0% found this document useful (0 votes)
17 views113 pages

Datexel Catalog

The document discusses Datexel, an Italian company that manufactures electronic equipment for industrial automation and process control. It highlights Datexel's expertise, reliability, and professionalism. The company's product range is vast and includes transmitters, temperature converters, galvanic isolators, and other devices that satisfy various industrial sectors. Datexel prioritizes technological innovation through constant research and development to offer integrated solutions and high quality testing.

Uploaded by

Mihailo Jovic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
17 views113 pages

Datexel Catalog

The document discusses Datexel, an Italian company that manufactures electronic equipment for industrial automation and process control. It highlights Datexel's expertise, reliability, and professionalism. The company's product range is vast and includes transmitters, temperature converters, galvanic isolators, and other devices that satisfy various industrial sectors. Datexel prioritizes technological innovation through constant research and development to offer integrated solutions and high quality testing.

Uploaded by

Mihailo Jovic
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 113

ELECTRONIC AND CONTROL PROCESS DEVICES

EXP ER TISE I R EL IAB ILI TY I P R OF ES S IO NA L IS M


01

WWW.DATEXEL.IT CATALOGU E
WWW.DATEXEL.IT ELECTRONIC AND CONTROL PROCESS DEVICES
Summary Series

01
Temperature and signal SLIM
converters (from PAG.1) series

02
Temperature and signal transmitters SMART
and converters for DIN rail mounting (from PAG.10) series

03
Temperature and signal transmitters and converters for use SMART ATEX
in potentially explosive atmospheres in according to the series
ATEX 94/9/EC directive . (from PAG.18)

04
Temperature and signal transmitters P.D.S.
and converters, isolators signal splitters (from PAG.28) series

05
Trip amplifiers for din DAT5028 / DAT5024
rail mounting (from PAG.38) Trip amplifiers

06
Signal transmitters and converters, DAT200 / DAT500
galvanic isolators (from PAG.44) series

07
Data acquisition and control modules DAT3000
(from PAG.50) series

08
Intelligent modules DAT9000
(from PAG.64) series

09
A/d interface Modules for plc DAT6000
“DAT6000 SERIES” (from PAG.73) series

10
Temperature transmitters for DIN B DAT1000
In-head mounting (from PAG.78) series

11
Digital meters and DAT 9550 / DAT8050
Indicators for panel mounting (from PAG.84) DAT700 series

12
MEANWELL DIN rail power supply. Accessories
Software and interfaces between device and PC (from PAG.90) and software

www.datexel.it
Product Index

Temperature and signal


converters SLIM series
(PAG.1 / PAG.9)

Temperature and signal transmitters


and converters SMART series
(PAG.10 / PAG.17)

Temperature and signal transmitters and converters for use in


potentially explosive atmospheres. ATEX 94/9/EC
(PAG.18 / PAG.27)

Temperature and signal transmitters


and converters for DIN rail mounting
P.D.S. series
(PAG.28 / PAG.37)

Trip amplifiers for din rail mounting


DAT5024/5028 series
(PAG.38 / PAG.43)

Signal transmitters and converters


DAT200 series
Galvanic isolators DAT500 series
(PAG.44 / PAG.49)
Data acquisition and control
modules DAT3000 series
(PAG.50 / PAG.63)

Intelligent units
DAT9000 series
(PAG.64 / PAG.71)

A/D interface Modules for PLC


DAT6000 series
(PAG.72 / PAG.77)

II

Temperature transmitters for DIN B


In-head mounting DAT1000 series
(PAG.78 / PAG.83)

Digital meters and indicators for panel mounting


DAT9550, DAT8050, DAT700 series
(PAG.84 / PAG.89)

Meanwell power supply MDR series


(PAG.92 / PAG.93)

Accessories and software


(PAG.94 / PAG.95)
expertise • reliability • professionalism
The Company
The success of a company depends on many factors:
expertise, reliability, professionalism.
If all this is also true for DATEXEL, nevertheless it is not
enough to draw a full picture.

DATEXEL was founded in 1992 on the commitment and


ambitions of a few partners as a small provincial company,
and through the years became a consolidated entity
that today operates on national and international
markets as a manufacturer of electronic equipment
for industrial automation and process control.

III

Products that represent innovative solutions


capable of satisfying the requirements of the main
industrial automation sectors:
• Energy production
• Oil
• Foodstuffs
• Pharmaceutical
• Chemical industry
• Water processing
• Automation & engineering
• Paper

www.datexel.it
a wide range
of products
The DATEXEL range is vast and complete :
Transmitters, Temperature converters (both analogue and
digital), Galvanic isolators, Signal splitters, Distributed I/O
modules, A/D interface modules for PLC, Trip amplifiers,
Power suppliers, Current loop isolators, Digital meters and
Indicators.

Products that represent innovative solutions capable


of satisfying the requirements of the main industrial
automation sectors: energy production, oil, foodstuffs,
pharmaceutical, chemical industry, water processing,
automation & engineering, paper.

IV

The DATEXEL range is vast and complete:

ELECTRONIC AND CONTROL PROCESS DEVICES


• Transmitters
• Temperature converters (both analogue and digital)
• Galvanic isolators
• Signal splitters
• Distributed I/O modules
• A/D interface modules for PLC
• Trip amplifiers
• Power suppliers
• Current loop isolators
• Digital meters and Indicators
The synergy
DATEXEL, there is
But behind the equipments and systems branded
the dedication and professionalism of our employees.
All work processes (design, assembly, testing) are carried out within our
company.

DATEXEL is organized:
• DESIGN/ RESEARCH & DEVELOPMENT
• PRODUCTION
• SALES ITALY / ABROAD
• ADMINISTRATION and PURCHASING
• QUALITY

Constant

expertise • reliability • professionalism


research and Technological innovation and the constant search
development for integrated solutions allow us to offer our
customers an exclusive service: the work process is carried
out automatically with the use of cutting-edge machinery (pick

and place for assembly), and the products are 100% tested,

also thanks to the use of specific software applications and

instruments regularly subjected to calibration.


The team
All departments and offices are perfectly integrated and
compatible one with the other. And each one contributes
to the company’s overall success.
Specifically, the SALES, RESEARCH & DEVELOPMENT–
DESIGN, PRODUCTION units play a crucial role.
During the design phase, a team of specialized technicians
assists the customer, identifying all its specific needs and
requirements.
In thePRODUCTION department, duly trained person-
nel handle the manufacture and finishing of DATEXEL
equipment, as well as the final testing (before the delivery).
In a constantly evolving sector such as industrial automa-
tion, RESEARCH & DEVELOPMENT represents a stra-
tegic department capable of acquiring and maintaining
COMPETITIVE ADVANTAGES.

VI

the ambitions
The company’s growth and expansion philosophy tran-
slates into a wider and wider product offer.

As a result, qualified personnel are always searching for


customers and distributors in order to acquire new mar-
kets: not only in Italy, but in EC and non-EC countries too,
specifically in developing countries such as Brazil, South
Africa, Australia and China.

New and distant horizons then: the same horizons that


DATEXEL is striving to reach in the areas of quality and
innovation as well.

www.datexel.it
Quality
control
DATEXEL invests significantly in RESEARCH & DEVELOPMENT,
obtaining first-class results thanks to the contribution of highly specia-
lized researchers and technicians.

And let’s not forget the QUALITY factor: DATEXEL has taken on the
quality challenge, developing a careful study of production processes
and paying great attention to materials and innovative systems.

Operating daily in full compliance with quality standards has made it


DATEXEL to obtain its certification according to Standard
possible for
UNI EN ISO 9001 (1996), subsequently converted into the current
standard ISO 9001:2008.

VII

Another important acknowledgement is the ATEX 94/9/EC certification,


concerning the type-approval of safety requirements for equipment
and protection systems intended for use in potentially explosive atmo-
spheres.

Lastly, in July 2006 DATEXEL conformed to the RoHS Directive (regu-


lation 2002/95/EC) which sets restrictions on the use of certain hazar-
dous substances when building various types of electric and electro-
nic equipment, thus offering environmental guarantees as well with its
products.
A well-structured organization, operating in facilities that
cover a surface area of 450 square meters, with spaces efficien-
tly subdivided into three macro areas: managerial, technical,
production.

With regards to the sales area, DATEXEL relies on an in-com-


pany division that interacts with Customers on a daily basis in
handling the usual commercial activities (issuing proposals or
negotiating discounts or delivery times), through a capillary net-
work of distributors (in Italy and abroad) that coordinates and
provides assistance with an uninterrupted series of contacts.

VIII

www.datexel.it
application
areas

The products of Datexel cover several type of applications due to a wide variety of conditions of use and
ambient factors:

Industries:

Industrial automation and control process linked to all sectors.

Food business:

Food production, Cellars, dairies, pasta production, packaging and bottling lines.

IX
Energy:

Thermal, hydropower, alternative energy (photovoltaic, solar, geothermal, wind, etc...)

Board Machine - Industrial automation:

Process control in steel plants, steel works, cement works, pharmaceutical, food and paper
industry, etc.

Water treatment:

Water recycling, dams, remote control and management, data-logging.

Petrochemical offshore:

Process control in the petrochemical and offshore sectors.


00
SLIM 01
Series

SMART
02
Series

SMART ATEX
03
Series

P.D.S.
04
Series
ELECTRONIC AND CONTROL PROCESS DEVICES

Trip amplifiers
05
DAT5028 / DAT5024

DAT200 / DAT500
06
Series

DAT3000
07
Series

DAT9000
08
Series

PRODUCT CATALOGUE
www.datexel.it

DAT6000
09
Series

DAT1000
10
Series

DAT 9550 / DAT8050


11
DAT700 Series

Accessories
12
and software
01 SLIM SERIES

ELECTRONIC AND CONTROL PROCESS DEVICES

Temperature and signal converters


“SLIM SERIES”
The line of converters “SLIM series”has been designed to provide to the
user the highest flexibility in the signals conversion.
The series is composed of:
- Converters for universal input with double output and trip amplifier
(DAT4530)
- Single channel converters dedicated for typology of input (DAT4531)
- Double channel converters (two independent inputs and outputs)
dedicated for typology of input (DAT4532)
- Signal splitters dedicated for typology of input (DAT4631)
- Mathematical modules (DAT4632D)
- Frequency converters (DAT4540)
It is possible to program the devices either via dip-switches to set the
most common input and output ranges or via Personal Computer using
the software DATESOFT by which the user can personalize the input and
output ranges for his own necessities.

All of these features are available in only 12.5 mm thickness.

INDEX
02 • DAT 4530
Universal isolated converter configurable by Dip-Switch or PC
double output & trip amplifier

03 • DAT 4531 A
Isolated converter for TC and mV configurable by Dip-Switch or PC
DAT 4531 B
Isolated converter for RTD and resistance configurable by Dip-Switch or PC

04 • DAT 4531 C
Isolated converter for PTC/NTC/Pot configurable by Dip-Switch or PC
DAT 4531 D
Isolated converter for voltage and current configurable by Dip-Switch or PC

05 • DAT 4532 A
Double channel, isolated converter for TC and mV configurable by Dip-Switch or PC
DAT 4532 B
Double channel, isolated converter for RTD and resistance configurable by Dip-Switch or PC

06 • DAT 4532 C
Isolated, double channel converter for PTC/NTC/Pot configurable by Dip-Switch or PC
DAT 4532 D
Double channel, isolated converter for voltage and current configurable by Dip-Switch or PC

07 • DAT 4540
Isolated F/V, F/I Converter Configurable by Dip-Switch or PC, Transistor or Relay Outputs
DAT 4631 A
Isolated Splitter / Converter for TC and mV configurable by Dip-Switch or PC

08 • DAT 4631 B
Isolated Splitter / Converter for RTD and resistance configurable by Dip-Switch or PC
DAT 4631 C
Isolated, Splitter / Converter for PTC/NTC/Pot configurable by Dip-Switch or PC

09 • DAT 4631 D
Isolated Splitter / Converter for voltage and current configurable by Dip-Switch or PC
DAT 4632 D
Isolated mathematical module for voltage and current input configurable by Dip-Switch or PC
SLIM SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
01

SLIM Temperature and signal


series converters
UNIVERSAL ISOLATED CONVERTER CONFIGURABLE BY
DIP-SWITCH OR PC DOUBLE OUTPUT & TRIP AMPLIFIER
DAT4530 GENERAL DESCRIPTION
The universal isolated converter DAT 4530 is able to measure and linearise voltage, current and resistance signals, potentiometers and
the standard thermocouples and Sensors with, if required, the cold junction compensation, the wires compensation.
For mV, V and mA input it is possible to set an option for the fast sampling (option HS) or to extract the square root of the measured
signal (option SQRT). In function of programming, the measured values are converted in a current or voltage signal on the two outputs.
Moreover an output contact is available as trip alarm.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - High accuracy


- Universal configurable input for: - On-field reconfigurable
mV, TC, RTD, Res, Potentiometer, V and mA - Galvanic isolation among all the ways
- Two outputs configurable in current or voltage - EMC compliant – CE mark
- Trip alarm - Suitable for DIN rail mounting in compliance with
- Configurable by dip-switch or PC EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY ISOLATION TEMPERATURE AND HUMIDITY


Operative temperature -20°C .. +60°C
Power supply voltage 20 .. 30 Vdc
Among all the 1500 Vac, Storage temperature -40°C .. +85°C
ways 50 Hz, 1 min
SLIM SERIES

Rever. polarity protection 60 Vdc max)


Humidity (not condensed) 0 .. 90 %

CURRENT CONSUMPTION EMC (for industrial environments) ALARM TRIP HOUSING


DIRECTIVE : 2004 / 108 / EC Contact SPST Material Self-extinguishing plastic
Current output 90 mA max.
Max Load (resistive):
Immunity EN 61000-6-2 Dimensions
W x L x H : 90 x 112 x 12.5
Voltage 48 V (ac/dc) (mm)
Voltage output 30 mA max.
Emission EN 61000-6-4 Current 0.4 A Weight about 90 g.

INPUT Linearity (1)


Input type Min Max Span min TC, RTD ± 0.1 % f.s.
2 TC (CJC int./ext.) mV, V, mA ± 0.05 % f.s.
J -200°C 1200°C 100°C Input impedance
K -200°C 1300°C 100°C TC, mV >= 10 MΩ
S 0°C 1750°C 400°C mA ~22 Ω
Sensor excitation current
R 0°C 1750°C 400°C
RTD,Res 400 uA
B 0°C 1850°C 400°C
Voltage Aux. >18 V @ 20 mA
E -200°C 1000°C 100°C
Line resistance influence (1)
T -200°C 400°C 100°C
TC, mV <=0.8 uV/Ohm
N -200°C 1300°C 100°C
RTD 3 wires 0.05%/Ω (50 Ω max balanced)
Voltage RTD 4 wires 0.005%/Ω (100 Ω max balanced)
mV -100 mV +90 mV 5 mV Thermal drift (1)
mV -100 mV +200 mV 10 mV Full scale ± 0.01 % / °C
mV -100 mV +800 mV 20 mV CJC ± 0.01 % / °C
RTD (2, 3, 4 wires) CJC compensation ± 0.5°C
Pt100 -200°C 850°C 50°C
Pt1000 -85°C 185°C 30°C OUTPUT (2 CHANNELS)
Ni100 -60°C 180°C 50°C Output type Min Max Span min
Ni1000 -60°C 150°C 30°C Current 0 mA 20 mA 4 mA
Voltage 0 V 10 V 1 V
0Ω 500 Ω 50 Ω
RES. (2, 3, 4 wires) Output calibration
0Ω 2000 Ω 50 Ω
Current ± 7 uA
Pot. (Rnom.< 50KΩ) 0% 100 % 10 %
Voltage ± 5 mV
Voltage -10 V 10 V 1V
Voltage Aux. >12V @ 20 mA
Current 0 mA 20 mA 1 mA
Burn-out values
Calibration (1) Max. output value 22 mA or 11 V
mV, TC the higher of ±0.1 % and ±12 uV Min. output value 0 mA or -0.6 V
RTD the higher of ±0.1 % and ±0.2°C Output load Resistance - Rload
Res. the higher of ±0.1 % and ±0.15 Current output < 500 Ω
Potentiometer ± 0.05 % f.s.
Voltage output > 10 KΩ
Volt the higher of ±0.1 % and ± 2 mV
Short circuit current 30 mA max
mA the higher of ±0.1 % and ± 6 uA
about 400 ms
mV, V, mA ± 0.5 % f.s (opt. HS) Response time (10÷ 90% of F.S)
100 ms (opt. HS)
(1) referred to the input Span (difference between max. and min.)

www.datexel.it
ISOLATED CONVERTER FOR TC AND mV CONFIGURABLE BY DIP-SWITCH OR PC

DAT 4531 A GENERAL DESCRIPTION


The isolated converter DAT 4531 A is able to measure and linearise the standard thermocouples with internal or external cold junction
compensation. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for TC and mV - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance
- High accuracy with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT Line resistance influence (1)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min TC, mV <=0.8 uV/Ohm
Rever. polarity protection 60 Vdc max TC (CJC int./ext.) Thermal drift (1)
CURRENT CONSUMPTION J -200°C 1200°C 100°C Full scale ± 0.01% / °C
Current output 35 mA max. K -200°C 1300°C 100°C CJC ± 0.01% / °C
Voltage output 20 mA max. S 0°C 1750°C 400°C CJC compensation ± 0.5°C
R 0°C 1750°C 400°C
ISOLATION OUTPUT
B 0°C 1850°C 400°C
Among all the 1500 Vac, Output type Min Max Span min
ways 50 Hz, 1 min E -200°C 1000°C 100°C
Current 0 mA 20 mA 4 mA
T -200°C 400°C 100°C
TEMPERATURE AND HUMIDITY Voltage 0 V 10 V 1 V
N -200°C 1300°C 100°C

SLIM SERIES
Operative temperature -20°C .. +60°C Output calibration
Voltage
Storage temperature -40°C .. +85°C mV -100 mV +90 mV 5 mV Current ± 7 uA
mV -100 mV +200 mV 10 mV Voltage ± 5 mV
Humidity (not condensed) 0 .. 90 %
mV -100 mV +800 mV 20 mV Burn-out values
EMC (for industrial environments) Input calibration (1) Max. output value 22 mA or 11 V
DIRECTIVE : 2004 / 108 / EC mV, TC > ± 0.1 % f.s. and ± 12 uV Min. output value 0 mA or -0.6 V
Immunity EN 61000-6-2 Output load Resistance - Rload
Linearity (1)
Emission EN 61000-6-4 TC ± 0.2 % f.s. Current output < 500 Ω
HOUSING mV ± 0.1 % f.s. Voltage output > 10 KΩ
Material Self-extinguishing plastic Input impedance (1) Short circuit current 26 mA max
Dim. (mm) W x L x H : 90 x 112 x 12.5 TC, mV >= 10 MΩ Response time (10÷90% of f.s.) about 500 ms
Weight about 90 g. (1) referred to the input Span (difference between max. and min.) 3
ISOLATED CONVERTER FOR RTD AND RESISTANCE CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4531 B

The isolated converter DAT 4531 B is able to measure and linearise the standard RTD and resistances with 2 or 3 wires cable
compensation.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD and resistance - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance with
- High accuracy EN-50022 and EN-50035
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max RTD (2, 3 wires) Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Pt100 -200°C 850°C 50°C Voltage 0 V 10 V 1 V
Current output 35 mA max. Pt1000 -85°C 185°C 30°C Output calibration
Voltage output 20 mA max. Ni100 -60°C 180°C 50°C Current ± 7 uA
ISOLATION Ni1000 -60°C 150°C 30°C Voltage ± 5 mV
Among all the 1500 Vac, RES. (2, 3 0Ω 500 Ω 50 Ω Burn-out values
ways 50 Hz, 1 min wires) 0Ω 2000 Ω 50 Ω Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Calibration (1) Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C RTD the higher of ±0.1 % f.s. and ±0.2°C Output load Resistance - Rload
Storage temperature -40°C .. +85°C Low Res. the higher of ±0.1 % f.s. and ±0.15 Ω Current output < 500 Ω
High Res. the higher of ±0.2 % f.s. and ± 1 Ω Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 %
Linearity (1) Short circuit current 26 mA max
EMC (for industrial environments)
RTD ± 0.1 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC
Immunity EN 61000-6-2 Sensor excitation current (1) referred to the input Span (difference between max. and min.)
Emission EN 61000-6-4 RTD, Res 500 uA
Line resistance influence (1)
HOUSING
RTD 3 wires 0.05%/Ω (50 Ω max balanced)
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
Weight about 90 g. Full scale ± 0.01% / °C

www.datexel.it
ISOLATED CONVERTER FOR PTC/NTC/POT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4531 C The isolated converter DAT 4531 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for PTC, NTC and Pot. - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance
- High accuracy with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max PTC Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION KTY81-210 -55°C 150°C 50°C Voltage 0 V 10 V 1 V
Current output 35 mA max. KTY81-220 -55°C 150°C 50°C Output calibration
Voltage output 20 mA max. KTY84-130 -40°C 300°C 50°C Current ± 7 uA
ISOLATION KTY84-150 -40°C 300°C 50°C Voltage ± 5 mV
Among all the 1500 Vac, NTC Burn-out values
ways 50 Hz, 1 min Coster 10K -10°C 100°C 50°C Max. output value 22 mA or 11 V
SLIM SERIES

TEMPERATURE AND HUMIDITY Coster 1K -30°C 40°C 25°C Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Pot. Output load Resistance - Rload
0% 100 % 10 %
(Rnom.< 50KΩ) Current output < 500 Ω
Storage temperature -40°C .. +85°C
Calibration (1) Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 % PTC, NTC the higher of ±0.1 % f.s. and ±0.2°C Short circuit current 26 mA max
EMC (for industrial environments) Potentiometer ± 0.05 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC Linearity (1)
Immunity EN 61000-6-2 PTC, NTC ± 0.1 % f.s.
Emission EN 61000-6-4 Sensor excitation current
HOUSING PTC,NTC 500 uA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full scale ± 0.01% / °C
4 Weight about 90 g. (1) referred to the input Span (difference between max. and min.)

ISOLATED CONVERTER FOR VOLTAGE AND CURRENT CONFIGURABLE BY DIP-SWITCH OR PC


GENERAL DESCRIPTION
DAT 4531 D

The isolated converter DAT 4531 D is able to measure voltage and current signals. In function of programming, the measured values
are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for voltage and current - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance with
- High accuracy EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max Voltage 0V 10 V 1V Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Current 0 mA 20 mA 1 mA Voltage 0 V 10 V 1 V
Current output 35 mA max. Calibration (1) Output calibration
Voltage output 20 mA max. Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
ISOLATION mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV
Among all the 1500 Vac, Linearity (1) Burn-out values
ways 50 Hz, 1 min
V, mA ± 0.05 % f.s. Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Input impedance Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Volt >= 1 MΩ Output load Resistance - Rload
Storage temperature -40°C .. +85°C Current <= 50 Ω Current output < 500 Ω

Humidity (not condensed) 0 .. 90 %


Thermal drift (1) Voltage output > 10 KΩ
Full scale ± 0.01% / °C Short circuit current 26 mA max
EMC (for industrial environments)
Response time (10÷90% of f.s.) about 100 ms
DIRECTIVE : 2004 / 108 / EC
Immunity EN 61000-6-2 (1) referred to the input Span (difference between max. and min.)
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.

www.datexel.it
DOUBLE CHANNEL, ISOLATED CONVERTER FOR TC AND mV CONFIGURABLE BY DIP-SWITCH OR PC

DAT 4532 A GENERAL DESCRIPTION


The isolated converter DAT 4532 A is able to measure and linearise the standard thermocouples with internal or external cold jun-
ction compensation. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.

FEATURES - High accuracy


- Configurable input for TC and mV - On-field reconfigurable
- Configurable output in Current or Voltage - Galvanic isolation among the ways
- Configuration by PC allows to program the two - EMC compliant – CE mark
channels with two independent settings - Suitable for DIN rail mounting in compliance
- Double channel in the same enclosure with EN-50022 and EN-50035
- Configurable by dip-switch or PC
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (2 CHANNELS) Line resistance influence (1)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min TC, mV <=0.8 uV/Ohm
Rever. polarity protection 60 Vdc max TC (CJC int./ext.) Thermal drift (1)
CURRENT CONSUMPTION J -200°C 1200°C 100°C Full scale ± 0.01 % / °C
Current output 55 mA max. K -200°C 1300°C 100°C CJC ± 0.01 % / °C
Voltage output 25 mA max. S 0°C 1750°C 400°C CJC compensation ± 0.5°C
R 0°C 1750°C 400°C
ISOLATION OUTPUT (2 CHANNELS)
B 0°C 1850°C 400°C
Among all the 1500 Vac, Output type Min Max Span min
ways 50 Hz, 1 min E -200°C 1000°C 100°C
Current 0 mA 20 mA 4 mA
T -200°C 400°C 100°C
TEMPERATURE AND HUMIDITY Voltage 0 V 10 V 1 V
N -200°C 1300°C 100°C

SLIM SERIES
Operative temperature -20°C .. +60°C Output calibration
Voltage
Storage temperature -40°C .. +85°C mV -100 mV +90 mV 5 mV Current ± 7 uA
mV -100 mV +200 mV 10 mV Voltage ± 5 mV
Humidity (not condensed) 0 .. 90 %
mV -100 mV +800 mV 20 mV Burn-out values
EMC (for industrial environments) Input calibration (1) Max. output value 22 mA or 10.6 V
DIRECTIVE : 2004 / 108 / EC mV, TC the higher of ±0.1 % f.s. and ±12 uV Min. output value 0 mA or -0.6 V
Immunity EN 61000-6-2 Output load Resistance - Rload
Linearity (1)
Emission EN 61000-6-4 TC ± 0.2 % f.s. Current output < 500 Ω
HOUSING mV ± 0.1 % f.s. Voltage output > 10 KΩ
Material Self-extinguishing plastic Input impedance Short circuit current 26 mA max
Dim. (mm) W x L x H : 90 x 112 x 12.5 TC, mV >= 10 MΩ Response time (10÷90% of f.s.) about 500 ms
Weight about 90 g. (1) referred to the input Span (difference between max. and min.) 5
DOUBLE CHANNEL, ISOLATED CONVERTER FOR RTD AND RESISTANCE CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 B

The isolated double channel converter DAT 4532 B is able to measure and linearise the standard RTD and resistances with 2 or 3 wires
cable compensation. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.

FEATURES - On-field reconfigurable


- Configurable input for RTD and resistance - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Double channel in the same enclosure - Suitable for DIN rail mounting in compliance with
- Configurable by dip-switch or PC EN-50022 and EN-50035
- High accuracy
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ss

nt
F
ne
B

Application areas

ALIMENTAZIONE
POWER SUPPLY INPUT (2 CHANNELS) OUTPUT
USCITA (2(2canali)
CHANNELS)
Tensione
Power supply
di alimentazione
voltage 18 .. 30 Vdc Input type Min Max Span min Output type
Tipo uscita Min Max Span min
Protezione
Rever. polarity
invers.
protection
polarità 60 Vdc max RTD (2, 3 wires) Current
Corrente 0 mA 20 mA 4 mA
CONSUMO
CURRENT CONSUMPTION
DI CORRENTE Pt100 -200°C 850°C 50°C Voltage
Tensione 0 V 10 V 1 V
Uscita
Currentinoutput
corrente 35
55 mA max. Pt1000 -85°C 185°C 30°C Output calibration
Calibrazione uscita
Uscita
Voltageinoutput
tensione 20
25 mA max. Ni100 -60°C 180°C 50°C Current
Corrente ± 7 uA
ISOLATION
ISOLAMENTO Ni1000 -60°C 150°C 30°C Voltage
Tensione ± 5 mV
Among all the 1500 Vac, RES. (2, 3 0Ω 500 Ω 50 Ω Burn-out values
Valori di fuori scala
Su tutte le vie
ways 50 Hz, 1 min wires) 0Ω 2000 Ω 50 Ω Max. output
Valore value
max. uscita 22 mA or 10.6VV
o 10.6
TEMPERATURE AND HUMIDITY Calibration (1) Min. output
Valore value
min. uscita 0 mA or -0.6VV
o -0.6
Operative temperature -20°C .. +60°C RTD the higher of ±0.1 % f.s. and ±0.2°C Output loaddiResistance
Resistenza - Rload
carico su uscita - Rload
Storage temperature -40°C .. +85°C Low Res. the higher of ±0.1 % f.s. and ±0.15 Ω Current
Uscita inoutput
corrente < 500 Ω
W
High Res. the higher of ±0.2 % f.s. and ± 1 Ω Voltage
Uscita inoutput
tensione > 10 KΩ
KW
Humidity (not condensed) 0 .. 90 %
Linearity (1) Short circuit
Corrente current
di corto-circuito 26 mA max
EMC (per
(for industrial
gli ambienti
environments)
industriali)
RTD ± 0.1 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRETTIVA
DIRECTIVE :: 2004
2004 // 108
108 // EC
EC
Immunità
Immunity EN 61000-6-2 Sensor excitation current (1) referred to the input Span (difference between max. and min.)
Emissione
Emission EN 61000-6-4 RTD, Res 500 uA
Line resistance influence (1)
CONTENITORE
HOUSING
RTD 3 wires 0.05 %/Ω (50 Ω max balanced)
Materiale
Material Plastica
Self-extinguishing
auto-estinguente
plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
Peso
Weight 90
about
g. circa
90 g. Full scale ± 0.01 % / °C

www.datexel.it
DOUBLE CHANNEL, ISOLATED CONVERTER FOR PTC/NTC/POT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 C The isolated double channel converter DAT 4532 C is able to measure and linearise the standard PTC and NTC sensors and poten-
tiometers. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.

FEATURES - On-field reconfigurable


- Configurable input for PTC, NTC and Pot. - Galvanic isolation among the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Double channel in the same enclosure - Suitable for DIN rail mounting in compliance with
- Configurable by dip-switch or PC EN-50022 and EN-50035
- High accuracy
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (2 CHANNELS) OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max PTC Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION KTY81-210 -55°C 150°C 50°C Voltage 0 V 10 V 1 V
Current output 55 mA max. KTY81-220 -55°C 150°C 50°C Output calibration
Voltage output 25 mA max. KTY84-130 -40°C 300°C 50°C Current ± 7 uA
ISOLATION KTY84-150 -40°C 300°C 50°C Voltage ± 5 mV
Among all the 1500 Vac, NTC Burn-out values
ways 50 Hz, 1 min Coster 10K -10°C 100°C 50°C Max. output value 22 mA or 10.6 V
SLIM SERIES

TEMPERATURE AND HUMIDITY Coster 1K -30°C 40°C 25°C Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Pot. Output load Resistance - Rload
0% 100 % 10 %
(Rnom.< 50KΩ) Current output < 500 Ω
Storage temperature -40°C .. +85°C
Calibration (1) Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 % PTC, NTC the higher of ±0.1 % f.s. and ±0.2 °C Short circuit current 26 mA max
EMC (for industrial environments) Potentiometer ± 0.05 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC Linearity (1)
Immunity EN 61000-6-2 PTC, NTC ± 0.1 % f.s.
Emission EN 61000-6-4 Sensor excitation current
HOUSING PTC,NTC 500 uA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full scale ± 0.01 % / °C
6 Weight about 90 g. (1) referred to the input Span (difference between max. and min.)

DOUBLE CHANNEL, ISOLATED CONVERTER FOR VOLTAGE AND CURRENT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 D

The isolated converter DAT 4532 D is able to measure voltage and current signals. In function of programming, the measured values
are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.

