 1"
Flue connection (D) Ø mm 130 130 150 150
Dimensions A mm 1497 1697 1497 1697
B mm 542 542 542 542
C mm 818 818 818 848
E mm 360 360 390 390
F mm 200 200 200 200
Weight empty Kg 159 170 182 208
Weight full Kg 316 348 314 359
Minimum working gas pressure mbar 20 (Nat Gas) / 37 (LPG)
Natural gas flow rate (BG2000-S) m3/h 2.65 3.7 4.76 5.8
LPG flow rate (BG2000-S) m3/h 1.02 1.43 1.84 2.25

Domestic Hot Water Performances

25 35 45 55

Peak flow 40°C L/10' 268 285 316 362


Peak flow 45°C L/10' 230 230 283 283
Peak flow 60°C L/10' 170 170 186 186
Peak flow 40°C L/60' 806 1035 1284 1533
Peak flow 45°C L/60' 799 1027 1112 1403
Delta Performance

Peak flow 60°C L/60' 568 727 867 977


Continuous flow 40°C L/h 645 900 1161 1405
Reheat time to 80°C min 32 29 16 16

Note : The above performances are based on the hot water being blended at point of use, with a boiler temperature of 80°C 18
16
and a domestic cold water inlet of 10°C, using a BG2000-S gas burner.

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

Delta Performance 24
1 25 2 3 4

FV/MV 23
5
6
7
22
8
21
20 9

10
19
11

18 12

17 13

14

16 15

1. Domestic hot water outlet 14. Primary drain connection


2. Removable top panel 15. Steel base
3. Flue collector with removable 16. Side panel
top 17. Oil or gas burner
4. Flue gas analysis section 18. Control thermostat (FV) or
5. Flue outlet / air intake control potentiometer
6. Top primary water return (MV) pocket
connection 19. Rigid polyurethane foam
7. Primary water flow connection insulation
8. Domestic cold water inlet 20. Air intake hose
9. Stainless steel inner tank 21. Primary heating circuit
10. Flue pipes 22. Removable front panel
11. Stainless steel flue turbulators 23. Manual reset high limit
12. Combustion chamber thermostat
13. Alternative primary water 24. Control panel
return connection 25. Lower limit thermostat and
thermometer pocket

Product Description
• Balanced flue combined boiler and water heater
BMV1 and BMV2 Oil Burners
• High efficiency
• Stainless steel Tank-in-Tank design These burners set new standards in oil burner
• Choice of burner : technology. Operating with a transparent flame and a
- BG2000-M Low-NOx premix modulating gas or LPG NOx output less than 120 mg/kWh and with low noise
- BMV pressure jet 28 sec oil (kerosene) levels, they allow easy commissioning and maintenance
• Choice of 3 flue options (see flue section on page 47): and offer exceptional efficiency.
- vertical or horizontal (all models)
- twin-tube parallel (gas/LPG only)
• Easy to maintain, with no requirement for flue removal
during servicing
Delta Performance FV/MV

• Anti-Legionellae : hot water stored at consistently


high temperature
• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
• Control panel including thermostats, thermometer,
indicators and on/off switch
• 32 to 46 kW output, with modulation down to 9.5 or 14.3 kW
for gas models
• Can be used in battery formation for high output installations
17 • Vented or unvented use, with mains pressure
SystemPaks available
• Primary heating sealed system kits also available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Maximum Operating


Pressure Temperature
Primary: 3 bar 90°C
Secondary: 10 bar
Factory Test Pressure Power Supply
Primary: 4.5 bar 230v 50Hz
Secondary: 13 bar

FV35 FV50 MV35 MV50

Code 01607101 01607401 02607301 02608301


Fuel 28 sec oil (kerosene) Natural gas/LPG
Burner options type BMV1 BMV2 BG2000-M/35 BG2000-M/50
Input kW 34.9 50 10–34.9 15–50
Output kW 32.5 46.5 9.5–32 14.3–45.7
Primary capacity L 62 82 62 82
Total capacity L 127 162 127 162
Heating surface area m2 1.99 2.46 1.99 2.46
Primary circuit pressure drop mbar 30 40 30 40
DHW connection (male BSP) Ø 3/ ” 3/ ” 3/ ” 3/ ”
4 4 4 4
Primary connection (female BSP) Ø 1" 1" 1" 1"
Flue connection (G) Ø mm 80/125 100/150 80/125 100/150
Dimensions A mm 1585 1830 1585 1830
B mm 390 390 390 390
C mm 200 200 200 200
D mm 542 542 542 542
E mm 125 125 125 125
F mm 645 645 645 645
H mm 1610 1880 1610 1880
I mm 800 800 800 800
Weight empty Kg 182 220 182 220
Weight full Kg 309 282 309 282
Minimum working gas pressure mbar n/a n/a 20 (Nat Gas)/37 (LPG)
Natural gas flow rate m3/h n/a n/a 1.06–3.7 1.6–5.3
LPG flow rate m3/h n/a n/a 0.41–1.43 0.61–2.05
Oil flow rate kg/h 2.95 4.22 n/a n/a

Domestic Hot Water Performances

FV35 FV50 MV35 MV50

Peak flow 40°C L/10' 283 377 291 377


Peak flow 60°C L/10' 151 191 151 191
Peak flow 40°C L/60' 1024 1485 1044 1485
Delta Performance FV/MV

Peak flow 60°C L/60' 598 710 598 710


Continuous flow 40°C L/h 920 1352 915 1352
Continuous flow 60°C L/h 513 648 513 648
Reheat time to 60°C min 20 13 20 13

Note : The above performances are based on the hot water being blended at point of use,
with a boiler temperature of 80°C and a domestic cold water inlet of 10°C. 20
18

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

11
HeatMaster® 30 8
13

12

9
1

5 4

2
7

10

1. Stainless steel inner tank 7. Atmospheric natural


2. Primary heating circuit gas/LPG burner
3. Flue pipes with stainless 8. Control panel
steel turbulators 9. Primary water flow connection
4. Rigid polyurethane 10. Primary water return
foam insulation connection
5. Primary shunt pump 11. Domestic cold water inlet
6. Combustion chamber 12. Domestic hot water outlet
13. Flue connection

Product Description

• High performance combined boiler and water heater


• Stainless steel Tank-in-Tank design
• Atmospheric natural gas/LPG burner with electronic ignition
• Anti-Legionellae : hot water stored at a consistently high temperature
• Built-in primary circuit shunt pump
• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
HeatMaster® 30

• Control panel including thermostats, combined temperature and pressure gauge,


indicators and on/off switch

• 34 kW output and up to 696 litres of hot water at 60ºC in one hour


19 • Vented or unvented use, with mains pressure SystemPaks available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 3 bar
Secondary: 10 bar
Factory Test Pressure
Primary: 4.5 bar
Secondary: 13 bar
Maximum Operating Temperature
90°C

