Datexel Catalog
Datexel Catalog
WWW.DATEXEL.IT CATALOGU E
WWW.DATEXEL.IT ELECTRONIC AND CONTROL PROCESS DEVICES
Summary Series
01
Temperature and signal SLIM
converters (from PAG.1) series
02
Temperature and signal transmitters SMART
and converters for DIN rail mounting (from PAG.10) series
03
Temperature and signal transmitters and converters for use SMART ATEX
in potentially explosive atmospheres in according to the series
ATEX 94/9/EC directive . (from PAG.18)
04
Temperature and signal transmitters P.D.S.
and converters, isolators signal splitters (from PAG.28) series
05
Trip amplifiers for din DAT5028 / DAT5024
rail mounting (from PAG.38) Trip amplifiers
06
Signal transmitters and converters, DAT200 / DAT500
galvanic isolators (from PAG.44) series
07
Data acquisition and control modules DAT3000
(from PAG.50) series
08
Intelligent modules DAT9000
(from PAG.64) series
09
A/d interface Modules for plc DAT6000
“DAT6000 SERIES” (from PAG.73) series
10
Temperature transmitters for DIN B DAT1000
In-head mounting (from PAG.78) series
11
Digital meters and DAT 9550 / DAT8050
Indicators for panel mounting (from PAG.84) DAT700 series
12
MEANWELL DIN rail power supply. Accessories
Software and interfaces between device and PC (from PAG.90) and software
www.datexel.it
Product Index
Intelligent units
DAT9000 series
(PAG.64 / PAG.71)
II
III
www.datexel.it
a wide range
of products
The DATEXEL range is vast and complete :
Transmitters, Temperature converters (both analogue and
digital), Galvanic isolators, Signal splitters, Distributed I/O
modules, A/D interface modules for PLC, Trip amplifiers,
Power suppliers, Current loop isolators, Digital meters and
Indicators.
IV
DATEXEL is organized:
• DESIGN/ RESEARCH & DEVELOPMENT
• PRODUCTION
• SALES ITALY / ABROAD
• ADMINISTRATION and PURCHASING
• QUALITY
Constant
and place for assembly), and the products are 100% tested,
VI
the ambitions
The company’s growth and expansion philosophy tran-
slates into a wider and wider product offer.
www.datexel.it
Quality
control
DATEXEL invests significantly in RESEARCH & DEVELOPMENT,
obtaining first-class results thanks to the contribution of highly specia-
lized researchers and technicians.
And let’s not forget the QUALITY factor: DATEXEL has taken on the
quality challenge, developing a careful study of production processes
and paying great attention to materials and innovative systems.
VII
VIII
www.datexel.it
application
areas
The products of Datexel cover several type of applications due to a wide variety of conditions of use and
ambient factors:
Industries:
Food business:
Food production, Cellars, dairies, pasta production, packaging and bottling lines.
IX
Energy:
Process control in steel plants, steel works, cement works, pharmaceutical, food and paper
industry, etc.
Water treatment:
Petrochemical offshore:
SMART
02
Series
SMART ATEX
03
Series
P.D.S.
04
Series
ELECTRONIC AND CONTROL PROCESS DEVICES
Trip amplifiers
05
DAT5028 / DAT5024
DAT200 / DAT500
06
Series
DAT3000
07
Series
DAT9000
08
Series
PRODUCT CATALOGUE
www.datexel.it
DAT6000
09
Series
DAT1000
10
Series
Accessories
12
and software
01 SLIM SERIES
INDEX
02 • DAT 4530
Universal isolated converter configurable by Dip-Switch or PC
double output & trip amplifier
03 • DAT 4531 A
Isolated converter for TC and mV configurable by Dip-Switch or PC
DAT 4531 B
Isolated converter for RTD and resistance configurable by Dip-Switch or PC
04 • DAT 4531 C
Isolated converter for PTC/NTC/Pot configurable by Dip-Switch or PC
DAT 4531 D
Isolated converter for voltage and current configurable by Dip-Switch or PC
05 • DAT 4532 A
Double channel, isolated converter for TC and mV configurable by Dip-Switch or PC
DAT 4532 B
Double channel, isolated converter for RTD and resistance configurable by Dip-Switch or PC
06 • DAT 4532 C
Isolated, double channel converter for PTC/NTC/Pot configurable by Dip-Switch or PC
DAT 4532 D
Double channel, isolated converter for voltage and current configurable by Dip-Switch or PC
07 • DAT 4540
Isolated F/V, F/I Converter Configurable by Dip-Switch or PC, Transistor or Relay Outputs
DAT 4631 A
Isolated Splitter / Converter for TC and mV configurable by Dip-Switch or PC
08 • DAT 4631 B
Isolated Splitter / Converter for RTD and resistance configurable by Dip-Switch or PC
DAT 4631 C
Isolated, Splitter / Converter for PTC/NTC/Pot configurable by Dip-Switch or PC
09 • DAT 4631 D