FEATURES - High accuracy


- Configurable input for voltage and current - On-field reconfigurable
- Configurable output in current or voltage - Galvanic isolation among the ways
- Double channel in the same enclosure - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance with
- Two independent channels EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT (2 CHANNELS) OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max Voltage 0V 10 V 1V Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Current 0 mA 20 mA 1 mA Voltage 0 V 10 V 1 V
Current output 55 mA max. Calibration (1) Output calibration
Voltage output 25 mA max. Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
ISOLATION mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV
Among all the 1500 Vac, Linearity (1) Burn-out values
ways 50 Hz, 1 min
V, mA ± 0.05 % f.s. Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Input impedance Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Volt >= 1 MΩ Output load Resistance - Rload
Storage temperature -40°C .. +85°C Current <= 50 Ω Current output < 500 Ω

Humidity (not condensed) 0 .. 90 %


Thermal drift (1) Voltage output > 10 KΩ
Full scale ± 0.01 % / °C Short circuit current 26 mA max
EMC (for industrial environments)
Response time (10÷90% of f.s.) about 100 ms
DIRECTIVE : 2004 / 108 / EC
Immunity EN 61000-6-2 (1) referred to the input Span (difference between max. and min.)
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.

www.datexel.it
ISOLATED FREQUENCY TO VOLTAGE, FREQUENCY TO CURRENT
CONVERTER CONFIGURABLE BY DIP-SWITCH OR PC, TRANSISTOR OR RELAY OUTPUTS
GENERAL DESCRIPTION
DAT 4540 The isolated frequency converter DAT 4540 is able to measure, up to 20 KHz, the frequency of TTL, Namur, NPN, PNP and
Tachometer digital signals. In function of programming, the measured values are converted in a current or voltage signal. Moreover
two relays are available in order to be programmed as trip alarm (version “-R”). For the Namur input is continuously checked the
integrity of the sensor; in case of fault (short circuit or interruption), on the transistor output is generated an alarm.
The device guarantees high accuracy and performances stability both versus time and temperature.
FEATURES - High accuracy
- Measure of the frequency for the following digital - On-field reconfigurable
contacts input: Namur, TTL, NPN, PNP, Tachometer, Volt - Galvanic isolation among all ways
- Configurable output as current or voltage - EMC compliant – CE mark
- Double optional trip alarm - Suitable for DIN rail mounting in according to
- Fault alarm condition for Namur sensor EN-50022 and EN-50035 standards
- Configurable by Dip-switch or PC
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT Frequency 0.1 Hz ÷ 20 KHz


Power supply voltage 18 .. 30 Vdc Namur ( DIN 19234 ) Sample Time < 50ms + period
Rever. polarity protection 60 Vdc max Low level Trig. < 1.2 mA
High level Trig. > 2.1 mA OUTPUT
CURRENT CONSUMPTION Output type Min Max Span min
Voltage Aux. 8.2 V – 8 mA
Current output 90 mA max. Current 0 mA 20 mA 4 mA
Impedance ~ 1000 Ohm
Voltage output 30 mA max. Voltage 0 V 10 V 1 V
Interruption Alarm < 0.2 mA
(+ 10mA for each relay output active ) Output calibration
Short Circuit Alarm > 7.0 mA
ISOLATION TTL Current ± 7 uA
Among all the ways 1500 Vac, 50 Hz, 1 min Low level Trig. < 0.8 V Voltage ± 5 mV
Voltage Aux. >12V @ 20 mA
TEMPERATURE AND HUMIDITY High level Trig. > 2.0 V
Burn-out values

SLIM SERIES
Operative temperature -20°C .. +60°C Impedance > 20 KOhm
Max. output value 22 mA or 11 V
PNP
Storage temperature -40°C .. +85°C Min. output value 0 mA or -0.6 V
Low level Trig. < 4.0 V
High level Trig. > 7.0 V
Output load Resistance - Rload
Humidity (not condensed) 0 .. 90 %
Current output < 500 Ω
Voltage Aux. 17 V – 20 mA
EMC (for industrial environments) Voltage output > 10 KΩ
Impedance ~ 2.2 KOhm
DIRECTIVE : 2004 / 108 / EC Short circuit current 30 mA max
Tachometer
Immunity EN 61000-6-2
Low level Trig. < -50 mV RELAY OUTPUTS
Emission EN 61000-6-4
High level Trig. > +50 mV Relay Outputs (Only for version “-R”)
HOUSING Impedance > 100 KOhm N° 2 SPDT
Material Self-extinguishing plastic Voltage (programmable) Max. load (Resistive) 250 Vac, 2A
DAT 4540 (mm) WxLxH: 90 x 112 x 12.5 Level Trigger 0.05 V ÷ 7.0 V Isolation between terminals 1000 Vac max
DAT 4540-R (mm) WxL xH: 90 x 112 x 22.5 Voltage Aux. 5 ÷ 17 V @ 20 mA Transistor Output
Weight about 90 g. Impedance > 20 KOhm Max. load (Resistive) 30 Vdc, 100mA 7

ISOLATED SPLITTER/CONVERTER FOR TC AND mV CONFIGURABLE BY DIP-SWITCH OR PC


DAT 4631 A

GENERAL DESCRIPTION
The isolated splitter/converter DAT 4631 A is able to measure and linearise the standard thermocouples with internal or external cold
junction compensation. In function of programming, the measured values are converted in a current or voltage signal. The device
guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for TC and mV - Galvanic isolation among the ways
- Double output configurable in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance
- High accuracy with EN-50022 and EN-50035

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
Settori di Impiego
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT Line resistance influence (1)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min TC, mV <=0.8 uV/Ohm
Rever. polarity protection 60 Vdc max TC (CJC int./ext.) Thermal drift (1)
CURRENT CONSUMPTION J -200°C 1200°C 100°C Full scale ± 0.01% / °C
Current output 55 mA max. K -200°C 1300°C 100°C CJC ± 0.01% / °C
Voltage output 25 mA max. S 0°C 1750°C 400°C CJC compensation ± 0.5°C
R 0°C 1750°C 400°C
ISOLATION OUTPUT (2 CHANNELS)
B 0°C 1850°C 400°C
Among all the 1500 Vac, Output type Min Max Span min
ways 50 Hz, 1 min E -200°C 1000°C 100°C
Current 0 mA 20 mA 4 mA
T -200°C 400°C 100°C
TEMPERATURE AND HUMIDITY Voltage 0 V 10 V 1 V
N -200°C 1300°C 100°C
Operative temperature -20°C .. +60°C Output calibration
Voltage
Storage temperature -40°C .. +85°C mV -100 mV +90 mV 5 mV Current ± 7 uA
mV -100 mV +200 mV 10 mV Voltage ± 5 mV
Humidity (not condensed) 0 .. 90 %
mV -100 mV +800 mV 20 mV Burn-out values
EMC (for industrial environments) Input calibration (1) Max. output value 22 mA or 10.6 V
DIRECTIVE : 2004 / 108 / EC mV, TC the higher of ±0.1 % f.s. and ±12 uV Min. output value 0 mA or -0.6 V
Immunity EN 61000-6-2 Linearity (1) Output load Resistance - Rload
Emission EN 61000-6-4 TC ± 0.2 % f.s. Current output < 500 Ω
HOUSING mV ± 0.1 % f.s. Voltage output > 10 KΩ
Material Self-extinguishing plastic Input impedance (1) Short circuit current 26 mA max
Dim. (mm) W x L x H : 90 x 112 x 12.5 TC, mV >= 10 MΩ Response time (10÷90% of f.s.) about 500 ms
Weight about 90 g. (1) referred to the input Span (difference between max. and min.)
www.datexel.it
ISOLATED SPLITTER/CONVERTER FOR RTD AND RESISTANCE CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4631 B The isolated Splitter/converter DAT 4631 B is able to measure and linearise the standard RTD and resistances with 2 or 3 wires cable
compensation. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD and resistance - Galvanic isolation among the ways
- Double output configurable in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in
- High accuracy compliance with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT OUTPUT


Frequency (2 CHANNELS) 0.1 Hz ÷ 20 KHz
Power
Tensione
supply
di alimentazione
voltage 18 .. 30 Vdc Input type Min Max Span min Output type
Sample Time Min < 50mSMax Span min
+ periodo
Rever.
Protezione
polarity
invers.
protection
polarità 60 Vdc max RTD (2, 3 wires) Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Pt100 -200°C 850°C 50°C Voltage 0 V 10 V 1 V
Current output 55 mA max. Pt1000 -85°C 185°C 30°C Output calibration
Voltage output 25 mA max. Ni100 -60°C 180°C 50°C Current ± 7 uA
ISOLATION Ni1000 -60°C 150°C 30°C Voltage ± 5 mV
ISOLAMENTO
Among all the 1500 Vac, RES. (2, 3 0Ω 500 Ω 50 Ω Burn-out values
ways 50 Hz,Vac,
1500 1 min wires)
Su tutte le vie 0Ω 2000 Ω 50 Ω Max. output value 22 mA or 10.6 V
50 Hz, 1 min
SLIM SERIES

TEMPERATURE AND HUMIDITY Calibration (1) Min. output value 0 mA or -0.6 V


Operative temperature -20°C .. +60°C RTD the higher of ±0.1 % f.s. and ±0.2 °C Output load Resistance - Rload
Storage temperature -40°C .. +85°C Low Res. the higher of ±0.1 % f.s. and ±0.15 Ω Current output < 500 Ω
High Res. the higher of ±0.2 % f.s. and ± 1 Ω Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 %
Linearity (1) Short circuit current 26 mA max
EMC (for industrial environments)
EMC (per gli: ambienti industriali) RTD ± 0.1 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE 2004 / 108 / EC
DIRETTIVAEN
Immunity : 2004 / 108 / EC
61000-6-2 Sensor excitation current (1) referred to the input Span (difference between max. and min.)
Immunità
Emission EN 61000-6-4
EN 61000-6-2 RTD, Res 500 uA
Emissione EN 61000-6-4 Line resistance influence (1)
HOUSING
RTD 3 wires 0.05 %/Ω (50 Ω max balanced)
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
8 Weight about 90 g. Full scale ± 0.01 % / °C

ISOLATED, SPLITTER/CONVERTER FOR PTC/NTC/POT CONFIGURABLE BY DIP-SWITCH OR PC


GENERAL DESCRIPTION
DAT 4631 C

The isolated Splitter/converter DAT 4631 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for PTC, NTC and Pot. - Galvanic isolation among the ways
- Double output configurable in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance
- High accuracy with EN-50022 and EN-50035
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max PTC Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION KTY81-210 -55°C 150°C 50°C Voltage 0 V 10 V 1 V
Current output 55 mA max. KTY81-220 -55°C 150°C 50°C Output calibration
Voltage output 25 mA max. KTY84-130 -40°C 300°C 50°C Current ± 7 uA
ISOLATION KTY84-150 -40°C 300°C 50°C Voltage ± 5 mV
Among all the 1500 Vac, NTC Burn-out values
ways 50 Hz, 1 min Coster 10K -10°C 100°C 50°C Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Coster 1K -30°C 40°C 25°C Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Pot. Output load Resistance - Rload
0% 100 % 10 %
(Rnom.< 50KΩ) Current output < 500 Ω
Storage temperature -40°C .. +85°C
Calibration (1) Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 % PTC, NTC the higher of ±0.1 % f.s. and ±0.2 °C Short circuit current 26 mA max
EMC (for industrial environments) Potentiometer ± 0.05 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC Linearity (1)
Immunity EN 61000-6-2 PTC, NTC ± 0.1 % f.s.
Emission EN 61000-6-4 Sensor excitation current
HOUSING PTC,NTC 500 uA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full scale ± 0.01 % / °C
Weight about 90 g. (1) referred to the input Span (difference between max. and min.)

www.datexel.it
ISOLATED SPLITTER/CONVERTER FOR VOLTAGE AND CURRENT CONFIGURABLE BY DIP-SWITCH OR PC

DAT 4631 D GENERAL DESCRIPTION


The isolated Splitter/converter DAT 4631 D is able to measure voltage and current signals. In function of programming, the measu-
red values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for voltage and current - Galvanic isolation among the ways
- Double output configurable in current or voltage - EMC compliant – CE mark
- Configurable by dip-switch or PC - Suitable for DIN rail mounting in compliance
- High accuracy with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max Voltage 0V 10 V 1V Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Current 0 mA 20 mA 1 mA Voltage 0 V 10 V 1 V
Current output 55 mA max. Calibration (1) Output calibration
Voltage output 25 mA max. Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
ISOLATION mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV
Among all the 1500 Vac, Linearity (1) Burn-out values
ways 50 Hz, 1 min
V, mA ± 0.05 % f.s. Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Input impedance Min. output value 0 mA or -0.6 V

SLIM SERIES
Operative temperature -20°C .. +60°C Volt >= 1 MΩ Output load Resistance - Rload
Storage temperature -40°C .. +85°C Current <= 50 Ω Current output < 500 Ω

Humidity (not condensed) 0 .. 90 %


Thermal drift (1) Voltage output > 10 KΩ
Full scale ± 0.01 % / °C Short circuit current 26 mA max
EMC (for industrial environments)
Response time (10÷90% of f.s.) about 100 ms
DIRECTIVE : 2004 / 108 / EC
Immunity EN 61000-6-2 (1) referred to the input Span (difference between max. and min.)
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.
9
ISOLATED MATHEMATICAL MODULE FOR VOLTAGE AND CURRENT INPUT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4632 D

The isolated converter DAT 4632 D is able to measure voltage and current signals, execute a programmable mathematical function
and provide on output a normalized current or voltage signal. The device guarantees high accuracy and performances stability both
versus time and temperature.

FEATURES - On-field reconfigurable


- Configurable input for voltage and current - Galvanic isolation among all the ways
- Configurable output in current or voltage - EMC compliant – CE mark
- Calculation function (two independent outputs) - Suitable for DIN rail mounting in compliance
- Configurable by dip-switch or PC with EN-50022 and EN-50035
- High accuracy
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT (2 CHANNELS) OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Rever. polarity protection 60 Vdc max Voltage 0V 10 V 1V Current 0 mA 20 mA 4 mA
CURRENT CONSUMPTION Current 0 mA 20 mA 1 mA Voltage 0 V 10 V 1 V
Current output 55 mA max. Calibration (1) Output calibration
Voltage output 25 mA max. Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
ISOLATION mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV
Among all the 1500 Vac, Linearity (1) Burn-out values
ways 50 Hz, 1 min
V, mA ± 0.05 % f.s. Max. output value 22 mA or 10.6 V
TEMPERATURE AND HUMIDITY Input impedance Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Volt >= 1 MΩ Output load Resistance - Rload
Storage temperature -40°C .. +85°C Current <= 50 Ω Current output < 500 Ω

Humidity (not condensed) 0 .. 90 %


Thermal drift (1) Voltage output > 10 KΩ
Full scale ± 0.01 % / °C Short circuit current 26 mA max
EMC (for industrial environments)
Response time (10÷90% of f.s.) about 100 ms
DIRECTIVE : 2004 / 108 / EC
Immunity EN 61000-6-2 (1) referred to the input Span (difference between max. and min.)
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.

www.datexel.it
2 SLIM SERIES

ELECTRONIC AND CONTROL PROCESS DEVICES

“SMART SERIES” Temperature and signal transmitters


and converters for DIN rail mounting
The SMART series devices can accept on their input several
types of signals coming from the field; the series is
composed of:

• 4÷20 mA two wires isolated Transmitter for universal


input (DAT4035)
• Isolated Converters for universal input with configurable
output as voltage or current (DAT4135, DAT 4235)
• Isolated Converter for universal input with configurable
output as voltage or current and trip amplifier (DAT4520)

INDEX
12 • DAT 4035
PC programmable Two wire isolated universal signal transmitter

13 • DAT 4135
PC programmable isolated universal signal converter

14 • DAT 4135/SEL
PC configurable universal signal converter with command of enable/disable output
15 • DAT 4235
PC programmable 3 ways isolated universal signal converter

16 • DAT 4520
Universal converter with Trip Amplifier
SMART SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
02

SMART Temperature and signal


series transmitters and converters for
DIN rail mounting
PC PROGRAMMABLE TWO WIRE ISOLATED UNIVERSAL TRANSMITTER
DAT 4035 GENERAL DESCRIPTION
The transmitter DAT 4035 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal, conversion of a voltage signal
even coming from a potentiometer connected on its input.
Moreover the DAT 4035 is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal. The device guarantees high accuracy and performances stability
both in time and in temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance
- 4 ÷ 20 mA configurable output on current loop with EN-50022 and EN-50035

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY ISOLATION VOLTAGE TEMPERATURE & HUMIDITY


Operative temperature -20°C .. +70°C
Power supply voltage 10 .. 30 Vdc
Input/Power 2000 Vac 50 Hz, Storage temperature -40°C .. +85°C
supply 1 min.
SMART SERIES

Reverse polarity
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) HOUSING


DIRECTIVE 2004/108/EC Material Self-extinguishing plastic

Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5

Emission EN 61000-6-4 Weight about 90 g.

INPUT INPUT
Input type Min Max Span min Input calibration (1)
12 TC (CJC int./ext.) RTD the higher of ±0.1% f.s. and ±0.2°C
J -200°C 1200°C 2 mV Res. Low the higher of ±0.1% f.s. and ±0.15 Ω
K -200°C 1370°C 2 mV Res. High the higher of ±0.2% f.s. and ±1 Ω
S -50°C 1760°C 2 mV mV, TC the higher of ±0.1% f.s. and ±18 uV
R -50°C 1760°C 2 mV Volt the higher of ±0.1% f.s. and ± 2 mV
B 400°C 1820°C 2 mV mA the higher of ±0.1% f.s. and ± 6 uA
E -200°C 1000°C 2 mV
Linearity (1)
T -200°C 400°C 2 mV
TC ± 0.2 % f.s.
N -200°C 1300°C 2 mV
RTD ± 0.1 % f.s
RTD 2,3,4 wires
Line resistance influence (1)
Pt100 -200°C 850°C 50°C
TC, mV,V <=0.4 uV/Ohm
Pt1000 -200°C 200°C 50°C
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
Ni100 -60°C 180°C 50°C
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Ni1000 -60°C 150°C 50°C
RTD excitation current
Voltage
mV -400 mV +400 mV 2 mV Typical 0.350 mA
mV -100 mV +700 mV 2 mV CJC Comp. ± 0.5 °C
Volt - 10 V +10 V 500 mV Thermal drift (1)
0Ω 200 Ω 10 % Full scale ± 0.01 % / °C
Potentiometer CJC ± 0.01 % / °C
200 Ω 500 Ω 10 %
(Nominal value)
0.5 KΩ 50 KΩ 10 % Burn-out values
Resistance 2,3,4 wires Max. value output about 22.5 mA
Low 0Ω 300 Ω 10 Ω Min. value output about 3.6 mA
High 0Ω 2000 Ω 200 Ω Response time (10÷90% of f.s.) about 400 ms
Current mA -10 mA +24 mA 2 mA (1) referred to input Span (difference between max. and min. values)
Input impedance
TC, mV >= 10 MΩ OUTPUT
Volt >= 1 MΩ Output type Min Max Span min
Current ~ 50 Ω Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Output calibration
Current ± 7 uA

www.datexel.it
PC PROGRAMMABLE ISOLATED UNIVERSAL SIGNAL CONVERTER
DAT 4135 GENERAL DESCRIPTION
The converter DAT 4135 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input. Moreover the DAT 4135 is able to measure and linearise the standard
thermocouples with internal cold junction compensation.
In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy
and performances stability both in time and in temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- Configurable output in current or voltage EN-50022 and EN-50035

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY ISOLATION VOLTAGE TEMPERATURE & HUMIDITY


Input/Power supply-Output 2000 Vac 50 Hz, 1 min. Operative temperature -20°C .. +70°C
Power supply voltage 18 .. 30 Vdc OUTPUT LOAD RESISTANCE (RLOAD)
Current output </= 650 Ω Storage temperature -40°C .. +85°C
Reverse polarity Voltage output >/= 3.5 KΩ

SMART SERIES
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %
Limitation current about 25 mA
CURRENT CONSUMPTION EMC (for industrial environments) HOUSING
DIRECTIVE 2004/108/EC Material Self-extinguishing plastic
Current output 40 mA max.
Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5

Voltage output 20 mA max.


Emission EN 61000-6-4 Weight about 90 g.

INPUT INPUT
Input type Min Max Span min Input impedance
TC (CJC int./ext.) TC, mV >= 10 MΩ
13
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10 % Max. value output about 23 mA or 10.8 Vdc
Potentiometer Min. value output about 0 mA or 0 Vdc
200 Ω 500 Ω 10 %
(Nominal value)
0.5 KΩ 50 KΩ 10 % Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C Direct current 0 mA 20 mA 4 mA
Reverse current 20 mA 0 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Direct voltage 0V 10 V 1V
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Reverse voltage 10 V 0V 1V
mV, TC the higher of ±0.1 % f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV

www.datexel.it
PC CONFIGURABLE UNIVERSAL SIGNAL CONVERTER WITH COMMAND OF ENABLE/DISABLE OUTPUT
DAT 4135/SEL GENERAL DESCRIPTION
The converter DAT 4135/SEL is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input.
Moreover the DAT 4135/SEL is able to measure and linearise the standard thermocouples with internal cold junction compensation.
In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy
and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- Configurable output in current or voltage EN-50022 and EN-50035
- On-field reconfigurable
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY ISOLATION VOLTAGE SEL INPUT COMMAND


Input/Power supply-Output 2000 Vac 50 Hz, 1 min. Disable output 4÷30 Vdc
Power supply voltage 18 .. 30 Vdc OUTPUT LOAD RESISTANCE (RLOAD) Enable output 0 Vdc or not connected
Current output </= 650 Ω
TEMPERATURE & HUMIDITY
SMART SERIES

Reverse polarity 60 Vdc max. Voltage output >/= 3.5 KΩ


protection Operative temperature -20°C .. +70°C
Limitation current 20 mA max.
Storage temperature -40°C .. +85°C
CURRENT CONSUMPTION EMC (for industrial environments)
Humidity (not condensed) 0 .. 90 %
DIRECTIVE 2004/108/EC HOUSING
Current output 40 mA max.
Immunity EN 61000-6-2 Material Self-extinguishing plastic
Dimensions (mm) W x L x H : 90 x 112 x 12.5
Voltage output 20 mA max.
Emission EN 61000-6-4 Weight about 90 g.

INPUT INPUT
Input type Min Max Span min Input impedance
14 TC (CJC int./ext.) TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05%/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005%/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01% / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01% / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10% Max. value output about 23 mA or 10.8 Vdc
Potentiometer Min. value output about 0 mA or 0 Vdc
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10% Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1% f.s. and ±0.2°C Direct current 0 mA 20 mA 4 mA
Reverse current 20 mA 0 mA 4 mA
Res. Low the higher of ±0.1% f.s. and ±0.15 Ω
Direct voltage 0V 10 V 1V
Res. High the higher of ±0.2% f.s. and ±1 Ω
Reverse voltage 10 V 0V 1V
mV, TC the higher of ±0.1% f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1% f.s. and ± 2 mV Current ± 7 uA
mA the higher of ±0.1% f.s. and ± 6 uA Voltage ± 5 mV

www.datexel.it
PC PROGRAMMABLE 3 WAYS ISOLATED UNIVERSAL SIGNAL CONVERTER
DAT 4235 GENERAL DESCRIPTION
The converter DAT 4235 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input.
Moreover the DAT 4235 is able to measure and linearise the standard thermocouples with internal cold junction compensation. In
function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and
performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac on the 3 ways
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- Configurable output in current or voltage EN-50022 and EN-50035
- On-field reconfigurable
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY ISOLATION VOLTAGE TEMPERATURE & HUMIDITY


Input/Power supply-Output 2000 Vac 50 Hz, 1 min. Operative temperature -20°C .. +70°C
Power supply voltage 18 .. 30 Vdc OUTPUT LOAD RESISTANCE (RLOAD)
Current output </= 650 Ω Storage temperature -40°C .. +85°C
Reverse polarity Voltage output >/= 600 Ω

SMART SERIES
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %
Limitation current 30 mA max.
CURRENT CONSUMPTION EMC (for industrial environments) HOUSING
DIRECTIVE 2004/108/EC Material Self-extinguishing plastic
Current output 70 mA max.
Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5

Voltage output 50 mA max.


Emission EN 61000-6-4 Weight about 90 g.

INPUT INPUT
Input type Min Max Span min Input impedance
TC (CJC int./ext.) TC, mV >= 10 MΩ 15
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10% Max. value output about 25 mA or 10.8 Vdc
Potentiometer Min. value output about -25 mA or -10.8 Vdc
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10% Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C Direct current -20 mA 20 mA 4 mA
Reverse current 20 mA -20 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Direct voltage -10 V 10 V 1V
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Reverse voltage 10 V -10 V 1V
mV, TC the higher of ±0.1 % f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA or ± 15 uA (2)
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 10 mV
(2) referred to the output ± 20 mA.

www.datexel.it
UNIVERSAL CONVERTER WITH TRIP AMPLIFIER
DAT 4520 GENERAL DESCRIPTION
The DAT 4520 device measures mV, V, mA or resistance signals, and can be directly connected to Thermocouple, RTD or potentio-
meter sensors.
The input signal is filtered, linearised, amplified and transfered to the output circuit, that converts it in a 0-10V range or 0-20mA range
signal. Auxiliary power supply allows to supply the output current loop. Moreover, the device is able to control two trip alarm relay
outputs. DAT 4520 has a 3 way isolation: input is 2000 Vac isolated from power supply and output; power supply and output are 1500
Vac isolated between them.

FEATURES
- Configurable input for Tc, RTD, Res, mV, V, mA, - 2000 Vac galvanic isolation between input, output
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliance – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- 0 to 10V, 0 to 20mA configurable output EN-50022 and EN-50035
- On-field reconfigurable

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

TRIP ALARMS Isolation voltage TEMPERATURE & HUMIDITY


Output type n° 2 Relay SPDT
Input/Output 2000 Vac, 50 Hz, 1min. Operative temperature -20°C .. +60°C
2A, 250 Vac
Contact rating
2A, 30 Vdc
Input/Supply 2000 Vac, 50 Hz, 1min. Storage temperature -40°C .. +85°C
Load resistive
SMART SERIES

Minimum load 5Vdc, 10mA Supply/Output 1500 Vac, 50 Hz, 1min. Humidity (not condensed) 0 .. 90 %
250 Vac (50/60 Hz)
Voltage max 110 Vdc EMC (for industrial environments) HOUSING
CONTENITORE
coil-to-contacts: 2000Vac
Isolation voltage Material Self-extinguishing plastic
between contacts: 1000Vac DIRECTIVE 2004/108/EC Materiale Plastica auto-estinguente
POWER SUPPLY Mounting DIN Rail
Immunity EN 61000-6-2 Dimensioni (mm) W x L x H : 90 x 112 x 12.5
Power supply voltage 20 .. 30 Vdc Dimensions (mm) W x L x H : 120 x 100 x 22.5
Reverse polarity protection 60 Vdc max. Emission EN 61000-6-4 Peso
Weight 90 g. circa
about 150 g.

INPUT INPUT
Input type Min Max Span min Input impedance
16 TC (CJC int./ext.) TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
Volt 0 mV 10 V 500 mV CJC ± 0.01 % / °C
0Ω 200 Ω 10% Response time (10÷90% of f.s.) about 400 ms
Potentiometer (1) referred to input Span (difference between max. and min. values)
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10%
Resistance 2,3,4 wires
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA 0 mA 20 mA 2 mA OUTPUT
Output type Min Max Span min
Direct voltage 0V 10 V 1V
Input calibration (1)
Direct current 0 mA 20 mA 4 mA
RTD the higher of ±0.1 % f.s. and ±0.2°C
Output calibration
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω Current ± 7 uA
Res. High the higher of ±0.2 % f.s. and ±1 Ω Voltage ± 10 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV Output Load Resistance
Volt the higher of ±0.1 % f.s. and ± 2 mV Current < 650 Ω
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage > 4.7 KΩ

www.datexel.it
www.datexel.it ELECTRONIC AND CONTROL PROCESS DEVICES

SMART SERIES
“SMART SERIES” Temperature and signal
transmitters and converters for Din rail mounting 17

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
3 SMART ATEX

ELECTRONIC AND CONTROL PROCESS DEVICES

Intrinsically safe smart series ATEX94/9/EC


The Intrinsically Safe SMART Series devices, type-approved according to Directive
ATEX94/9/EC, are subdivided into three different product categories: universal input
transmitters to be installed in a potentially explosive atmosphere (Zone 0) codes:
DAT 2015 IS, DAT 4035 IS, DAT 1010 IS, DAT 1015 IS, DAT 1065 IS.

Converters / Barriers for universal input or current loop (0-4…..20 mA), suitable for
installation in safe zone for connections towards zone 0. codes:

DAT 4235 IS in the following versions:


A= Converter/Barrier, B= Double trip amplifier,
C= Converter/Barrier + Double trip amplifier.

DAT 5030 IS in the following versions:


A= Single-channel barrier, AH= HART transparent single-channel
barrier, B= Double-channel barrier, BH= HART transparent
double-channel barrier.

INDEX
20 • DAT 2015IS
DAT 2015 IS/HT
Universal Intrinsically Safe transmitter

21 • DAT 4035 IS
DAT 4035 IS/HT
Universal Intrinsically Safe isolated transmitter

22 • DAT 4235 IS
Signal Converter with Trip Amplifier for hazardous area sensors

23 • DAT 5030 IS
Current Loop Repeater / Supply for hazardous area sensors

24 • DAT 1010 IS
DAT 1010 IS/HT
Intrinsically safe PC configurable transmitter for RTD

25 • DAT 1015 IS
DAT 1015 IS/HT
Intrinsically safe PC configurable transmitter for universal input

26 • DAT 1065 IS
DAT 1065 IS/HT
Isolated Intrinsically safe PC configurable transmitter for universal input
SMART ATEX SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
ATEX94/9/EC

03

SMART Transmitters and converters


ATEX for use in potentially explosive
series atmospheres
UNIVERSAL INTRINSICALLY SAFE TRANSMITTER
DAT 2015 IS GENERAL DESCRIPTION
DAT 2015 IS/HT The transmitter DAT 2015 IS is able to execute many functions such as measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input.
Moreover the DAT 2015 IS is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, Tc, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN rail mounting in compliance with
EN-50022 and EN-50035

u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES

-20°C .. +70°C Output /supply Input


Power supply voltage 11 .. 30 Vdc Operative temperature
-20°C .. +85°C (vers. ‘HT’) Ui = 30 V Uo = 6.2 V

Storage temperature -40°C .. +85°C Ii = 100 mA Io = 100 mA


Reverse polarity 60 Vdc max.
protection Humidity (not condensed) 0 .. 90 % Pi = 0.75 W Po = 500 mW

EMC (for industrial environments) HOUSING Li = 0.1 mH Lo = 3.6 mH

DIRECTIVE 2004/108/EC Material Self-extinguishing plastic Ci = 10 nF Co = 5 uF

Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5 T6 : -20 ÷ +55°C


T5 : -20 ÷ +70°C
Emission EN 61000-6-4 Weight about 90 g. T4 : -20 ÷ +85°C (vers. ‘HT’)

INPUT INPUT
20 Input type Min Max Span min Input calibration (1)
TC CJC int./ext. RTD the higher of ±0.1 % f.s. and ±0.2 °C

J -200°C 1200°C 2 mV Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV
S -50°C 1760°C 2 mV
Input impedance
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence (1)
RTD 2,3,4 wires TC, mV,V <=0.4 uV/Ohm

Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5 °C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 2 KΩ 10% Max. output value about 22.5 mA

RES. 2,3,4 wires Min. output value about 3.6 mA


Response time (10÷90% of f.s.) about 400 ms
Low 0Ω 300 Ω 10 Ω
(1) referred to input Span (difference between max. and min. values)
High 0Ω 2000 Ω 200 Ω
OUTPUT
Output type Min Max Span min
Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Output calibration
Current ± 7 uA

www.datexel.it
UNIVERSAL INTRINSICALLY SAFE ISOLATED TRANSMITTER
DAT 4035 IS GENERAL DESCRIPTION
DAT 4035 IS/HT The isolated transmitter DAT 4035 IS is able to execute many functions such as: measure and linearisation of the temperature cha-
racteristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentio-
meter connected on its input.
Moreover the DAT 4035 IS is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, Tc, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- Galvanic isolation at 2000 Vac - Suitable for DIN rail mounting in compliance with
- On-field reconfigurable EN-50022 and EN-50035

u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
Output /supply Input

SMART ATEX SERIES


-20°C .. +70°C
Power supply voltage 11 .. 30 Vdc Operative temperature
-20°C .. +85°C (vers. ‘HT’) Ui = 30 V Uo = 6.2 V

Storage temperature -40°C .. +85°C Ii = 100 mA Io = 100 mA


Reverse polarity 60 Vdc max.
protection Humidity (not condensed) 0 .. 90 % Pi = 0.75 W Po = 500 mW

EMC (for industrial environments) HOUSING Li = 0.1 mH Lo = 3.6 mH

DIRECTIVE 2004/108/EC Material Self-extinguishing plastic Ci = 10 nF Co = 5 uF

Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5 T6 : -20 ÷ +55°C


T5 : -20 ÷ +70°C
Emission EN 61000-6-4 Weight about 90 g. T4 : -20 ÷ +85°C (vers. ‘HT’)

INPUT INPUT
Input type Min Max Span min Input calibration (1)
21
TC CJC int./ext. RTD the higher of ±0.1 % f.s. and ±0.2 °C

J -200°C 1200°C 2 mV Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV
S -50°C 1760°C 2 mV
Input impedance
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence (1)
RTD 2,3,4 wires TC <=0.8 uV/Ohm

Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5 °C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 2 KΩ 10% Max. output value about 22.5 mA

RES. 2,3,4 wires Min. output value about 3.6 mA


Response time (10÷90% of f.s.) about 400 ms
Low 0Ω 300 Ω 10 Ω
(1) referred to input Span (difference between max. and min. values)
High 0Ω 2000 Ω 200 Ω
OUTPUT
Output type Min Max Span min
Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Output calibration
Current ± 7 uA

www.datexel.it
SIGNAL CONVERTER WITH TRIP AMPLIFIER FOR HAZARDOUS AREA SENSORS
DAT 4235 IS GENERAL DESCRIPTION
The DAT 4235 IS device is a galvanic isolated Intrinsically Safety Barrier, defined as “Associated Apparatus”.
The input measures mV, V, mA or resistance signals, and can be directly connected to Thermocouple, RTD or potentiometer sensors.
The input signal is filtered, linearized, amplified and transfered to the output circuit, that converts it in a 0-10V range or 0-20mA range
signal.