Power Supply
230v 50Hz

HM30 G HM30 GP Domestic Hot Water Performances


Code 02400101 03400101
Fuel Natural Gas LPG
Burner options type Atmospheric Atmospheric
HM30 G HM30 GP
Input kW 39.2 40
Maximum output kW 34.2 34.9
Peak flow 40°C L/10' 382 382
Primary capacity L 87.5 87.5 Peak flow 45°C L/10' 326 326
Total capacity L 163.5 163.5 Peak flow 60°C L/10' 203 203
Heating surface area m2 2.46 2.46 Peak flow 40°C L/60' 1187 1204
Primary circuit pressure drop mbar 29 29 Peak flow 45°C L/60' 1016 1030
DHW tank pressure drop mbar 20 20 Peak flow 60°C L/60' 686 696
Flue circuit pressure drop mbar Nil Nil Continuous flow 40°C L/h 966 986
DHW connection (male BSP) Ø 3/ ” 3/ ”
4 4 Continuous flow 45°C L/h 828 845
Primary connection (female BSP) Ø 11/4” 11/4” Continuous flow 60°C L/h 580 592
Flue connection (G) Ø mm 150 150 Reheat time to 90°C min 32 32
Flue connection options type B11 BS B11 BS
Dimensions A mm 1691 1691
B mm 1513 1513 Note : The above performances are based on the hot
C mm 538 538 water being blended at point of use, with a boiler
D mm 801 801 temperature of 90°C and a domestic cold water
E mm 540 540 inlet of 10°C.
F mm 390 390
H mm 898 898
J mm 286 286
Weight empty Kg 190 190
Weight full Kg 353.5 353.5
Minimum working gas pressure mbar 20 37
Burner pressure mbar 12.3 28.5
Gas flow rate m3/h 4.13 1.64

Atmospheric Gas Burners


HeatMaster® 30

• Burner design ensures a good flame


distribution in the combustion chamber
• Stainless steel provides a long working life
• Electronic ignition
22
20
• Gas burner preset in the factory
HM30 G – Natural gas HM30 GP – LPG

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

HeatMaster® 60
11
8
12

1
5 3
4

7 2

10
6

1. Stainless steel inner tank 7. Oil or gas burner


2. Primary heating circuit 8. Control panel
3. Flue pipes with stainless 9. Primary water flow
steel turbulators connection
4. Rigid polyurethane 10. Primary water return
foam insulation connection
5. Primary shunt pump 11. Domestic cold water inlet
6. Combustion chamber 12. Domestic hot water outlet

Product Description
• High performance combined boiler and water heater
BG2000-S/60 burner
• Stainless steel Tank-in-Tank design
• Choice of burner :
- Low NOx premix gas or LPG (BG2000-S)
- Pressure jet natural gas or LPG (Riello)
- Pressure jet 28 sec or 35 sec oil (Riello)
• Can also be used as a stand-alone water heater
• Anti-Legionellae : hot water stored at a consistently
high temperature
• Built-in primary circuit shunt pump
• Fully insulated with rigid polyurethane foam
• Stove enamelled casing
HeatMaster® 60

• Control panel including thermostats, combined ACV has developed this burner specially for the HeatMaster 60.
temperature and pressure gauge, indicators One of the BG 2000-S air/gas premix burner range, it has a metal
and on/off switch fibre (NIT) flame tube and smooth and near-silent ignition and
• Available with balanced flue (BG2000-S burner only) operation. It is ideal for use in applications where burner noise
• 63 kW output and up to 1106 litres of hot water must be kept to a minimum. Factory set for natural gas, and
at 60ºC in one hour
includes a simple conversion kit for LPG use.
21 • Vented or unvented use, with mains pressure
SystemPaks available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications
Maximum Operating Pressure Maximum Operating Temperature
Primary: 3 bar 90°C
Secondary: 10 bar
Power Supply
Factory Test Pressure
230v 50Hz
Primary: 4.5 bar
Secondary: 13 bar

HM60 HM60
Oil Gas/LPG
Code 04124101 04124101
Fuel Oil (28 sec or 35 sec) Natural gas/LPG
Burner options type Riello BG2000-S or Riello
Input kW 69.9 69.9
Maximum output kW 62.5 63.0
Primary capacity L 82 82
Total capacity L 162 162
Heating surface area m2 2.46 2.46
Primary circuit pressure drop mbar 54 54
DHW tank pressure drop mbar 45 45
Flue circuit pressure drop mbar 0.6 0.6
DHW connection (male BSP) Ø 3/ ” 3/ ”
4 4
Primary connection (female BSP) Ø 11/2” 11/2”
Flue connection (G) Ø mm 150 150
Flue connection options type B23 B23/C13/C33/C53
Dimensions A mm 1698 1698
B mm 1583 1583
C mm 538 538
D mm 791 801(BG 2000)/838(Riello)
E mm 540 540
F mm 390 390
H mm 1098 1098
J mm 281 281
BG2000 air intake connection Ø mm n/a 80
Weight empty Kg 229 229
Weight full Kg 391 391
Minimum working gas pressure mbar n/a 20(Nat Gas)/37(LPG)
Gas flow rate m3/h n/a 7.40(Nat Gas/2.86(LPG)

Domestic Hot Water Performances

HM60
(all burners)

Peak flow 40°C L/10' 474


Peak flow 45°C L/10' 378
Peak flow 60°C L/10' 245
Peak flow 40°C L/60' 1942 Note : These performances are based on the hot water being
blended at point of use, with a boiler temperature of
Peak flow 45°C L/60' 1656
HeatMaster® 60

90°C and a domestic cold water inlet of 10°C.


Peak flow 60°C L/60' 1106
Continuous flow 40°C L/h 1835
Continuous flow 45°C L/h 1573
Continuous flow 60°C L/h 1101
Reheat time to 60°C min 9
24
22

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

HeatMaster® 1 2 3 4 5 6

70 - 100 24
24 7

23
8
22 9

10
21
20 11
19
12
18
13
17
14
16
15

1. High limit thermostats pocket 13. Primary water return


2. Domestic cold water inlet connection
3. Automatic primary air vent 14. Combustion chamber
4. Flue connection 15. Steel base
5. Domestic hot water outlet 16. Oil or gas burner
and temperature and pressure 17. Combustion chamber plate
relief valve connection 18. NIT coated flame tube
6. Stove enamelled metal casing (BG2000-S only)
7. Primary water flow 19. Control thermostat pocket
connection 20. Primary shunt pump
8. Stainless steel flue turbulators 21. Control panel
9. Flue pipes 22. Primary expansion vessels
10. Rigid polyurethane foam 23. Primary filling loop with
insulation detachable hose and
11. Stainless steel inner tank non-return valve
12. Primary heating circuit 24. Removable front panel

Product Description
• High performance combined boiler and water heater
• Stainless steel Tank-in-Tank design
• Choice of burner : BG2000-S/70 and BG2000-S/100 burner
- Low-NOx premix gas or LPG (BG2000-S),
ACV has developed these burners specially for the
- Pressure jet natural gas or LPG (Riello) HeatMaster 70 and 100 models. Part of the BG 2000-S air/gas
- Pressure jet 28 sec or 35 sec oil (Riello) premix burner range, they have a metal fibre (NIT) flame tube
• Can also be used as a stand-alone water heater and smooth and near-silent ignition and operation. They are
• Anti-Legionellae : hot water stored at a consistently ideal for use in applications where burner noise must be kept
high temperature to a minimum.
• Built-in primary circuit shunt pump
• Fully insulated with rigid polyurethane foam
HeatMaster® 70 -100

• Stove enamelled casing


• Control panel including thermostats, combined
temperature and pressure gauge, indicators
and on/off switch
• Available with balanced flue (BG2000-S burner only)
• 63 kW output and up to 1219 litres of hot water at
60oC in one hour (HM70)
• 96.3 kW output and up to 1813 litres of hot water at
23 60oC in one hour (HM100)
• Vented or unvented use, with mains pressure
SystemPaks available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Maximum Operating