Isolated Splitter / Converter for voltage and current configurable by Dip-Switch or PC
DAT 4632 D
Isolated mathematical module for voltage and current input configurable by Dip-Switch or PC
SLIM SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
01
ne
ss
nt
F
B
Application areas
www.datexel.it
ISOLATED CONVERTER FOR TC AND mV CONFIGURABLE BY DIP-SWITCH OR PC
ne
ss
nt
F
B
Application areas
SLIM SERIES
Operative temperature -20°C .. +60°C Output calibration
Voltage
Storage temperature -40°C .. +85°C mV -100 mV +90 mV 5 mV Current ± 7 uA
mV -100 mV +200 mV 10 mV Voltage ± 5 mV
Humidity (not condensed) 0 .. 90 %
mV -100 mV +800 mV 20 mV Burn-out values
EMC (for industrial environments) Input calibration (1) Max. output value 22 mA or 11 V
DIRECTIVE : 2004 / 108 / EC mV, TC > ± 0.1 % f.s. and ± 12 uV Min. output value 0 mA or -0.6 V
Immunity EN 61000-6-2 Output load Resistance - Rload
Linearity (1)
Emission EN 61000-6-4 TC ± 0.2 % f.s. Current output < 500 Ω
HOUSING mV ± 0.1 % f.s. Voltage output > 10 KΩ
Material Self-extinguishing plastic Input impedance (1) Short circuit current 26 mA max
Dim. (mm) W x L x H : 90 x 112 x 12.5 TC, mV >= 10 MΩ Response time (10÷90% of f.s.) about 500 ms
Weight about 90 g. (1) referred to the input Span (difference between max. and min.) 3
ISOLATED CONVERTER FOR RTD AND RESISTANCE CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4531 B
The isolated converter DAT 4531 B is able to measure and linearise the standard RTD and resistances with 2 or 3 wires cable
compensation.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.
ss
nt
F
B
Application areas
www.datexel.it
ISOLATED CONVERTER FOR PTC/NTC/POT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4531 C The isolated converter DAT 4531 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.
ne
ss
nt
F
B
Application areas
TEMPERATURE AND HUMIDITY Coster 1K -30°C 40°C 25°C Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Pot. Output load Resistance - Rload
0% 100 % 10 %
(Rnom.< 50KΩ) Current output < 500 Ω
Storage temperature -40°C .. +85°C
Calibration (1) Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 % PTC, NTC the higher of ±0.1 % f.s. and ±0.2°C Short circuit current 26 mA max
EMC (for industrial environments) Potentiometer ± 0.05 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC Linearity (1)
Immunity EN 61000-6-2 PTC, NTC ± 0.1 % f.s.
Emission EN 61000-6-4 Sensor excitation current
HOUSING PTC,NTC 500 uA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full scale ± 0.01% / °C
4 Weight about 90 g. (1) referred to the input Span (difference between max. and min.)
The isolated converter DAT 4531 D is able to measure voltage and current signals. In function of programming, the measured values
are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.
ss
nt
F
B
Application areas
www.datexel.it
DOUBLE CHANNEL, ISOLATED CONVERTER FOR TC AND mV CONFIGURABLE BY DIP-SWITCH OR PC
ne
ss
nt
F
B
Application areas
SLIM SERIES
Operative temperature -20°C .. +60°C Output calibration
Voltage
Storage temperature -40°C .. +85°C mV -100 mV +90 mV 5 mV Current ± 7 uA
mV -100 mV +200 mV 10 mV Voltage ± 5 mV
Humidity (not condensed) 0 .. 90 %
mV -100 mV +800 mV 20 mV Burn-out values
EMC (for industrial environments) Input calibration (1) Max. output value 22 mA or 10.6 V
DIRECTIVE : 2004 / 108 / EC mV, TC the higher of ±0.1 % f.s. and ±12 uV Min. output value 0 mA or -0.6 V
Immunity EN 61000-6-2 Output load Resistance - Rload
Linearity (1)
Emission EN 61000-6-4 TC ± 0.2 % f.s. Current output < 500 Ω
HOUSING mV ± 0.1 % f.s. Voltage output > 10 KΩ
Material Self-extinguishing plastic Input impedance Short circuit current 26 mA max
Dim. (mm) W x L x H : 90 x 112 x 12.5 TC, mV >= 10 MΩ Response time (10÷90% of f.s.) about 500 ms
Weight about 90 g. (1) referred to the input Span (difference between max. and min.) 5
DOUBLE CHANNEL, ISOLATED CONVERTER FOR RTD AND RESISTANCE CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 B
The isolated double channel converter DAT 4532 B is able to measure and linearise the standard RTD and resistances with 2 or 3 wires
cable compensation. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.
nt
F
ne
B
Application areas
ALIMENTAZIONE
POWER SUPPLY INPUT (2 CHANNELS) OUTPUT
USCITA (2(2canali)
CHANNELS)
Tensione
Power supply
di alimentazione
voltage 18 .. 30 Vdc Input type Min Max Span min Output type
Tipo uscita Min Max Span min
Protezione
Rever. polarity
invers.