FEATURES
- Configurable input Tc, RTD, Res, mV, V, mA, Potentiometer - Suitable for DIN rail mounting in according to
- High accuracy EN-50022
- Configurable by PC
- 0 to 10V , 0 to 20mA configurable output Available in 3 different versions:
- 2000 Vac galvanic isolation between input and output - DAT4235 IS A Signal converter
- Programming of the unit measure as °C / °F - DAT4235 IS B Double trip amplifier
- EMC compliance - CE mark - DAT4235 IS C Signal converter + Double trip
- PROTECTION MODE: II (1) G D [ Ex ia ] IIC - [ Ex iaD] in amplifier
according to the Directive ATEX 94/9/EC
u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
TRIP ALARMS ISOLATION TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES

Output type n° 2 Relays SPDT 2000 Vac, Terminals A-B-C-D; E-F-G-H-I-J; K-L
Input/Output Operative
Contact 2A , 250 Vac 50 Hz, 1min. -20°C .. +60°C Um=250V
temperature
rating 2A , 30 Vdc 2000 Vac, Terminals Terminals
Input/Supply
Load resistive 50 Hz, 1min. 1-2-3-4-5-6-7 5-6-7
Humidity (not
Minimum load 5Vdc, 10mA 1500 Vac, 0 .. 90 % Uo = 7.8 V Uo = 30 V
Supply/Output condensed)
50 Hz, 1min.
Max Voltage 250 Vac (50/60 Hz) 110 Vdc Io = 32 mA Ii = 100 mA
EMC (for industrial environments) HOUSING
Isolation coil-to-contacts: 2000Vac Po = 140 mW Pi = 0.75W
between contacts: 1000Vac DIRECTIVE 2004/108/EC Material Self-extinguish
plastic
POWER SUPPLY Lo = 20 mH Li = ~0 mH
Mounting DIN Rail
Immunity EN 61000-6-2
Power supply voltage 20 .. 30 Vdc Dimensions 120 x 100 x 22.5 Co = 2 uF Ci = 24 nF

Reverse polarity protection 60 Vdc max Emission EN 61000-6-4 Weight about 150 g. Ta : -20 ÷ +55°C

INPUT INPUT
22 Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV V >= 1 MΩ
K -200°C 1370°C 2 mV mA <= 50 Ω
S -50°C 1760°C 2 mV Linearity
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence
T -200°C 400°C 2 mV TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C RTD excitation current
Pt1000 -200°C 200°C 50°C Typical 0.350 mA
Ni100 -60°C 180°C 50°C CJC comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
V 0V 10 V 500 mV Response time (10÷90% of f.s.) about 0.4 sec.
Current mA 0 mA 20 mA 2 mA (1) referred to input Span (difference between max. and min. values)
0Ω 200 Ω 10%
Potentiometer OUTPUT
200 Ω 500 Ω 10%
(Nominal value) Output type Min Max Span min
0.5 KΩ 2 KΩ 10%
Voltage 0V 10 V 1V
Resistance
Current 0 mA 20 mA 4 mA
Low 0Ω 300 Ω 10 Ω
Output calibration
High 0Ω 2000 Ω 200 Ω
Current ± 7 uA
Input calibration (1)
Voltage ± 10 mV
RTD the higher of ±0.1 % f.s. and ±0.2 °C
Output Rload resistance
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Current < 650 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Voltage > 4.7 KΩ
mV, TC the higher of ±0.1 % f.s. and ±10 uV
V the higher of ±0.2 % f.s. and ±2 Ω
mA the higher of ±0.1 % f.s. and ±6 uV

www.datexel.it
CURRENT LOOP REPEATER / SUPPLY FOR HAZARDOUS AREA SENSORS
DAT 5030 IS GENERAL DESCRIPTION
The DAT 5030 IS device is a galvanic isolated Intrinsically Safety Barrier, defined as “Associated Apparatus”
The input can measure 0-20 mA or 4-20 mA current loops, both active or passive mode; auxiliary power supply is available to supply
the current loop through the hazardous area (ZONE 0).
The measure is converted in output as voltage signal (0-10V or 2-10V) or current signal (0-20mA or 4-20mA). Auxiliary power supply
is available to supply the current loop connected to the output.

FEATURES - PROTECTION MODE: II (1) G D [ Ex ia ] IIC - [ Ex iaD ]


- 0-20mA or 4-20mA active or passive configurable input according to the Directive ATEX 94/9/EC
- 0-10V, 2-10V, 0-20mA, 4-20mA configurable output - Din Rail mounting suitable in according to EN-50022
- Configurable by DIP – switch
- Single or Double Channel
Available in 4 different versions:
- HART Compatible on request
- Galvanic isolation on all ways - DAT5030 IS A Single channel
- Power supply for current loop in hazardous area (ZONE 0) - DAT5030 IS B Double channel
- EMC compliance – CE Mark - DAT5030 IS AH Single channel HART compatible
- DAT5030 IS BH Double channel HART compatible
u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY HOUSING

SMART ATEX SERIES


Power supply voltage 20 ÷ 30 Vdc Operating temperature -20°C .. +60°C Material Self-extinguish
plastic
80 mA per channel with
Current consumption Storage temperature -40 ÷ 85 °C
Vaux operating Mounting DIN Rail

Reverse polarity protection 60 Vdc max. Relative humidity Dimensions


0 .. 90 % 120 x 100 x 22.5
(not condensed) (mm)

ISOLATION EMC (for industrial environments) WEIGHT


Input/Output 2000 Vac @ 50 Hz, 1min. DIRECTIVE 2004/108/EC
Single CH about 100 g.
Input/Supply 2000 Vac @ 50 Hz, 1min.
Immunity EN 61000-6-2
Supply/Output 1500 Vac @ 50 Hz, 1min.
Double CH about 160 g.
Between channels 2000 Vac @ 50 Hz, 1min. Emission EN 61000-6-4

INPUT
Input EX DATA
Terminals J-I; A-B-C-D; O-P-Q-R Um=250V
Input signal Active or passive current loop
23
Range 4.6; 14-16;
Terminals 4-6; 14-16;

Configurable 0÷20 mA , 4÷20 mA Ui ==26.4


Uo 26.4VV Ui = 30 V
Zero regulation ±5% Io = 93 mA Ii = 100 mA
Span regulation ±5%
Po = 615 mW Pi = 0.75W
Auxiliary Supply > 15V @ 20mA
Lo = 4.2 mH Li = ~0 mH
Input impedance < 25 Ω
Co = 75 nF Ci = 12 nF

OUTPUT
USCITA Terminals 6-5;
4.6; 14-16;
16-15;

Output signal Ui ==1,2


Uo 1.2VV Ui = 30 V

Configurable 4÷20
4÷20 mA,
mA, 0÷20
0÷20mA,
mA,0÷10
0÷10VVand 2÷10VV
e 2÷10 Io = 46 mA Ii = 100 mA
Output Rload resistance
load resistance Po = 14 mW Pi = 0.75W
Voltage > 5 KΩ
Li = ~0 mH
Current < 500 Ω
Ci = 12 nF
Auxiliary Supply > 12V @ 20mA
Ta : -20 ÷ +60°C
PERFORMANCES
Calibration error ± 0.1 % of f.s.
Linearity error (*) ± 0.2 % of f.s.
Thermal drift 0.02 % of Full scale/°C
Response
Responsetime (10÷90% of f.s.)
time < 0.2 sec.
Frequency response
bidirectional 0.5 ÷ 4 Khz @ 3dB
(HART Protocol)
(*) = inclusive of hysteresis, power supply variation and linearisation error.

www.datexel.it
INTRINSICALLY SAFE PC CONFIGURABLE TRANSMITTER FOR RTD
DAT 1010 IS GENERAL DESCRIPTION
DAT 1010 IS/HT The transmitter DAT 1010 IS is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input. The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN B in-head mounting

u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES

-20°C .. +70°C Output /supply Input


Power supply voltage 11 .. 30 Vdc Operative temperature
-20°C .. +85°C (vers. ‘HT’) Ui = 30 V Uo = 6.2 V

Storage temperature -40°C .. +85°C Ii = 100 mA Io = 100 mA


Reverse polarity 60 Vdc max.
protection Humidity (not condensed) 0 .. 90 % Pi = 0.75 W Po = 500 mW

EMC (for industrial environments) HOUSING Li = 0.1 mH Lo = 3.6 mH

DIRECTIVE 2004/108/EC Material Self-extinguishing plastic Ci = 10 nF Co = 5 uF


Dimensions Ø= 43 mm ; H = 24 mm
Immunity EN 61000-6-2 T6 : -20 ÷ +55°C
Weight about 50 g. T5 : -20 ÷ +70°C
Emission EN 61000-6-4 Mounting DIN B head or bigger T4 : -20 ÷ +85°C (vers. ‘HT’)

INPUT INPUT
24 Input type Min Max Span min Line resistance influence (1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
Pt1000 -200°C 200°C 50°C RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Ni100 -60°C 180°C 50°C RTD excitation current
Ni1000 -60°C 150°C 50°C Typical 0.350 mA
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% Burn-out values
Potentiometer
200 Ω 500 Ω 10% Max. output value about 22.5 mA
(Nominal value)
0.5 KΩ 2 KΩ 10% Min. output value about 3.6 mA
RES. 2,3,4 wires Response time (10÷90% of f.s.) about 400 ms
Low 0Ω 300 Ω 10 Ω (1) referred to input Span (difference between max. and min. values)
High 0Ω 2000 Ω 200 Ω
OUTPUT
Input calibration (1)
Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C
Direct current 4 mA 20 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Reverse current 20 mA 4 mA 4 mA
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Output calibration
mV the higher of ±0.1 % f.s. and ±10 uV
Current ± 7 uA
Input impedance
mV >= 10 MΩ
Linearity (1)
RTD ± 0.1 % f.s

www.datexel.it
INTRINSICALLY SAFE PC CONFIGURABLE TRANSMITTER FOR UNIVERSAL INPUT
DAT 1015 IS
GENERAL DESCRIPTION
DAT 1015 IS/HT The transmitter DAT 1015 IS is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input. Moreover the DAT 1015 IS is able to measure and linearise the standard thermocouples with internal cold junction com-
pensation. The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, TC, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN B in-head mounting

u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
Output /supply Input

SMART ATEX SERIES


-20°C .. +70°C
Power supply voltage 11 .. 30 Vdc Operative temperature
-20°C .. +85°C (vers. ‘HT’) Ui = 30 V Uo = 6.2 V

Storage temperature -40°C .. +85°C Ii = 100 mA Io = 100 mA


Reverse polarity 60 Vdc max.
protection Humidity (not condensed) 0 .. 90 % Pi = 0.75 W Po = 500 mW

EMC (for industrial environments) HOUSING Li = 0.1 mH Lo = 3.6 mH

DIRECTIVE 2004/108/EC Material Self-extinguishing plastic Ci = 10 nF Co = 5 uF


Dimensions Ø= 43 mm ; H = 24 mm
Immunity EN 61000-6-2 T6 : -20 ÷ +55°C
Weight about 50 g. T5 : -20 ÷ +70°C
Emission EN 61000-6-4 Mounting DIN B head or bigger T4 : -20 ÷ +85°C (vers. ‘HT’)

INPUT INPUT
Input type Min Max Span min Input impedance
25
TC CJC int./ext. TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Linearity (1)
K -200°C 1370°C 2 mV TC ± 0.2 % f.s.
S -50°C 1760°C 2 mV RTD ± 0.1 % f.s
R -50°C 1760°C 2 mV Line resistance influence
B 400°C 1820°C 2 mV TC, mV <=0.8 uV/Ohm
E -200°C 1000°C 2 mV RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
T -200°C 400°C 2 mV RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
N -200°C 1300°C 2 mV RTD excitation current
RTD 2,3,4 wires Typical 0.350 mA
Pt100 -200°C 850°C 50°C CJC comp. ± 0.5 °C
Pt1000 -200°C 200°C 50°C Thermal drift (1)
Ni100 -60°C 180°C 50°C Full scale ± 0.01 % / °C
Ni1000 -60°C 150°C 50°C CJC ± 0.01 % / °C
Voltage Burn-out values
mV -100 mV +700 mV 2 mV Max. output value about 22.5 mA
0Ω 200 Ω 10% Min. output value about 3.6 mA
Potentiometer
200 Ω 500 Ω 10% Response time (10÷90% of f.s.) about 400 ms
(Nominal value)
0.5 KΩ 2 KΩ 10% (1) referred to input Span (difference between max. and min. values)
Resistance
Low 0Ω 300 Ω 10 Ω OUTPUT
High 0Ω 2000 Ω 200 Ω Output type Min Max Span min
Input calibration (1) Direct current 4 mA 20 mA 4 mA
RTD the higher of ±0.1 % f.s. and ±0.2 °C Reverse current 20 mA 4 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω Output calibration
Res. High the higher of ±0.2 % f.s. and ±1 Ω Current ± 7 uA
mV, TC the higher of ±0.1 % f.s. and ±10 uV

www.datexel.it
ISOLATED INTRINSICALLY SAFE PC CONFIGURABLE
TRANSMITTER FOR UNIVERSAL INPUT
DAT 1065 IS GENERAL DESCRIPTION
DAT 1065 IS/HT The isolated transmitter DAT 1065 IS is able to execute many functions such as: measure and linearisation of the temperature cha-
racteristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentio-
meter connected on its input.
Moreover the DAT 1065 IS is able to measure and linearise the standard thermocouples with internal cold junction compensation. The
measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, TC, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- Galvanic isolation at 2000 Vac - Suitable for DIN B in-head mounting
- On-field reconfigurable
u s tri es E n er g y er treat me m ic a l o f
In d at he f

sh
W

nt

petro
Application areas

ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES

Power supply voltage 11 .. 30 Vdc -20°C .. +70°C Output /supply Input


Operative temperature
Reverse polarity protection 60 Vdc max. -20°C .. +85°C (vers. ‘HT’) Ui = 30 V Uo = 6.2 V
ISOLATION Storage temperature -40°C .. +85°C Ii = 100 mA Io = 100 mA
Input - Output/Power 2000 Vac, 50
supply Hz,1 min. Humidity (not condensed) 0 .. 90 % Pi = 0.75 W Po = 500 mW

EMC (for industrial environments) HOUSING Li = 0.1 mH Lo = 3.6 mH

DIRECTIVE 2004/108/EC Material Self-extinguishing plastic Ci = 10 nF Co = 5 uF


Mounting DIN B head or bigger
Immunity EN 61000-6-2 T6 : -20 ÷ +55°C
Dimensions (mm) Ø = 43 mm ; H = 24 mm T5 : -20 ÷ +70°C
Emission EN 61000-6-4 Weight about 90 g. T4 : -20 ÷ +85°C (vers. ‘HT’)

INPUT INPUT
26 Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ

J -200°C 1200°C 2 mV Linearity (1)


TC ± 0.2 % f.s.
K -200°C 1370°C 2 mV
RTD ± 0.1 % f.s
S -50°C 1760°C 2 mV
Line resistance influence (1)
R -50°C 1760°C 2 mV
TC, mV <=0.4 uV/Ohm
B 400°C 1820°C 2 mV RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
E -200°C 1000°C 2 mV RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
T -200°C 400°C 2 mV RTD excitation current
N -200°C 1300°C 2 mV Typical 0.350 mA
RTD 2,3,4 wires CJC comp. ± 0.5 °C

Pt100 -200°C 850°C 50°C Thermal drift (1)


Full scale ± 0.01 % / °C
Pt1000 -200°C 200°C 50°C
CJC ± 0.01 % / °C
Ni100 -60°C 180°C 50°C
Burn-out values
Ni1000 -60°C 150°C 50°C
Max. output value about 22.5 mA
Voltage Min. output value about 3.6 mA
mV -100 mV +700 mV 2 mV Response time (10÷90% of f.s.) about 400 ms
0Ω 200 Ω 10% (1) referred to input Span (difference between max. and min. values)
Potentiometer
200 Ω 500 Ω 10%
(Nominal value) OUTPUT
0.5 KΩ 2 KΩ 10%
Output type Min Max Span min
RES. 2,3,4 wires
Direct current 4 mA 20 mA 4 mA
Low 0Ω 300 Ω 10 Ω
Reverse current 20 mA 4 mA 4 mA
High 0Ω 2000 Ω 200 Ω Output calibration
Input calibration (1) Current ± 7 uA
RTD the higher of ±0.1 % f.s. and ±0.2°C
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
mV, TC the higher of ±0.1 % f.s. and ±10 uV

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

SMART ATEX SERIES


SMART series intrinsically safe ATEX94/9/EC
www.datexel.it

temperature and signal transmitters 27


and converters
u s tri es E n er g y er treat me m ic a l o f
In d at he f
c

sh
W

nt

petro

ore

Application areas

www.datexel.it
4 PDS

ELECTRONIC AND CONTROL PROCESS DEVICES

“P.D.S. SERIES”: temperature and signal transmitters


and converters for DIN rail mounting
The P.D.S. (programmable by dip-switches) series transmitters and converters
can accept on their input signals coming from 2 or 3 wires Pt100. Thermocou-
ple and Strain Gauge sensors or Voltage and Current signals.

• Single and double channel 4÷20 mA two wires transmitters for Pt100 input
without galvanic isolation (DAT2065, DAT2066)
• 4÷20 mA two wires transmitter for Thermocouple input without galvanic
isolation (DAT2045)
• Single and double channel converters for Pt100 input with configurable
output as voltage or current without galvanic isolation (DAT2165, DAT2166)
• Isolated converter for Pt100 input with configurable output as voltage or
current (DAT2061)
• Converter for Thermocouple input with configurable output as voltage or
current without galvanic isolation (DAT2145)
• Isolated signal converters with configurable input and output as voltage or
current (DAT5020. DAT5021, DAT5023I, DAT5023V)
• Isolated signal splitter with configurable input and output as voltage or
current (DAT5022)
• Isolated signal converter for Strain Gauge input with configurable output as
voltage or current (DAT5025)

INDEX
30 • DAT 2065
Dip Switch Configurable transmitter for Pt100
DAT 2066
Double channel Dip Switch Configurable transmitter for Pt100

31 • DAT 2165
Dip Switch Configurable converter for Pt100
DAT 2166
Double Channel Dip Switch Configurable converter for Pt100

32 • DAT 2061
Isolated Dip switch configurable converter for Pt100
DAT 2045
Not linearized Dip Switch configurable transmitter for thermocouple

33 • DAT 2145
Not linearized Dip Switch configurable converter for thermocouple
DAT 5020
Dip Switch configurable 3 ways isolated signal converter

34 • DAT 5021
3 ways isolated Dip Switch configurable signal converter
DAT 5022
4 ways isolated Dip Switch configurable signal converter/signal splitter

35 • DAT 5023 lac


Dip Switch configurable converter for AC current signal
DAT 5023 ldc
Isolated converter for DC current signal with fixed input, and Dip Switch configurable output

36 • DAT 5023/V
Dip Switch configurable converter for AC / DC voltage signal
DAT 5025
Isolated programmable Dip Switch converter for Strain Gauge / Bridge sensors
P.D.S. SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
04

P.D.S. Temperature and signal transmitters


series and converters, isolators, signal
splitters
DIP SWITCH CONFIGURABLE TRANSMITTER FOR PT100

DAT 2065 GENERAL DESCRIPTION


The transmitter DAT 2065 is designed to provide on its output a linearised 4÷20 mA current loop signal proportional with the
temperature characteristic of the Pt100 sensor connected on its input.
It is possible to connect on the input both 3 wires and 2 wires Pt100.

FEATURES
- Configurable Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with
- 4 to 20 mA linearised output on current loop EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (RTD) Linearity error (*)


Power supply voltage 10 .. 30 Vdc Input type Min Max Span min ± 0.15 % of f.s.
Rever. polarity protection 60 Vdc max Pt100 (2-3 wires) -50°C 650°C 50°C Burn-out values
TEMPERATURE & HUMIDITY Max. value output >20 mA
OUTPUT
Operative temperature -20°C .. +70°C Line resistance influence (1)
Storage Output type Min Max Span min 0.05 % f.s. / Ω (100 Ω max balanced for wire)
-40°C .. +85°C
temperature Direct current 4 mA 20 mA -
Response time (10÷90% of f.s.) about 300 ms
Humidity (not condensed) 0 .. 90 % Min. input value programmability
(1) = referred to the input Span
P.D.S. SERIES

EMC (for industrial environments) Programmable -50 ÷ 50 °C (difference between max. and min.)
DIRECTIVE 2004 / 108 / EC Input Calibration (1) (*) = inclusive of hysteresis, power supply variation
Immunity EN 61000-6-2 the higher of ± 0.1 % f.s. and 0.2 °C and linearisation error.
Emission EN 61000-6-4 RTD sensor excitation current
HOUSING Typ. 0.6 mA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full Scale ± 0.02 % / °C
Weight about 80 g.

30

DOUBLE CHANNEL DIP SWITCH CONFIGURABLE TRANSMITTER FOR PT100


GENERAL DESCRIPTION
The double channel transmitter DAT 2066 is designed to provide on the output two linearised 4÷20 mA current loop signals propor-
DAT 2066

tional with the temperature characteristics of the Pt100 sensors connected on its inputs.
It is possible to connect on the input both 3 wire Pt100 and 2 wire Pt100.

FEATURES - 1000 Vac isolation among the channels


- Configurable double Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with
- 4 to 20 mA linearised double output on current loop EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT (RTD) Linearity error (*)


Power supply voltage 10 .. 30 Vdc Input type Min Max Span min ± 0.15 % of f.s.
Rever. polarity protection 60 Vdc max Pt100 (2-3 wires) -50°C 650°C 50°C Burn-out values
TEMPERATURE & HUMIDITY Max. value output >20 mA
OUTPUT
Operative temperature -20°C .. +70°C Line resistance influence (1)
Storage Output type Min Max Span min 0.05 % f.s. / Ω (100 Ω max balanced for wire)
-40°C .. +85°C
temperature Direct current 4 mA 20 mA -
Response time (10÷90% of f.s.) about 300 ms
Humidity (not condensed) 0 .. 90 % Min. input value programmability
(1) = referred to the input Span
EMC (for industrial environments) Programmable -50 ÷ 50 °C (difference between max. and min.)
DIRECTIVE 2004 / 108 / EC Input Calibration (1) (*) = inclusive of hysteresis, power supply variation
Immunity EN 61000-6-2 the higher of ± 0.1 % f.s. and 0.2 °C and linearisation error.
Emission EN 61000-6-4 RTD sensor excitation current
HOUSING Typ. 0.6 mA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full Scale ± 0.02 % / °C
Weight about 80 g.

www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR PT100

DAT 2165 GENERAL DESCRIPTION


The converter DAT 2165 is designed to provide on its output a linearised voltage or current signal proportional with the temperature
characteristic of the Pt100 sensor connected on its input.
It is possible to connect on the input both 3 wires and 2 wires Pt100.

FEATURES
- Configurable Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with EN-50022
- Linearised voltage or current output and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (RTD) Linearity error (*)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min ± 0.15 % of f.s.
Rever. polarity protection 60 Vdc max Pt100 (2-3 wires) -50°C 650°C 50°C Burn-out values
CURRENT CONSUMPTION Max. value output >20 mA or > 10 Vdc
Current output 40 mA max. OUTPUT
Line resistance influence (1)
Voltage output 10 mA max. Output type Min Max Span min 0.05 % f.s. / Ω (100 Ω max balanced for wire)
TEMPERATURE & HUMIDITY Direct current 0 mA 20 mA -
Response time (10÷90% of f.s.) about 300 ms
Operative temperature -20°C .. +70°C Direct Voltage 0V 10 V -
(1) = referred to the input Span
Storage Min. input value programmability
-40°C .. +85°C (difference between max. and min.)

P.D.S. SERIES
temperature
Programmable -50 ÷ 50 °C (*) = inclusive of hysteresis, power supply variation
Humidity (not condensed) 0 .. 90 %
Input Calibration (1) and linearisation error.
EMC (for industrial environments)
the higher of ± 0.1 % f.s. and 0.2 °C
DIRECTIVE 2004 / 108 / EC
RTD sensor excitation current
Immunity EN 61000-6-2
Typ. 0.6 mA
Emission EN 61000-6-4
Thermal drift (1)
HOUSING
Full Scale ± 0.02 % / °C
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 80 g.
31
DOUBLE CHANNEL DIP SWITCH CONFIGURABLE CONVERTER FOR PT100
DAT 2166

GENERAL DESCRIPTION
The double channel converter DAT 2166 is designed to provide on the output two linearised voltage or current signals proportional
with the temperature characteristics of the Pt100 sensors connected on its inputs. It is possible to connect on the input both 3 wire
and 2 wire Pt100.

FEATURES - 1000 Vac isolation among the channels


- Configurable double Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with
- Linearised double voltage or current output EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y
In d oa
d busine er treat me
ne
B

oo at
Application areas
ss

nt
F

POWER SUPPLY INPUT (RTD) Linearity error (*)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min ± 0.15 % of f.s.
Rever. polarity protection 60 Vdc max Pt100 (2-3 wires) -50°C 650°C 50°C Burn-out values
CURRENT CONSUMPTION Max. value output >20 mA or > 10 Vdc
(for each channel) OUTPUT
Line resistance influence (1)
Current output 40 mA max. Output type Min Max Span min
0.05 % f.s. / Ω (100 Ω max balanced for wire)
Voltage output 15 mA max. Direct current 0 mA 20 mA -
TEMPERATURE & HUMIDITY Response time (10÷90% of f.s.) about 300 ms
Direct Voltage 0V 10 V -
Operative temperature -20°C .. +70°C (1) = referred to the input Span
Min. input value programmability
(difference between max. and min.)
Storage
-40°C .. +85°C Programmable -50 ÷ 50 °C (*) = inclusive of hysteresis, power supply variation
temperature
Input Calibration (1) and linearisation error.
Humidity (not condensed) 0 .. 90 %
the higher of ± 0.1 % f.s. and 0.2 °C
EMC (for industrial environments)
RTD sensor excitation current
DIRECTIVE 2004 / 108 / EC
Typ. 0.6 mA
Immunity EN 61000-6-2
Thermal drift (1)
Emission EN 61000-6-4
Full Scale ± 0.02 % / °C
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 80 g.
www.datexel.it
ISOLATED DIP SWITCH CONFIGURABLE CONVERTER FOR PT100
GENERAL DESCRIPTION
DAT 2061 The converter DAT 2061 is designed to provide on its output a linearised voltage or current signal proportional with the temperature
characteristic of the Pt100 sensor connected on its input.
It is possible to connect on the input both 3 wires and 2 wires Pt100.

FEATURES - Galvanic isolation at 2000 Vac between


- Input for RTD type Pt100 input / output and power supply
- Unit of measure configurable in °C or °F - Good accuracy and performance stability
- Zero and Span values configurable by DIP-switches - EMC compliant – CE mark
- Voltage or current output - DIN rail mounting in compliance with
- Output values configurable by DIP-switches EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (RTD) Linearity error (*)


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min ± 0.15 % of f.s.
Rever. polarity protection 60 Vdc max Pt100 (2-3 wires) -50°C 650°C 50°C Burn-out values
CURRENT CONSUMPTION Max. value output >20 mA or > 10 Vdc
Current output 60 mA max. OUTPUT
Line resistance influence (1)
Voltage output 40 mA max. Output type Min Max Span min 0.05 % f.s. / Ω (100 Ω max balanced for wire)
ISOLATION Direct current 0 mA 20 mA -
Response time (10÷90% of f.s.) about 500 ms
2000 Vac, 50 Hz, 1 min. Direct Voltage 0V 10 V -
(1) = referred to the input Span
P.D.S. SERIES

TEMPERATURE & HUMIDITY Min. input value programmability (difference between max. and min.)
Operative temperature -20°C .. +70°C Programmable -50 ÷ 50 °C (*) = inclusive of hysteresis, power supply variation
Storage and linearisation error.
temperature
-40°C .. +85°C Input Calibration (1)
Humidity (not condensed) 0 .. 90 % the higher of ± 0.1 % f.s. and 0.2 °C

EMC (for industrial environments) RTD sensor excitation current


DIRECTIVE 2004 / 108 / EC Typ. 0.6 mA
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full Scale ± 0.02 % / °C
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
32
Weight about 80 g.

NOT LINEARIZED DIP SWITCH CONFIGURABLE TRANSMITTER FOR THERMOCOUPLE


GENERAL DESCRIPTION
DAT 2045

The transmitter DAT 2045 is designed to provide on its output a 4÷20 mA current loop signal linear and proportional with the value
of voltage generated from the thermocouple connected to its input.
The DAT 2045 doesn’t execute the linearisation of the input signal; this feature allows to use the transmitter with acquisition systems
with an internal linearisation software.

FEATURES
- Configurable Input for thermocouples type K, J, R, S and T - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with EN-
- 4 to 20 mA “voltage linear” output on current loop 50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT (TC) Thermal drift (1)


Power supply voltage 10 .. 30 Vdc Input type Min Max Span min Full Scale ± 0.02 % / °C
Rever. polarity protection 60 Vdc max J -50°C 950°C 100°C Linearity error (*)
TEMPERATURE & HUMIDITY K -50°C 1370°C 100°C ± 0.05 % of f.s.
Operative temperature -20°C .. +70°C S -50°C 1760°C 700°C Burn-out values
Storage R -50°C 1760°C 700°C Max. value output >20 mA
-40°C .. +85°C
temperature
T -50°C 450°C 100°C Input Impedance
Humidity (not condensed) 0 .. 90 %
10 MΩ
EMC (for industrial environments) OUTPUT
Line resistance influence (1)
DIRECTIVE 2004 / 108 / EC Output type Min Max Span min
0.2 µV / Ω
Immunity EN 61000-6-2 Direct current 4 mA 20 mA -
Response time (10÷90% of f.s.) about 500 ms
Emission EN 61000-6-4 Min. input value programmability
Programmable -50 ÷ 50 °C (1) = referred to the input Span
HOUSING
(difference between max. and min.)
Material Self-extinguishing plastic Input Calibration (1)
(*) = inclusive of hysteresis, power supply variation
Dim. (mm) W x L x H : 90 x 112 x 12.5 the higher of ± 0.1 % f.s. and 0.2 °C and linearisation error.
Weight About 90 g. CJC compensation ± 0.5°C

www.datexel.it
NOT LINEARIZED DIP SWITCH CONFIGURABLE CONVERTER FOR THERMOCOUPLE

DAT 2145 GENERAL DESCRIPTION


The converter DAT 2145 is designed to provide on its output a voltage or current signal linear and proportional with the value of
voltage generated from the thermocouple connected to its input.
The DAT 2145 doesn’t execute the linearisation of the input signal; this feature allows to use the converter with acquisition systems
with an internal linearisation software.