Primary: 3 bar Temperature
Secondary: 10 bar 90°C
Power Supply
Factory Test Pressure
230v 50Hz
Primary: 4.5 bar
Secondary: 13 bar

HM70 HM70 HM100 HM100


Oil Gas/LPG Oil Gas/LPG
Code 04604501 04604501 04604401 04604401
Fuel Oil (28 sec or 35 sec) Natural gas/LPG Oil (28 sec or 35 sec) Natural gas/LPG
Burner options type Riello BG2000-S or Riello Riello BG2000-S or Riello
Input kW 69.9 69.9 107 107
Maximum output kW 63 63 96.3 96.3
Primary capacity L 108 108 130 130
Total capacity L 239 239 330 330
Heating surface area m2 3.14 3.14 3.95 3.95
Primary circuit pressure drop mbar 46 46 83 83
DHW tank pressure drop mbar 45 45 180 180
Flue circuit pressure drop mbar 0.6 0.6 1.4 1.4
DHW connection (male BSP) Ø 1" 1" 1" 1"
Primary connection (female BSP) Ø 11/2” 11/2” 11/2” 11/2”
Flue connection (G) Ø mm 150 150 150 150
Flue connection options type B23 B23/C13/ C33/C53 B23 B23/C13/C33/C5
Dimensions A mm 1743 1743 2093 2093
B mm 1630 1630 2030 2030
C mm 678 678 678 678
D mm 931 937(BG 2000)/958(Riello) 931 937(BG 2000)/958(Riello)
E mm 680 680 680 680
F mm 390 390 390 390
H* mm 1289 1289 1693 1693
J mm 285 285 285 285
BG2000 air intake connection Ø mm n/a 80 n/a 100
Weight empty Kg 279 279 333 333
Weight full Kg 518 518 663 663
Minimum working gas pressure mbar n/a 20(Nat Gas)/37(LPG) n/a 20(Nat Gas)/37(LPG)
Gas flow rate m3/h n/a 7.40(Nat Gas)/2.86(LPG) n/a 8.99(Nat Gas)/3.47(LPG)

* The HeatMaster 100 is currently fitted with two heating flow outlets – the upper connection (recommended) is
shown by the dimension H. A second connection (compatible with the previous HM100N) is positioned 365mm lower.

Domestic Hot Water Performances

HM70 HM100
(all burners) (all burners)

Peak flow 40°C L/10' 646 905


Peak flow 45°C L/10' 543 777
Peak flow 60°C L/10' 346 514
HeatMaster® 70 -100

Peak flow 40°C L/60' 2133 3172


Peak flow 45°C L/60' 1794 2680
Peak flow 60°C L/60' 1219 1813
Continuous flow 40°C L/h 1835 2776
Continuous flow 45°C L/h 1573 2379
Continuous flow 60°C L/h 1067 1665
Reheat time to 60°C min 16 13 26
24

Note : The above performances are based on the hot water being blended at point of
use, with a boiler temperature of 90°C and a domestic cold water inlet of 10°C.

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters
8
HeatMaster®
150 - 200 12
11

1 4

2
10
7

1. Stainless steel inner tank 7. Combustion chamber plate


2. Primary heating circuit 8. Flue connection
3. Flue pipes with stainless steel 9. Primary water flow
turbulators connection
4. Rigid polyurethane foam 10. Primary water return
insulation connection
5. Primary drain connection 11. Domestic cold water inlet
6. Combustion chamber 12. Domestic hot water outlet

Product Description Project Reference


• Very high performance combined boiler and water heater
• Stainless steel Tank-in-Tank design
• Choice of burner :
- Pressure jet natural gas or LPG (Riello)
- Pressure jet 28 sec or 35 sec oil (Riello)
• Can also be used as a stand-alone water heater
• Anti-Legionellae: hot water stored at a consistently high temperature
• Built-in primary circuit shunt pumps
• Fully insulated with very thick mineral wool
HeatMaster® 150 - 200

• Stove enamelled casing


• Control panel including thermostats, combined temperature
and pressure gauge, indicators and on/off switch Allied Distillers, Glasgow
• 139 kW output and up to 2864 litres of hot water at 60oC High temperature, high pressure hot water for a cleaning
in one hour (HM150) process of stainless steel pipework which carries blends
• 178 kW output and up to 3348 litres of hot water at 60oC of whisky. After each blend the pipework is blasted with
in one hour (HM200) hot water at up to 70oC and at high pressure for 20
• Vented or unvented use, with mains pressure SystemPaks available minutes at 3 litres a second before the next blend can be
25 sent through the pipework. Four HeatMaster 150 and
one Jumbo 1000 tank for each of the 2 processing areas.

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Maximum Operating


Primary: 3 bar Temperature
Secondary: 10 bar 90°C
Factory Test Pressure Power Supply
Primary: 4.5 bar 230v 50Hz
Secondary: 13 bar

HM150 HM150 HM200 HM200


Oil Gas/LPG Oil Gas/LPG
Code 04125301 04125301 01618301 04607401
Fuel Oil (28 sec or 35 sec) Natural gas/LPG Oil (28 sec or 35 sec) Natural gas/LPG
Burner options type Riello Riello Riello Riello
Input kW 154 154 196 196
Maximum output kW 139 139 178 178
Primary capacity L 245 245 241 241
Total capacity L 645 645 641 641
Heating surface area m2 5.3 5.3 5.3 5.3
Primary circuit pressure drop mbar 120 120 240 240
DHW tank pressure drop mbar 190 190 190 190
Flue circuit pressure drop mbar 0.6 0.6 1.5 1.5
DHW connection (male BSP) Ø 2" 2" 2" 2"
Primary connection (female BSP) Ø 2" 2" 2" 2"
Flue connection (G) Ø mm 250 250 250 250
Dimensions A mm 2124 2124 2124 2124
B mm 2250 2250 2250 2250
C mm 1020 1020 1020 1020
D mm 1315 1321 1315 1321
E mm 1020 1020 1020 1020
F mm 600 600 600 600
H mm 1383 1383 1383 1383
J mm 590 590 590 590
Weight empty Kg 545 545 545 545
Weight full Kg 1190 1190 1190 1190
Minimum working gas pressure mbar n/a 20(Nat Gas)/37(LPG) n/a 20(Nat Gas)/37(LPG)
Gas flow rate m3/h n/a 16.3(Nat Gas)/6.29(LPG) n/a 23(Nat Gas)/9(LPG)

Domestic Hot Water Performances

HM150 HM200
(all burners) (all burners)

Peak flow 40°C L/10’ 1504 1675


Peak flow 45°C L/10’ 1289 1444
Peak flow 60°C L/10’ 870 961
HeatMaster® 150 - 200

Peak flow 40°C L/60’ 4828 5890


Peak flow 45°C L/60’ 4138 5057
Peak flow 60°C L/60’ 2864 3348
Continuous flow 40°C L/h 3989 5058
Continuous flow 45°C L/h 3419 4335
Continuous flow 60°C L/h 2393 2865
Reheat time to 60°C min 17 13
28
26
Note : The above performances are based on the hot water being blended at point of use,
with a boiler temperature of 90°C and a domestic cold water inlet of 10°C.