protection
polarità 60 Vdc max RTD (2, 3 wires) Current
Corrente 0 mA 20 mA 4 mA
CONSUMO
CURRENT CONSUMPTION
DI CORRENTE Pt100 -200°C 850°C 50°C Voltage
Tensione 0 V 10 V 1 V
Uscita
Currentinoutput
corrente 35
55 mA max. Pt1000 -85°C 185°C 30°C Output calibration
Calibrazione uscita
Uscita
Voltageinoutput
tensione 20
25 mA max. Ni100 -60°C 180°C 50°C Current
Corrente ± 7 uA
ISOLATION
ISOLAMENTO Ni1000 -60°C 150°C 30°C Voltage
Tensione ± 5 mV
Among all the 1500 Vac, RES. (2, 3 0Ω 500 Ω 50 Ω Burn-out values
Valori di fuori scala
Su tutte le vie
ways 50 Hz, 1 min wires) 0Ω 2000 Ω 50 Ω Max. output
Valore value
max. uscita 22 mA or 10.6VV
o 10.6
TEMPERATURE AND HUMIDITY Calibration (1) Min. output
Valore value
min. uscita 0 mA or -0.6VV
o -0.6
Operative temperature -20°C .. +60°C RTD the higher of ±0.1 % f.s. and ±0.2°C Output loaddiResistance
Resistenza - Rload
carico su uscita - Rload
Storage temperature -40°C .. +85°C Low Res. the higher of ±0.1 % f.s. and ±0.15 Ω Current
Uscita inoutput
corrente < 500 Ω
W
High Res. the higher of ±0.2 % f.s. and ± 1 Ω Voltage
Uscita inoutput
tensione > 10 KΩ
KW
Humidity (not condensed) 0 .. 90 %
Linearity (1) Short circuit
Corrente current
di corto-circuito 26 mA max
EMC (per
(for industrial
gli ambienti
environments)
industriali)
RTD ± 0.1 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRETTIVA
DIRECTIVE :: 2004
2004 // 108
108 // EC
EC
Immunità
Immunity EN 61000-6-2 Sensor excitation current (1) referred to the input Span (difference between max. and min.)
Emissione
Emission EN 61000-6-4 RTD, Res 500 uA
Line resistance influence (1)
CONTENITORE
HOUSING
RTD 3 wires 0.05 %/Ω (50 Ω max balanced)
Materiale
Material Plastica
Self-extinguishing
auto-estinguente
plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5 Thermal drift (1)
Peso
Weight 90
about
g. circa
90 g. Full scale ± 0.01 % / °C
www.datexel.it
DOUBLE CHANNEL, ISOLATED CONVERTER FOR PTC/NTC/POT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 C The isolated double channel converter DAT 4532 C is able to measure and linearise the standard PTC and NTC sensors and poten-
tiometers. In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.
ne
ss
nt
F
B
Application areas
TEMPERATURE AND HUMIDITY Coster 1K -30°C 40°C 25°C Min. output value 0 mA or -0.6 V
Operative temperature -20°C .. +60°C Pot. Output load Resistance - Rload
0% 100 % 10 %
(Rnom.< 50KΩ) Current output < 500 Ω
Storage temperature -40°C .. +85°C
Calibration (1) Voltage output > 10 KΩ
Humidity (not condensed) 0 .. 90 % PTC, NTC the higher of ±0.1 % f.s. and ±0.2 °C Short circuit current 26 mA max
EMC (for industrial environments) Potentiometer ± 0.05 % f.s. Response time (10÷90% of f.s.) about 500 ms
DIRECTIVE : 2004 / 108 / EC Linearity (1)
Immunity EN 61000-6-2 PTC, NTC ± 0.1 % f.s.
Emission EN 61000-6-4 Sensor excitation current
HOUSING PTC,NTC 500 uA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full scale ± 0.01 % / °C
6 Weight about 90 g. (1) referred to the input Span (difference between max. and min.)
DOUBLE CHANNEL, ISOLATED CONVERTER FOR VOLTAGE AND CURRENT CONFIGURABLE BY DIP-SWITCH OR PC
GENERAL DESCRIPTION
DAT 4532 D
The isolated converter DAT 4532 D is able to measure voltage and current signals. In function of programming, the measured values
are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature. The double channel allows the
high density mounting where is necessary to reduce the encumbrances.
ss
nt
F
B
Application areas
www.datexel.it
ISOLATED FREQUENCY TO VOLTAGE, FREQUENCY TO CURRENT
CONVERTER CONFIGURABLE BY DIP-SWITCH OR PC, TRANSISTOR OR RELAY OUTPUTS
GENERAL DESCRIPTION
DAT 4540 The isolated frequency converter DAT 4540 is able to measure, up to 20 KHz, the frequency of TTL, Namur, NPN, PNP and
Tachometer digital signals. In function of programming, the measured values are converted in a current or voltage signal. Moreover
two relays are available in order to be programmed as trip alarm (version “-R”). For the Namur input is continuously checked the
integrity of the sensor; in case of fault (short circuit or interruption), on the transistor output is generated an alarm.