FEATURES - Voltage or current “voltage linear” output


- Configurable Input for thermocouples type K, - Unit of measure configurable in °C or °F
J, R, S and T - EMC compliant – CE mark
- Good accuracy and performance stability - DIN rail mounting in compliance with EN-50022
- Configurable by DIP-switches and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT (TC)


(RTD) Linearity error (*)
Power supply voltage 18 .. 30 Vdc Input type Min
Min Max
Max Span min ± 0.05 % of f.s.
Rever. polarity protection 60 Vdc max JPt100 (2-3 fili) -50°C 950°C
50°C 100°C
650°C Burn-out values
CURRENT CONSUMPTION K -50°C 1370°C 100°C Max. value output >20 mA or 10 Vdc
Current output 40 mA max. S -50°C 1760°C 700°C Input Impedance
Voltage output 10 mA max. R -50°C 1760°C 700°C
10 MΩ
TEMPERATURE & HUMIDITY T -50°C 450°C 100°C
Line resistance influence (1)
Operative temperature -20°C .. +70°C
OUTPUT 0.2 µV / Ω
Storage
-40°C .. +85°C Response time (10÷90% of f.s.) about 500 ms
Output type Min Max Span min

P.D.S. SERIES
temperature
Humidity (not condensed) 0 .. 90 % Direct current 4 mA 20 mA - (1) = referred to the input Span
EMC (for industrial environments) Direct Voltage 0V 10 V - (difference between max. and min.)
(*) = inclusive of hysteresis, power supply variation
DIRECTIVE 2004 / 108 / EC Min. input value programmability
and linearisation error.
Immunity EN 61000-6-2 Programmable -50 ÷ 50 °C
Emission EN 61000-6-4 Input Calibration (1)
HOUSING the higher of ± 0.1 % f.s. and 0.2 °C

Material Self-extinguishing plastic CJC compensation ± 0.5°C


Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
Weight About 90 g. Full Scale ± 0.02 % / °C
33
DIP SWITCH CONFIGURABLE 3 WAYS ISOLATED SIGNAL CONVERTER
GENERAL DESCRIPTION
DAT 5020

The converter DAT 5020 is designed to provide on its output a voltage or current signal proportional with the value of the normalised signal or
the potentiometer applied on its input. The user can program the input and output ranges by the proper DIP-switches available after opening the
suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the
top of device. The 2000 Vac isolation between input, power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications. On the input side, an auxiliary supply source
isolated from the power supply is provided; this allows to connect on input both active and passive current loops.

FEATURES - Isolated power supply source for passive current


- Input for voltage, current and potentiometer signal transmitter on input
- Voltage or current configurable output - Good accuracy and performance stability
- High number of Input / output configuration - EMC compliant – CE mark
- Galvanic isolation at 2000 Vac on the 3 ways - DIN rail mounting in compliance with EN-50022
and EN-50035
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING Input Impedance


Power supply voltage 18 .. 32 Vdc Material Self-extinguishing plastic Voltage >/= 1 MΩ, Current: ~ 50 Ω
Rever. polarity protection 60 Vdc max Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
18 Vdc min
Aux. Power Supply Weight about 80 g. Full Scale ± 0.02 % / °C
@ 20 mA
Current consumption
Current output with active Power supply INPUT OUTPUT
aux operative input (20 mA): 110 mA max.
Input type Min Max Span min Output type Min Max Span min
Voltage output 80 mA max.
Current 0 mA 20 mA - Current 0 mA 20 mA -
ISOLATION
Voltage -10 V 10 V - Voltage -10 V 10 V -
2000 Vac,
All the ways
50 Hz, 1 min Potentiometer Max output signal
TEMPERATURE & HUMIDITY (Rnom. from 15 Vdc or 30 mA
0% 100 % -
1KΩ to 5 KΩ )
Operative temperature -20°C .. +60°C Response time (10÷90% of f.s.) about 500 ms
Max input signal
Storage
-40°C .. +85°C (1) = referred to the input Span
temperature 30 Vdc or 50 mA
(difference between max. and min.)
Humidity (not condensed) 0 .. 90 % Input Calibration (1)
(*) = inclusive of hysteresis and power supply variation.
EMC (for industrial environments) ± 0.1 % f.s.
DIRECTIVE 2004 / 108 / EC Linearity (*)
Immunity EN 61000-6-2 ± 0.15 % f.s.
Emission EN 61000-6-4
www.datexel.it
3 WAYS ISOLATED DIP SWITCH CONFIGURABLE SIGNAL CONVERTER
GENERAL DESCRIPTION
DAT 5021 The converter DAT 5021 is designed to provide on its output a voltage or current signal proportional with the value of the normalised
signal applied on its input. The user can program the input and output ranges by the proper DIP-switches available after opening the
suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers
located on the top of device.
FEATURES - Galvanic isolation at 2000 Vac between input, power
- Input for voltage and current signal supply and output
- Input range configurable by DIP-switches - Good accuracy and performance stability
- Isolated power supply source for passive current - EMC compliant – CE mark
transmitter on input - DIN rail mounting in compliance with EN-50022
- Isolated power supply source for passive loads on output and EN-50035
- Voltage or current output configurable by DIP-switches
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING OUTPUT


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic Output type Min Max Span min
Rever. polarity protection 60 Vdc max
Dim. (mm) W x L x H : 90 x 112 x 12.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT @ 20 mA Weight About 90 g. 4 mA 20 mA -
Aux. Power Supply IN 18 Vdc @ 20 mA
0V 10 V -
CURRENT CONSUMPTION INPUT 2V 10 V -
Current output with active Power supply Voltage
aux operative input (20 mA): 90 mA max. Input type Min Max Span min 0V 5V -
Voltage output 40 mA max. 0 mA 20 mA -
Current 1V 5V -
P.D.S. SERIES

ISOLATION 4 mA 20 mA -
Load resistance (Rload)
All the ways 2000 Vac, 50 Hz, 1 min
0V 10 V - Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY 2V 10 V -
Voltage
Current output </= 500 Ω
Operative temperature -20°C .. +60°C
0V 5V - (*) = inclusive of hysteresis and power supply variation.
Storage
-40°C .. +85°C 1V 5V -
temperature
Humidity (not condensed) 0 .. 90 % Input Calibration ± 0.1 % f.s.
EMC (for industrial environments) Linearity (*) ± 0.05 % f.s.
DIRECTIVE 2004 / 108 / EC Thermal drift
Immunity EN 61000-6-2 Full Scale ± 0.02 % / °C
Emission EN 61000-6-4 Response time (from 10 to 90 % of f.s.) < 10 ms
34
4 WAYS ISOLATED DIP SWITCH CONFIGURABLE SIGNAL CONVERTER/SIGNAL SPLITTER
GENERAL DESCRIPTION
DAT 5022

The converter DAT 5022 is designed to provide on its output two voltage or current signals proportional with the value of the normali-
sed signal applied on its input. The user can program the input and outputs ranges by the proper DIP-switches available after opening
the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.

FEATURES - Isolated power supply source for passive loads on


- Input for voltage and current signal outputs
- Input range configurable by DIP-switches - Galvanic isolation at 2000 Vac between input, power
- Voltage or Current two independent output channels supply and outputs
- Voltage or current outputs configurable by DIP-switches - Good accuracy and performance stability
- EMC compliant – CE mark
- Isolated power supply source for passive current
- DIN rail mounting in compliance with EN-50022
transmitter on input and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING OUTPUT (2 CHANNELS)


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic Output type Min Max Span min
Rever. polarity protection 60 Vdc max
Dim. (mm) W x L x H : 90 x 112 x 12.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT @ 20 mA Weight About 90 g. 4 mA 20 mA -
Aux. Power Supply IN 18 Vdc @ 20 mA
0V 10 V -
CURRENT CONSUMPTION INPUT
2V 10 V -
Current output with active Power supply Input type Min Max Span min Voltage
aux operative input (20 mA): 120 mA max. 0V 5V -
Voltage output 60 mA max. 0 mA 20 mA -
Current 1V 5V -
ISOLATION 4 mA 20 mA -
Load resistance (Rload)
All the ways 2000 Vac, 50 Hz, 1 min 0V 10 V -
Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY 2V 10 V -
Voltage Current output </= 500 Ω
Operative temperature -20°C .. +60°C 0V 5V -
(*) = inclusive of hysteresis and power supply variation.
Storage 1V 5V -
-40°C .. +85°C
temperature
Input Calibration ± 0.1 % f.s.
Humidity (not condensed) 0 .. 90 %
Linearity (*) ± 0.05 % f.s.
EMC (for industrial environments)
Thermal drift
DIRECTIVE 2004 / 108 / EC
Full Scale ± 0.02 % / °C
Immunity EN 61000-6-2
Response time (from 10 to 90 % of f.s.) < 10 ms
Emission EN 61000-6-4

www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR AC CURRENT SIGNAL
GENERAL DESCRIPTION
DAT 5023Iac The converter DAT 5023Iac is designed to detect the TRMS value of the AC current signal from 0÷5 A to 0÷60 A applied on its input providing
a voltage or current output signal. The user can program the input and output ranges by the proper DIP-switches available after opening the
suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on
the top of device. The 2000 Vac isolation between power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications.
The measure of the input signal is executed by a cross connector and a Hall effect transducer; this allows to isolate the input side from the
output and power supply.
FEATURES
- Input for AC current signal - Isolated power supply source for passive loads on output
- Build-in cross connector (8mm diameter) - Independent zero and full scale regulations
- Measure by Hall effect transducer - EMC compliant – CE mark
- True Root Mean Square (TRMS) measure - DIN rail mounting in compliance with
- Galvanic isolation at 2000 Vac EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING OUTPUT


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic output type Min Max Span min
Rever. polarity protection 60 Vdc max Dim. (mm) W x L x H : 90 x 112 x 22.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT Weight About 170 g. 4 mA 20 mA -
@ 20 mA
CURRENT CONSUMPTION 0V 10 V -
Current output with Aux supply out ope- INPUT
2V 10 V -
rative (20 mA): 90 mA max. Input type Min Max Span min Voltage
Voltage output 60 mA max. 0V 5V -
DAT5023Iac/A 0÷5 A 0÷10 A -
ISOLATION 1V 5V -

P.D.S. SERIES
DAT5023Iac/B 0÷20 A 0÷30 A -
All the ways
2000 Vac, Load resistance (Rload)
50 Hz, 1 min DAT5023Iac/D 0÷40 A 0÷60 A -
Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY Bandwidth (-3dB)
Current output </= 500 Ω
Operative temperature -20°C .. +60°C 40 Hz ÷ 1KHz
Storage Response time (10÷90% of f.s.) About 400 ms
-40°C .. +85°C Input Calibration ± 0.1 % f.s.
temperature (*) = inclusive of hysteresis and power supply variation.
Linearity (*) ±1 % f.s.
Humidity (not condensed) 0 .. 90 %
Thermal drift
EMC (for industrial environments)
Full Scale ± 0.02 % / °C
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2
Emission EN 61000-6-4
35
ISOLATED CONVERTER FOR DC CURRENT SIGNAL
WITH FIXED INPUT AND DIP SWITCH CONFIGURABLE OUTPUT
GENERAL DESCRIPTION
DAT 5023Idc

The converter DAT 5023Idc is designed to convert the DC current signal from 0÷5 A to 0÷60 A applied on its input in a voltage or current
output signal. The device is available in three versions (A, B and D) in function of the input current value.
The user can program the output ranges by the proper DIP-switches available after opening the suitable door located on the side
of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.

FEATURES - Isolated power supply source for passive loads on output


- Input for DC current signal - Independent zero and full scale regulations
- Build-in cross connector (8mm diameter) - EMC compliant – CE mark
- Measure by Hall effect transducer - DIN rail mounting in compliance with
- Galvanic isolation at 2000 Vac EN-50022 and EN-50035
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING OUTPUT


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic output type Min Max Span min
Rever. polarity protection 60 Vdc max Dim. (mm) W x L x H : 90 x 112 x 22.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT Weight About 170 g. 4 mA 20 mA -
@ 20 mA
CURRENT CONSUMPTION 0V 10 V -
Current output with Aux supply out
INPUT
2V 10 V -
operative (20 mA): 90 mA max. Input type Min Max Span min Voltage
Voltage output 60 mA max. 0V 5V -
Current (A) (1) 0÷5 A 0÷60 A -
ISOLATION 1V 5V -
Input Calibration ± 0.1 % f.s.
All the ways
2000 Vac, Load resistance (Rload)
50 Hz, 1 min Linearity (*) ±1 % f.s. Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY
Thermal drift Current output </= 500 Ω
Operative temperature -20°C .. +60°C
Storage
Full Scale ± 0.02 % / °C Response time (10÷90% of f.s.) About 400 ms
-40°C .. +85°C
temperature (1) = To choose the input range refer to the technical (*) = inclusive of hysteresis and power supply variation.
Humidity (not condensed) 0 .. 90 % data sheet.
EMC (for industrial environments)
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2
Emission EN 61000-6-4

www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR AC / DC VOLTAGE SIGNAL
GENERAL DESCRIPTION
DAT 5023/V The converter DAT 5023/V is designed to detect the TRMS value of the AC voltage signal or to convert the DC voltage signal
applied on its input in a voltage or current output signal. The user can program the input type and output ranges by the proper
DIP-switches available after opening the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.
The 1500 Vac isolation between input, power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications.

FEATURES - Voltage or current output configurable by DIP-switches


- Input for AC/DC voltage signal - Galvanic isolation at 1500 Vac between input, power supply and
- Dedicated measure inputs output
- Input type of measure ( AC / DC ) configurable by DIP-switches - Good accuracy and performance stability
- True Root Mean Square (TRMS) measure - EMC compliant – CE mark
- Isolated power supply source for passive loads on output - DIN rail mounting in compliance with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING OUTPUT


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic Output type Min Max Span min
Rever. polarity protection 60 Vdc max Dim. (mm) W x L x H : 90 x 112 x 12.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT Weight About 90 g. 4 mA 20 mA -
@ 20 mA
CURRENT CONSUMPTION 0V 10 V -
Current output with Aux supply out ope- INPUT
2V 10 V -
rative (20 mA): 80 mA max. Input type(1) Min Max Span min Voltage
Voltage output 60 mA max. 0V 5V -
Voltage (Vac) 0÷36 Vac 0÷550 Vac -
P.D.S. SERIES

ISOLATION 1V 5V -
Voltage (Vdc) 0÷36 Vdc 0÷550 Vdc -
All the ways
1500 Vac, Load resistance (Rload)
50 Hz, 1 min Bandwidth (-3dB)
Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY 40 Hz ÷ 1KHz
Current output </= 500 Ω
Operative temperature -20°C .. +60°C Input Calibration ± 0.1 % f.s.
(AC) 250 ms
Storage Linearity (*) Response time (10÷90% of f.s.)
-40°C .. +85°C
temperature (DC) 20 ms
(AC) ±1 % f.s. (DC) ± 0.1 % f.s.
Humidity (not condensed) 0 .. 90 %
Thermal drift (1) = To choose the input range refer to the technical
EMC (for industrial environments) data sheet.
Full Scale ± 0.02 % / °C
DIRECTIVE 2004 / 108 / EC (*) = Inclusive of hysteresis and power supply variation.
Immunity EN 61000-6-2
Emission EN 61000-6-4
36
ISOLATED PROGRAMMABLE DIP SWITCH CONVERTER
FOR STRAIN GAUGE / BRIDGE SENSORS
GENERAL DESCRIPTION
DAT 5025

The converter DAT 5025 is designed to provide on its output a voltage or current signal linear and proportional with the output
voltage coming from the output of a bridge transducer applied on its input.
The user can program the bridge excitation voltage value, the input and the output ranges by the proper DIP-switches available
after opening the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.

FEATURES
- Input for Strain-Gauge - Isolated power supply source for passive loads on output
- Input range configurable from 0÷10 mV up to 0÷200 - Independent zero and full scale regulations
mV or from ± 5 mV up to ± 200 mV - EMC compliant – CE mark
- Current limiter on the input side - Din rail mounting in compliance with EN-50022
- Galvanic isolation at 2000 Vac on the 3 ways and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING OUTPUT


Power supply voltage 18 .. 30 Vdc Material Self-extinguishing plastic Output type Min Max Span min
Rever. polarity protection 60 Vdc max Dim. (mm) W x L x H : 90 x 112 x 12.5 0 mA 20 mA -
12 Vdc min Current
Aux. Power Supply OUT Weight About 90 g. 4 mA 20 mA -
@ 20 mA
CURRENT CONSUMPTION 0V 10 V -
Current output with active Power supply INPUT
2V 10 V -
aux operative (20 mA): 120 mA max. Input type(1) Min Max Span min Voltage
Voltage output 80 mA max. 0V 5V -
0 mV 10 mV -
ISOLATION 1V 5V -
Strain-Gauge 0 mV 200 mV -
All the ways
2000 Vac, ± 5 mV ± 200 mV - Load resistance (Rload)
50 Hz, 1 min
Bridge excitation voltage (Vexc) Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY
3.60 Vdc ± 0.1% (with bridge’s resistance included between 100 Ω and 10 KΩ) Current output </= 500 Ω
Operative temperature -20°C .. +60°C
10 Vdc ± 0.1% (with bridge’s resistance included between 300 Ω and 10 KΩ) Response time (10÷ 90% of f.s.) 40 ms
Storage
-40°C .. +85°C Bridge excitation current
temperature (1) = To choose the input range refer to the technical
Humidity (not condensed) 0 .. 90 % 65 mA max. data sheet.
EMC (for industrial environments) Input Calibration ± 0.1 % f.s. (*) = Inclusive of hysteresis and power supply variation.
DIRECTIVE 2004 / 108 / EC Linearity (*) ± 0.1 % f.s.
Immunity EN 61000-6-2 Thermal drift
Emission EN 61000-6-4 Full Scale ± 0.01 % / °C

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

P.D.S. SERIES
P.D.S. series temperature and signal transmitters
www.datexel.it

and converters for DIN rail mounting 37

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
05 Trip amplifiers

ELECTRONIC AND CONTROL PROCESS DEVICES

DAT5028-DAT5024 SERIES:
Trip amplifiers for DIN rail mounting
The devices of the “DAT5028 - DAT5024” series can accept on input several
types of sensor coming from the field.

• TRIP AMPLIFIERS with universal analog input configurable


by Dip-switch indication on display of the trip level value (DAT5028)

• TRIP AMPLIFIERS with dedicated analog input (DAT5024)

• TRIP AMPLIFIERS with configurable input Voltage or Current (DAT5024E)

INDEX
40 • DAT 5028
Trip amplifier with display for universal analog input

41 • DAT 5024
Trip amplifier with dedicated analog input

42 • DAT 5024E
Economic, isolated trip amplifier configurable by Dip-Switches
TRIP AMPLIFIERS
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
05

Trip “DAT5028 / DAT5024 series” trip


amplifiers amplifiers for DIN rail mounting
TRIP AMPLIFIER WITH DISPLAY FOR UNIVERSAL ANALOG INPUT
DAT 5028 GENERAL DESCRIPTION
The DAT 5028 device is able to acquire RTD or Tc sensors, mV, V or mA input signals connected to the universal analog input.
By means of push-button and 4-digit display on the front panel, four different trip alarms are configurable. Each alarm threshold
commands an output relay. Input signal can be retransmitted on the analog output in a Voltage or Current signal, configurable by
means of dip-switch on the side of the device.
By means of an internal 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
The 1500 Vac isolation on all ways removes eventual ground-loop effects, allowing the use of the device even in the heavy envi-
ronmental conditions.

FEATURES
- Universal Analog Input : Voltage, Current, TC, RTD, Resistance - 1500 Vac galvanic isolation on all ways
- 2 SPDT + 2 SPST Relay Outputs (Version with 4 trips) - High Accuracy
- 2 SPDT Relay Outputs (Version with 2 trips) - EMC compliance – CE Mark
- 1 V/mA Analog Output for signal transmission - DIN rail suitable mounting (EN-50022)

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY TEMPERATURE AND HUMIDITY


Power supply voltage 12 ÷ 30 Vdc Operative temperature -30°C ÷ +60°C
TRIP AMPLIFIERS

Current Consumption 120 mA @24Vdc (300mA max) Storage temperature -40°C ÷ +85°C

Rever. polarity protection 60 Vdc max Humidity (not condensed) 0 ÷ 90 %

ISOLATION HOUSING
Isolation voltage 1500 Vac (on all ways) Material Self-extinguishing plastic
EMC (for industrial environments) Mounting DIN Rail
DIRECTIVE 2004/108/EC
Dimensions (mm) W x L x H : 90 x 112 x 22.5
Immunity EN 61000-6-2
Emission EN 61000-6-4 Weight about 150 g.

ANALOG INPUT Lead wire res. influence


40
Type Range Accuracy Linearity Thermal drift RTD (3 wires) 0.05 %/Ω (50 Ω max)
100 mV -100 / +100 mV ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C mV, Tc < 0.8 uV/Ohm
10 V -10 / +10 V ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C RTD excitation current, Res, Pot ~ 0.7 mA
20 mA 0 / 20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Pot. Nominal value 2 KOhm
Pt100 -200 / +850 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Sample Time 1 sec.
Pt1K -200 / +200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Warm-up time 3 min.
Ni100 -60 / +180°C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
DIGITAL OUTPUT
Ni1K -60 / +150 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
n.2 SPDT + n.2 SPST Relay
Res 0 / 2 Kohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
2 A @ 250 Vac (per contact)
Pot 0 / 100 % ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Max Load (resistive)
2 A @ 30 Vdc (per contact)
Tc J -210 / +1200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Tc K -210 / +1370 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Min Load 5Vdc , 10mA

Tc R -50 / +1760 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Voltage Max. 250Vac (50 / 60 Hz) ,110Vdc

Tc S -50 / +1760 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C


ANALOG OUTPUT
Tc B +400 / +1825 C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Type Range Accuracy Linearity Thermal drift
Tc E -210 / +1000 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
10 V 0 / +10 V ±0.1 % f.s. ±0.05 % f.s. 100 ppm/°C
Tc T -210 / +400 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
20 mA 0 / +20 mA ±0.1 % f.s. ±0.05 % f.s. 100 ppm/°C
Tc N -210 / +1300 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
< 500 Ohm (current output)
Load Resistance
> 5 KOhm (voltage output)
Auxiliary Voltage >12V

www.datexel.it
TRIP AMPLIFIER WITH DEDICATED ANALOG INPUT
DAT 5024 GENERAL DESCRIPTION
The trip amplifier DAT 5024 is able to accept on its input a wide range of normalised voltage signals, normalised current signals
coming from both active and passive current loop, signals coming from RTDs, Thermocouples and resistance sensors. The input type
and the input range are fixed: refer to the section “Technical Specifications”, table “ Input type ” to order the device. The Threshold 1
is programmed as high alarm, while, by dip-switches, it is possible to set the Threshold 2 either as high or low alarm. The trip level of
each threshold can be adjusted by the potentiometers and checked by the test-points located on the front of the device. It is possible
to adjust by potentiometers also the values of the hysteresis level and delay time. The isolation between input and power supply is
2000 Vac. The isolation between input and contacts of relays is 2000 Vac.The isolation between power supply and contacts of relays
is 1500 Vac. The isolations eliminate the effects of all ground loops eventually existing and allows the use of the converter in heavy
environmental conditions found in industrial applications.

FEATURES - Two relays SPDT 250Vac, 2A


- Available analog inputs: RTD, TC, Voltage, Resistance and Current - Galvanic isolated among the three ways
- Two independent threshold: two high alarm or one high and - High accuracy
one low alarm - EMC compliant – CE mark
- Trip level and hysteresis adjustable by potentiometer - Suitable for DIN rail mounting in compliance with
- Delay time adjustable by potentiometer up to 25 sec. EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY EMC (for industrial environments) TEMPERATURE AND HUMIDITY


Power supply voltage 18 ÷ 32 Vdc
DIRECTIVE 2004/108/EC Operative temperature -30°C ÷ +60°C
Current Consumption 110 mA max @ 24 Vdc
Rever. polarity protection 60 Vdc max Immunity EN 61000-6-2 Storage temperature -40°C ÷ +85°C

TRIP AMPLIFIERS
AUXILIARY SUPPLY
(only for mA input) > 18 V @ 20 mA Emission EN 61000-6-4 Humidity (not condensed) 0 ÷ 90 %

ISOLATION HOUSING

Input – power supply 2000 Vac 50 Hz, 1 min Material Self-extinguishing plastic

Input – contact of relays 2000 Vac 50 Hz, 1 min Dimensions (mm) W x L x H : 90 x 112 x 22.5

Power supply – contact of relays 1500 Vac 50 Hz, 1 min. Weight about 90 g.

INPUT Input calibration (1) ±0.1% f.s.


Input type* Min Max Linearity (1)
Voltage mV, V, mA ± 0.05% f.s. 41
50 mV 0 mV +50 mV Tc, RTD ± 0.2% f.s.
100 mV 0 mV +100 mV Input impedance

500 mV 0 mV +250 mV mV, Tc > 1 MΩ

1V 0 mV +1 V V > 100 KΩ

10 V 0 mV +10 V mA < 50 Ω

Thermocouple RTD excitation current

J -210 °C +1200 °C Typical 0.6 mA

K -210 °C +1370 °C Thermal drift (1)


Full scale ± 0.02 % / °C
R -50 °C +1760 °C
CJC comp.
S -50 °C +1760 °C
Tc ± 0.5 °C
B +400 °C +1820 °C
Thermal drift CJC
E -210 °C +1000 °C
Full scale ± 0.02 °C/ °C
T -210 °C +400 °C
Line resistance influence (1)
N -210 °C +1300 °C
mV, Tc < 0.8 uV/Ohm
RTD
Threshold Adjustable from 2 up to 98% f.s.
Pt100 -50 °C +400 °C
Hysteresis Adjustable from 0.5 up to 10 % f.s.
Pt1000 -200 °C +200 °C
Delay Adjustable up to 25 sec.
Ni100 -60 °C +180 °C
Ni1000 -60 °C +150 °C RELAY OUTPUT
Resistance N° 2 SPDT
250 Ω 0Ω 250 Ω Contact rating 250 Vac, 2A
2 KΩ 0Ω 2000 Ω Isolation between contact 1000 Vac max
Current mA (1) referred to input Span (difference between max. and min. values)
20 mA 0 mA 20 mA
* Specify in phase of order

www.datexel.it
ECONOMIC, ISOLATED TRIP AMPLIFIER CONFIGURABLE BY DIP-SWITCHES
DAT 5024E GENERAL DESCRIPTION
The DAT 5024E is an economic trip amplifier able to accept on its input normalised voltage and current signals coming from both active
and passive current loops. Both the trips can be configured as high or low alarm, the adjustment of the trip values is performed by the
potentiometers THR1 and THR2 located on the front side of the device.
The adjustment of the hysteresis and delay value can be performed by the potentiometers accessible opening the suitable door loca-
ted on the side of the device.
On the devices are foreseen the following isolation power supply/input: 1500 Vac; contact of relays/output-input: 1000 Vac.

FEATURES
- Input for Voltage and Current - Delay time adjustable by potentiometer from 1 up to 6 sec.
- Two independent thresholds - Two relays SPDT (Form C)
- Type of alarm programmable by dip-switch as high - Good accuracy and linearity
or low - EMC compliant – CE mark
- Galvanic isolated among the ways - Suitable for DIN rail mounting in compliance with EN-50022
- Trip level and hysteresis adjustable by potentiometers and EN-50035

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

Power Supply EMC (for industrial environments) TEMPERATURE AND HUMIDITY


Power supply voltage 18 ÷ 30 Vdc
DIRECTIVE 2004/108/EC Operative temperature -20°C ÷ +60°C
Current Consumption 110 mA max @ 24 Vdc
TRIP AMPLIFIERS

Rever. polarity protection 60 Vdc max Immunity EN 61000-6-2 Storage temperature -40°C ÷ +85°C
AUXILIARY SUPPLY
Emission EN 61000-6-4 Humidity (not condensed) 0 ÷ 90 %
(only for mA input) > 18 V @ 20 mA

ISOLATION HOUSING

Input – Power Supply 1500 Vac 50 Hz, 1 min Material Self-extinguishing plastic

Input – contact of relays 1000 Vac 50 Hz, 1 min Dimensions (mm) W x L x H : 90 x 112 x 12.5

Power Supply – Contact of relays 1000 Vac 50 Hz, 1 min. Weight about 90 g.

INPUT Input calibration (1)


Input type Min Max ±0.1% f.s.
42
0V 5V Thermal drift (1)
0V 10 V Full scale ± 0.02 % / °C
Voltage
1V 5V
RELAY OUTPUT
2V 10 V
N° 2 SPDT (Form C)
0 mA 20 mA
Current (1) referred to input Span (difference between max. and min. values)
4 mA 20 mA
Maximum operating voltage (on resistive load)
125 Vac, 30 Vdc
Maximum operating current (on resistive load)
0.5 A @ 125 Vac, 1 A @ 30 Vdc
Maximum switching capacity (on resistive load)
62.5 VA, 30 W
Trip value regulation
Configurable from 2 to 96 % of f.s.
Delay time value regulation
Configurable from 1 to 6 sec.
Hysteresis value regulation
Configurable from 1 al 9.5 % of f.s.

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

TRIP AMPLIFIERS
“DAT5028 / DAT5024 series”
www.datexel.it

trip amplifiers for din rail mounting 43

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

“DAT200, DAT500 SERIES”: signal transmitters


and converters,galvanic isolators
The transmitters and converters of the DAT200 series can accept on their
input signal coming from potentiometer sensors (DAT205) or voltage and
current signals (DAT207) The series is composed of:
• Not isolated transmitter for potentiometer input from 1 Kohm up to 10
Kohm. Powered from 4÷20 mA current loop (DAT205 2W).
• Not isolated converter for potentiometer input from 1 Kohm up to 10
Kohm. Fixed range (DAT205 3W).
• Not isolated transmitter for mV, V, mA input . Fixed range. Powered from
4÷20 mA current loop (DAT207 2W).
• Not isolated converter for mV, V, mA input . Fixed range. (DAT207 3W).
• Self-powered, 3000 Vac isolated converter for 0÷20 mA current loop.
(DAT511).
• Self-powered, 1500 Vac isolated converter for 0÷20 mA current loop. Hart
compatible (DAT511-H).

INDEX
46 • DAT 205 2W
Fixed range Transmitter for potentiometer
DAT 205 3W
Fixed range Converter for potentiometer

47 • DAT 207 2W
Fixed range transmitter for mV,V and mA signals
DAT 207 3W
Converter for mV,V and mA signals

48 • DAT 511
Self-powered current loop isolator
DAT 511/H
Self-powered current loop isolator HART compatible
DAT200/500 SERIES

06

DAT200 Signal transmitters and


DAT500 converters, galvanic
SERIES isolators
FIXED RANGE TRANSMITTER FOR POTENTIOMETER
GENERAL DESCRIPTION
DAT 205 2W The transmitter DAT 205 2W is designed to provide on output a 4÷20 mA current loop linearised signal proportional with the
variation of resistance introduced from the potentiometer connected to its input; to make the measure, a 1 Vdc voltage reference
is provided at the ends of the potentiometer. The regulation of the zero and full-scale value are made using the ZERO and SPAN
potentiometers; there is not influence between the regulations.