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters
1 2 3 4 5 6
HeatMaster®
71 - 101 23 7

22
8

21 9

10
20

11
19
12
18
13
17
14
16 15

1. Primary NTC sensors 1 and 2 13. Primary water return


pocket connection
2. Domestic cold water inlet 14. Combustion chamber
3. Automatic primary air vent 15. Steel base
4. Flue connection 16. Gas burner
5. Domestic hot water outlet and 17. Combustion chamber plate
hot water NTC3 pocket 18. NIT coated flame tube
6. Stove enamelled metal casing 19. Primary shunt pump
7. Primary water flow connection 20. Control panel
8. Stainless steel flue turbulators 21. Primary expansion vessels
9. Flue pipes 22. Primary filling loop with
10. Rigid polyurethane foam detachable hose and
insulation non-return valve
11. Stainless steel inner tank 23. Removable front panel
12. Primary heating circuit

Product Description Exceptional Performance


The MCBA electronic controller regulates the boiler (start-up, safety,
modulation), the shunt pump and the heating pump in response to
• High performance fully modulating combined boiler hot water and heating demand. The MCBA offers numerous advanced
and water heater features :
• Stainless steel Tank-in-Tank design - A large burner modulation range - down to less than 30%
• Low-NOx premix natural gas/LPG modulating burners - Extremely accurate hot water priority : even very small draw-offs
- from 18.4 to 63 kW for HM71 are immediately detected
- The hot water tank is always kept at an optimum temperature
- from 23 to 96.8 kW for HM101 - Excellent hot water performance
• Can also be used as a stand-alone water heater - Energy efficiency is optimised in both hot water and heating modes.
• Anti-Legionellae : hot water stored at a consistently
high temperature
• Built-in primary circuit shunt pump
The HeatMaster 71 and 101
HeatMaster® 71 -101

• Fully insulated with rigid polyurethane foam are fitted with the BG2000-M
• Stove enamelled casing modulating burner, which
• Control panel including digital MCBA controller complete has a metal fibre (NIT) flame
with self diagnostic system and combined temperature tube and smooth and near-
and pressure gauge silent ignition and operation
- ideal for use in applications
• Available with balanced flue where burner noise must be
• Up to 1219 litres of hot water at 60oC in one hour (HM71) kept to a minimum.
27 • Up to 1813 litres of hot water at 60oC in one hour (HM101)
• Vented or unvented use, with mains pressure
SystemPaks available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Maximum Operating


Primary: 3 bar Temperature
Secondary: 10 bar 90°C
Factory Test Pressure Power Supply
Primary: 4.5 bar 230v 50Hz
Secondary: 13 bar

HM71 HM101

Code 02604501 02604401


Fuel Natural gas/LPG Natural gas/LPG
Burner options type BG2000-M BG2000-M
Input kW 20 to 69.9 25 to 107/22 to 110
Maximum output kW 18.4 to 63 23 to 96.8/20.2 to 99
Primary capacity L 108 130
Total capacity L 239 330
Heating surface area m2 3.14 3.95
Primary circuit pressure drop mbar 46 83
DHW tank pressure drop mbar 45 180
Flue circuit pressure drop mbar 0.6 1.4
DHW connection (male BSP) Ø 1" 1"
Primary connection (female BSP) Ø 11/2” 11/2”
Flue connection (G) Ø mm 150 150
Flue connection options type B23/C13/C33/C53 B23/C13/C33/C53
Dimensions A mm 1743 2093
B mm 1630 2030
C mm 678 678
D mm 937 937
E mm 680 680
F mm 390 390
H* mm 1289 1693
J mm 285 285
Air intake connection Ø mm 80 100
Weight empty Kg 282 335
Weight full Kg 521 665
Minimum working gas pressure mbar 20(Nat Gas)/37(LPG) 20(Nat Gas)/37(LPG)
Gas flow rate m3/h 2.12 to 7.4(Nat Gas/0.82 to 2.86 (LPG) 2.65 to 11.32(Nat Gas/0.9 to 4.5(LPG)
*The HeatMaster 101 is currently fitted with two heating flow outlets – the upper connection (recommended)
is shown by the dimension H. A second connection (compatible with the previous HM100N) is positioned 365mm lower.

Domestic Hot Water Performances

HM71 HM101

Peak flow 40°C L/10' 646 905


Peak flow 45°C L/10' 543 777
HeatMaster® 71 -101

Peak flow 60°C L/10' 346 514


Peak flow 40°C L/60' 2133 3172
Peak flow 45°C L/60' 1794 2680
Peak flow 60°C L/60' 1219 1813
Continuous flow 40°C L/h 1835 2776
Continuous flow 45°C L/h 1573 2379
Continuous flow 60°C L/h 1067 1665
30
28
Reheat time to 60°C min 16 13

Note : The above performances are based on the hot water being blended at point of use,
with a boiler temperature of 90°C and a domestic cold water inlet of 10°C.

Downloaded from www.Manualslib.com manuals search engine


Combined Boilers & Water Heaters

HeatMaster® 4

201 5 2

1
6

7
9
10
8

11

12

13
16

14
15

1. Primary NTC sensors 1 and 9. Flue pipes


2 pocket 10. Rigid polyurethane foam
2. Domestic cold water inlet insulation
3. Primary drain connection 11. Stainless steel inner tank
4. Flue connection 12. Primary heating circuit
5. Domestic hot water outlet and 13. Primary water return
hot water NTC3 pocket connection
6. Control panel mounting bracket 14. Combustion chamber
7. Primary water flow connection 15. Steel base
8. Stainless steel flue turbulators 16. Combustion chamber plate

Product Description

• Very high performance fully modulating combined boiler and water heater
• Stainless steel Tank-in-Tank design
• Low-NOx premix natural gas/LPG modulating burner, from 56 to 214 kW
• Can also be used as a stand-alone water heater
• Anti-Legionellae : hot water stored at a consistently high temperature
• Built-in primary circuit shunt pump
• Fully insulated with 50mm rigid polyurethane foam
HeatMaster® 201

• Stove enamelled casing


• Control panel including digital MCBA controller complete with self diagnostic system
and combined temperature and pressure gauge
• Up to 3534 litres of hot water at 60oC in one hour

29 • Vented or unvented use, with mains pressure SystemPaks available

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Maximum Operating


Primary: 3 bar Temperature
Secondary: 10 bar 90°C
Factory Test Pressure Power Supply
Primary: 4.5 bar 230v 50Hz
Secondary: 13 bar

HM201 Domestic Hot Water Performances


Code 02607401
Fuel Natural gas/LPG
Burner options type BG2000-M HM201
Input - heating kW 60 to 220
Peak flow 40°C L/10' 1745
Input – hot water kW 60 to 240
Peak flow 45°C L/10' 1489
Output - heating kW 55 to 198
Peak flow 60°C L/10' 971
Output – hot water kW 55 to 213
Peak flow 40°C L/60' 6690
Primary capacity L 241
Peak flow 45°C L/60' 5667
Total capacity L 641
Peak flow 60°C L/60' 3534
Heating surface area m2 5.3
Continuous flow 40°C L/h 6117
Primary circuit pressure drop mbar 240
Continuous flow 45°C L/h 5039
DHW tank pressure drop mbar 190
Continuous flow 60°C L/h 2914
Flue circuit pressure drop mbar 2.9
Reheat time to 60°C min 10.5
DHW connection (male BSP) Ø 2"
Primary connection (female BSP) Ø 2"
Flue connection (G) Ø mm 250
Flue connection options type B23/C13/C33/C53 Exceptional Performance
Dimensions A mm 2085
The MCBA electronic controller regulates the boiler
B mm 2252 (start-up, safety, modulation), the shunt pump and the
C mm 1020 heating pump in response to hot water and heating
D mm 1320 demand. The MCBA offers numerous advanced features :
E mm 1020
F mm 600 - A large burner modulation range - down to less
H mm 1383 than 30%
J mm 590 - Extremely accurate hot water priority : even very small
Weight empty Kg 550 draw-offs are immediately detected
Weight full Kg 1191 - The hot water tank is always kept at an optimum
Minimum working gas pressure mbar 20(Nat Gas)/37(LPG) temperature
Gas flow rate – heating m3/h 6.35 to 23.28 (Nat Gas) - Excellent hot water performance
2.45 to 9 (LPG) - Energy efficiency is optimised in both hot water and
Gas flow rate – hot water m3/h 6.35 to 25.4 (Nat Gas) heating modes.
2.45 to 9.81 (LPG)
The HeatMaster 201 is fitted with the BG2000-M
modulating burner, which has a metal fibre (NIT) flame
Note : The above performances are based on the hot tube and smooth and near-silent ignition and operation -
HeatMaster® 201

water being blended at point of use, with a boiler ideal for use in applications where burner noise must be
temperature of 90°C and a domestic cold water kept to a minimum.
inlet of 10°C.