The device guarantees high accuracy and performances stability both versus time and temperature.
FEATURES - High accuracy
- Measure of the frequency for the following digital - On-field reconfigurable
contacts input: Namur, TTL, NPN, PNP, Tachometer, Volt - Galvanic isolation among all ways
- Configurable output as current or voltage - EMC compliant – CE mark
- Double optional trip alarm - Suitable for DIN rail mounting in according to
- Fault alarm condition for Namur sensor EN-50022 and EN-50035 standards
- Configurable by Dip-switch or PC
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
SLIM SERIES
Operative temperature -20°C .. +60°C Impedance > 20 KOhm
Max. output value 22 mA or 11 V
PNP
Storage temperature -40°C .. +85°C Min. output value 0 mA or -0.6 V
Low level Trig. < 4.0 V
High level Trig. > 7.0 V
Output load Resistance - Rload
Humidity (not condensed) 0 .. 90 %
Current output < 500 Ω
Voltage Aux. 17 V – 20 mA
EMC (for industrial environments) Voltage output > 10 KΩ
Impedance ~ 2.2 KOhm
DIRECTIVE : 2004 / 108 / EC Short circuit current 30 mA max
Tachometer
Immunity EN 61000-6-2
Low level Trig. < -50 mV RELAY OUTPUTS
Emission EN 61000-6-4
High level Trig. > +50 mV Relay Outputs (Only for version “-R”)
HOUSING Impedance > 100 KOhm N° 2 SPDT
Material Self-extinguishing plastic Voltage (programmable) Max. load (Resistive) 250 Vac, 2A
DAT 4540 (mm) WxLxH: 90 x 112 x 12.5 Level Trigger 0.05 V ÷ 7.0 V Isolation between terminals 1000 Vac max
DAT 4540-R (mm) WxL xH: 90 x 112 x 22.5 Voltage Aux. 5 ÷ 17 V @ 20 mA Transistor Output
Weight about 90 g. Impedance > 20 KOhm Max. load (Resistive) 30 Vdc, 100mA 7
GENERAL DESCRIPTION
The isolated splitter/converter DAT 4631 A is able to measure and linearise the standard thermocouples with internal or external cold
junction compensation. In function of programming, the measured values are converted in a current or voltage signal. The device
guarantees high accuracy and performances stability both versus time and temperature.
ss
nt
F
B
Application areas
ne
ss
nt
F
B
Application areas
The isolated Splitter/converter DAT 4631 C is able to measure and linearise the standard PTC and NTC sensors and potentiometers.
In function of programming, the measured values are converted in a current or voltage signal.
The device guarantees high accuracy and performances stability both versus time and temperature.
ss
nt
F
B
Application areas
www.datexel.it
ISOLATED SPLITTER/CONVERTER FOR VOLTAGE AND CURRENT CONFIGURABLE BY DIP-SWITCH OR PC
ne
ss
nt
F
B
Application areas
SLIM SERIES
Operative temperature -20°C .. +60°C Volt >= 1 MΩ Output load Resistance - Rload
Storage temperature -40°C .. +85°C Current <= 50 Ω Current output < 500 Ω
The isolated converter DAT 4632 D is able to measure voltage and current signals, execute a programmable mathematical function
and provide on output a normalized current or voltage signal. The device guarantees high accuracy and performances stability both
versus time and temperature.
ss
nt
F
B
Application areas
www.datexel.it
2 SLIM SERIES
INDEX
12 • DAT 4035
PC programmable Two wire isolated universal signal transmitter
13 • DAT 4135
PC programmable isolated universal signal converter
14 • DAT 4135/SEL
PC configurable universal signal converter with command of enable/disable output
15 • DAT 4235
PC programmable 3 ways isolated universal signal converter
16 • DAT 4520
Universal converter with Trip Amplifier
SMART SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
02
ne
ss
nt
F
B
Application areas
Reverse polarity
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %
INPUT INPUT
Input type Min Max Span min Input calibration (1)
12 TC (CJC int./ext.) RTD the higher of ±0.1% f.s. and ±0.2°C
J -200°C 1200°C 2 mV Res. Low the higher of ±0.1% f.s. and ±0.15 Ω
K -200°C 1370°C 2 mV Res. High the higher of ±0.2% f.s. and ±1 Ω
S -50°C 1760°C 2 mV mV, TC the higher of ±0.1% f.s. and ±18 uV
R -50°C 1760°C 2 mV Volt the higher of ±0.1% f.s. and ± 2 mV
B 400°C 1820°C 2 mV mA the higher of ±0.1% f.s. and ± 6 uA
E -200°C 1000°C 2 mV
Linearity (1)
T -200°C 400°C 2 mV
TC ± 0.2 % f.s.