FEATURES - 4÷20 mA current loop linearised output


- Input for potentiometer - High accuracy
- Zero and Span values adjustable by - EMC compliant – CE mark
potentiometers - Suitable for DIN rail mounting in compliance with
- Independent Zero and Span adjustment EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 10 .. 32 Vdc Input type Min Max Span min Output type Min Max Span min
Reverse polarity protection 60 Vdc max Potentiometer Current 4 mA 20 mA -
0% 100% -
TEMPERATURE & HUMIDITY (Rnom.1 ... 10KΩ) Burn-out values
DAT200, DAT500 SERIES

Operative temperature -20°C .. +70°C Calibration Max. value output 25 mA

Storage temperature -40°C .. +85°C Potentiometer ± 0.1 % f.s. Response time (10÷90%) about 500 ms
Linearity
Humidity (not condensed) 0 .. 90 %
± 0.1 % f.s.
EMC (for industrial environments)
Thermal drift
DIRECTIVE 2004/108/EC
Full scale ± 0.02 % / °C
Immunity EN 61000-6-2
Emission EN 61000-6-4

HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.

46
FIXED RANGE CONVERTER FOR POTENTIOMETER
GENERAL DESCRIPTION
DAT 205 3W

The converter DAT 205 3W is designed to provide on output a linearised voltage or current signal proportional with the variation of
resistance introduced from the potentiometer connected to its input; to make the measure, a 1 Vdc voltage reference is provided at
the ends of the potentiometer. The regulations of the zero and full-scale value are made using the ZERO and SPAN potentiometers;
there is not influence between the regulations.

FEATURES - Output in voltage or current


- Input for potentiometer - High accuracy
- Zero and Span values adjustable by - EMC compliant – CE mark
potentiometers - Suitable for DIN rail mounting in compliance with
- Independent Zero and Span adjustment EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Reverse polarity protection 60 Vdc max Potentiometer Current 0 mA 20 mA -
0% 100% -
CURRENT CONSUMPTION (Rnom.1 ... 10KΩ) Voltage 0V 10 V -
Current output 30 mA max. Calibration Burn-out values
Voltage output 10 mA max. Potentiometer ± 0.1 % f.s. Max. value output 25 mA or 15V

TEMPERATURE & HUMIDITY Linearity Response time (10÷90%) about 500 ms


Operative temperature -20°C .. +70°C ± 0.1 % f.s.
Thermal drift
Storage temperature -40°C .. +85°C
Full scale ± 0.02 % / °C
Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments)


DIRECTIVE 2004/108/EC
Immunity EN 61000-6-2
Emission EN 61000-6-4

HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.

www.datexel.it
FIXED RANGE TRANSMITTER FOR mV,V AND mA SIGNALS
DAT 207 2W GENERAL DESCRIPTION
The transmitter DAT 207 2W is designed to provide on output a 4÷20 mA current loop signal proportional with the variation
of the normalised current or voltage signal applied to its input.

FEATURES The transmitter is available in 3 different versions:


- Input for current or voltage signals - DAT 207A 2W to measure voltage signals included
- Zero and Span values adjustable by potentiometers between 0 ÷ 5 mV and 0 ÷ 200 mV;
- Independent Zero and Span adjustment
- 4÷20 mA current loop output - DAT 207B 2W to measure voltage signals included
- High accuracy between 0 ÷ 200 mV and 0 ÷ 20 V;
- EMC compliant – CE mark - DAT 207C 2W to measure current signals
- Suitable for DIN rail mounting in compliance with between 0 ÷ 5 mA and 0 ÷ 50 mA.
EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 10 .. 32 Vdc Input type Min Max Span min Output type Min Max Span min
Reverse polarity protection 60 Vdc max
Voltage Current 4 mA 20 mA -

DAT200, DAT500 SERIES


TEMPERATURE & HUMIDITY
Version“A” 0 ÷ 5 mV 0 ÷ 200 mV - Burn-out values
Operative temperature -20°C .. +70°C
Version“B” 0 ÷ 200 mV 0 ÷ 20 V - Max. value output 25 mA
Storage temperature -40°C .. +85°C
Current Response time (10÷90%) about 300 ms
Humidity (not condensed) 0 .. 90 % Version“C” 0 ÷ 5 mA 0 ÷ 50 mA -
EMC (for industrial environments) Calibration
DIRECTIVE 2004/108/EC mV, V, mA ± 0.1 % f.s.
Immunity EN 61000-6-2
Linearity
Emission EN 61000-6-4
± 0.1 % f.s.
HOUSING
Thermal drift
Material Self-extinguishing plastic
Full scale ± 0.02 % / °C
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.

CONVERTER FOR mV,V AND mA SIGNALS 47


GENERAL DESCRIPTION
DAT 207 3W

The converter DAT 207 3W is designed to provide on output a 4÷20 mA current loop signal proportional with the variation of
the normalised current or voltage signal applied to its input.

FEATURES The converter is available in 3 different versions:


- Input for current or voltage signals - DAT 207A 3W to measure voltage signals included
- Zero and Span values adjustable by potentiometers between 0 ÷ 5 mV and 0 ÷ 200 mV;
- Independent Zero and Span adjustment
- Output in voltage or current - DAT 207B 3W to measure voltage signals included
- High accuracy between 0 ÷ 200 mV and 0 ÷ 20 V;
- EMC compliant – CE mark
- DAT 207C 3W to measure current signals between
- Suitable for DIN rail mounting in compliance with
0 ÷ 5 mA and 0 ÷ 50 mA.
EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT OUTPUT


Power supply voltage 18 .. 30 Vdc Input type Min Max Span min Output type Min Max Span min
Reverse polarity protection 60 Vdc max
Voltage Current 0 mA 20 mA -
CURRENT CONSUMPTION
Version“A” 0 ÷ 5 mV 0 ÷ 200 mV - Voltage 0V 10 V -
Current output 30 mA max.
Version“B” 0 ÷ 200 mV 0 ÷ 20 V - Burn-out values
Voltage output 10 mA max.
Current Max. value output 25 mA or 15V
TEMPERATURE & HUMIDITY
Version“C” 0 ÷ 5 mA 0 ÷ 50 mA - Response time (10÷90%) about 300 ms
Operative temperature -20°C .. +70°C
Calibration
Storage temperature -40°C .. +85°C
mV, V, mA ± 0.1 % f.s.
Humidity (not condensed) 0 .. 90 %
Linearity
EMC (for industrial environments)
± 0.1 % f.s.
DIRECTIVE 2004/108/EC
Thermal drift
Immunity EN 61000-6-2
Emission EN 61000-6-4 Full scale ± 0.02 % / °C

HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.

www.datexel.it
SELF-POWERED CURRENT LOOP ISOLATOR
GENERAL DESCRIPTION
DAT 511 The transmitter DAT 511 is a passive 0÷20 mA current loop isolator.
The input current, variable from 0 up to 20 mA, is converted in an output current of the same value but keeping a galvanic isolation
from the input circuit.
The converter is a passive isolator: this means that the device employs the measurement signal to power it self, so it does not require
any external power supply.

FEATURES - Good accuracy and performance stability


- 0÷20 mA isolated conversion - EMC compliant – CE mark
- No external supply required - Suitable for DIN rail mounting in compliance with
- 3000 Vac galvanic isolation EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

TEMPERATURE & HUMIDITY INPUT OUTPUT


Operative temperature -20°C .. +70°C Input type Min Max Span min Output type Min Max Span min
Storage temperature -40°C .. +85°C Current 0 mA 20 mA - Current 0 mA 20 mA -
Max. INPUT signal 50 mA Burn-out values
DAT200, DAT500 SERIES

Humidity (not condensed) 0 .. 90 %


Load resistance (Rload) Max. value output 25 mA
EMC (for industrial environments)
From 0 to 700 ohm Isolation voltage
DIRECTIVE 2004/108/EC
Thermal drift 3000 Vac, 50 Hz 1 min.
Immunity EN 61000-6-2
Full scale ± 0.02 % / °C Response time (10÷90%) About 20 ms
Emission EN 61000-6-4

HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight About 60 g.

48
SELF-POWERED CURRENT LOOP ISOLATOR HART COMPATIBLE
GENERAL DESCRIPTION
DAT 511/H

The transmitter DAT 511/H is a passive 0÷20 mA current loop isolator. The input current, variable from 0 up to 20 mA, is converted
in an output current of the same value but keeping a galvanic isolation from the input circuit. The device allows the bidirectional
communication of signals HART protocol compatible. The converter is a passive isolator: this means that the device employs the
measurement signal to power itself, so it does not require any external power supply.

FEATURES - Good accuracy and performance stability


- 0÷20 mA isolated conversion - EMC compliant – CE mark
- Hart compatible - Suitable for DIN rail mounting in
- No external supply required compliance with EN-50022 and EN-50035
- 1500 Vac galvanic isolation
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

TEMPERATURE & HUMIDITY INPUT OUTPUT


Operative temperature 0°C .. +55°C Input type Min Max Span min Output type Min Max Span min
Storage temperature -40°C .. +85°C Current 0 mA 20 mA - Current 0 mA 20 mA -
Max. INPUT signal 50 mA Burn-out values
Humidity (not condensed) 0 .. 90 %
Load resistance (Rload) Max. value output 25 mA
EMC (for industrial environments)
From 0 to 700 ohm Isolation voltage
DIRECTIVE 2004/108/EC
Thermal drift 1500 Vac, 50 Hz 1 min.
Immunity EN 61000-6-2
Full scale ± 0.02% / °C Response time (10÷90%) About 20 ms
Emission EN 61000-6-4
Bandwidth
HOUSING
From 0.5 up to 4 KHz bidirectional within 3 dB
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight About 60 g.

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

DAT200, DAT500 SERIES


Signal transmitters and converters,
www.datexel.it

galvanic isolators 49

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

“DAT3000 SERIES” data acquisition and control


modules
The distributed I/O modules of the DAT3000 series represent a complete
solution for the acquisition and control of the analog and digital I/O signals.
The series is composed of:
• Serial line converters and repeaters (DAT3580, DAT3580 USB,
DAT3580 MBTCP, DAT3590).
• Modules for digital inputs and outputs (DAT3130, DAT3140, DAT3148/8,
DAT3148/12, DAT3188/4, DAT3188/8).
• Modules for analog inputs (DAT3011, DAT3014, DAT3015, DAT3016,
DAT3017, DAT3018, DAT3019).
• Modules with analog outputs (DAT3022, DAT3024, DAT3028).
The devices communicate on the RS-485 serial line by the MODBUS RTU com-
munication protocol and are able to communicate with the host computer on
multipoint net using only two wires.

INDEX
52 • DAT 3580
Isolated converter RS232 RS485 / 422
DAT 3580-USB
Isolated converter USB RS485 / 422
53 • DAT 3580-MBTCP
Isolated Ethernet Gateway Modbus TCP Modbus RTU
DAT 3590
Repeater/ Isolator RS485 / 422
54 • DAT 3130
Distributed I/O Module 4 digital inputs + 4 relay outputs on RS-485 network
DAT 3140
Distributed I/O Module 4 digital inputs + 8 NPN outputs on RS-485 network
55 • DAT 3148/8
Distributed I/O Module 8 digital inputs on RS-485 network
DAT 3148/12
Distributed I/O Module 12 digital inputs on RS-485 network
56 • DAT 3188/4
Distributed I/O Module 4 digital inputs + 8 PNP outputs on RS-485 network
DAT 3188/8
Distributed I/O Module 8 digital inputs + 8 PNP outputs on RS-485 network
57 • DAT 3011
Universal Remote I/O module on RS-485 network
58 • DAT 3014
Remote I/O module 4 channels RTD input on RS-485 network
DAT 3015-I
Remote I/O module 4 channels +/-20mA input on RS-485 network
59 • DAT 3015-V
Remote I/O module 4 channels +/-10V input on RS-485 network
DAT 3016
Remote I/O module 4 channels mV / TC input on RS-485 network
60 • DAT 3017-I
Remote I/O module 8 channels ±20mA input on RS-485 network
DAT 3017-V
Remote I/O module 8 channels ±10V input on RS-485 network
61 • DAT 3018
Remote I/O module 8 channels mV / TC input on RS-485 network
DAT 3019
Remote I/O module 8 channels RTD input on RS-485 network
62 • DAT 3022
Remote I/O module 2 channels V / mA output on RS-485 network
DAT 3024
Remote I/O module 4 channels V / mA output on RS-485 network
63 • DAT 3028
Remote I/O module 8 channels Voltage output on RS-485 network
DAT3000 SERIES

07

DAT3000 Data acquisition and


SERIES control modules
ISOLATED CONVERTER RS232 RS485 / 422

DAT 3580 GENERAL DESCRIPTION


The device DAT3580 is an isolated interface converter between asynchronous serials lines RS232 and RS485 or RS422 that guaran-
tees a full isolation between power supply, serial line RS-232 and serial line RS-485 or 422 removes eventual ground-loop effects,
allowing the use of the device even in the heavy environmental conditions.
It is designed to operate either on serial interface RS-422 full-duplex 4 wires or RS485 half-duplex 2 wires, with a baud-rate transmis-
sion up to 115.2 Kbps. The transmission is asynchronous without settings of protocol, data format and baud rate.
On the line RS-232 are not necessary handshake commands (RTS, CTS, etc..) to control the baud rate.

FEATURES - Galvanic isolation on all ways


- Asynchronous serial data transmission - RS232 connection on DB9 or removable terminals
- Automatic baud-rate fitting up to 115.2 Kbps - EMC compliance – CE mark
- Distance up to 1200 m - EIA RS232, RS485 and RS422 compliant
- Point to point connection or multipoint connection up to - Suitable for DIN rail mounting in compliance with
32 modules EN-50022
- DC or AC power supply
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY EMC (for industrial environments) RS485 Interface


10 ÷ 30 Vdc DIRECTIVE 2004 / 108 / EC Baud-rate up to 115.2 Kbps
9 ÷ 18 Vac (18 ÷ 30 Vac optional) Immunity EN 61000-6-2 1.2 Km @ 38400 bps
CURRENT CONSUMPTION Emission EN 61000-6-4
DAT3000 SERIES

2 Km @ 19200 bps
35 mA typ. @ 24Vdc HOUSING 3 Km @ 9600 bps
Max. distance / baud-rate
ISOLATIONS Material Self-extinguishing plastic ratio (recommended) (1) 4 Km @ 4800 bps
Power Supply/ RS232 Mounting DIN rail
5 Km @ 2400 bps
2000 Vac, 50 Hz, Dim. (mm) W x L x H : 120 x 100 x 22.5
Power Supply/ RS485-422
1 min. 7 Km @ 1200 bps
Weight About 150 g.
RS232 / RS485-422 Number of modules in multipoint 32 max.
CONNECTION
TEMPERATURE & HUMIDITY RS-232 DB9 and removable screw terminals Switching time TX/RX (RS485) 150 us.
Operative temperature -20°C ÷ +60°C RS-485/422 removable screw terminals Internal terminator resistance (optional) 120 Ohm (optional)
Storage temperature -40°C ÷ +85°C (1) = The maximum distance depends of: number of
devices connected, type of cabling, noises, etc...
Humidity (not condensed) 0 ÷ 90 %

52

ISOLATED CONVERTER USB RS485 / 422


GENERAL DESCRIPTION
DAT 3580-USB

The device DAT3580-USB is an isolated interface converter between USB port and asynchronous serial lines RS485 or RS422 that
guarantees a full isolation between power supply, USB and serial line RS-485 or 422 removes eventual ground-loop effects, allowing
the use of the device even in the heavy environmental conditions.
It is designed to operate either on serial interface RS-422 full-duplex 4 wires or RS485 half-duplex 2 wires, with a baud-rate transmis-
sion up to 115.2 Kbps. The transmission is asynchronous without settings of protocol, data format and baud rate.

FEATURES - DC or AC power supply


- Asynchronous serial data transmission - Galvanic isolation on all ways
- Automatic baud-rate fitting up to 115.2 Kbps - EMC compliance – CE mark
- Distance up to 1200 m - USB 2.0. EIA RS485 and RS422 compliant
- Point to point connection or multipoint connection up to - Suitable for DIN rail mounting in compliance
32 modules with EN-50022
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY EMC (for industrial environments) RS485 Interface


10 ÷ 30 Vdc DIRECTIVE 2004 / 108 / EC Baud-rate up to 115.2 Kbps
9 ÷ 18 Vac (18 ÷ 30 Vac optional) Immunity EN 61000-6-2 1.2 Km @ 38400 bps
CURRENT CONSUMPTION Emission EN 61000-6-4
2 Km @ 19200 bps
35 mA typ. @ 24Vdc HOUSING 3 Km @ 9600 bps
Max. distance / baud-rate
ISOLATIONS Material Self-extinguishing plastic ratio (recommended) (1) 4 Km @ 4800 bps
Power Supply/ USB Mounting DIN rail
5 Km @ 2400 bps
2000 Vac, 50 Hz, Dim. (mm) W x L x H : 120 x 100 x 22.5
Power Supply/ RS485-422
1 min. 7 Km @ 1200 bps
Weight About 150 g.
USB / RS485-422 Number of modules in multipoint 32 max.
CONNECTION
TEMPERATURE & HUMIDITY USB USB cable integrated Switching time TX/RX (RS485) 150 us.
Operative temperature -20°C ÷ +60°C Internal terminator resistance (optional) 120 Ohm (optional)
RS-485/422 removable screw terminals
Storage temperature -40°C ÷ +85°C (1) = The maximum distance depends of: number of
devices connected, type of cabling, noises, etc...
Humidity (not condensed) 0 ÷ 90 %

www.datexel.it
ETHERNET ISOLATED GATEWAY MODBUS TCP MODBUS RTU
DAT 3580-MBTCP GENERAL DESCRIPTION
The gateway DAT3580-MBTCP allows to connect the Modbus RTU devices of a RS-485 network to the Ethernet network throu-
gh the Modbus TCP protocol.
By means of the Telnet interface it is possible to configure all the Modbus TCP side options (IP address, subnet mask, etc..) and
the Modbus RTU side options (baud rate, etc...).
The device guarantees a full isolation between lines, allowing the use even in the heavy environmental conditions.

FEATURES
- Network interface - Distance up to 1200 m, up to 32 devices in multipoint
- Ethernet 10/100Base-T, Modbus TCP - Removable screw-terminal connection
- Telnet configuration - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- RJ45 connection - Galvanic Isolation on all ways
- RS-485 Serial interface - EMC compliance – CE mark
- Modbus RTU Master - Ethernet IEEE 802.3 and RS485 compliant
- Baud rate up to 115.2 Kbps - Suitable for DIN rail mounting in compliance with EN-50022
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY EMC (for industrial environments) Network interface Ethernet 10/100 Base-T
18 ÷ 30 Vdc DIRECTIVE 2004 / 108 / EC Protocol Modbus TCP
CURRENT CONSUMPTION Immunity EN 61000-6-2 Connection RJ-45
45 mA typ. @ 24Vdc (sleep mode) Emission EN 61000-6-4 Baud-rate (RS-485) up to 115.2 Kbps

DAT3000 SERIES
80 mA max HOUSING 1.2 Km @ 38400 bps
ISOLATIONS Material Self-extinguishing plastic 2 Km @ 19200 bps
Power Supply/ Ethernet 1500 Vac, 50 Hz, 1 min. Mounting DIN rail Max. distance / baud-rate 3 Km @ 9600 bps
Power Supply/ RS485 2000 Vac, 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 22.5 ratio (recommended) (1) 4 Km @ 4800 bps
Ethernet / RS485 2000 Vac, 50 Hz, 1 min. Weight About 150 g. 5 Km @ 2400 bps

TEMPERATURE & HUMIDITY CONNECTION 7 Km @ 1200 bps


Operative temperature -20°C ÷ +60°C Ethernet RJ-45 Number of modules in multipoint 32 max.

Storage temperature -40°C ÷ +85°C RS-485 removable screw terminals Switching time TX/RX (RS485) 150 us.

Humidity (not condensed) 0 ÷ 90 % Internal terminator resistance (optional) 120 Ohm (optional)

(1) = The maximum distance depends of: number of


devices connected, type of cabling, noises, etc...
53

REPEATER/ ISOLATOR RS485 / 422


GENERAL DESCRIPTION
DAT 3590

The device DAT 3590 is an isolated repeater between asynchronous serials lines RS485 or RS422 that guarantees a full isolation
between power supply and serial line removing eventual ground-loop effects, allowing the use of the device even in the heavy
environmental conditions. It is designed to operate either on serial interface RS-422 full-duplex 4 wires or RS485 half-duplex 2
wires, with a baud-rate transmission up to 115.2 Kbps.
The transmission is asynchronous without settings of protocol, data format and baud rate.

FEATURES - DC or AC power supply


- Asynchronous serial data transmission - Galvanic isolation
- Automatic baud-rate fitting up to 115.2 Kbps - EMC compliance – CE mark
- Distance up to 1200 m - EIA RS485 and RS422 compliant
- Point to point connection or multipoint - Suitable for DIN rail mounting in compliance
connection up to 32 modules with EN-50022
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY EMC (for industrial environments) Baud-rate up to 115.2 Kbps


10 ÷ 30 Vdc DIRECTIVE 2004 / 108 / EC 1.2 Km @ 38400 bps
9 ÷ 18 Vac (18÷24 Vac optional) Immunity EN 61000-6-2 2 Km @ 19200 bps
CURRENT CONSUMPTION Emission EN 61000-6-4 Max. distance / baud-rate 3 Km @ 9600 bps
35 mA @ 24Vdc HOUSING ratio (recommended) (1) 4 Km @ 4800 bps
Material Self-extinguishing plastic 5 Km @ 2400 bps
ISOLATIONS
Power Supply/ RS485-422 2000 Vac, 50 Hz, 1 min. Mounting DIN rail 7 Km @ 1200 bps

RS485-422 / RS485-422 2000 Vac, 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 22.5 Number of modules in multipoint 32 max.
Weight About 150 g. Switching time TX/RX (RS485) 150 us.
TEMPERATURE & HUMIDITY
CONNECTION Internal terminator resistance (optional) 120 Ohm
Operative temperature -20°C ÷ +60°C
RS485/422 removable screw terminals (1) = The maximum distance depends of: number of
Storage temperature -40°C ÷ +85°C devices connected, type of cabling, noises, etc...
Humidity (not condensed) 0 ÷ 90 %

www.datexel.it
DISTRIBUTED I/O MODULE 4 DIGITAL INPUTS + 4 RELAY OUTPUTS ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3130 The device DAT 3130 is able to acquire up to 4 digital inputs and to drive up to 4 relay outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. The 1500 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial
line cancels any ground-loop effect noise, allowing the use of the device in worst ambient conditions.

FEATURES - Watch-Dog alarm


- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Three ways galvanic isolation 1500 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 4 digital inputs - EMC compliance – CE Mark
- 4 relay outputs (2 SPDT + 2 SPST) - In compliance to EN-50022 DIN rail mounting

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING OUTPUT


Supply Voltage 18 .. 30 Vdc Material Self-extinguishing plastic Output channels 4
Current consumption 45 mA @ 24 Vdc Mounting DIN rail Type
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 22.5
n° 2 SPDT relays
ISOLATIONS Weight About 210 g.
n° 2 SPST N.O. relays
DAT3000 SERIES

Inputs – RS485
1500 Vac 50 Hz, 1 DIGITAL INPUTS Switching power (max.)
Inputs – Supply
min. Input channels 4 2 A @ 250 Vac (resistive load) per contact
RS-485 – Supply
Input voltage (bipolar) 2 A @ 30 Vdc (resistive load) per contact
TEMPERATURE & HUMIDITY
OFF State 0÷3V
Operating Temperature -10°C .. +60°C Minimum load 5Vdc , 10mA
ON State 10 ÷ 30 V
Storage Temperature -40°C .. +85°C Max. Voltage 250Vac (50 / 60 Hz), 110Vdc
Humidity (not condensed) 0 .. 90 %
Impedance 4.7 KΩ
Data Transmission (asynchronous serial)
EMC (for industrial environments)
Baud rate up to 38.4 Kbps
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Max. Distance 1.2 Km - 4000ft
Emission EN 61000-6-4 Sample time 5 ms max

54 DISTRIBUTED I/O MODULE 4 DIGITAL INPUTS + 8 NPN OUTPUTS ON RS-485 NETWORK


GENERAL DESCRIPTION
DAT 3140

The device DAT 3140 is able to acquire up to 4 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. The galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels
any ground-loop effect noise, allowing the use of the device in worst ambient conditions.

FEATURES - Watch-Dog alarm


- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Galvanic isolation on all ways
- MODBUS RTU/ASCII protocol - High accuracy
- 4 digital inputs - EMC compliance – CE Mark
- 8 digital outputs, NPN type - In compliance to EN-50022 DIN rail mounting

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING OUTPUT


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic Output channels 8
Current consumption 45 mA @ 24 Vdc Mounting DIN rail Type NPN
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5
600 mA per channel
ISOLATIONS Weight About 210 g. Max. Load
3 A max per module
Inputs – Outputs 1000 Vac 50 Hz, 1 min.
DIGITAL INPUTS Max. Voltage 30 Vdc
Inputs – RS485 2000 Vac 50 Hz, 1 min.
Input channels 4
Inputs – Supply 2000 Vac 50 Hz, 1 min. Over-current NO
Input voltage (bipolar) protection
Outputs – RS485 2000 Vac 50 Hz, 1 min.
OFF State 0÷3V
Outputs –Supply 2000 Vac 50 Hz, 1 min.
RS-485 – Supply 2000 Vac 50 Hz, 1 min. ON State 10 ÷ 30 V
Impedance 4.7 KΩ
TEMPERATURE & HUMIDITY
Operating Temperature -10°C .. +60°C Data Transmission (asynchronous serial)
Storage Temperature -40°C .. +85°C Baud rate up to 38.4 Kbps
Humidity (not condensed) 0 .. 90 % Max. Distance 1.2 Km - 4000ft
EMC (for industrial environments) Sample time 20 ms max
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2
Emission EN 61000-6-4

www.datexel.it
DISTRIBUTED I/O MODULE 8 DIGITAL INPUTS ON RS-485 NETWORK

DAT 3148/8 GENERAL DESCRIPTION


The device DAT 3148/8 is able to acquire up to 8 digital inputs. The data are transmitted with MODBUS RTU/ASCII on RS-485 net-
work. To assure safe operation of the system, the device is equipped with two Watch-Dog timers.
The 2000 Vac galvanic isolation between inputs, power supply and RS-485 serial line cancels any ground-loop effect noise, allowing
the use of the device in worst ambient conditions.

FEATURES
- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Four ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 8 digital inputs - EMC compliance – CE Mark
- Watch-Dog alarm - In compliance to EN-50022 DIN rail mounting
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY EMC (for industrial environments) DIGITAL INPUTS


Supply Voltage 10 .. 30 Vdc DIRECTIVE 2004 / 108 / EC Input channels 8

Current consumption 35 mA @ 24 Vdc Immunity EN 61000-6-2 Input voltage (bipolar)


Rever. Polarity protection 60 Vdc max Emission EN 61000-6-4 OFF State 0÷3V
ON State 10 ÷ 30 V
ISOLATIONS HOUSING
Impedance 4.7 KΩ

DAT3000 SERIES
Input 0÷7 1500 Vac 50 Hz, 1 min. Material Self-extinguishing plastic
Data Transmission (asynchronous serial)
Inputs – RS485 2000 Vac 50 Hz, 1 min. Mounting DIN rail Baud rate 38.4 Kbps
Inputs – Supply 2000 Vac 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 17.5 Max. Distance 1.2 Km - 4000ft
RS-485 – Supply 2000 Vac 50 Hz, 1 min. Weight About 210 g. Sample time 5 ms max
TEMPERATURE & HUMIDITY
Operating Temperature -10°C .. +60°C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 %

DISTRIBUTED I/O MODULE 12 DIGITAL INPUTS ON RS-485 NETWORK 55


DAT 3148/12

GENERAL DESCRIPTION
The device DAT 3148/12 is able to acquire up to 12 digital inputs. The data are transmitted with MODBUS RTU/ASCII on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers.
The 2000 Vac galvanic isolation between inputs, power supply and RS-485 serial line cancels any ground-loop effect noise, allowing
the use of the device in worst ambient conditions.

FEATURES
- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Four ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 12 digital inputs - EMC compliance – CE Mark
- Watch-Dog alarm - In compliance to EN-50022 DIN rail mounting

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY EMC (for industrial environments) DIGITAL INPUTS


Supply Voltage 10 .. 30 Vdc DIRECTIVE 2004 / 108 / EC Input channels 12

Current consumption 35 mA @ 24 Vdc Immunity EN 61000-6-2 Input voltage (bipolar)


Rever. Polarity protection 60 Vdc max Emission EN 61000-6-4 OFF State 0÷3V
ON State 10 ÷ 30 V
ISOLATIONS HOUSING
Impedance 4.7 KΩ
Input 0÷7 / 8÷11 1500 Vac 50 Hz, 1 min. Material Self-extinguishing plastic
Data Transmission (asynchronous serial)
Inputs – RS485 2000 Vac 50 Hz, 1 min. Mounting DIN rail Baud rate 38.4 Kbps
Inputs – Supply 2000 Vac 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 17.5 Max. Distance 1.2 Km - 4000ft
RS-485 – Supply 2000 Vac 50 Hz, 1 min. Weight About 210 g. Sample time 5 ms max
TEMPERATURE & HUMIDITY
Operating Temperature -10°C .. +60°C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 %

www.datexel.it
DISTRIBUTED I/O MODULE 4 DIGITAL INPUTS + 8 PNP OUTPUTS ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3188/4 The device DAT 3188/4 is able to acquire up to 4 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network (is available the RS-232 interface model).
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. Also, the outputs are protected against over currents and over temperature.
The 2000 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels any ground-loop effect noise,
allowing the use of the device in worst ambient conditions.

FEATURES - Over-temperature and over-current protection


- Field Bus data acquisition - Watch-Dog alarm
- Master/Slave communication on RS-485 network - All the ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 4 digital inputs - EMC compliance – CE Mark
- 8 digital outputs, PNP type - In compliance to EN-50022 DIN rail mounting
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING DIGITAL OUTPUTS


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic Output channels 8
Current consumption 45 mA @ 24 Vdc Mounting DIN rail Type PNP
Dim. (mm) W x L x H : 120 x 100 x 17.5
Rever. Polarity protection 60 Vdc max 500 mA per channel*
Weight About 210 g. Max. Load
ISOLATIONS (Input / Output / RS485 / Supply) 1 A per module
DAT3000 SERIES

DIGITAL INPUTS Inductive Load 48 Ω - 2 H max.


2000 Vac 50 Hz, 1 min.
Input channels 4
Voltage 10.5 ÷ 30 Vdc
TEMPERATURE & HUMIDITY
Input voltage (bipolar)
Operating Temperature -10°C .. +60°C (*) = Protection against over-current and over-temperature
OFF State 0÷3V Short circuit current 1.7 A max.
Storage Temperature -40°C .. +85°C
ON State 10 ÷ 30 V
Humidity (not condensed) 0 .. 90 %
Impedance 4.7 KΩ
EMC (for industrial environments) Data Transmission (asynchronous serial)
DIRECTIVE 2004 / 108 / EC Baud rate 115.2 Kbps
Immunity EN 61000-6-2 Max. Distance 1.2 Km - 4000ft
Emission EN 61000-6-4 Sample time 5 ms max

56

DISTRIBUTED I/O MODULE 8 DIGITAL INPUTS + 8 PNP OUTPUTS ON RS-485 NETWORK


GENERAL DESCRIPTION
DAT 3188/8

The device DAT 3188/8 is able to acquire up to 8 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network (is available the RS-232 interface model).
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. Also, the outputs are protected against over currents and over temperature.
The 2000 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels any ground-loop effect noise,
allowing the use of the device in worst ambient conditions.