32
30

Downloaded from www.Manualslib.com manuals search engine


Electric Combined Boilers & Water Heaters

E-Tech S 2 1

12

10

3
11

8 6

1. Domestic water and 7. Control thermostat pocket


temperature and pressure 8. Primary water return
relief valve connections connection
2. Primary water flow connection 9. Primary heating circuit
3. Expansion vessel 10. Primary safety valve
4. Stainless steel inner tank 11. Primary low water pressure
5. Primary drain connection switch
6. Heating elements 12. Rigid polyurethane foam
insulation

Product Description
Flexible Installation Options
• Electric combined boiler and water heater
• Power input modulation variable in accordance
with heat demand
The E-Tech S has three
• Stainless steel Tank-in-Tank design
connections for heating
• Can also be used as a stand-alone water heater flow and return, which
• Very easy to maintain allows a choice of
• Anti-Legionellae : hot water stored at consistently installation positions and
high temperature means that the E-Tech S
• Fully insulated with 70mm rigid polyurethane foam can be installed in a corner
for minimal heat loss and against a wall without
• Stove enamelled casing the need to allow free
• Control panel including thermostats, combined space around the unit.
temperature and pressure gauge, All hot and cold water
indicators and on/off switch connections can be fitted
• Up to 14.4 kW output in single phase, up to under the removable top
28.8kW tri-phase
E-Tech S

panel, again saving space


• Vented or unvented use, with mains pressure and resulting in a very tidy
SystemPaks available
installation.
• Integral primary heating sealed system kit and
circulating pump
31 • Small footprint enabling compact installation

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 3 bar
Secondary: 10 bar
Factory Test Pressure
Primary: 4.5 bar
Secondary: 13 bar
Maximum Operating Temperature
90°C

E-Tech S E-Tech S E-Tech S E-Tech S E-Tech S E-Tech S


160 240 290 290 380 380
Single Phase Single Phase Single Phase Tri-Phase Single Phase Tri-Phase
Code 00601001 00601101 00601201 00601201 00601301 00601301
Maximum output kW 14.4 14.4 14.4 28.8 14.4 28.8
Nominal supply V 230 230 230 3 x 400 + N 230 3 x 400 + N
Nominal supply amps 63 63 63 3 x 42 63 3 x 42
Primary capacity L 55 68 97 97 127 127
Total capacity L 161 242 295 295 394 394
Heating surface area m2 1.26 1.87 2.0 2.0 2.6 2.6
DHW connection (male BSP) Ø 3/ ” 3/ ” 1” 1” 11/2” 11/2”
4 4
Primary connection (female BSP) Ø 1" 1" 1" 1" 1" 1"
Dimensions A mm 1432 1953 1784 1784 2134 2134
B mm 620 620 720 720 720 720
C mm 720 720 800 800 800 800
D mm 1282 1800 1627 1627 1985 1985
E mm 290 290 300 300 300 300
Weight empty Kg 115 155 202 202 230 230
Weight full Kg 276 397 497 497 524 524

Domestic Hot Water Performances

E-Tech S E-Tech S E-Tech S E-Tech S E-Tech S E-Tech S


160 240 290 290 380 380
Single Phase Single Phase Single Phase Tri-Phase Single Phase Tri-Phase
Peak flow 40°C L/10' 310 532 645 660 855 870
Peak flow 45°C L/10' 250 452 548 561 725 739
Peak flow 60°C L/10' 168 294 356 365 468 472
Peak flow 40°C L/60' 690 880 990 1305 1200 1516
Peak flow 45°C L/60' 570 750 845 1090 1021 1270
Peak flow 60°C L/60' 375 465 527 625 636 752
Continuous flow 40°C L/h 413 413 413 826 413 826
Continuous flow 45°C L/h 354 354 354 708 354 708
Continuous flow 60°C L/h 248 248 248 415 248 448
Heat up time to 80°C min 61 93 113 91 150 120
E-Tech S

Note : The above performances are based on the hot water being blended at point of use, with a boiler
temperature of 85°C and a domestic cold water inlet of 10°C.
34
32

Downloaded from www.Manualslib.com manuals search engine


Electric Boilers

ETS 1

11

10

8 7 6 5

1. Control panel 6. Control circuit cable


2. Stove enamelled metal entry point
casing 7. Circulating pump
3. Steel boiler shell 8. Primary water flow
4. Primary water return connection
connection 9. Primary expansion vessel
5. Power cable entry position 10. Wiring plate
11. Primary safety valve

Product Description
• Wall hung electric system boiler
• Choice of three sizes and single or tri-phase Plug and Play Installation
- ETS 09 and ETS 15 in single or tri-phase The boiler includes all the necessary components to allow
- ETS 24 tri-phase only direct connection to a heating system without the need for
a feed and expansion cistern, including:
• Up to 14.4 kW output in single phase, up to
28.8kW tri-phase
• Primary 8 litre expansion vessel
• Compatible with Honeywell S-plan and Y-plan (suitable for a system water content of up to 128 litres)
wiring systems • Pressure and temperature gauge
• Built-in control circuit protected by internal 3 amp MCB • Safety valve
• Removable stainless steel immersion elements • Circulating pump
• Quiet operation • Low water pressure switch
• Control and high limit thermostats
• Very low maintenance
• On/off and power level switches
• Stove enamelled casing
• Control panel including thermostats, combined
ETS

temperature and pressure gauge and on/off switch


• Wall mounting bracket included
• Simple connection to heating systems
33
• Can also be used in multiple boiler installations

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Factory Test Pressure Maximum Operating Temperature


Primary: 3 bar Primary: 4.5 bar 85°C

ETS 09 ETS 09 ETS 15 ETS 15 ETS 24


Single Phase Tri-Phase Single Phase Tri-Phase Tri-Phase
Code 00078001 00078001 00078101 00078101 00078201
Nominal Output * kW 8.4 8.4 14.4 14.4 21.6
Nominal supply V 230 3 x 400 + N 230 3 x 400 + N 3 x 400 + N
Nominal supply amps 36 3 x 12 63 3 x 21 3 x 31
Total capacity L 13 13 13 13 13
Primary expansion vessel capacity L 8 8 8 8 8
Primary connection (female BSP) Ø 3/ ” 3/ ” 3/ ” 3/ ” 3/ ”
4 4 4 4 4
Primary pressure drop mbar 1 1 2 2 5
Dimensions Height mm 720 720 720 720 720
Width mm 430 430 430 430 430
Depth mm 300 300 300 300 300
Weight empty Kg 36 36 36 36 36
Weight full Kg 49 49 49 49 49

*Outputs vary depending upon voltage – see technical manual for further clarification

A Modulating Electric Boiler


Boiler temperature with the ETS is controlled by a dual stage thermostat which is set by the user to give the desired boiler
temperature. When the boiler has heated up to within 7°C of the set temperature, the thermostat switches off one power stage and
therefore reduces the heat input.