N -200°C 1300°C 2 mV
RTD ± 0.1 % f.s
RTD 2,3,4 wires
Line resistance influence (1)
Pt100 -200°C 850°C 50°C
TC, mV,V <=0.4 uV/Ohm
Pt1000 -200°C 200°C 50°C
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
Ni100 -60°C 180°C 50°C
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Ni1000 -60°C 150°C 50°C
RTD excitation current
Voltage
mV -400 mV +400 mV 2 mV Typical 0.350 mA
mV -100 mV +700 mV 2 mV CJC Comp. ± 0.5 °C
Volt - 10 V +10 V 500 mV Thermal drift (1)
0Ω 200 Ω 10 % Full scale ± 0.01 % / °C
Potentiometer CJC ± 0.01 % / °C
200 Ω 500 Ω 10 %
(Nominal value)
0.5 KΩ 50 KΩ 10 % Burn-out values
Resistance 2,3,4 wires Max. value output about 22.5 mA
Low 0Ω 300 Ω 10 Ω Min. value output about 3.6 mA
High 0Ω 2000 Ω 200 Ω Response time (10÷90% of f.s.) about 400 ms
Current mA -10 mA +24 mA 2 mA (1) referred to input Span (difference between max. and min. values)
Input impedance
TC, mV >= 10 MΩ OUTPUT
Volt >= 1 MΩ Output type Min Max Span min
Current ~ 50 Ω Direct current 4 mA 20 mA 4 mA
Reverse current 20 mA 4 mA 4 mA
Output calibration
Current ± 7 uA
www.datexel.it
PC PROGRAMMABLE ISOLATED UNIVERSAL SIGNAL CONVERTER
DAT 4135 GENERAL DESCRIPTION
The converter DAT 4135 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input. Moreover the DAT 4135 is able to measure and linearise the standard
thermocouples with internal cold junction compensation.
In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy
and performances stability both in time and in temperature.
ne
ss
nt
F
B
Application areas
SMART SERIES
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %
Limitation current about 25 mA
CURRENT CONSUMPTION EMC (for industrial environments) HOUSING
DIRECTIVE 2004/108/EC Material Self-extinguishing plastic
Current output 40 mA max.
Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5
INPUT INPUT
Input type Min Max Span min Input impedance
TC (CJC int./ext.) TC, mV >= 10 MΩ
13
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10 % Max. value output about 23 mA or 10.8 Vdc
Potentiometer Min. value output about 0 mA or 0 Vdc
200 Ω 500 Ω 10 %
(Nominal value)
0.5 KΩ 50 KΩ 10 % Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C Direct current 0 mA 20 mA 4 mA
Reverse current 20 mA 0 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Direct voltage 0V 10 V 1V
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Reverse voltage 10 V 0V 1V
mV, TC the higher of ±0.1 % f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 5 mV
www.datexel.it
PC CONFIGURABLE UNIVERSAL SIGNAL CONVERTER WITH COMMAND OF ENABLE/DISABLE OUTPUT
DAT 4135/SEL GENERAL DESCRIPTION
The converter DAT 4135/SEL is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input.
Moreover the DAT 4135/SEL is able to measure and linearise the standard thermocouples with internal cold junction compensation.
In function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy
and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- Configurable output in current or voltage EN-50022 and EN-50035
- On-field reconfigurable
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
INPUT INPUT
Input type Min Max Span min Input impedance
14 TC (CJC int./ext.) TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05%/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005%/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01% / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01% / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10% Max. value output about 23 mA or 10.8 Vdc
Potentiometer Min. value output about 0 mA or 0 Vdc
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10% Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1% f.s. and ±0.2°C Direct current 0 mA 20 mA 4 mA
Reverse current 20 mA 0 mA 4 mA
Res. Low the higher of ±0.1% f.s. and ±0.15 Ω
Direct voltage 0V 10 V 1V
Res. High the higher of ±0.2% f.s. and ±1 Ω
Reverse voltage 10 V 0V 1V
mV, TC the higher of ±0.1% f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1% f.s. and ± 2 mV Current ± 7 uA
mA the higher of ±0.1% f.s. and ± 6 uA Voltage ± 5 mV
www.datexel.it
PC PROGRAMMABLE 3 WAYS ISOLATED UNIVERSAL SIGNAL CONVERTER
DAT 4235 GENERAL DESCRIPTION
The converter DAT 4235 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a standard active current signal , conversion of a voltage signal
even coming from a potentiometer connected on its input.
Moreover the DAT 4235 is able to measure and linearise the standard thermocouples with internal cold junction compensation. In
function of programming, the measured values are converted in a current or voltage signal. The device guarantees high accuracy and
performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, TC, mV, V, mA, Resistance - Galvanic isolation at 2000 Vac on the 3 ways
and Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- Configurable output in current or voltage EN-50022 and EN-50035
- On-field reconfigurable
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
SMART SERIES
60 Vdc max.
protection Humidity (not condensed) 0 .. 90 %
Limitation current 30 mA max.