FEATURES - Over-temperature and over-current protection


- Field Bus data acquisition - Watch-Dog alarm
- Master/Slave communication on RS-485 network - All the ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 8 digital inputs - EMC compliance – CE Mark
- 8 digital outputs, PNP type - In compliance to EN-50022 DIN rail mounting
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING DIGITAL OUTPUTS


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic Output channels 8
Current consumption 45 mA @ 24 Vdc Mounting DIN rail Type PNP
Dim. (mm) W x L x H : 120 x 100 x 17.5
Rever. Polarity protection 60 Vdc max 500 mA per channel*
Weight About 210 g. Max. Load
ISOLATIONS (Input / Output / RS485 / Supply) 1 A per module
DIGITAL INPUTS Inductive Load 48 Ω - 2 H max.
2000 Vac 50 Hz, 1 min.
Input channels 8
Voltage 10.5 ÷ 30 Vdc
TEMPERATURE & HUMIDITY
Input voltage (bipolar)
Operating Temperature -10°C .. +60°C (*) = Protection against over-current and over-temperature
OFF State 0÷3V Short circuit current 1.7 A max.
Storage Temperature -40°C .. +85°C
ON State 10 ÷ 30 V
Humidity (not condensed) 0 .. 90 %
Impedance 4.7 KΩ
EMC (for industrial environments) Data Transmission (asynchronous serial)
DIRECTIVE 2004 / 108 / EC Baud rate 115.2 Kbps
Immunity EN 61000-6-2 Max. Distance 1.2 Km - 4000ft
Emission EN 61000-6-4 Sample time 5 ms max

www.datexel.it
UNIVERSAL REMOTE I/O MODULE ON RS-485 NETWORK
DAT 3011 GENERAL DESCRIPTION
The device DAT 3011 is able to acquire RTD or Tc sensors, mV, V or mA input signals connected to the universal analog input. Moreo-
ver a second V/mA analog input is available. The device is able to acquire up to 3 digital inputs and to drive one solid-state relay and
two SPST relays. Data values are transmitted with MODBUS RTU protocol on the RS-485 network.
By means of a 16 bit converter, the device guarantee a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 1500 Vac isolation on all ways (Power Supply / RS485 / Universal input / V-mA input / Digital inputs / Relay outputs) removes
eventual ground-loop effects, allowing the use of the device even in the heavy environmental conditions.

FEATURES
- Field-Bus remote data acquisition - 1 SSR Digital Output + 2 Relay Outputs
- RS-485 Modbus RTU (Slave) communication - Watch-Dog Alarm
- 1 Universal Analog Input - 1500 Vac galvanic isolation on all ways
- 1 V/mA Analog Input - High Accuracy
- 2 0-20mA Analog Outputs - EMC compliance – CE Mark
- 3 Digital Inputs - DIN rail suitable mounting (EN-50022)
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY SERIAL PORT TEMPERATURE & HUMIDITY


Supply Voltage 18 ÷ 30 Vdc Type RS-485 Operating Temperature -10°C .. +60°C

DAT3000 SERIES
Current consumption 30 mA (100mA max) Protocol Modbus RTU (Slave) Storage Temperature -40°C .. +85°C

Rever. Polarity protection 60 Vdc max Baud Rate up to 38400 bps Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) ISOLATIONS HOUSING


DIRECTIVE 2004 / 108 / EC Material Self-extinguishing plastic

Type of 1500 Vac Mounting DIN rail


Immunity EN 61000-6-2
Isolation ( on all ways) Dimensions (mm) W x L x H : 120 x 100 x 22.5
Emission EN 61000-6-4 Weight About 150 g.

ANALOG INPUTS ANALOG OUTPUT


Thermal Thermal
Type Range Accuracy Linearity Type Range Accuracy Linearity 57
Drift Drift
100 mV -100 ÷ +100 mV ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C 20 mA 0 ÷ +20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
10 V -10 ÷ +10 V ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Load Resistance < 500 Ohm
20 mA 0 ÷ +20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Auxiliary Voltage >12V
Pt100 -200 ÷ +850 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
DIGITAL INPUTS
Pt1K -200 ÷ +200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Input channels 3
Ni100 -60 ÷ +180 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
OFF State : 0÷3 V
Ni1K -60 ÷ +150 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Input voltage (bipolar)
ON State : 10÷30 V
Res 0 ÷ 2000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Input Impedance 4.7 KOhm
Pot 20 ÷ 2000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Tc J -210 ÷ +1200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
DIGITAL OUTPUTS
Tc K -210 ÷ +1370 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
N.1 Solid State Relay (dry contacts)
Tc R -50 ÷ +1760 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Max. Voltage 48 V (ac/dc)
Tc S -50 ÷ +1760 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Max. Load 0.4A max (resistive)
Tc B +400 ÷ +1825 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
N.2 Relays SPST
Tc E -210 ÷ +1000 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Switching power 2 A @ 250 Vac (per contact)
Tc T -210 ÷ +400 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C (resistive load) 2 A @ 30 Vdc (per contact)
Tc N -210 ÷ +1300 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Minimum load 5 Vdc , 10mA
Lead wire res. influence
Max. Voltage 250 Vac (50 / 60 Hz) ,110Vdc
RTD (3 wires) 0.05 %/Ω (50 Ω max)
Dielectric strength between contacts 1000 Vac, 50 Hz, 1 min.
mV, Tc < 0.8 uV/Ohm
Dielectric strength between 4000 Vac, 50 Hz, 1 min.
Excitation current coil and contacts

RTD, Res, Pot ~ 0.7 mA


Sample time 1 sec.
Warm-up time 3 min.

www.datexel.it
REMOTE I/O MODULE 4 CHANNELS RTD INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3014 The DAT 3014 device is able to acquire up to 4 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect RTD , Potentiometers or Resistance signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 4 channel input - EMC compliance – CE mark
- RTD, Resistance and Potentiometer configurable input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING Input Calibration (1)


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic RTD ±0.05 % f.s.

Current consumption 30 mA @ 24 Vdc Mounting DIN rail Res. ±0.05 % f.s..


Dim. (mm) W x L x H : 120 x 100 x 17.5 Pot. ±0.05 % f.s..
Rever. Polarity protection 60 Vdc max
Linearity (1)
DAT3000 SERIES

Weight About 150 g.


ISOLATIONS RTD ± 0.1 % f.s.
Inputs – RS485 INPUT
Lead wire res. influence (1)
2000 Vac 50 Hz, Input type Min Max 0.05 %/Ω (50 Ω max
Power Supply– Input
1 min. RTD 2 or 3 wires RTD/res.3 wires
balanced)
Power Supply– RS-485
Pt100 -200°C 850°C RTD excitation current
TEMPERATURE & HUMIDITY Pt1000 -200°C 200°C Typical 0.350 mA
Operating Temperature -10°C .. +60°C Ni100 -60°C 180°C Thermal drift (1)
Storage Temperature -40°C .. +85°C Ni1000 -60°C 150°C Full scale ± 0.01 % / °C
Humidity (not condensed) 0 .. 90 % Resistance 2 or 3 wires Sample time 0.5 ÷ 1 sec.
Low 0Ω 500 Ω Data Transmission (asynchronous serial)
EMC (for industrial environments)
High 0Ω 2000 Ω Baud rate 38.4 Kbps
DIRECTIVE 2004 / 108 / EC POT. (nom. value) Max. Distance 1.2 Km - 4000ft
Immunity EN 61000-6-2 Low 20 Ω 500 Ω Warm-up time 3 min.
58 Emission EN 61000-6-4 High 20 Ω 2000 Ω (1) Referred to input Span (difference between max. and min. values)

REMOTE I/O MODULE 4 CHANNELS +/-20mA INPUT ON RS-485 NETWORK


GENERAL DESCRIPTION
DAT 3015-I

The device DAT 3015I is able to acquire on input up to 4 analog current signals. Data values are transmitted with MODBUS RTU/ASCII
protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 20mA current signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 4 channel input - EMC compliance – CE mark
- Up to ± 20mA input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING Sample time


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic 0.5 ÷ 1 sec.
Current consumption 30 mA @ 24 Vdc Mounting DIN rail Data Transmission (asynchronous serial)
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5
Baud rate 38.4 Kbps
ISOLATIONS Weight About 150 g.
Max. Distance 1.2 Km - 4000ft
Inputs – RS485
2000 Vac 50 Hz, (1) Referred to input Span (difference between max. and min. values)
Power Supply– Input
1 min. INPUT
Power Supply– RS-485 Input type Min Max
TEMPERATURE & HUMIDITY Current
Operating Temperature -10°C .. +60°C 20 mA -20 mA +20 mA
Storage Temperature -40°C .. +85°C
Input Calibration (1) ± 20 uA
Humidity (not condensed) 0 .. 90 %
Linearity (1) ± 0.1% f.s.
EMC (for industrial environments)
Input Impedance </= 50 Ω
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full scale ± 0.005 % / °C

www.datexel.it
REMOTE I/O MODULE 4 CHANNELS +/-10V INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3015-V The device DAT 3015V is able to acquire on input up to 4 analog voltage signals. Data values are transmitted with MODBUS RTU/
ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 10V voltage signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 4 channel input - EMC compliance – CE mark
- Up to ± 10V input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING Sample time


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic 0.5 ÷ 1 sec.
Current consumption 30 mA @ 24 Vdc Mounting DIN rail Data Transmission (asynchronous serial)
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5 Baud rate 38.4 Kbps
ISOLATIONS Weight About 150 g.
Max. Distance 1.2 Km - 4000ft

DAT3000 SERIES
Inputs – RS485
2000 Vac 50 Hz, (1) Referred to input Span (difference between max. and min. values)
Power Supply– Input INPUT
1 min.
Power Supply– RS-485 Type input Min Max
TEMPERATURE & HUMIDITY Voltage
Operating Temperature -10°C .. +60°C
10 V -10 V +10 V
Storage Temperature -40°C .. +85°C
Input Calibration (1) ± 10 mV
Humidity (not condensed) 0 .. 90 %
Linearity (1) ± 0.1% f.s.
EMC (for industrial environments)
Input Impedance > 100 KΩ
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full scale ± 0.005 % / °C

REMOTE I/O MODULE 4 CHANNEL mV / TC INPUT ON RS-485 NETWORK


59
GENERAL DESCRIPTION
DAT 3016

The DAT 3016 device is able to acquire up to 4 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol on
the RS-485 network (RS-232 interface is available). It is possible to connect Thermocouples or up to +/- 1V voltage signals.
The Cold Junction compensation for thermocouples is performed internally. By means of a 16 bit converter, the device guarantees high
accuracy and a stable measure versus time and temperature. To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the device
even in the heavy environmental conditions. The DAT 3016 is in compliance with the Directive 2004/108/EC on the electromagnetic
compatibility. The device is housed in a rough self-extinguishing plastic container which, thanks to its thin profile of 17.5mm only, allows
a high density mounting on EN-50022 standard DIN rail.

FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 4 channel input - High Accuracy
- Up to +/- 1V and TC configurable input - EMC compliance – CE mark
Type J,K,R,S,B,E,T,N - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT Linearity (1)


Supply Voltage 10 .. 30 Vdc Input type Min Max mV ± 0.1% f.s.
Current consumption 30 mA @ 24 Vdc Voltage TC ± 0.2% f.s.
Rever. Polarity protection 60 Vdc max
25 mV -25 mV +25 mV CJC Comp. ± 0.5 °C
ISOLATIONS 100 mV -100 mV +100 mV Input Impedance
Inputs – RS485
2000 Vac 50 Hz, 250 mV -250 mV +250 mV mV, TC >=1 MΩ
Power Supply– Input
1 min. 1000 mV -1000 mV +1000 mV Thermal drift (1)
Power Supply– RS-485
Thermocouple Full scale ± 0.005 % / °C
TEMPERATURE & HUMIDITY
J -210 °C +1200 °C CJC Thermal drift
Operating Temperature -10°C .. +60°C
K -210 °C +1372 °C Full scale ± 0.02 °C / °C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 % R -50 °C +1767 °C Lead wire res. influence (1)
S -50 °C +1767 °C mV, Tc < 0.8 uV/Ohm
EMC (for industrial environments)
DIRECTIVE 2004 / 108 / EC B +400 °C +1825 °C Response time 0.5 ÷ 1 sec.
Immunity EN 61000-6-2 E -210 °C +1000 °C Data Transmission (asynchronous serial)
Emission EN 61000-6-4 T -210 °C +400 °C Baud rate 38.4 Kbps
HOUSING N -210 °C +1300 °C Max. Distance 1.2 Km - 4000ft
Material Self-extinguishing plastic Warm-up time 3 min.
Mounting DIN rail Input Calibration (1)
(1) Referred to input Span (difference between max. and min. values)
Dim. (mm) W x L x H : 120 x 100 x 17.5 the higher of ± 0.05% or 5 uV (1)
Weight About 150 g.
www.datexel.it
REMOTE I/O MODULE 8 CHANNELS ± 20mA INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3017-I The device DAT 3017I is able to acquire on input up to 8 analog current signals. Data values are transmitted with MODBUS RTU/ASCII
protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 20mA current signals.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 8 channel input - EMC compliance – CE mark
- Up to ± 20mA input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING Sample time


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic 0.5 ÷ 2 sec.
Current consumption 30 mA @ 24 Vdc Mounting DIN rail Data Transmission (asynchronous serial)
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5 Baud rate 38.4 Kbps
DAT3000 SERIES

ISOLATIONS Weight About 150 g. Max. Distance 1.2 Km - 4000ft


Inputs – RS485
2000 Vac 50 Hz, (1) Referred to input Span (difference between max. and min. values)
Power Supply– Input
1 min. INPUT
Power Supply– RS-485 Type input Min Max
TEMPERATURE & HUMIDITY Current
Operating Temperature -10°C .. +60°C 20 mA -20 mA +20 mA
Storage Temperature -40°C .. +85°C
Input Calibration (1) ± 20 uA
Humidity (not condensed) 0 .. 90 %
Linearity (1) ± 0.1% f.s.
EMC (for industrial environments)
Input Impedance <=50 Ω
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full scale ± 0.005 % / °C

60
REMOTE I/O MODULE 8 CHANNELS ±10V INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3017-V

The devices DAT 3017V is able to acquire on input up to 8 analog voltage signals. Data values are transmitted with MODBUS RTU/
ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 10V voltage signals.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 8 channel input - EMC compliance – CE mark
- Up to ± 10V input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING Sample time


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic 0.5 ÷ 2 sec.
Current consumption 30 mA @ 24 Vdc Mounting DIN rail Data Transmission (asynchronous serial)
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5 Baud rate 38.4 Kbps
ISOLATIONS Weight About 150 g. Max. Distance 1.2 Km - 4000ft
Inputs – RS485
2000 Vac 50 Hz, (1) Referred to input Span (difference between max. and min. values)
Power Supply– Input
1 min. INPUT
Power Supply– RS-485 Type input Min Max
TEMPERATURE & HUMIDITY Voltage
Operating Temperature -10°C .. +60°C 10 V -10 V +10 V
Storage Temperature -40°C .. +85°C
Input Calibration (1) ± 10 mV
Humidity (not condensed) 0 .. 90 %
Linearity (1) ± 0.1% f.s.
EMC (for industrial environments)
Input Impedance > 100 KΩ
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full scale ± 0.005 % / °C

www.datexel.it
REMOTE I/O MODULE 8 CHANNELS mV / TC INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3018 The device DAT 3018 is able to acquire up to 8 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect Thermocouples or up to +/- 1V voltage signals. The Cold Junction compensation for thermocouples is
performed internally. By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and
temperature. To ensure the plant safety, two Watch-Dog timer alarms are provided. The 2000 Vac isolation between input, power
supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, allowing the use of the device even in the heavy
environmental conditions.

FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 8 channel input - High Accuracy
- Up to +/- 1V and TC configurable input ± 1V and - EMC compliance – CE mark
TC Type J,K, R,S,B,E,T,N - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT Linearity (1)


Supply Voltage 10 .. 30 Vdc Input type Min Max mV ± 0.1% f.s.
Current consumption 30 mA @ 24 Vdc Voltage TC ± 0.2% f.s.
Rever. Polarity protection 60 Vdc max
25 mV -25 mV +25 mV CJC Comp. ± 0.5 °C
ISOLATIONS 100 mV -100 mV +100 mV Input Impedance

DAT3000 SERIES
Inputs – RS485
2000 Vac 50 Hz, 250 mV -250 mV +250 mV mV, TC >/=1 MΩ
Power Supply– Input
1 min. 1000 mV -1000 mV +1000 mV Thermal drift (1)
Power Supply– RS-485
Thermocouple Full scale ± 0.005 % / °C
TEMPERATURE & HUMIDITY
J -210 °C +1200 °C Thermal drift CJC
Operating Temperature -10°C .. +60°C
K -210 °C +1372 °C Full scale ± 0.02 % / °C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 % R -50 °C +1767 °C Lead wire res. influence (1)
S -50 °C +1767 °C mV, TC < 0.8 uV/Ohm
EMC (for industrial environments)
DIRECTIVE 2004 / 108 / EC B +400 °C +1825 °C Sample time 0.5 ÷ 2 sec.
Immunity EN 61000-6-2 E -210 °C +1000 °C Data Transmission (asynchronous serial)
Emission EN 61000-6-4 T -210 °C +400 °C Baud rate 38.4 Kbps
HOUSING N -210 °C +1300 °C Max. Distance 1.2 Km - 4000ft
Material Self-extinguishing plastic Input Calibration (1) Warm-up time 3 min
Mounting DIN rail
61
The higher of ± 0.05% or 5 uV (1) (1) Referred to input Span (difference between max. and min. values)
Dim. (mm) W x L x H : 120 x 100 x 17.5
Weight About 150 g.

REMOTE I/O MODULE 8 CHANNELS RTD INPUT ON RS-485 NETWORK


GENERAL DESCRIPTION
DAT 3019

The device DAT 3019 is able to acquire up to 8 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect 2-wires RTD sensors or up to 2 KΩ resistance signals.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the
device even in the heavy environmental conditions.

FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 8 channel 2 wires input - High Accuracy
- Pt100, Pt1K, Ni100, Ni1K and resistance up to 2 KΩ - EMC compliance – CE mark
configurable input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING Input Calibration (1)


Supply Voltage 10 .. 30 Vdc Material Self-extinguishing plastic RTD ±0.2 % f.s.
Current consumption 30 mA @ 24 Vdc Mounting DIN rail Res. ±0.2 % f.s..
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5 Linearity (1)
ISOLATIONS Weight About 150 g. RTD ± 0.2 % f.s.
Inputs – RS485 Excitation current RTD
2000 Vac 50 Hz, Typical 0.450 mA
Power Supply– Input INPUT
1 min.
Power Supply– RS-485 Thermal drift (1)
Input type Min Max
Full scale ± 150 ppm/ °C
TEMPERATURE & HUMIDITY RTD 2 wires
Sample time 0.5 ÷ 2 sec.
Operating Temperature -10°C .. +60°C Pt100 -200°C 850°C
Data Transmission (asynchronous serial)
Storage Temperature -40°C .. +85°C Pt1000 -200°C 200°C
Baud rate 38.4 Kbps
Humidity (not condensed) 0 .. 90 % Ni100 -60°C 180°C
Max. Distance 1.2 Km - 4000ft
EMC (for industrial environments) Ni1000 -60°C 150°C
Warm-up time 3 min.
DIRECTIVE 2004 / 108 / EC Resistance 2 or 3 wires
(1) Referred to input Span (difference between max. and min. values)
Immunity EN 61000-6-2 Low 0Ω 500 Ω
Emission EN 61000-6-4 High 0Ω 2000 Ω
www.datexel.it
REMOTE I/O MODULE 2 CHANNEL V / mA OUTPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3022 The DAT 3022 device generates up to 2 output analog signals from digital commands. Data values are transmitted with MODBUS
RTU/ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to generate voltage signals up to 10V and current signals up to 20mA, both active or passive loops.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 2 channel output - EMC compliance – CE mark
- Voltage or Current configurable outputs - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING Thermal drift


Supply Voltage 18 .. 30 Vdc Material Self-extinguishing plastic Full scale 100 ppm /°C

Current consumption
typ. 35 mA @ 24 Mounting DIN rail Auxiliary Voltage > 12V @ 20mA (2 channels)
Vdc 60 mA max
Dim. (mm) W x L x H : 120 x 100 x 17.5 Rise time
Rever. Polarity protection 60 Vdc max
DAT3000 SERIES

Weight About 150 g. Analog output Slew-rate


ISOLATIONS (independent programmation for each channel)
Output – RS485 OUTPUT
2000 Vac 50 Hz, Output type Min Max Voltage V/s Current mA/s
Power Supply– Output
1 min. Voltage 0.125 0.250
Power Supply– RS-485 0.250 0.500
V 0V +10 V
TEMPERATURE & HUMIDITY Current 0.500 1.000
Operating Temperature -10°C .. +60°C mA 0 mA +20 mA 1.000 2.000
Storage Temperature -40°C .. +85°C Output calibration 2.000 4.000
Humidity (not condensed) 0 .. 90 % Voltage ±10 mV 4.000 8.000
EMC (for industrial environments) Current ±20 mA Immediate Immediate

DIRECTIVE 2004 / 108 / EC Load Resistance Data Transmission (asynchronous serial)


Immunity EN 61000-6-2 Voltage > 5 KΩ Baud rate 115.2 Kbps
Emission EN 61000-6-4 Current < 500 Ω Max. Distance 1.2 Km - 4000ft
62
REMOTE I/O MODULE 4 CHANNELS V / mA OUTPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3024

The device DAT 3024 generates up to 4 output analog signals from digital commands. Data values are transmitted with MODBUS
RTU/ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to generate voltage signals up to 10V and current signals up to 20mA, both active or passive loops.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the
device even in the heavy environmental conditions.

FEATURES - Watch-Dog Alarm


- Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 4 channel output - EMC compliance – CE mark
- Voltage or Current configurable outputs - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY HOUSING Thermal drift


Supply Voltage 18 .. 30 Vdc Material Self-extinguishing plastic Full scale 100 ppm /°C

Current consumption
typ. 35 mA @ 24 Mounting DIN rail Auxiliary Voltage > 12V @ 20mA (4 channels)
Vdc 100 mA max
Dim. (mm) W x L x H : 120 x 100 x 17.5 Rise time
Rever. Polarity protection 60 Vdc max
Weight About 150 g. Analog output Slew-rate
ISOLATIONS (independent programmation for each channel)
Output – RS485 OUTPUT
2000 Vac 50 Hz, Output type Min Max Voltage V/s Current mA/s
Power Supply– Output
1 min. Voltage 0.125 0.250
Power Supply– RS-485 0.250 0.500
V 0V +10 V
TEMPERATURE & HUMIDITY Current 0.500 1.000
Operating Temperature -10°C .. +60°C mA 0 mA +20 mA 1.000 2.000
Storage Temperature -40°C .. +85°C Output calibration 2.000 4.000
Humidity (not condensed) 0 .. 90 % Voltage ±10 mV 4.000 8.000
EMC (for industrial environments) Current ±20 mA Immediate Immediate

DIRECTIVE 2004 / 108 / EC Load Resistance Data Transmission (asynchronous serial)


Immunity EN 61000-6-2 Voltage > 5 KΩ Baud rate 115.2 Kbps
Emission EN 61000-6-4 Current < 500 Ω Max. Distance 1.2 Km - 4000ft

www.datexel.it
REMOTE I/O MODULE 8 CHANNELS VOLTAGE OUTPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3028 The device DAT 3028 generates up to 8 output analog signals from digital commands. Data values are transmitted with MODBUS
RTU/ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to generate voltage signals up to 10V.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (o RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.r

FEATURES
Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 8 channel 0-10 V output - EMC compliance – CE mark
- Watch-Dog Alarm - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY HOUSING Rise time


Supply Voltage 18 .. 30 Vdc Material Self-extinguishing plastic Analog output Slew-rate
typ. 35 mA @ 24 Mounting DIN rail (independent programmation for each channel)
Current consumption
Vdc 100 mA max
Rever. Polarity protection 60 Vdc max Dim. (mm) W x L x H : 120 x 100 x 17.5
Weight About 150 g. Voltage V/s

DAT3000 SERIES
ISOLATIONS
0.125
Output – RS485
2000 Vac 50 Hz, 0.250
Power Supply– Output
1 min. 0.500
Power Supply– RS-485
OUTPUT 1.000
TEMPERATURE & HUMIDITY Output type Min Max 2.000
Operating Temperature -10°C .. +60°C
Voltage 4.000
Storage Temperature -40°C .. +85°C
V 0V +10 V Immediate
Humidity (not condensed) 0 .. 90 %
Output calibration ±10 mV
EMC (for industrial environments)
Load Resistance > 5 KΩ Data Transmission (asynchronous serial)
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift Baud rate 115.2 Kbps

Emission EN 61000-6-4 Full scale 100 ppm /°C Max. Distance 1.2 Km - 4000ft
63

ELECTRONIC AND CONTROL PROCESS DEVICES

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

“DAT9000 SERIES” Intelligent units

The DAT9000 Series intelligent units were designed by DATEXEL to


offer its customers products that, thanks to their capabilities, allow
them to manage various architectures in the area of small to medium
size automation systems and process control through the connection
of a network of MODBUS RTU Master/Slave devices connected by
way of RS-485.

The DAT9000 units read and write the parameters of the field
devices to which they are connected, processing functions of the
logical/mathematical type, including complex ones, such as
for example: alarms, linearization, means, square roots, etc..

INDEX
66 • DAT 9000
Intelligent unit with Ethernet interface
DAT 9000-DL
Intelligent unit with Data-logger and Ethernet interface

67 • DAT 9000IO
Intelligent unit with Ethernet Interface and digital I/O

68 • DAT 9000-DL-IO
Intelligent unit with Data-logger, Ethernet interface and digital I/O

69 • DAT 9011
Intelligent unit with Ethernet Interface and digital and analogue I/O

70 • DAT 9011-DL
Intelligent unit with Data-Logger function, Ethernet Interface and digital and analogue I/O
DAT9000 SERIES

08

DAT9000 Intelligent
SERIES units
INTELLIGENT UNIT WITH ETHERNET INTERFACE
GENERAL DESCRIPTION
DAT 9000 The device DAT9000 is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for
the system working. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real
time, the internal registers value.
Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to:
- Programming of the Control Logic
- Monitor, request of data, programming in real time the Intelligent Unit
- Direct programming and request of data from the Slave devices connected on the RS-485 Master.

FEATURES - Connection by removable screw-terminals


- N.1 serial interface RS-485 Modbus RTU Master - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- N.1 serial interface RS-485/232 Modbus RTU Slave - Galvanic Isolation on all the ways
- Interface Ethernet 10Base-T, Modbus TCP - EMC compliance – CE mark
- Functional Block programming software - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- Remotely programmable - Suitable for DIN rail mounting in compliance with EN-50022 standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY CONNECTIONS Network interface


10 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Ethernet 10 Base-T
CURRENT CONSUMPTION RS-232D RJ-45 (on front side) Protocol Modbus TCP
DAT9000 SERIES

45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals RS-485 Interface
80 mA max EMC (for industrial environments) Baud-rate up to 38.4 Kbps
ISOLATIONS DIRECTIVE 2004 / 108 / EC Max. distance (1) 1.2 Km @ 38.4 Kbps
Power supply / Ethernet Immunity EN 61000-6-2 Number of modules
1500 Vac, 50 Hz, up to 32
Power supply / RS485 Emission EN 61000-6-4 in multipoint
1 min.
Internal termination
Ethernet / RS485 HOUSING 120 Ohm (optional)
resistance
TEMPERATURE & HUMIDITY Material Self-extinguishing plastic
(1) = The maximum distance depends of: number of devices con-
Operative temperature -20°C ÷ +60°C Mounting DIN rail nected, type of cabling, noises, etc...
Storage temperature -40°C ÷ +85°C Dim. (mm) W x L x H : 120 x 100 x 22.5
Relative humidity (not cond.) 0 ÷ 90 % Weight About 160 g.

INTELLIGENT UNIT WITH DATA-LOGGER AND ETHERNET INTERFACE


66
GENERAL DESCRIPTION
DAT 9000-DL

The device DAT9000 DL is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing
- the logical and mathematical functions necessary for
the system working, managing up to 8 task of recording memorized on files saved on the microSD card. By means of the Ethernet
interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal registers value. By Ethernet it
is possible to get access to the files saved on the microSD card when the Data-Logger function is active.
Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to: Programming of the Control
Logic; Monitor, request of data, programming in real time the Intelligent Unit; Direct programming and request of data from the Slave
devices connected on the RS-485 Master.

FEATURES - Connection by removable screw-terminals


- N.1 serial interface RS-485 Modbus RTU Master - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- N.1 serial interface RS-485/232 Modbus RTU Slave - Galvanic Isolation on all the ways
- N.1 slot for microSD card - EMC compliance – CE mark
- Interface Ethernet 10Base-T, Modbus TCP - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- Functional Block programming software - Suitable for DIN rail mounting in compliance with EN-50022
- Remotely programmable standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY CONNECTIONS Network interface


10 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Ethernet 10 Base-T

CURRENT CONSUMPTION RS-232D RJ-45 (on front side) Protocol Modbus TCP

45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals RS-485 Interface
Baud-rate up to 38.4 Kbps
100 mA max EMC (for industrial environments)
Max. distance (1) 1.2 Km @ 38.4 Kbps
ISOLATIONS DIRECTIVE 2004 / 108 / EC Number of modules
up to 32
Power supply / Ethernet Immunity EN 61000-6-2 in multipoint
1500 Vac, 50 Hz, Internal termination
Power supply / RS485 Emission EN 61000-6-4 120 Ohm (optional)
1 min. resistance
Ethernet / RS485 HOUSING Compatible SD card
TEMPERATURE & HUMIDITY Material Self-extinguishing plastic Type microSD
Operative temperature -20°C ÷ +60°C Mounting DIN rail Memory size Up to 8 GB
Storage temperature -40°C ÷ +85°C Dim. (mm) W x L x H : 120 x 100 x 22.5 Format FAT16 or FAT32
Relative humidity (not cond.) 0 ÷ 90 % Weight About 160 g. (1) = The maximum distance depends of: number of devices con-
nected, type of cabling, noises, etc...

www.datexel.it
INTELLIGENT UNIT WITH ETHERNET INTERFACE AND DIGITAL I/O
DAT 9000IO GENERAL DESCRIPTION
The device DAT9000IO is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working. Moreover, the device is equipped with 4 digital inputs channels and 2 relay outputs. On digital inputs are available
32-bit counters and the measure of the frequency up to 300Hz.
By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to:
- Programming of the Control Logic
- Monitor, request of data, programming in real time the Intelligent Unit.
- Direct programming and request of data from the Slave devices connected on the RS-485 Master.

FEATURES - Connection by removable screw-terminals


- N.1 serial interface RS-485 Modbus RTU Master - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- N.1 serial interface RS-485/232 Modbus RTU Slave - LED signalling for digital inputs and digital outputs state
- Interface Ethernet 10Base-T, Modbus TCP - Galvanic Isolation on all the ways
- N.4 Digital Inputs - EMC compliance – CE mark
- N.2 SPDT Relay Outputs - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- Functional Block programming software - Suitable for DIN rail mounting in compliance with
- Remotely programmable EN-50022 standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY CONNECTIONS TEMPERATURE & HUMIDITY

DAT9000 SERIES
18 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
CURRENT CONSUMPTION RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals
100 mA max Relative humidity (not cond.) 0 .. 90 %
ISOLATIONS

EMC (for industrial environments) Power supply / Ethernet HOUSING


1500 Vac, 50 Hz,
Power supply / RS-485 Material Self-extinguishing plastic
DIRECTIVE 2004 / 108 / EC 1 min.
Ethernet / RS-485 Mounting DIN rail
Immunity EN 61000-6-2
Inputs / RS-485 2000 Vac, 50 Hz, Dimensions (mm) W x L x H : 120 x 100 x 22.5
Emission EN 61000-6-4 Inputs / Power supply 1 min. Weight About 190 g.