Thanks to this simple but effective form of modulation, the ETS has longer working cycles and requires less stops and starts, thus
resulting in a more even temperature across the boiler. It also means less wear and tear on components and importantly, it uses less
power once it has reached working temperature.

1. Control circuit connections


2. Control circuit MCB (3amp)
3. Dual stage control thermostat 4 5 6 7 8 9
4. On/off switch
5. 1st stage power level switch
6. 2nd stage power level switch
7. Manual reset high limit thermostat 3
8. Space for optional timeclock
9. Combined temperature and pressure gauge
10. Element supply contactor
11. Power stage delay timer 2 10
12. Power cable connections
13. Control panel 11
14. Primary low water pressure switch
15. Thermostats pocket 1
16. Automatic air vent
17. Heating elements
13
12

14

17
ETS

36
34
16
15

Downloaded from www.Manualslib.com manuals search engine


Electric Boilers

2
TER 1

3
9

8 5

6
7

1. Control panel 6. Element supply contactors


2. Power cable entry position 7. Stove enamelled metal casing
3. Power cable connections 8. Heating elements
4. Control circuit terminals 9. Rigid polyurethane foam
5. Power stage delay timer insulation

Product Description

• Floor standing high output electric boiler Typical Installation


• Steel heating body and removable stainless Three TER boilers providing full heating and hot water
steel heating elements capabilities in conjunction with a Jumbo 1000 hot water
• Six standard models of 57.6 to 259 kW storage tank.
• Four power stages – controlled by a stage delay timer
• Can easily be de-rated to provide less output if required
• Fully wired power and control circuits
• 50mm rigid polyurethane foam insulation
• Stove enamelled casing
• Control panel including thermostats, thermometer,
indicators and on/off switch
• Very little maintenance required
• Can also be used in multiple boiler installations
TER

35

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 4 bar

Factory Test Pressure


Primary: 6 bar

Maximum Operating Temperature


90°C

Rear Front Right Hand Side

TER 57 TER 86 TER 115 TER 144 TER 201 TER 259

Code 00080401 00080801 00081201 00081601 00079101 00079901


Maximum output kW 57.6 86.4 115.2 144 201.6 259.2
Nominal supply V 3 x 400 + N
Nominal supply (total) amps 250.5 376 501 626 876.5 1127
Nominal supply (per phase) amps 83.5 125.3 167 209 292 376
Dual heating elements * # 12 18 24 30 42 54
Total capacity L 155 155 155 155 250 250
Primary connection (female BSP) Ø 2" 2" 2" 2" DN100 DN100
Dimensions A mm 80 80 80 80 80 80
B mm 124 124 124 124 190 190
C mm 1134 1134 1134 1134 1060 1060
D mm 130 130 130 130 197 197
E mm 610 610 610 610 752 752
F mm 1380 1380 1380 1380 1380 1380
G mm 610 610 610 610 752 752
Weight empty Kg 102 102 102 102 195 195
Weight full Kg 257 257 257 257 545 545

* A dual element consists of two elements on a single flange, with a combined output of 4.8 kW at 230 volts

1 2 3 4 5 6 7 8 9

Control Panel

1. Thermometer 5. 3rd stage indicator


2. On/off switch 6. 4th stage indicator
3. 1st stage indicator 7. High temperature overheat indicator
4. 2nd stage indicator 8. Manual reset high limit thermostat
9. Control thermostat
TER

38
36

Downloaded from www.Manualslib.com manuals search engine


Condensing Boilers

Prestige 24-32 11
2

3
1

4
10

5 8

6 7

1. Stainless steel heat exchanger 7. Primary safety valve


2. Low NOx premix gas burner 8. Primary low water pressure
3. Flue connection switch
4. Heating pump 9. Hot water tank (Aquaspeed)
5. Removable front panel 10. DHW feed pump
6. Control panel 11. Insulated casing

Product Description
Optional Wall Mounting Plate

• Very high efficiency wall hung gas condensing boiler


• Stainless steel construction with self-cleaning flueways
• 3 models available :
- Prestige Solo – boiler-only version
- Prestige AquaSpeed – combi boiler with internal
6 litre tank for immediate supply of hot water
- Prestige Excellence – combi boiler with internal
62 litre tank to cope with large peak demands
• Power input modulation variable in accordance with
heat demand
• Very easy to maintain
Prestige 24-32

• Stove enamelled casing


• Control panel including digital MCBA controller complete
with self diagnostic system, and combined temperature The Prestige Solo and AquaSpeed models are available with a
and pressure gauge wall mounting plate containing a primary expansion vessel and
• Heating pump included pre-plumbed boiler connections which allows the system to be
• Suitable for use with polypropylene flue, either concentric connected and filled without the need to mount the boiler. The
37 or twin-tube parallel boiler can thus remain protected in its packaging until all work is
finished and the system is ready for commissioning.

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Factory Test Pressure Maximum Operating Temperature


Primary: 3 bar Primary: 4.5 bar 90°C
Secondary: 10 bar Secondary: 13 bar

24 24 24 32 32 32
Solo AquaSpeed Excellence Solo AquaSpeed Excellence

Code 05605501 05610301 05617501 05605601 05610401 05617613


Fuel Natural gas *
Input kW 7 – 24.4 7 – 24.4 7 – 24.4 7 - 32 7 – 32 7 - 32
Maximum output 80/60oC kW 23 23 23 30.5 30.5 30.5
Minimum output 80/60oC kW 6.9 6.9 6.9 6.9 6.9 6.9
Efficiency max output 45/30oC % 105 105 105 104 104 104
Efficiency min output 45/30oC % 107 107 107 107 107 107
CO emissions min/max mg/kWh 45/20 45/20 45/20 52/20 52/20 52/20
NOx emissions (EN483) mg/kWh 66 66 66 66 66 66
NOx classification 5 5 5 5 5 5
Maximum flue gas temp 80/60oC o
C 92 92 92 108 108 108
Primary capacity L 8 14 16 8 14 16
Total capacity L 8 14.9 70 8 14.9 70
DHW connection (female BSP) Ø 1/ ” 1/ ” 1/ ” 1/ ” 1/ ” 1/ ”
2 2 2 2 2 2
Primary connection (female BSP) Ø 1" 1" 1" 1" 1" 1"
Gas connection (male BSP) Ø 3/ ” 3/ ” 3/ ” 3/ ” 3/ ” 3/ ”
4 4 4 4 4 4
Minimum gas pressure mbar 20 20 20 20 20 20
Flue connection Ø mm 80/125 80/125 80/125 80/125 80/125 80/125
Maximum flue length m 20 20 20 20 20 20
Height mm 900 900 900 900 900 900
Width mm 500 500 630 500 500 630
Depth mm 400 400 470 400 400 470
Depth with mounting plate mm 530 530 n/a 530 530 n/a
Weight empty Kg 50 60 86 50 60 86
Weight full Kg 58 75 156 58 75 156
*LPG models also available

Domestic Hot Water Performances

24 24 24 32 32 32
Solo AquaSpeed Excellence Solo AquaSpeed Excellence
Peak flow 40°C L/10' n/a n/a 175 n/a n/a 224
Peak flow 60°C L/10' n/a n/a 102 n/a n/a 103
Peak flow 40°C L/60' n/a n/a 733 n/a n/a 835
Peak flow 60°C L/60' n/a n/a 352 n/a n/a 353
Continuous flow 40°C L n/a 11/min 653/h n/a 14.5/min 745/h
Continuous flow 60°C L n/a 6.6/min 316/h n/a 8.3/min 320/h

Note : The above performances are based on a domestic cold water inlet of 10°C with the boiler at full working temperature.