CURRENT CONSUMPTION EMC (for industrial environments) HOUSING
DIRECTIVE 2004/108/EC Material Self-extinguishing plastic
Current output 70 mA max.
Immunity EN 61000-6-2 Dimensions (mm) W x L x H : 90 x 112 x 12.5
INPUT INPUT
Input type Min Max Span min Input impedance
TC (CJC int./ext.) TC, mV >= 10 MΩ 15
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -400 mV +400 mV 2 mV Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
Volt - 10 V +10 V 500 mV Burn-out values
0Ω 200 Ω 10% Max. value output about 25 mA or 10.8 Vdc
Potentiometer Min. value output about -25 mA or -10.8 Vdc
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10% Response time (10÷90% of f.s.) about 400 ms
Resistance 2,3,4 wires (1) referred to input Span (difference between max. and min. values)
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA -10 mA +24 mA 2 mA OUTPUT
Input calibration (1) Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C Direct current -20 mA 20 mA 4 mA
Reverse current 20 mA -20 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Direct voltage -10 V 10 V 1V
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Reverse voltage 10 V -10 V 1V
mV, TC the higher of ±0.1 % f.s. and ±18 uV
Output calibration
Volt the higher of ±0.1 % f.s. and ± 2 mV Current ± 7 uA or ± 15 uA (2)
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage ± 10 mV
(2) referred to the output ± 20 mA.
www.datexel.it
UNIVERSAL CONVERTER WITH TRIP AMPLIFIER
DAT 4520 GENERAL DESCRIPTION
The DAT 4520 device measures mV, V, mA or resistance signals, and can be directly connected to Thermocouple, RTD or potentio-
meter sensors.
The input signal is filtered, linearised, amplified and transfered to the output circuit, that converts it in a 0-10V range or 0-20mA range
signal. Auxiliary power supply allows to supply the output current loop. Moreover, the device is able to control two trip alarm relay
outputs. DAT 4520 has a 3 way isolation: input is 2000 Vac isolated from power supply and output; power supply and output are 1500
Vac isolated between them.
FEATURES
- Configurable input for Tc, RTD, Res, mV, V, mA, - 2000 Vac galvanic isolation between input, output
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliance – CE mark
- Configurable by Personal Computer - Suitable for DIN rail mounting in compliance with
- 0 to 10V, 0 to 20mA configurable output EN-50022 and EN-50035
- On-field reconfigurable
ne
ss
nt
F
B
Application areas
Minimum load 5Vdc, 10mA Supply/Output 1500 Vac, 50 Hz, 1min. Humidity (not condensed) 0 .. 90 %
250 Vac (50/60 Hz)
Voltage max 110 Vdc EMC (for industrial environments) HOUSING
CONTENITORE
coil-to-contacts: 2000Vac
Isolation voltage Material Self-extinguishing plastic
between contacts: 1000Vac DIRECTIVE 2004/108/EC Materiale Plastica auto-estinguente
POWER SUPPLY Mounting DIN Rail
Immunity EN 61000-6-2 Dimensioni (mm) W x L x H : 90 x 112 x 12.5
Power supply voltage 20 .. 30 Vdc Dimensions (mm) W x L x H : 120 x 100 x 22.5
Reverse polarity protection 60 Vdc max. Emission EN 61000-6-4 Peso
Weight 90 g. circa
about 150 g.
INPUT INPUT
Input type Min Max Span min Input impedance
16 TC (CJC int./ext.) TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Volt >= 1 MΩ
K -200°C 1370°C 2 mV Current ~ 50 Ω
S -50°C 1760°C 2 mV Linearity (1)
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence (1)
T -200°C 400°C 2 mV
TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV
RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C
RTD excitation current
Pt1000 -200°C 200°C 50°C
Typical 0.350 mA
Ni100 -60°C 180°C 50°C
CJC Comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
Volt 0 mV 10 V 500 mV CJC ± 0.01 % / °C
0Ω 200 Ω 10% Response time (10÷90% of f.s.) about 400 ms
Potentiometer (1) referred to input Span (difference between max. and min. values)
200 Ω 500 Ω 10%
(Nominal value)
0.5 KΩ 50 KΩ 10%
Resistance 2,3,4 wires
Low 0Ω 300 Ω 10 Ω
High 0Ω 2000 Ω 200 Ω
Current mA 0 mA 20 mA 2 mA OUTPUT
Output type Min Max Span min
Direct voltage 0V 10 V 1V
Input calibration (1)
Direct current 0 mA 20 mA 4 mA
RTD the higher of ±0.1 % f.s. and ±0.2°C
Output calibration
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω Current ± 7 uA
Res. High the higher of ±0.2 % f.s. and ±1 Ω Voltage ± 10 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV Output Load Resistance
Volt the higher of ±0.1 % f.s. and ± 2 mV Current < 650 Ω
mA the higher of ±0.1 % f.s. and ± 6 uA Voltage > 4.7 KΩ
www.datexel.it
www.datexel.it ELECTRONIC AND CONTROL PROCESS DEVICES