DIGITAL INPUTS DIGITAL OUTPUTS 67


Channels 4 Channels 2
Input voltage (bipolar) Type SPDT Relays
OFF state 0÷3V Switching Power (max.)
ON state 10 ÷ 30 V 2 A @ 250 Vac (resistive load) per contact
Impedance 4.7 KΩ 2 A @ 30 Vdc (resistive load) per contact
Frequency up to 300 Hz Minimum load 5Vdc , 10mA
Network interface Max. voltage
Ethernet 10Base-T 250Vac (50 / 60 Hz) , 30Vdc
Protocol Modbus TCP Dielectric strength between contacts
RS-485 Interface 1000 Vac, 50 Hz, 1 min.
Baud-rate up to 38.4 Kbps Dielectric strength between coil and contacts
Max. distance (1) 1.2 Km @ 38.4 Kbps 4000 Vac, 50 Hz, 1 min.
Number of modules (1) = The maximum distance depends of: number of devices connected, type of
up to 32
in multipoint cabling, noises, etc...
Internal termination 120 Ohm (optional)
resistance

www.datexel.it
INTELLIGENT UNIT WITH DATA-LOGGER, ETHERNET INTERFACE AND DIGITAL I/O
DAT 9000-DL-IO GENERAL DESCRIPTION
The device DAT9000-DL-IO is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-
485 Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for
the system working, managing up to 8 task of recording memorized on files saved on the microSD card. The device is equipped with
4 digital inputs channels and 2 relay outputs. For the digital inputs, are also available 32 bit counters and the measure of the frequency
up to 300 Hz. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the
internal registers value. By Ethernet it is possible to get access to the files saved on the microSD card when the Data-Logger function
is active. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to: Programming of
the Control Logic; Monitor, request of data, programming in real time the Intelligent Unit; Direct programming and request of data
from the Slave devices connected on the RS-485 Master.

FEATURES - Connection by removable screw-terminals


- N.1 serial interface RS-485 Modbus RTU Master - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- N.1 serial interface RS-485/232 Modbus RTU Slave - LED signalling for digital input and output state
- N.1 slot for microSD card - Galvanic Isolation on all the ways
- Interface Ethernet 10Base-T, Modbus TCP - EMC compliance – CE mark
- N.4 Digital Inputs + N.2 SPDT Relays - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- Functional Block programming software - Suitable for DIN rail mounting in compliance with
- Remotely programmable EN-50022 standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY CONNECTIONS TEMPERATURE & HUMIDITY


DAT9000 SERIES

18 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
CURRENT CONSUMPTION RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals
100 mA max ISOLATIONS Relative humidity (not cond.) 0 .. 90 %

EMC (for industrial environments) Power supply / Ethernet HOUSING


1500 Vac, 50 Hz,
Power supply / RS485 Material Self-extinguishing plastic
DIRECTIVE 2004 / 108 / EC 1 min.
Ethernet / RS485 Mounting DIN rail
Immunity EN 61000-6-2
Inputs / RS485 2000 Vac, 50 Hz, Dimensions (mm) W x L x H : 120 x 100 x 22.5
Emission EN 61000-6-4 Inputs / Power supply 1 min. Weight About 160 g.

68 DIGITAL INPUTS DIGITAL OUTPUTS

Channels 4 Channels 2

Input voltage (bipolar) Type SPDT Relays

OFF state 0÷3V Switching Power (max.)

ON state 10 ÷ 30 V 2 A @ 250 Vac (resistive load) per contact

Impedance 4.7 KΩ 2 A @ 30 Vdc (resistive load) per contact

Network interface Minimum load 5Vdc, 10mA

Ethernet 10Base-T Max. voltage

Protocol Modbus TCP 250Vac (50 / 60 Hz), 30Vdc

RS485 Interface Dielectric strength between contacts

Baud-rate up to 38.4 Kbps 1000 Vac, 50 Hz, 1 min.

Max. distance (1) 1.2 Km @ 38.4 Kbps Dielectric strength between coil and contacts

Number of modules 4000 Vac, 50 Hz, 1 min.


up to 32
in multipoint
(1) = The maximum distance depends of: number of devices connected, type of
Internal termination cabling, noises, etc...
120 Ohm (optional)
resistance
Compatible SD card
Type microSD
Memory size Up to 8 GB
Format FAT16 or FAT32

www.datexel.it
INTELLIGENT UNIT WITH ETHERNET INTERFACE AND DIGITAL AND ANALOGUE I/O
DAT 9011 GENERAL DESCRIPTION
The device DAT9011 is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working. The device is equipped with one universal analogue input channel, one channel for Volt and mA input, two digital
inputs and 2 relay outputs. On input an Auxiliary source is available to supply passive sensors on the field.
By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to program the
Control Logic, to monitor, to request data and programming in real time the Intelligent Unit, to program directly the Slave devices
connected on the RS-485 Master and to request data from them.

FEATURES
- N°1 serial interface RS-485 Modbus RTU Master - Remotely programmable
- N°1 serial interface RS-485/232 Modbus RTU Slave - Connection by removable screw-terminals
- Interface Ethernet 10Base-T, Modbus TCP - LED signallingmfor
u s tri es
Link/ActergEthernet, serial RX-TX,trepower
In d r d a c hi En y d busine er a t m e
- N°1 universal analogue input + N°1 current and voltage supply oa oo at

ne

ss

nt
F
B
analogue input - LED signalling for digital inputs and digital outputs state
- N°2 digital Inputs - Galvanic Isolation on all the ways
- Auxiliary supply to power sensors on field - EMC compliance – CE mark
- N°2 passive 4-20 mA analogue outputs - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- N°2 SPDT Relay Outputs - Suitable for DIN rail mounting in compliance with
- Functional Block programming software EN-50022 standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

DAT9000 SERIES
POWER SUPPLY CONNECTIONS TEMPERATURE & HUMIDITY
Power supply Voltage 9 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
Current consumption @ 24 Vdc 60 mA (170 mA max) RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
Current consumption @ 10 Vdc 147 mA (300 mA max) RS-485
Master / Slave Screw terminals pitch
Reverse polarity protection 60 Vdc max 5.08mm Relative humidity (not cond.) 0 .. 90 %
Outputs Relay
EMC (for industrial environments) Supply/Inputs/ HOUSING
Screw terminals pitch
Analogue Material Self-extinguishing plastic
DIRECTIVE 2004 / 108 / EC 3.81mm
outputs
Mounting DIN rail
Immunity EN 61000-6-2 ISOLATIONS
Dimensions (mm) W x L x H : 120 x 100 x 22.5
Isolations voltage 1500 Vac
Emission EN 61000-6-4 (50 Hz, 1 min.) (on all the ways) Weight About 190 g. 69
ANALOGUE INPUTS Sensor excitation current
Thermal RTD, Res, Pot ~ 400 uA
Type Range Calibration Linearity
Drift CJC comp. ± 1 °C
100 mV -100 ÷ +100 mV ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Sample time 1 sec.
10 V -10 ÷ +10 V ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Warm-up time (TC,RTD) 3 min.
20 mA -20 ÷ +20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C DIGITAL INPUTS
Pt100 -200 ÷ +850 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Channels 2
Pt1K -200 ÷ +200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C OFF state : 0÷3 V
Input voltage (bipolar)
ON state : 10÷30 V
Ni100 -60 ÷ +180 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Input impedance 4.7 KOhm
Ni1K -60 ÷ +150 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
N°2 Digital counter 32 bit (up to 300 Hz)
Res 0 ÷ 2000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
ANALOGUE OUTPUTS (2 CHANNELS)
Pot 20 ÷ 50000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Type Range Calibration Linearity Thermal Drift
Tc J -210 ÷ +1200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
20 mA 4 ÷ +20 mA ±0.05 % f.s. ±0.05 % f.s. 100 ppm/°C
Tc K -210 ÷ +1370 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
DIGITAL OUTPUTS
Tc R -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C
N.2 SPDT Relays
Tc S -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C 2 A @ 250 Vac (per contact)
Switching Power (resistive load)
Tc B +400 ÷ +1825 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C 2 A @ 30 Vdc (per contact)
Tc E -210 ÷ +1000 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Minimum load 5Vdc , 10mA
Tc T -210 ÷ +400 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Max. voltage 250Vac (50 / 60 Hz) ,110Vdc
Tc N -210 ÷ +1300 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Dielectric strength between contacts 1000 Vac, 50 Hz, 1 min.
Tc, mV >= 10 MΩ Dielectric strength between 4000 Vac, 50 Hz, 1 min.
coil and contacts
Input impedance Volt >= 1 MΩ
Serial Ports RS-485 (Master & Slave)
Current ~ 22 Ω
Protocol Modbus RTU
Auxiliary voltage >14 V @ 20 mA
Baud Rate up to 115.2 Kbps
Line resistance influence Max. recommended distance (1) 1.2 Km @ 38.4 Kbps
RTD 3 wires 0.05 %/Ω (50 Ω max) Number of modules in multipoint up to 32
mV, Tc < 0.8 uV/Ohm Internal termination resistance 120 Ohm (optional)
(1) = The maximum distance depends of: number of devices connected, type of cabling, noises, etc...
www.datexel.it
INTELLIGENT UNIT WITH DATA-LOGGER FUNCTION, ETHERNET INTERFACE AND DIGITAL AND ANALOGUE I/O
DAT 9011-DL GENERAL DESCRIPTION
The device DAT9011-DL is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working and managing up to 8 tasks of storage data. The data are saved on microSD card; it is possible to get access to the
saved files by means of the Ethernet connection. The device is equipped with one universal analogue input channel, one channel for
Volt and mA input, two digital inputs and 2 relay outputs. On input an Auxiliary source is available to supply passive sensors on the
field. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to program the
Control Logic,to monitor, to request data and programming in real time the Intelligent Unit,to program directly the Slave devices
connected on the RS-485 Master and to request data from them.

FEATURES - Functional Block programming software


- N°1 serial interface RS-485 Modbus RTU Master - Remotely programmable
- N°1 serial interface RS-485/232 Modbus RTU Slave - Connection by removable screw-terminals
- N°1 Slot for microSD card - LEDst signalling mfor Link/Act eEthernet, serial RX-TX, power
In d
u ri es r d a c hi E n rgy d busine er treat me
- Interface Ethernet 10Base-T, Modbus TCP supply oa oo at

ne

ss

nt
F
B
- N°1 universal analogue input + N°1 current and voltage - LED signalling for digital inputs and digital outputs state
analogue input - Galvanic Isolation on all the ways
- N°2 digital Inputs - EMC compliance – CE mark
- Auxiliary supply to power sensors on field - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- N°2 passive 4-20 mA analogue outputs - Suitable for DIN rail mounting in compliance with EN-50022
- N°2 SPDT Relay Outputs standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas
DAT9000 SERIES

POWER SUPPLY CONNECTIONS TEMPERATURE & HUMIDITY


Power supply Voltage 9 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
Current consumption @ 24 Vdc 60 mA (170 mA max) RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +60°C
Current consumption @ 10 Vdc 147 mA (300 mA max) RS-485
Master / Slave Screw terminals pitch
Reverse polarity protection 60 Vdc max 5.08mm Relative humidity (not cond.) 0 .. 90 %
Outputs Relay
EMC (for industrial environments) Supply/Inputs/ HOUSING
Screw terminals pitch
Analogue Material Self-extinguishing plastic
DIRECTIVE 2004 / 108 / EC 3.81mm
outputs
Mounting DIN rail
Immunity EN 61000-6-2 ISOLATIONS
Dimensions (mm) W x L x H : 120 x 100 x 22.5
Isolations voltage 1500 Vac
70 Emission EN 61000-6-4 (50 Hz, 1 min.) (on all the ways) Weight About 190 g.

ANALOGUE INPUTS DIGITAL INPUTS


Type Range Calibration Linearity Thermal Drift Channels 2
100 mV -100 ÷ +100 mV ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C OFF state : 0÷3 V
Input voltage (bipolar)
10 V -10 ÷ +10 V ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C ON state : 10÷30 V
20 mA -20 ÷ +20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Input impedance 4.7 KOhm
Pt100 -200 ÷ +850 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C N°2 Digital counter 32 bit (up to 300 Hz)
Pt1K -200 ÷ +200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
ANALOGUE OUTPUTS (2 CHANNELS)
Ni100 -60 ÷ +180 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Type Range Calibration Linearity Thermal Drift
Ni1K -60 ÷ +150 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
20 mA 4 ÷ +20 mA ±0.05 % f.s. ±0.05 % f.s. 100 ppm/°C
Res 0 ÷ 2000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Pot 20 ÷ 50000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C DIGITAL OUTPUTS
Tc J -210 ÷ +1200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C N.2 SPDT Relays
Tc K -210 ÷ +1370 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C 2 A @ 250 Vac (per contact)
Switching Power (resistive load)
Tc R -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C 2 A @ 30 Vdc (per contact)
Tc S -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C Minimum load 5Vdc , 10mA
Tc B +400 ÷ +1825 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Max. voltage 250Vac (50 / 60 Hz) ,110Vdc
Tc E -210 ÷ +1000 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Dielectric strength between contacts 1000 Vac, 50 Hz, 1 min.
Tc T -210 ÷ +400 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Dielectric strength between
Tc N -210 ÷ +1300 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C 4000 Vac, 50 Hz, 1 min.
coil and contacts
Tc, mV >= 10 MΩ
Serial Ports RS-485 (Master & Slave)
Input impedance Volt >= 1 MΩ
Current ~ 22 Ω Protocol Modbus RTU

Auxiliary voltage >14 V @ 20 mA Baud Rate up to 115.2 bps

Line resistance influence Max. distance (1) 1.2 Km @ 38.4 Kbps


RTD 3 wires 0.05 %/Ω (50 Ω max) Number of modules in multipoint up to 32
mV, Tc < 0.8 uV/Ohm Internal termination resistance 120 Ohm (optional)

Compatible SD card
Sensor excitation current
Type microSD
RTD, Res, Pot ~ 400 uA
Memory size Up to 8 GB
CJC comp. ± 1 °C
Format FAT16 or FAT32
Sample time 1 sec.
(1) = The maximum distance depends of: number of devices connected, type of
Warm-up time (TC,RTD) 3 min. cabling, noises, etc...

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

DAT9000 SERIES
“DAT9000 SERIES”
www.datexel.it

intelligent units 71

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

“DAT6000 SERIES”: A/D interface modules for PLC

The DAT6000 series devices are an evolution in the connection techni-


ques of the analog signals to the PLC.
Each device amplify, linearise, filter and isolate the analog signal coming
from the sensors on field and convert it in an high resolution 16 bits
length “word” digital signal that is transferred to the PLC by the data line
of the controller.
The data transfer is controlled by the PLC trough a clock signal genera-
ted on its digital port; at each pulse of clock is transferred a bit of the
data.

By few and simple instructions the PLC is able to acquire more analog
signals on a single digital input. Moreover each module has an Enable
signal, that allows the controller to multiplexing more devices to one
data line and one clock signal.

INDEX
74 • DAT 6011
A/D interface for PLC 2 input channels for mV or Tc
DAT 6012
A/D interface for PLC 2 input channels for RTD, Res

75 • DAT 6013
A/D interface for PLC 2 input channels for V, mA
DAT 6021
A/D interface for PLC 4 input channels for mV, Tc

76 • DAT 6023-I
A/D interface for PLC 4 input channels for +/- 20 mA
DAT 6023-V
A/D interface for PLC 4 input channels for +/- 10V
DAT6000 SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
09

DAT6000 A/D interface modules


SERIES for PLC
A/D INTERFACE FOR PLC 2 INPUT CHANNELS FOR mV OR Tc
GENERAL DESCRIPTION
DAT 6011 The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC. The devices of this series
amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analogue signals on PLC’s digital I/O - Configurable by DIP-switch
- Analogue input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for voltage up to ± 1V or Tc type with EN-50022 and EN-50035
J,K, R,S,B,E,T,N
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT Input impedance


Power supply voltage 18 .. 30 Vdc Input type Min Max mV, Tc >= 1 MΩ
Current consumption 30 mA @ 24 Vdc Voltage Thermal drift (1)
Rever. polarity protection 60 Vdc max 50 mV -50 mV +50 mV Full Scale ± 0.005 % / °C
100 mV -100 mV +100 mV Thermal drift CJC
ISOLATION VOLTAGE
500 mV -500 mV +500 mV Full Scale ± 0.02 %/ °C
INPUT – PLC
2000 Vac 1000 mV -1000 mV +1000 mV Line resistance influence
Power supply– INPUT
50 Hz, 1 min. Thermocouple
DAT 6000 SERIES

mV, Tc < 0.8 uV/Ohm


Power supply– PLC
J -210 °C +1200 °C
TEMPERATURE AND HUMIDITY K -210 °C +1372 °C DIGITAL INTERFACE
Operative temperature -10°C .. +60°C R -50 °C +1767 °C Voltage on terminals typical 24 Vdc (30 Vdc max.)
Storage S -50 °C +1767 °C ON state >9 Vdc
-40°C .. +85°C
temperature B +400 °C +1825 °C Input impedance
Humidity (not cond) 0 .. 90 % E -210 °C +1000 °C (ENABLE, CLK) 4.7 KOhm
EMC (for industrial environments) T -210 °C +400 °C Minimum output load
DIRECTIVE 2004/108/EC N -210 °C +1300 °C
(DATA) 560 Ohm (2)
Immunity EN 61000-6-2 INPUT CHANNELS 2
Max. frequency
Emission EN 61000-6-4 Input calibration (1) ±0.05% f.s.
Clock signal 500 Hz
HOUSING Linearity (1)
Rise / Fall time (Tr) < 0.2 ms
Material Self-extinguishing plastic mV ± 0.1 % f.s.
(1) referred to input Span (difference between max. and min. values)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Tc ± 0.2 % f.s.
74 (2) The load on the output DATA is controlled with the current
Weight about 90 g. Cold junction compensation ± 0.5 °C taken from the ENABLE signal.
A/D INTERFACE FOR PLC 2 INPUT CHANNELS FOR RTD, Res
GENERAL DESCRIPTION
DAT 6012

The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC.
The devices of this series amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high reso-
lution. The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance with
- Configurable input for Pt100, Pt1000, Ni100, Ni1000, EN-50022 and EN-50035
Resistance and Potentiometers up to 2 Kohm
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT Thermal drift (1)


Power supply voltage 18 .. 30 Vdc Input type Min Max Full Scale ± 0.005 % / °C
Current consumption 30 mA @ 24 Vdc RTD Line resistance influence
Rever. polarity protection 60 Vdc max Pt100 -200 °C +850 °C RTD, Res < 0.05%/Ohm
ISOLATION VOLTAGE Pt1000 -200 °C +200 °C (50 Ω max , 3 wires connection)
INPUT – PLC Ni100 -80 °C +180 °C
2000 Vac DIGITAL INTERFACE
Power supply– INPUT Ni1000 -60 °C +150 °C
50 Hz, 1 min.
Power supply– PLC Resistance Voltage on terminals typical 24 Vdc (30 Vdc max.)

TEMPERATURE AND HUMIDITY 500 Ω 0Ω 500 Ω ON state >9 Vdc

Operative temperature -10°C .. +60°C 2 KΩ 0Ω 2000 Ω Input impedance


(ENABLE, CLK) 4.7 KOhm
Storage temperature -40°C .. +85°C Potentiometer
< 500 Ω* 0% 100 % Minimum output load
Humidity (not cond) 0 .. 90 % (DATA) 560 Ohm (2)
< 2 KΩ* 0% 100 %
EMC (for industrial environments) Max. frequency
Input channels 2
DIRECTIVE 2004/108/EC Clock signal 500 Hz
Input calibration (1) ±0.1 % f.s.
Immunity EN 61000-6-2 Rise / Fall time (Tr) < 0.2 ms
Linearity (1)
Emission EN 61000-6-4 (1) referred to input Span (difference between max. and min.
Res, Pot. ± 0.1 % f.s.
HOUSING values)
RDT ± 0.2 % f.s. (2) The load on the output DATA is controlled with the cur-
Material Self-extinguishing plastic
RTD / Res. excitation current 0.350 mA typ. rent taken from the ENABLE signal
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g. * nominal value

www.datexel.it
A/D INTERFACE FOR PLC 2 INPUT CHANNELS FOR V, mA
GENERAL DESCRIPTION
DAT 6013 The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC. The devices of this series
amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 10 V and ± 20 mA with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT DIGITAL INTERFACE


Power supply voltage 18 .. 30 Vdc Input type Min Max Voltage on terminals typical 24 Vdc (30 Vdc max.)
Current consumption 30 mA @ 24 Vdc Voltage ON state >9 Vdc
Rever. polarity protection 60 Vdc max
10 V -10 V +10 V Input impedance
ISOLATION VOLTAGE
Current (ENABLE, CLK) 4.7 KOhm
INPUT – PLC
2000 Vac 20 mA -20 mA +20 mA Minimum output load
Power supply– INPUT
50 Hz, 1 min. Input channels 2 (DATA) 560 Ohm (2)
Power supply– PLC

DAT 6000 SERIES


TEMPERATURE AND HUMIDITY Input calibration (1) ±0.1 % f.s. Max. frequency
Operative temperature -10°C .. +60°C Linearity (1) ±0.1 % f.s. Clock signal 500 Hz
Storage Input impedance Rise / Fall time (Tr) < 0.2 ms
-40°C .. +85°C
temperature V >= 100 KΩ (1) referred to input Span (difference between max. and min.
Humidity (not cond) 0 .. 90 % values)
mA <= 50 Ω
EMC (for industrial environments) (2) The load on the output DATA is controlled with the cur-
Thermal drift (1) rent taken from the ENABLE signal
DIRECTIVE 2004/108/EC
Full Scale ± 0.005 % / °C
Immunity EN 61000-6-2
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.
75
A/D INTERFACE FOR PLC 4 INPUT CHANNELS FOR mV, TC
GENERAL DESCRIPTION
DAT 6021

The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC. The devices of this series
amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analogue signals on PLC’s digital I/O - Galvanic isolation at 2000 Vac on three ways
- Analogue input to any PLC or micro PLC - EMC compliant – CE mark
- Up to 16-bit resolution with Full Scale high accuracy - Suitable for DIN rail mounting in compliance with
- 4 input channels EN-50022 and EN-50035
- Configurable input for ± 1 V or Tc type J,K, R,S,B,E,T,N
- Configurable by DIP-switch
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ss

nt
F
ne
B

Application areas

POWER SUPPLY INPUT Input impedance


Power supply voltage 18 .. 30 Vdc Input type Min Max mV, Tc >= 1 MΩ
Current consumption 30 mA @ 24 Vdc Voltage Thermal drift (1)
Rever. polarity protection 60 Vdc max 50 mV -50 mV +50 mV Full Scale ± 0.005 % / °C
100 mV -100 mV +100 mV Thermal drift CJC
ISOLATION VOLTAGE
500 mV -500 mV +500 mV Full Scale ± 0.02 %/ °C
INPUT – PLC
2000 Vac 1000 mV -1000 mV +1000 mV Line resistance influence
Power supply– INPUT
50 Hz, 1 min. Thermocouple mV, Tc < 0.8 uV/Ohm
Power supply– PLC
J -210 °C +1200 °C
TEMPERATURE AND HUMIDITY K -210 °C +1372 °C DIGITAL INTERFACE
Operative temperature -10°C .. +60°C R -50 °C +1767 °C Voltage on terminals typical 24 Vdc (30 Vdc max.)
Storage -40°C .. +85°C S -50 °C +1767 °C ON state >9 Vdc
temperature
B +400 °C +1825 °C Input impedance
Humidity (not cond) 0 .. 90 %
E -210 °C +1000 °C (ENABLE, CLK) 4.7 KOhm
EMC (for industrial environments)
T -210 °C +400 °C Minimum output load
DIRECTIVE 2004/108/EC N -210 °C +1300 °C (DATA) 560 Ohm (2)
Immunity EN 61000-6-2
Input channels 4 Max. frequency
Emission EN 61000-6-4 Input calibration (1) ±0.05 % f.s. Clock signal 500 Hz
HOUSING Linearity (1) Rise / Fall time (Tr) < 0.2 ms
Material Self-extinguishing plastic mV ± 0.1 % f.s.
(1) referred to input Span (difference between max. and min. values)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Tc ± 0.2 % f.s. (2) The load on the output DATA is controlled with the current taken
Weight about 90 g. Cold junction compensation ± 0.5 °C from the ENABLE signal
www.datexel.it
A/D INTERFACE FOR PLC 4 INPUT CHANNELS FOR +/- 20 mA
GENERAL DESCRIPTION
DAT 6023-I The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC.
The devices of this series amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 4 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 20 mA with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY INPUT DIGITAL INTERFACE


Power supply voltage 18 .. 30 Vdc Input type Min Max Voltage on terminals typical 24 Vdc (30 Vdc max.)
Current consumption 30 mA @ 24 Vdc Current ON state >9 Vdc
Rever. polarity protection 60 Vdc max
20 mA -20 mA +20 mA Input impedance
ISOLATION VOLTAGE
Input channels 4 (ENABLE, CLK) 4.7 KOhm
INPUT – PLC
2000 Vac Input calibration (1) ±0.1 % f.s. Minimum output load
Power supply– INPUT
50 Hz, 1 min. Linearity (1)
DAT 6000 SERIES

±0.1 % f.s. (DATA) 560 Ohm (2)


Power supply– PLC
TEMPERATURE AND HUMIDITY Max. frequency
Input impedance
Operative temperature -10°C .. +60°C Clock signal 500 Hz
mA <= 50 Ω
Storage Rise / Fall time (Tr) < 0.2 ms
temperature
-40°C .. +85°C Thermal drift (1)
(1) referred to input Span (difference between max. and min. values)
Humidity (not cond) 0 .. 90 % Full Scale ± 0.005 % / °C
(2) The load on the output DATA is controlled with the current
EMC (for industrial environments) taken from the ENABLE signal
DIRECTIVE 2004/108/EC
Immunity EN 61000-6-2
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
76 Weight about 90 g.
A/D INTERFACE FOR PLC 4 INPUT CHANNELS FOR +/- 10V
GENERAL DESCRIPTION
DAT 6023-V

The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC.
The devices of this series amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.

FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 4 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 10 V with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

POWER SUPPLY INPUT DIGITAL INTERFACE


Power supply voltage 18 .. 30 Vdc Input type Min Max Voltage on terminals typical 24 Vdc (30 Vdc max.)
Current consumption 30 mA @ 24 Vdc Voltage ON state >9 Vdc
Rever. polarity protection 60 Vdc max
10V -10 V +10 V Input impedance
ISOLATION VOLTAGE
Input channels 4 (ENABLE, CLK) 4.7 KOhm
INPUT – PLC
2000 Vac Input calibration (1) ±0.1% f.s. Minimum output load
Power supply– INPUT
50 Hz, 1 min. Linearity (1) ±0.1% f.s. (DATA) 560 Ohm (2)
Power supply– PLC
TEMPERATURE AND HUMIDITY Max. frequency
Input impedance
Operative temperature -10°C .. +60°C Clock signal 500 Hz
Volt >/= 100 KΩ
Storage Rise / Fall time (Tr) < 0.2 ms
temperature
-40°C .. +85°C Thermal drift (1)
(1) referred to input Span (difference between max. and min.
Humidity (not cond) 0 .. 90 % Full Scale ± 0.005 % / °C
values)
EMC (for industrial environments) (2) The load on the output DATA is controlled with the cur-
rent taken from the ENABLE signal
DIRECTIVE 2004/108/EC
Immunity EN 61000-6-2
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 90 g.

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

DAT 6000 SERIES


“DAT6000 SERIES”
www.datexel.it

A/D interface modules for PLC 77

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

“DAT1000 SERIES”: temperature transmitters for


DIN B in-head mounting
The transmitters of the DAT1000 series can accept at their input signals
coming from 2,3 or 4 wires Pt100, thermocouple and potentiometer sen-
sors or voltage signals (mV).The devices provide a 4÷20 mA two wire
current loop output signal.

The series is composed of devices with input configurable by PC with


or without galvanic isolation. Moreover it is available a version of the
transmitters of the DAT1000 series developed for the use in potential-
ly explosive atmospheres certified in according to the DIRECTIVE ATEX
94/9/EC. (see p. 24 to 26).

INDEX
80 • DAT 1010
Two wire transmitter for RTD programmable by PC

81 • DAT 1015
Two wire universal transmitter programmable by PC

82 • DAT 1061
Isolated two wire Transmitter for RTD programmable by PC

83 • DAT 1066
Isolated two wire universal transmitter programmable by PC
DAT1000 SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
10

DAT1000 Temperature transmitters for


SERIES DIN B in-head mounting
TWO WIRE TRANSMITTER FOR RTD PROGRAMMABLE BY PC
DAT 1010 GENERAL DESCRIPTION
The transmitter DAT 1010 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input.
The measured values are converted in a 4÷20 mA current signal .
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD, mV, Resistance and - Programming of the unit measure as °C or °F
Potentiometer - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“KIT DIN RAIL” Option)

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY TEMPERATURE & HUMIDITY


Operative temperature -40°C .. +85°C
Power supply voltage 10 .. 32Vdc
Storage temperature -40°C .. +85°C
DAT1000 SERIES

Reverse polarity protection 60 Vdc max


Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) HOUSING


DIRECTIVE 2004/108/EC Material PC + ABS V0
Mounting DIN B head or bigger
Immunity EN 61000-6-2
Dimensions (mm) Ø= 43 mm ; H = 24 mm
Emission EN 61000-6-4 Weight about 50 g.

INPUT INPUT
Input type Min Max Span min Line resistance influence(1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
80
Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100mV +700mV 2 mV Burn-out values
Potentiometer Max. value output about 21.6 mA
0Ω 200 Ω 10% Min. value output about 3.5 mA
Nominal value 200 Ω 500 Ω 10% Response time (10÷90% of f.s.) about 400 ms

0.5 KΩ 2 KΩ 10% (1) referred to input Span (difference between max. and min. values)

RES. 2,3,4 wires


OUTPUT
Low 0Ω 300 Ω 10 Ω Output type Min Max Span min
High 0Ω 2000 Ω 200 Ω Direct current 4 mA 20 mA 4 mA
Input calibration(1) Reverse current 20 mA 4 mA 4 mA
RTD the higher of ±0.1 % f.s. or ±0.2 °C Output calibration
Res. Low the higher of ±0.1 % f.s. or ±0.15 Ω Current ± 7 uA
Res. High the higher of ±0.2 % f.s. or ±1 Ω
mV the higher of ±0.1 % f.s. or ±18 uV
Input impedance
mV >= 10 MΩ
Linearity (1)
RTD ± 0.1 % f.s

www.datexel.it
TWO WIRE UNIVERSAL TRANSMITTER PROGRAMMABLE BY PC
DAT 1015 GENERAL DESCRIPTION
The transmitter DAT 1015 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input.
Moreover the DAT 1015 is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES - On-field reconfigurable


- Configurable input for RTD, TC, mV, Resistance and - Programming of the unit measure as °C or °F
Potentiometer - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“KITDIN RAIL” Option)

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY TEMPERATURE & HUMIDITY


Operative temperature -40°C .. +85°C
Power supply voltage 10 .. 32Vdc
Storage temperature -40°C .. +85°C

DAT1000 SERIES
Reverse polarity protection 60 Vdc max
Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) HOUSING


DIRECTIVE 2004/108/EC Material PC + ABS V0
Mounting DIN B head or bigger
Immunity EN 61000-6-2
Dimensions (mm) Ø= 43 mm ; H = 24 mm
Emission EN 61000-6-4 Weight about 50 g.