Heart of Stainless Steel


Prestige 24-32

ACV’s 80 years of experience using stainless steel in heating and hot water production
have led to the development of a new heat exchanger in stainless steel which is at the
heart of the Prestige 24-32.
Since there is no oxidation in the exchanger, the Prestige attains exceptional output
with efficiency remaining constant throughout the life of the boiler.
The Prestige is also self-cleaning – by trickling along the flue gas pipes, the
condensates constantly clean any combustion residues. The boiler continues to 40
38
function at very high output, and maintenance is limited to the routine annual visits.

Downloaded from www.Manualslib.com manuals search engine


Condensing Boilers

Prestige 47-64-85 2

11

9
3

10
8

6
1
5

7
4

1. Sectional aluminium heat 6. Primary return NTC sensor


exchanger 7. Primary flow NTC sensor
2. Low NOx premix gas burner 8. Primary low water pressure
3. Burner plate switch
4. Control panel with digital 9. Gas pressure switch
display 10. Automatic air vent
5. Inspection plate 11. Flue connection

Product Description

Multiple Boiler Installations


• Very high efficiency wall hung fan-flued gas
condensing boiler
• Aluminium heat exchanger
• Low NOx premix gas or LPG modulating burners
- from 13 to 43 kW for Prestige 47
- from 13 to 58 kW for Prestige 64
- from 20 to 78 kW for Prestige 85
• Power input modulation variable in accordance with
heat demand
Prestige 47-64-85

• Very easy to maintain


• Compact unit, mounted in a room sealed stove
enamelled casing
• Control panel including digital MCBA controller complete The Prestige can be used in battery formation with a cascade of
with self diagnostic system, DHW priority and up to four boilers for high output installations up to 312kW. A
combined temperature and pressure gauge range of pipework connection kits and control systems are
available to suit most applications – details available on request.
39

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 4 bar
Factory Test Pressure
Primary: 6 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz

Prestige 47 Prestige 64 Prestige 85

Code 05602901 05603001 05603101


Fuel Natural gas / LPG
Maximum Input kW 45 60 80
Maximum output kW 13 13 20
Maximum output 80/60oC kW 43.7 58.9 78.2
Minimum output 80/60oC kW 12.6 12.6 19.5
Efficiency max output 80/60oC % 97 98.1 97.7
Efficiency min output 80/60oC % 96.7 96.7 97.5
Efficiency max output 50/30oC % 104.2 103.9 103.4
Efficiency min output 50/30oC % 107.3 107.3 106.8
CO emissions (RAL-UZ 61) mg/kWh 14 27 30
NOx emissions (RAL-UZ 61) mg/kWh 45 55 60
Mass rate of combustion products Kg/h 68 91 121
Flue circuit pressure drop mbar 1.0 1.4 1.5
Primary circuit pressure drop mbar 20 50 70
Flue gas temp 75/60oC oC
58 64 64
Total capacity L 8 8 10
Primary connections (B flow, C return) Ø 11/4” 11/4” 11/4”
Gas connection (D) Ø mm 22 22 22
Condense trap connection (E) Ø mm 25 25 25
Minimum working gas pressure mbar 20 (natural gas) / 37 (LPG)
Maximum gas flow rate m3/h 4.7 (NG) / 3.5 (LPG) 6.3 (NG) / 4.7 (LPG) 8.3 (NG) / 6 (LPG)
Flue connection (A) Ø mm 100/150 100/150 100/150
Maximum flue length * m 34 24 25
Weight empty Kg 87 88 101
Weight full Kg 95 96 111

* 1 bend is equivalent in length to 1m of flue

Domestic Hot Water Requirement?


Prestige boilers can be combined with any
of the ACV range of hot water storage tanks,
in particular the SmartLine range of tanks, to
provide full DHW capabilities. ACV hot water
tanks are ideally suited for use with
condensing boilers because the large heat
exchange area means that the low return
Prestige 47-64-85

temperatures required by the boiler can be


achieved.

42
40

Downloaded from www.Manualslib.com manuals search engine


Oil/Gas Boilers

Compact N
1
11

10

9 2
8
3

7 4

1. Top cover 7. Oil or gas burner


2. Primary water flow and 8. Removable combustion
return connections chamber plate
3. Flue connection 9. Heat exchanger
4. Primary circuit 10. Removable front panel
5. Combustion chamber 11. Control panel
6. Primary drain connection

Product Description

• Floor standing boiler with robust and reliable steel construction


• Ideal low-cost choice for both replacement and new installations
• Choice of pressure jet oil or gas burner
• 3 models with range rateable outputs of 20 to 51 kW
• Factory fitted stove enamelled steel casing and glass wool insulation
• Simple to install – and very easy to maintain with left/right handed door opening
• Control panel including thermostats, combined temperature and pressure gauge,
and on/off switch
Compact N

• Can be used in battery formation for higher output installations

41

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 3 bar
Factory Test Pressure
Primary: 4.5 bar
Maximum Operating Temperature
90°C
Power Supply
230v 50Hz

Compact N1 Compact N2 Compact N3

Code 01130501 01130601 01130701


Fuel Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options Riello oil - Riello pressure jet natural gas/LPG
Minimum input kW 22 30 40
Maximum input kW 28 41 57
Minimum output kW 20 28 36.5
Maximum output kW 25 36 51
Total capacity L 31 37 53
Primary connection (female BSP) Ø 1” 1” 11/4”
Flue circuit pressure drop mbar 0.15 0.17 0.15
Flue connection (D) mm 130 130 150
Dimensions A mm 470 470 530
B mm 700 765 805
C mm 566 566 656
E mm 550 615 645
F mm 445 510 550
G mm 260 260 260
Weight empty (excluding burner) Kg 108 122 157
Weight full (excluding burner) Kg 139 159 210

Simple Installation
The Compact N is supplied fully assembled, with its
robust casing and insulation fitted in the factory.
This makes for a simple installation by the installer,
with heating flow and return and chimney
connections all easily accessible at the rear of the
boiler. There’s even a multi pin plug and socket for
electrical connection.
Compact N

44
42

Downloaded from www.Manualslib.com manuals search engine


Oil/Gas Boilers

Compact A
5 7 9 10

1 2 3 6

1. Ceramic fibre insulation 6. Flue tubes with bimetallic


moulded in one piece spiral turbulators
overlaid on mineral 7. Primary water flow
wool mattress connection
2. Combustion chamber 8. Primary water return
3. Glass wool insulation connection
4. Combustion chamber door 9. Safety valve connection
5. Control panel 10. Open vent connection

Product Description
• Floor standing reverse flame heating boiler
Easy Maintenance
• Robust and reliable steel construction Easy access to the combustion chamber means that
• Choice of pressure jet oil or gas burner, high/low cleaning of the boiler and flueways is straightforward.
and fully modulating versions available
• 3 models of 74 to 235 kW output
• 125mm glass wool insulation
• Combustion chamber door equipped with facility
for left or right hand opening
• Control panel including thermostats, thermometer,
indicators, power socket and on/off switch
• Delivered to site as a bare shell
Compact A