SMART SERIES
“SMART SERIES” Temperature and signal
transmitters and converters for Din rail mounting 17
ss
nt
F
B
Application areas
www.datexel.it
3 SMART ATEX
Converters / Barriers for universal input or current loop (0-4…..20 mA), suitable for
installation in safe zone for connections towards zone 0. codes:
INDEX
20 • DAT 2015IS
DAT 2015 IS/HT
Universal Intrinsically Safe transmitter
21 • DAT 4035 IS
DAT 4035 IS/HT
Universal Intrinsically Safe isolated transmitter
22 • DAT 4235 IS
Signal Converter with Trip Amplifier for hazardous area sensors
23 • DAT 5030 IS
Current Loop Repeater / Supply for hazardous area sensors
24 • DAT 1010 IS
DAT 1010 IS/HT
Intrinsically safe PC configurable transmitter for RTD
25 • DAT 1015 IS
DAT 1015 IS/HT
Intrinsically safe PC configurable transmitter for universal input
26 • DAT 1065 IS
DAT 1065 IS/HT
Isolated Intrinsically safe PC configurable transmitter for universal input
SMART ATEX SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
ATEX94/9/EC
03
FEATURES
- Configurable input for RTD, mV, Tc, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN rail mounting in compliance with
EN-50022 and EN-50035
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES
INPUT INPUT
20 Input type Min Max Span min Input calibration (1)
TC CJC int./ext. RTD the higher of ±0.1 % f.s. and ±0.2 °C
J -200°C 1200°C 2 mV Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV
S -50°C 1760°C 2 mV
Input impedance
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence (1)
RTD 2,3,4 wires TC, mV,V <=0.4 uV/Ohm
Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5 °C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 2 KΩ 10% Max. output value about 22.5 mA
www.datexel.it
UNIVERSAL INTRINSICALLY SAFE ISOLATED TRANSMITTER
DAT 4035 IS GENERAL DESCRIPTION
DAT 4035 IS/HT The isolated transmitter DAT 4035 IS is able to execute many functions such as: measure and linearisation of the temperature cha-
racteristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentio-
meter connected on its input.
Moreover the DAT 4035 IS is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, mV, Tc, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- Galvanic isolation at 2000 Vac - Suitable for DIN rail mounting in compliance with
- On-field reconfigurable EN-50022 and EN-50035
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
Output /supply Input
INPUT INPUT
Input type Min Max Span min Input calibration (1)
21
TC CJC int./ext. RTD the higher of ±0.1 % f.s. and ±0.2 °C
J -200°C 1200°C 2 mV Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. and ±10 uV
S -50°C 1760°C 2 mV
Input impedance
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence (1)
RTD 2,3,4 wires TC <=0.8 uV/Ohm
Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5 °C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 2 KΩ 10% Max. output value about 22.5 mA
www.datexel.it
SIGNAL CONVERTER WITH TRIP AMPLIFIER FOR HAZARDOUS AREA SENSORS
DAT 4235 IS GENERAL DESCRIPTION
The DAT 4235 IS device is a galvanic isolated Intrinsically Safety Barrier, defined as “Associated Apparatus”.
The input measures mV, V, mA or resistance signals, and can be directly connected to Thermocouple, RTD or potentiometer sensors.
The input signal is filtered, linearized, amplified and transfered to the output circuit, that converts it in a 0-10V range or 0-20mA range
signal.
FEATURES
- Configurable input Tc, RTD, Res, mV, V, mA, Potentiometer - Suitable for DIN rail mounting in according to
- High accuracy EN-50022
- Configurable by PC
- 0 to 10V , 0 to 20mA configurable output Available in 3 different versions:
- 2000 Vac galvanic isolation between input and output - DAT4235 IS A Signal converter
- Programming of the unit measure as °C / °F - DAT4235 IS B Double trip amplifier
- EMC compliance - CE mark - DAT4235 IS C Signal converter + Double trip
- PROTECTION MODE: II (1) G D [ Ex ia ] IIC - [ Ex iaD] in amplifier
according to the Directive ATEX 94/9/EC
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
TRIP ALARMS ISOLATION TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES
Output type n° 2 Relays SPDT 2000 Vac, Terminals A-B-C-D; E-F-G-H-I-J; K-L
Input/Output Operative
Contact 2A , 250 Vac 50 Hz, 1min. -20°C .. +60°C Um=250V
temperature
rating 2A , 30 Vdc 2000 Vac, Terminals Terminals
Input/Supply
Load resistive 50 Hz, 1min. 1-2-3-4-5-6-7 5-6-7
Humidity (not
Minimum load 5Vdc, 10mA 1500 Vac, 0 .. 90 % Uo = 7.8 V Uo = 30 V
Supply/Output condensed)