INPUT INPUT
Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ
Linearity (1) 81
J -200°C 1200°C 2 mV
TC ± 0.2 % f.s.
K -200°C 1370°C 2 mV
RTD ± 0.1 % f.s
S -50°C 1760°C 2 mV
Line resistance influence(1)
R -50°C 1760°C 2 mV
TC, mV <=0.8 uV/Ohm
B 400°C 1820°C 2 mV RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
E -200°C 1000°C 2 mV RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
T -200°C 400°C 2 mV RTD excitation current
N -200°C 1300°C 2 mV Typical 0.350 mA
RTD 2,3,4 wires CJC comp. ± 0.5°C

Pt100 -200°C 850°C 50°C Thermal drift (1)


Full scale ± 0.01 % / °C
Pt1000 -200°C 200°C 50°C
CJC ± 0.01 % / °C
Ni100 -60°C 180°C 50°C
Burn-out values
Ni1000 -60°C 150°C 50°C
Max. value output about 21.6 mA
Voltage Min. value output about 3.5 mA
mV -100 mV +700 mV 2 mV Response time (10÷90% of f.s.) about 400 ms
0Ω 200 Ω 10% (1) referred to input Span (difference between max. and min. values)
Potentiometer
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 2 KΩ 10% OUTPUT
Resistance 2,3,4 wires Output type Min Max Span min
Low 0Ω 300 Ω 10 Ω Direct current 4 mA 20 mA 4 mA

High 0Ω 2000 Ω 200 Ω Reverse current 20 mA 4 mA 4 mA

Input calibration(1) Output calibration


Current ± 7 uA
RTD the higher of ±0.1 % f.s. or ±0.2 °C
Res. Low the higher of ±0.1 % f.s. or ±0.15 Ω
Res. High the higher of ±0.2 % f.s. or ±1 Ω
mV, TC the higher of ±0.1 % f.s. or ±18 uV

www.datexel.it
ISOLATED TWO WIRE TRANSMITTER FOR RTD PROGRAMMABLE BY PC
DAT 1061 GENERAL DESCRIPTION
The isolated transmitter DAT 1061 is able to execute many functions such as : measure and linearisation of the temperature characte-
ristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer
connected on its input. The measured values are converted in a 4÷20 mA current signal. The device guarantees high accuracy and
performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, mV, Resistance and - On-field reconfigurable
Potentiometer - Programming of the unit measure as °C or °F
- Galvanic isolation at 1500 Vac - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“DIN RAIL” Option)
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY TEMPERATURE & HUMIDITY


Power supply voltage 07 .. 32Vdc Operative temperature -40°C .. +85°C
Reverse polarity protection 60 Vdc max
Storage temperature -40°C .. +85°C
DAT1000 SERIES

ISOLATION VOLTAGE
Input- output/Power supply 1500 Vac, 50 Hz,1 min. Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) HOUSING


DIRECTIVE 2004/108/EC Material PC + ABS V0
Mounting DIN B head or bigger
Immunity EN 61000-6-2
Dimensions (mm) Ø= 43 mm ; H = 24 mm
Emission EN 61000-6-4 Weight about 50 g.

Input Input
Input type Min Max Span min Line resistance influence(1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
82
Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100mV +700mV 2 mV Burn-out values
Potentiometer Max. value output about 20.5 mA
0Ω 200 Ω 10% Min. value output about 3.8 mA
Nominal value 200 Ω 500 Ω 10% Value max. fault about 21.6 mA

0.5 KΩ 50 KΩ 10% Value min. fault about 3.5 mA


Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires
(1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
OUTPUT
Input calibration(1)
Output type Min Max Span min
RTD the higher of ±0.1 % f.s. or ±0.2 °C
Direct current 4 mA 20 mA 4 mA
Res. Low the higher of ±0.1 % f.s. or ±0.15 Ω
Reverse current 20 mA 4 mA 4 mA
Res. High the higher of ±0.2 % f.s. or ±1 Ω
Output calibration
mV the higher of ±0.1 % f.s. or ±10 uV
Current ± 7 uA
Input impedance
mV >= 10 MΩ
Linearity (1)
RTD ± 0.1 % f.s

www.datexel.it
ISOLATED TWO WIRE UNIVERSAL TRANSMITTER PROGRAMMABLE BY PC
DAT 1066 GENERAL DESCRIPTION
The isolated transmitter DAT 1066 is able to execute many functions such as : measure and linearisation of the temperature characte-
ristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer
connected on its input.
Moreover the DAT 1066 is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.

FEATURES
- Configurable input for RTD, TC, mV, Resistance and - On-field reconfigurable
Potentiometer - Programming of the unit measure as °C or °F
- Galvanic isolation at 1500 Vac - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“KITDIN RAIL” Option)

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY TEMPERATURE & HUMIDITY


Power supply voltage 07 .. 32Vdc Operative temperature -40°C .. +85°C
Reverse polarity protection 60 Vdc max
Storage temperature -40°C .. +85°C
ISOLATION VOLTAGE

DAT1000 SERIES
Input- output/Power supply 1500 Vac, 50 Hz,1 min. Humidity (not condensed) 0 .. 90 %

EMC (for industrial environments) HOUSING


DIRECTIVE 2004/108/EC Material PC + ABS V0
Mounting DIN B head or bigger
Immunity EN 61000-6-2
Dimensions (mm) Ø= 43 mm ; H = 24 mm
Emission EN 61000-6-4 Weight about 50 g.

Input Input
Input type Min Max Span min Input calibration(1)
TC CJC int./ext. RTD the higher of ±0.1 % f.s. or ±0.2 °C
Res. Low the higher of ±0.1 % f.s. or ±0.15 Ω 83
J -200°C 1200°C 2 mV
Res. High the higher of ±0.2 % f.s. or ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. or ±10 uV
S -50°C 1760°C 2 mV
Input impedance Application areas
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence(1)
RTD 2,3,4 wires TC, mV <=0.8 uV/Ohm

Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5°C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 50 KΩ 10% Max. value output about 20.5 mA

Resistance 2,3,4 wires Min. value output about 3.8 mA


Value max. fault about 21.6 mA
Low 0Ω 300 Ω 10 Ω
Value min. fault about 3.5 mA
High 0Ω 2000 Ω 200 Ω
Response time (10÷90% of f.s.) about 400 ms
(1) referred to input Span (difference between max. and min. values)
OUTPUT
Output type Min Max Span min
Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Output calibration
Current ± 7 uA

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

Digital indicators for panel mounting


DAT9550, DAT8050 and “DAT700 SERIES”
The series is composed of devices dedicated to process and
temperature measurement.

The DAT9550 is graphic display size 48 x 96 mm communicating on


RS-485 with MODBUS RTU protocol.

The DAT8050 is a programmable digital indicator for current loop size


48x96 mm with 4 digit LED visualization.

The DAT700 series is composed of devices size 36x72 mm


(DAT701, DAT702, DAT733. DAT734, DAT735).

INDEX
86 • DAT 9550
Remote Graphic Display on RS-485 with Modbus RTU protocol
• DAT 8050
Loop powered 4 digit LED programmable digital indicator

87 • DAT 701
3.5 digit LED digital indicator
• DAT 702
3.5 digit LCD digital indicator
88 • DAT 733
3.5 digit LCD digital indicator
• DAT 734
3.5 digit LCD or LED display digital thermometer for Pt100

89 • DAT 735
3.5 digit LCD or LED display digital thermometer for Thermocouple
DIGITAL INDICATORS
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
11

DAT9550
DAT8050 Digital indicators for
DAT700 SERIES panel mounting
REMOTE GRAPHIC DISPLAY ON RS-485 WITH MODBUS RTU PROTOCOL
GENERAL DESCRIPTION
DAT 9550 The device DAT 9550 is a graphic display designed for panel mounting and communicating with Modbus RTU protocol on RS-485
and RS-232 serial Slave port. Moreover on the device there is a RS-485 Master port by means of which it is possible to communi-
cate with the eventual Modbus Slave devices connected. It can be used as Slave peripheral for the visualization of the data coming
from the Intelligent Units of the DAT9000 series or from a PC, PLC or panel operator.

FEATURES supply & RS-485) and RJ45 (RS-232)


- Graphic display 132x32 pixels - Compact enclosure dimensions (DIN 48 x 96 mm)
- RS-485/RS-232 Modbus-RTU Slave Interface - Galvanic Isolation on all the ways
- RS-485 Modbus-RTU Master Interface - EMC compliance – CE mark
- Remotely programmable - Suitable for panel mounting in compliance with
- Connection by removable screw-terminals (power DIN-43700
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

POWER SUPPLY CONNECTIONS


Power supply voltage 10 ÷ 30 Vdc RS-232D RJ-45

45 mA typ. @ 24Vdc (standby,max. brightness) RS-485/Supply Removable screw terminal blocks


Current consumption
80 mA max HOUSING
Material Noryl self-extinguishing plastic (UL94-V0)
DIGITAL INDICATORS

ISOLATIONS Mounting Panel mounting


Power supply/ RS485 1500 Vac, 50 Hz, 1 min. Dim. (mm) W x L x T : 96 x 48 x 74
Weight about 160 g.
TEMPERATURE & HUMIDITY
Operative temperature -20°C .. +60°C In compliance with IEE 802.3 EIA RS-485 and RS-232
Storage temperature -30°C .. +80°C Baud-rate up to 38.4 Kbps
Max. distance (1) 1.2 Km @ 38.4 Kbps
Humidity (not condensing) 0 .. 90 %
Internal termination resistance 120 Ohm (optional)
EMC (for industrial environments)
Display
DIRECTIVE 2004/108/EC 132x32 pixel
Immunity EN 61000-6-2 Graphic Area
13.2 * 48.1 mm
Emission EN 61000-6-4 (1) = The maximum distance depends of: number of devices connected, type
of cabling, noises, etc...

86
LOOP POWERED 4 DIGIT LED PROGRAMMABLE DIGITAL INDICATOR
GENERAL DESCRIPTION
DAT 8050

The digital panel indicator DAT 8050 accept on the input a 4 - 20 mA current loop signal.
The input current signal is used to supply the device introducing a 5 Vdc voltage drop-out on the current loop, so is not required
any external supply source. The user can program the visualisation of the measure in the range from -1999 up to 9999 points in
order to set the values of the physical or electrical parameter transmitted on the current loop in the desired format.
The programming of the visualization is made by the buttons “SET” and “ENTER” located on the front side of the instrument.

FEATURES
- 4÷20 mA loop powered - Visualization configurable on the front side
- Voltage Drop-out < 5V - Connections on removable screw terminals
- High accuracy and linearity - Compact case size (DIN 48 x 96 mm)
- 0.52” LED display - EMC compliance - CE mark

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

TEMPERATURE & HUMIDITY INPUT


Operative temperature -20°C .. +60°C Input signal 4 ÷ 20 mA
Storage temperature -40°C .. +85°C Voltage drop-out <5V
Humidity (not condensing) 0 .. 90 % Limitation current < 50 mA
EMC (for industrial environments) DISPLAY
DIRECTIVE 2004/108/EC Type of visualization 4 digits LED
Immunity EN 61000-6-2 Digit height 0.52“
Emission EN 61000-6-4 Programmable on the front side, from “-1999” up to
Range of visualization (*)
HOUSING “9999”, with High: 1( on left side). Low: -1( on left side)
Minimum measurable
Material Noryl self-extinguishing plastic (UL94-V0) 3.8 mA (visualization “Lo“ in case of lower measure)
current
Dim. (mm) W x H x T : 48 x 96 x 74 Maximum measurable
20.2 mA (visualization “Hi“ in case of higher measure)
current
Weight about 150 g.
CHARACTERISTICS AND PERFORMANCES
Reading accuracy the better than ± 0.05 % of f.s. or ± 1 digit.
Resolution 4 uA
Response time < 0.5 sec.
Thermal drift ± 0.01 % of f.s. / °C
(*)= default visualization : 4.00 ÷ 20.00

www.datexel.it
3.5 DIGIT LED DIGITAL INDICATOR

DAT 701 GENERAL DESCRIPTION


The DAT 701 is a 3.5 digit LED digital indicator with high accuracy and reliability able to measure the normalised current or voltage
signal applied to its input .
In function of the parameters requested in phase of order, the following versions of the device are available:
- DAT 701 V - A: measure of voltage signal with amplitude from ± 200 mV up to ± 20 V ;
- DAT 701 V - B: measure of voltage signal with amplitude from ± 2 V up to ± 200 V;
- DAT 701 I - A: measure of current signal with amplitude from ± 200 mA up to ± 2 mA;
- DAT 701 I - B: measure of current signal with amplitude from ± 2 mA up to ± 200 mA.

FEATURES - Measuring freeze by command


- Voltage or current inputs - Options for low consumption or high brightness
- Programmable decimal point and Attenuation - EMC compliant – CE mark
ratio - Low profile (15 mm) DIN 36 x 72 mm housing
- High accuracy and linearity - Mounting on panel in according to DIN-43700
- Auto-zero standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

TEMPERATURE & HUMIDITY INPUT VISUALISATION


Operative temperature -10°C .. +60°C Bipolar, true diffe- 2000 points (from 0 up to 1999 or
Configuration Scale of visualisation
rential from -1999 up to 0)
Storage temperature -40°C .. +85°C

DIGITAL INDICATORS
Input impedance Out of range visualisation High = 1; Low = -1
Humidity (not condensing) 0 .. 90 %
basic scale: 10 MΩ Type of visualization 3.5 digit standard LED display (version S)
EMC (for industrial environments) Voltage Display LED 3.5 digit high efficiency LED display (version H)
attenuated scale: 1 MΩ
DIRECTIVE 2004/108/EC Digit height 0.52 ‘‘
Current From 1 Ω up to 1KΩ
Immunity EN 61000-6-2
Maximum input signal 2.5 full scale
Emission EN 61000-6-4 CHARACTERISTICS AND PERFORMANCES
± 2 V referred to the
Common mode voltage Reading accuracy ± 0.1 % of f.s.
HOUSING power supply ground
Common mode Thermal drift 0.005 % of f.s./°C
Material Self-extinguishing plastic rejection ratio 86 dB
Reading rate 3 read/second
Mounting Panel mounting Normal mode
rejection ratio 50 dB @ 50 Hz Power supply voltage 5 Vdc ± 5 %
Dim. (mm) W x H x T : 72 x 36 x 15
Decimal point From front side, on Version S: 90 mA
Weight about 50 g. programming Current consumption
three decades Version H: 180 mA

3.5 DIGIT LCD DIGITAL INDICATOR 87


GENERAL DESCRIPTION
DAT 702

The DAT 702 is a 3.5 digit LCD digital indicator with high accuracy and reliability able to measure the normalised current or voltage
signal applied to its input .
In function of the parameters requested in phase of order, the following versions of the device are available:
- DAT 702 V - A: measure of voltage signal with amplitude from ± 200 mV up to ± 20 V ;
- DAT 702 V - B: measure of voltage signal with amplitude from ± 2 V up to ± 200 V;
- DAT 702 I - A: measure of current signal with amplitude from ± 200 µA up to ± 2 mA;
- DAT 702 I - B: measure of current signal with amplitude from ± 2 mA up to ± 200 mA.

FEATURES - Measuring freeze by command


- Voltage or current inputs - Single power supply voltage (5 Vdc or 9 Vdc)
- Programmable decimal point and Attenuation - EMC compliant – CE mark
ratio - Low profile (15 mm) DIN 36 x 72 mm housing
- High accuracy and linearity - Mounting on panel in according to DIN-43700
- Auto-zero standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne

ss

nt
F
B

Application areas

TEMPERATURE & HUMIDITY INPUT VISUALISATION


Operative temperature -10°C .. +60°C Bipolar, true Static polarised Liquid Cristal Display for
Configuration Type of visualization
differential wide angle of visualization
Storage temperature -40°C .. +85°C
Input impedance Digit height 0.35‘‘
Humidity (not condensing) 0 .. 90 %
basic scale: 10 MΩ
EMC (for industrial environments) Voltage CHARACTERISTICS AND PERFORMANCES
attenuated scale: 1 MΩ
DIRECTIVE 2004/108/EC Reading accuracy ± 0.1 % of f.s.
Current From 1 Ω up to 1KΩ
Immunity EN 61000-6-2 Thermal drift 0.005 % of f.s./°C
Maximum input signal 2.5 full scale
Emission EN 61000-6-4 Reading rate 3 read/second
± 2 V referred to the
Common mode voltage Version 5 : 5 Vdc ± 5 %
power supply ground
HOUSING Power supply voltage
Common mode 86 dB Version 9 : 9 Vdc ± 10 %
Material Self-extinguishing plastic rejection ratio
Version 5 : 3 mA
Mounting Panel mounting Normal mode 50 dB @ 50 Hz Current consumption
rejection ratio Version 9 : 0.5 mA
Dim. (mm) W x H x T : 72 x 36 x 15
Decimal point From rear side, on three
Weight about 50 g. programming decades

www.datexel.it
3.5 DIGIT LCD DIGITAL INDICATOR
GENERAL DESCRIPTION
DAT 733 The DAT 733 is a current loop, 3.5 digit LCD digital indicator with high accuracy and reliability.
By dip-switches and potentiometers, it is possible to set the visualisation of the input measure in engineering units in a range
included between 100 and 2000 points, to set the zero point between -1999 and 1999 and the position of the decimal point.

FEATURES
- 4 ÷ 20 mA current loop self-powered - EMC compliant – CE mark
- Visualisation configurable in engineering units - DIN 36 x 72 mm housing
- High accuracy and linearity - Mounting on panel in according to DIN 43700
- Measure freezing by command standard

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at

ne

ss

nt
F
B
Application areas

TEMPERATURE & HUMIDITY INPUT VISUALISATION


Operative temperature -10°C .. +60°C 4÷20 mA from current Static polarised Liquid Crystal Display
Signal type Type of visualization
loop for wide angle of visualisation
Storage temperature -40°C .. +80°C
Voltage drop 2.5 V Digit height 0.35‘‘
Humidity (not condensing) 0 .. 90 %
Maximum input signal 50 mA
DIGITAL INDICATORS

By dip switch and CHARACTERISTICS AND PERFORMANCES


EMC (for industrial environments)
Visualisation settings regulation by Reading accuracy ±0.1 % del f.s.
DIRECTIVE 2004/108/EC potentiometers
Thermal drift 0.005 % of f.s./°C
Immunity EN 61000-6-2 Zero value visualisation
From -1999 up to 1999 Reading rate 3 read/second
range
Emission EN 61000-6-4
Scale 1 from 100 up to 700 points Self-powered from the input
Power supply
Scales of visualisation Scale 2 from 700 up to 1400 points signal
HOUSING
Scale 3 from 1400 up to 2000 points
Material Self-extinguishing plastic
Decimal point setting
Mounting Panel mounting From rear side, on three decades by dip-switch
Dim. (mm) W x H x T : 72 x 36 x 39 Out of scale visualisation
Weight About 100 g. High: 1( on left side). Low: -1( on left side)

88
3.5 DIGIT LCD OR LED DISPLAY DIGITAL THERMOMETER FOR PT100
GENERAL DESCRIPTION
DAT 734

The DAT 734 is a 3.5 digit LCD or LED display, digital thermometer for Pt100 2 or 3 wires sensor with high accuracy and reliability.
The range of measure must be chosen in phase of order between the two options : -50 ÷ 200 °C or 0 ÷ 600 °C.

FEATURES - Low current consumption


- Input for Pt100 2 or 3 wires sensors - EMC compliant – CE mark
- Visualisation on LCD or LED display - DIN 36 x 72 mm housing
- High accuracy - Mounting on panel in according to DIN 43700
- Measure freezing by command standard

u s tri es r d m a c hi E n er g y d busine er treat me


In d oa oo at
ne

ss

nt
F
B

Application areas

TEMPERATURE & HUMIDITY INPUT


Operative temperature -10°C .. +60°C Signal type 2 or 3 wires Pt100 sensor
Storage temperature -40°C .. +80°C Input range -50 ÷ 200 °C / 0 ÷ 600 °C
Relative Humidity (not condensing) 0 .. 90 % Out of scale visualisation High: 1 (on left side). Low: -1 (on left side)
EMC (for industrial environments) VISUALISATION
DIRECTIVE 2004/108/EC Type of visualization (LCD Static polarised Liquid Cristal Display for wide angle
Immunity EN 61000-6-2 - Version C) of visualization
Emission EN 61000-6-4 Digit height 0.35“
Type of visualization (LED
HOUSING - Version D)
High efficiency LED display or standard LED display
Material Self-extinguishing plastic Digit height 0.52‘’
Mounting Panel mounting
Dim. (mm) W x H x T : 72 x 36 x 39 CHARACTERISTICS AND PERFORMANCES
Weight About 100 g. Reading accuracy ± 0.25 % of f.s.
Response time 800 ms
Power supply voltage 5 Vdc ± 5 %
Thermal drift 0.02 % of f.s./°C
Current consumption
Version D 180 mA (high efficiency), 90 mA (standard)
Version C 10 mA

www.datexel.it
3.5 DIGIT LCD OR LED DISPLAY DIGITAL THERMOMETER FOR THERMOCOUPLE

DAT 735 GENERAL DESCRIPTION


The DAT 735 is a 3.5 digit LCD or LED display, digital thermometer for Thermocouple sensor type E, K, J, N, S and T with high
accuracy and reliability.

FEATURES
- Input for Thermocouple sensors type E, K, J, N, S and T - Low current consumption
- Visualisation on LCD or LED display - EMC compliant – CE mark
- High accuracy - DIN 36 x 72 mm housing
- Measure freezing by command - Mounting on panel in according to DIN-43700
standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at

ne

ss

nt
F
B
Application areas

TEMPERATURE & HUMIDITY INPUT VISUALISATION


Operative temperature -10°C .. +60°C Thermocouple type Type of visualization Static polarised Liquid Cristal Display
Signal type (LCD - Version C ) for wide angle of visualization
Storage temperature -40°C .. +80°C E, K, J, N, S and T
Humidity (not condensing) 0 .. 90 % Ranges of measure Digit height 0.35‘’
Type of visualization High efficiency LED display or stan-
EMC (for industrial environments) Thermocouple type E 0 ÷ 900 °C (LED - Version D) dard LED display

DIGITAL INDICATORS
DIRECTIVE 2004/108/EC Thermocouple type K 0 ÷ 1200 °C Digit height 0.52‘‘
Immunity EN 61000-6-2
Thermocouple type J 0 ÷ 600 °C
Emission EN 61000-6-4 CHARACTERISTICS AND PERFORMANCES
Thermocouple type N 0 ÷ 1200 °C Reading accuracy ±0.25 % of f.s.
HOUSING
Thermocouple type S 0 ÷ 1600 °C Cold Junction Compensation ±0.5 °C
Material Self-extinguishing plastic
Thermocouple type T 0 ÷ 300 °C Thermal drift 0.02 % of f.s./°C
Mounting Panel mounting
Response time 800 ms
Dim. (mm) W x H x T : 72 x 36 x 39 High: 1 (On the left side);
Out of scale visualisation Power supply voltage 5 Vdc ± 5 %
Weight About 100 g. Low -1 (On the left side)
Version D: 180 mA (high efficiency),
Current consumption
90 mA (standard)

89

ELECTRONIC AND CONTROL PROCESS DEVICES

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

ACCESSORIES AND SOFTWARE


Power Supply:
• Power Supply MEANWELL MDR-series

Accessories / Software:
All of the DATEXEL devices configurable by PC need,
for their configuraton, special software combined with communication
interface between device and PC.

Configuration interface with USB INPUT (PRODAT USB)

The software available to configure the DATEXEL devices are the following:

• PROSOFT: configuration software for SMART + SMART IS series devices

• DATESOFT: configuration software for SLIM series devices

• DEV 9K: configuration software for intelligent unit DAT9000 series

INDEX
92 • MDR 20-12 / MDR 40-12 / MDR 60-12 / MDR 100-12
Power Supply DIN rail

93 • MDR 20-24 / MDR 40-24 / MDR 60-24 / MDR 100-24


Power Supply DIN rail

94 • SOFTWARE
PRODAT USB
Configuration interface for USB port
PROSOFT
Configuration software for SMART series devices

DATESOFT
Configuration software for SLIM series devices

Dev 9K
Configuration software for intelligent units DAT9000 series
ACCESSORIES AND SOFTWARE
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c

qu
bo

na

t
tr a

e
12

Power Supply MEANWELL.


Devices and software with
ACCESSORIES interface between devices
AND SOFTWARE and PC.
DIN RAIL POWER SUPPLY

MDR-60-12

MDR-20-12
POWER SUPPLY

85....264 VAC 85....264 VAC


INPUT INPUT
120....370 VDC 120....370 VDC
OUTPUT 12 VDC @ 5 A OUTPUT 12 VDC @ 1.67 A
MDR-100-12

MDR-40-12

92

85....264 VAC 85....264 VAC


INPUT INPUT
120....370 VDC 120....370 VDC
OUTPUT 12 VDC @ 7.5 A OUTPUT 12 VDC @ 3.33 A

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

Other devices are available on request. For more technical information log on to the website: www.meanwell.com

www.datexel.it
DIN RAIL POWER SUPPLY
MDR-60-24

MDR-20-24
85....264 VAC 85....264 VAC

POWER SUPPLY
INPUT INPUT
120....370 VDC 120....370 VDC
OUTPUT 24 VDC @ 2.5 A OUTPUT 24 VDC @ 1 A
MDR-100-24

MDR-40-24

93

85....264 VAC 85....264 VAC


INPUT INPUT
120....370 VDC 120....370 VDC
OUTPUT 24 VDC @ 4 A OUTPUT 24 VDC @ 1.7 A

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

Other devices are available on request. For more technical information log on to the website: www.meanwell.com

www.datexel.it
CONFIGURATION INTERFACE FOR USB PORT

PRODAT-USB GENERAL DESCRIPTION


The program interface PRODAT USB is suitable to program, by proper software, all the
DATEXEL devices of SMART and SLIM series using any Personal Computer, both desktop
and laptop type with USB serial port.

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at

ne

ss

nt
F
B
Application areas
ACCESSORIES / SOFTWARE

CONFIGURATION SOFTWARE FOR SMART SERIES DEVICES

GENERAL DESCRIPTION
PROSOFT

PROSOFT is a software developed by Datexel srl, running under the operative system
Windows® and designed to program and visualize the measure of the converters and
transmitters programmable by PC.

To operate with PROSOFT it is necessary to use the programming interface (PRODAT)


between the P.C. and the device; refer to prosoft user guide to use the right interface
and device.
SYSTEM REQUIREMENTS
Operative System........................Windows® 98 / 2000 / NT / ME / XP / Vista / Win 7
Available Hard Disk space......................2 MB

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at

ne

ss

nt
F
B
Application areas
94

CONFIGURATION SOFTWARE FOR SLIM SERIES DEVICES

GENERAL DESCRIPTION
DATESOFT

DATESOFT is a software developed by Datexel srl, running under the operative system
Windows® designed to program and visualize the measure of the converters program-
mable by PC.

To operate with DATESOFT it is necessary to use the programming interface (PRODAT)


between the P.C. and the device on programming.

SYSTEM REQUIREMENTS
Operative System........................Windows® 98 / 2000 / NT / ME / XP / Vista / Win 7
Available Hard Disk space......................2 MB

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

CONFIGURATION SOFTWARE FOR INTELLIGENT UNITS DAT9000 SERIES

GENERAL DESCRIPTION
Dev 9K

Dev9K is an Integrated Development Environment running under the Windows® Ope-


rative System that allows to design and debug the applications based on the DAT9000
series intelligent units.

With Dev9K it is possible to set the DAT9000 series devices to execute I/O read and write
operations (DAT3000 series), mathematical and logic operations and timers.
Moreover it is possible to read and write in real time the Internal Registers of the Con-
troller or connect it directly to the slave devices connected to its Modbus Master Port.

SYSTEM REQUIREMENTS
Operative System........................Windows 2000 / NT / ME / XP / Vista / Win 7
Available Hard Disk space......................2 MB

In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne

ss

nt
F
B

Application areas

www.datexel.it
DATEXEL: CONFIGURATION SOFTWARE

ACCESSORIES / SOFTWARE
95

www.datexel.it
GENERAL CONDITIONS OF SALE

General conditions
The sale of the products described, in this catalog, is in compliance with the requirements listed below that are considered
in force after formal order will be accepted only if received by us in writing. These terms and conditions of sale (including
any type of written specification, quotation and / or additional terms and conditions) will determine only the sale of all
goods and services (including, without limitation, hardware, software and accessories in the Catalog and described in the
proper price list). The receipt or acceptance of delivery by the buyer of any product ordered or purchased will constitute
your acceptance of these terms and conditions.

Minimum billable amount


The minimum billable amount for each order is € 150.00. For orders less than this amount, for orders more than one device
GENERAL CONDITIONS OF SALE

for which the total amount does not exceed the minimum billable (€ 150.00) will be required to pay on delivery or bank
transfer at ready goods.

Payment terms
All payments must be made with a bank document. At the first delivery cash payment or bank transfer is required. Unless
otherwise agreed, payment standards are provided within 30 calendar days from date of invoice. In case of late or missed
payment, the company DATEXEL act in accordance with the provisions of Legislative Decree n. 231 October 9, 2002 as
required by Directive 2000/35/EC.

Prices
All prices quoted in the catalog list are exclusive of VAT Ex-works our factory Work Tradate (VA).

Guarantee
All products are guaranteed against defects and manufacturing faults under current law. We don’t accept returns for re-
pair or replacement under warranty even if not previously authorized. The transportation costs of any product returned for
repair or replacement even if under warranty are responsibility of the buyer. Will not be accepted unless agreed in advan-
ce, collect shipments (if received materials c / repair or replace, under warranty, shipped freight collect, the same will be
rejected). The guarantee of all material we produce is valid for a period of 24 months from date of shipment. All work done
under warranty will be ex works DATEXEL (VA). All repaired or replaced products are covered for the remaining period
by the remaining term of the original warranty. Are not covered, by warranty products or components subject to wear.

Repairs
Unless otherwise specified, the return devices shall be subject to repair. In advance DATEXEL will provide, to the customer,
by fax or e-mail, a document that will be described the type of fault / anomaly. This document, once completed, will be
returned to DATEXEL that examined the content, will grant the authorization to return by providing all necessary informa-
tion regarding the individual appearing on the shipping document and the method of delivery. It will care by DATEXEL,
than, to inform the internal staff responsible for return acceptance. Upon receipt of the goods, authorized personnel will
verify that the same is accompanied by the documents agreed during a return authorization and will repair or replace the
defective product. If the goods were not accompanied by the documents mentioned above can be made to the sender
rejected. Will not be repaired under warranty all products received outside the period of 24 months from the delivery date
and all products that are damaged due to misuse or failure to comply with the conditions of use indicated on identification
labels and related technical data sheets.

Order cancellation
Any cancellation of an order, by the customer, before the shipment must be notified in writing, by fax or e-mail. It will be
discretion of the DATEXEL staff whether to accept or reject such request. DATEXEL also has the right to cancel an order for
right cause at any time upon written notice.

www.datexel.it
GENERAL CONDITIONS OF SALE

Claims and liability limitation


Any complaints must be received from DATEXEL within 8 days of receipt of goods. To the fullest extent permitted by ap-
plicable law, DATEXEL will not be responsible for disruption or loss of profits, revenues, materials or any form of liability for
incidental, indirect or consequential damages of any kind arising from the misuse of its products.

Force majeure
DATEXEL will not be responsible for any loss, damage or delays due to causes beyond its reasonable control, including,
without limitation, acts of God, causes or omissions attributable to the buyer, causes of civil or military authority, fires,
strikes, floods, epidemics, quarantine restrictions, wars, riots, acts of terrorism, delays in transportation or transportation
embargoes.

GENERAL CONDITIONS OF SALE


Changes or order replacement
All requested changes of order, including those relating to the type, scope and delivery of products, must be documented
in writing and are subject to prior approval and price adjustment, programming and other relevant terms and conditions
by DATEXEL, which, however reserves the right to reject any change that is deemed unsafe, technically inadvisable or
inconsistent with the established technical, or quality, standard criteria, or is not compatible with their ability to design
or production. DATEXEL also reserves the right to make substitutions using the latest version or set of replacement or an
equivalent product that has the comparable shape, size and functions.

Responsibility
DATEXEL will not be responsible for problems, breakages, accidents due to lack of knowledge or lack of compliance with
the requirements indicated on products for its use or on technical Data Sheets.
DATEXEL is also not responsible for problems caused by not authorized changes made on their products.
DATEXEL reserves the right to make changes to its products without obligation to promptly update their technical docu-
mentation.

Technical data
The technical data in this catalog are provided only as a guideline for compatibility verification with the application of the
product’s user and does not constitute a functional guarantee or performance of any kind.

DATEXEL
Reserves the right to modify or change the content of this publication without notice at any time.

www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES

Powered by:
www.datexel.it

Comunicazione& Immagine Srl


www.comimm.it
Art Director: Alessandro Casazza
Coordinator: Lorenzo Stella - Managing Director
DATEXEL srl
Via Monte Nero, 40/B - 21049 Tradate (VA) Italy
Tel. +39 0331 841070 - Fax +39 0331 841950
[email protected] - www.datexel.it

You might also like