- Allows easy off-loading and positioning


- Insulation and casing are packed separately,
for assembly after installation thus avoiding
damage
43

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure Factory Test Pressure Maximum Operating Temperature


Primary: 5 bar Primary: 7.5 bar 90°C

CA100 CA150 CA200

Code 04120101 04120201 04120301


Fuel Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options Riello oil - Riello pressure jet natural gas/LPG
Minimum input kW 82 134 197
Maximum input kW 109 161 260
Minimum output kW 74 115 185
Maximum output kW 100 140 235
Mass rate of combustion products - gas Kg/h 189 254 451
Mass rate of combustion products – oil Kg/h 199 288 466
Total capacity L 102 122 150
Primary connections (flange) Ø DN50 DN50 DN65
Safety valve connection (female BSP) Ø 1” 1” 1”
Open vent connection (female BSP) Ø 1” 1” 1”
Primary pressure drop mbar 2-5 5 - 11 11 - 31
Flue circuit pressure drop mbar 0.22 – 0.48 0.68 – 0.96 1.83 – 2.5
Flue connection mm 200 200 200
Dimensions (excluding burner)
Length mm 1295 1495 1795
Height mm 1000 1000 1000
Width mm 796 796 796
Weight empty (excluding burner) Kg 315 380 470
Weight full (excluding burner) Kg 417 502 620

Control Panel
The control panel includes :
- On/off switch
- Thermometer
- High/Low thermostats
- High/Low indicator lamps
- High limit thermostat
- Door open warning lamp

Project Reference

Birley Secondary School, Sheffield


A temporary plantroom housed three CA200
boilers providing 705kW of heating for the
temporary teaching classrooms whilst the
school was rebuilt. The boilers were then
moved into their permanent home in a new
plantroom once the building was completed.
Compact A

46
44

Downloaded from www.Manualslib.com manuals search engine


Oil/Gas Boilers

Compact S
3 4 5 6 7

2 8

1 9

10

11

12

1. Flame inspection port 6. Mineral wool insulation


2. Combustion chamber 7. Primary water flow
plate insulation connection
3. Control panel 8. Flue connection
4. Primary water return 9. Primary circuit
connection 10. Combustion chamber
5. Flue tubes and (1st pass)
turbulators (3rd pass) 11. Primary drain connection
12. Heat exchanger (2nd pass)

Product Description

• Floor standing 3 pass high efficiency boiler Control Panel


• Ideal low-cost choice for both replacement
The control panel includes :
and new installations
- On/off switch
• Robust and reliable steel construction - Thermometer
• Choice of pressure jet oil or gas burner, high/low - High/Low thermostats
and fully modulating versions available - High limit thermostat
• 9 models in 3 sizes offering outputs from 176 to 648 kW - Door open warning lamp
• Ceramic fibre door insulation and glass wool insulation - Control fuse
to the boiler body
• Combustion chamber door equipped with facility for
left or right hand opening
• Control panel including thermostats, thermometer,
indicators, power socket and on/off switch
Compact S

• Delivered to site as a bare shell


- Allows easy off-loading and positioning
- Insulation and casing are packed separately, for
assembly after installation thus avoiding damage
• Suitable for low return temperature installations
45

Downloaded from www.Manualslib.com manuals search engine


Technical Specifications

Maximum Operating Pressure


Primary: 5 bar

Factory Test Pressure


Primary: 7.5 bar

Maximum Operating Temperature


90°C

S180 S230 S290 S350 S410 S470 S520 S580 S640

Code 04612+ 001 101 201 301 401 501 601 701 801
Fuel Oil (28 sec or 35 sec) or Natural gas/LPG
Burner options Riello oil - Riello pressure jet natural gas/LPG
Input kW 190.2 255.7 318.2 384 448.3 509.8 575.6 639.7 707.4
Output kW 176.5 235.8 294.7 354.4 412.9 471.6 531.9 588.5 648.7
Net combustion efficiency % 92.8 92.2 92.6 92.3 92.1 92.5 92.4 92 91.7
Flue gas temperature oC 185 188 190 193 195 190 193 195 198
Mass rate of combustion products (oil) Kg/sec 80.5 108.2 134.7 168.1 195.0 223.2 250.3 276.4 299.4
Primary pressure drop mbar 15.1 22.2 15.1 21.2 31.8 14.2 17.8 24.4 28.5
Flue circuit pressure drop mbar 1 1.5 2.0 2.4 2.8 2.8 3.0 3.4 3.8
Total capacity L 290 456 681
Primary connections (flange) Ø DN65 DN80 DN100
Safety valve connection (female BSP) Ø 11/4“ DN50 DN65
Flue connection mm 200 200 250
Dimensions A mm 1870 2135 2395
B mm 1300 1504 1742
C mm 800 800 855
D mm 160 160 190
E mm 850 830 1050
F mm 280 440 440
G mm 150 250 320
H mm 960 1200 1365
L mm 600 720 780
M mm 1390 1600 1770
N mm 1295 1540 1700
Weight empty (excluding burner) Kg 550 925 1130
Weight full (excluding burner) Kg 840 1381 1811

Easy Access
The left/right hinged door offers the best possible accessibility to
the chamber and to the flue gas tubes, even in confined plantrooms.
Compact S

48
46

Downloaded from www.Manualslib.com manuals search engine


Concentric Flue Systems
Prestige 24 - 32
Delta Performance FV/MV 35
STEEL - STAINLESS STEEL Ø 80/125

A TERMINALS
A Code Type
537d6196 Vertical terminal
537d6173 Horizontal terminal

B
B FLUE PIPE
Code Type
537d6174 Length 250 mm
537d6175 Length 500 mm
537d6176 Length 1000 mm

D
C ADJUSTABLE FLUE PIPE
Code Type
537d6177 500 mm adjustable
length 325-400

D FLUE BENDS
Code Type
C 537d6178 Bend 43°- 45°
537d6179 Bend 87°- 90°

E CONDENSATE RECOVERY AND GAS ANALYSER CONNECTOR

Code Type
537d6180 Gas analyser with
condensate recovery
Concentric Flue Systems

F FLASHINGS AND BRACKETS


Code Type
537d6181 Flat roof flashing
537d6182 Adjustable flashing
537d6183 Bracket 125 mm

47

Downloaded from www.Manualslib.com manuals search engine


Prestige 47 - 64 - 85
Delta Performance FV/MV 50
FULLY STAINLESS STEEL Ø 100/150

A TERMINALS
Code Type
A
537d6197 Vertical terminal
537d6198 Horizontal terminal

B
B FLUE PIPE
Code Type
537d6199 Length 250 mm
537d6200 Length 500 mm
537d6201 Length 1000 mm

C ADJUSTABLE FLUE PIPE D


Code Type
537d6202 500 mm adjustable
length 325-400

D FLUE BENDS
Code Type
537d6203 Bend 43°- 45°
537d6204 Bend 87°- 90°
C
E

E CONDENSATE RECOVERY AND GAS ANALYSER CONNECTOR

Code Type
537d6205 Condensate recovery device
537d6206 Gas analyser connector
537d6207 Adaptor 100/150 - 100/100
Concentric Flue Systems

F FLASHINGS AND BRACKETS


Code Type
537d6208 Flat roof flashing
537d6209 Adjustable flashing
537d6210 Bracket 150 mm