50 Hz, 1min.
Max Voltage 250 Vac (50/60 Hz) 110 Vdc Io = 32 mA Ii = 100 mA
EMC (for industrial environments) HOUSING
Isolation coil-to-contacts: 2000Vac Po = 140 mW Pi = 0.75W
between contacts: 1000Vac DIRECTIVE 2004/108/EC Material Self-extinguish
plastic
POWER SUPPLY Lo = 20 mH Li = ~0 mH
Mounting DIN Rail
Immunity EN 61000-6-2
Power supply voltage 20 .. 30 Vdc Dimensions 120 x 100 x 22.5 Co = 2 uF Ci = 24 nF
Reverse polarity protection 60 Vdc max Emission EN 61000-6-4 Weight about 150 g. Ta : -20 ÷ +55°C
INPUT INPUT
22 Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV V >= 1 MΩ
K -200°C 1370°C 2 mV mA <= 50 Ω
S -50°C 1760°C 2 mV Linearity
R -50°C 1760°C 2 mV TC ± 0.2 % f.s.
B 400°C 1820°C 2 mV RTD ± 0.1 % f.s
E -200°C 1000°C 2 mV Line resistance influence
T -200°C 400°C 2 mV TC, mV,V <=0.8 uV/Ohm
N -200°C 1300°C 2 mV RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
RTD 2,3,4 wires RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Pt100 -200°C 850°C 50°C RTD excitation current
Pt1000 -200°C 200°C 50°C Typical 0.350 mA
Ni100 -60°C 180°C 50°C CJC comp. ± 0.5°C
Ni1000 -60°C 150°C 50°C Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100 mV +700 mV 2 mV CJC ± 0.01 % / °C
V 0V 10 V 500 mV Response time (10÷90% of f.s.) about 0.4 sec.
Current mA 0 mA 20 mA 2 mA (1) referred to input Span (difference between max. and min. values)
0Ω 200 Ω 10%
Potentiometer OUTPUT
200 Ω 500 Ω 10%
(Nominal value) Output type Min Max Span min
0.5 KΩ 2 KΩ 10%
Voltage 0V 10 V 1V
Resistance
Current 0 mA 20 mA 4 mA
Low 0Ω 300 Ω 10 Ω
Output calibration
High 0Ω 2000 Ω 200 Ω
Current ± 7 uA
Input calibration (1)
Voltage ± 10 mV
RTD the higher of ±0.1 % f.s. and ±0.2 °C
Output Rload resistance
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Current < 650 Ω
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Voltage > 4.7 KΩ
mV, TC the higher of ±0.1 % f.s. and ±10 uV
V the higher of ±0.2 % f.s. and ±2 Ω
mA the higher of ±0.1 % f.s. and ±6 uV
www.datexel.it
CURRENT LOOP REPEATER / SUPPLY FOR HAZARDOUS AREA SENSORS
DAT 5030 IS GENERAL DESCRIPTION
The DAT 5030 IS device is a galvanic isolated Intrinsically Safety Barrier, defined as “Associated Apparatus”
The input can measure 0-20 mA or 4-20 mA current loops, both active or passive mode; auxiliary power supply is available to supply
the current loop through the hazardous area (ZONE 0).
The measure is converted in output as voltage signal (0-10V or 2-10V) or current signal (0-20mA or 4-20mA). Auxiliary power supply
is available to supply the current loop connected to the output.
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY HOUSING
INPUT
Input EX DATA
Terminals J-I; A-B-C-D; O-P-Q-R Um=250V
Input signal Active or passive current loop
23
Range 4.6; 14-16;
Terminals 4-6; 14-16;
OUTPUT
USCITA Terminals 6-5;
4.6; 14-16;
16-15;
Configurable 4÷20
4÷20 mA,
mA, 0÷20
0÷20mA,
mA,0÷10
0÷10VVand 2÷10VV
e 2÷10 Io = 46 mA Ii = 100 mA
Output Rload resistance
load resistance Po = 14 mW Pi = 0.75W
Voltage > 5 KΩ
Li = ~0 mH
Current < 500 Ω
Ci = 12 nF
Auxiliary Supply > 12V @ 20mA
Ta : -20 ÷ +60°C
PERFORMANCES
Calibration error ± 0.1 % of f.s.
Linearity error (*) ± 0.2 % of f.s.
Thermal drift 0.02 % of Full scale/°C
Response
Responsetime (10÷90% of f.s.)
time < 0.2 sec.
Frequency response
bidirectional 0.5 ÷ 4 Khz @ 3dB
(HART Protocol)
(*) = inclusive of hysteresis, power supply variation and linearisation error.
www.datexel.it
INTRINSICALLY SAFE PC CONFIGURABLE TRANSMITTER FOR RTD
DAT 1010 IS GENERAL DESCRIPTION
DAT 1010 IS/HT The transmitter DAT 1010 IS is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input. The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, mV, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN B in-head mounting
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES
INPUT INPUT
24 Input type Min Max Span min Line resistance influence (1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
Pt100 -200°C 850°C 50°C RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
Pt1000 -200°C 200°C 50°C RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
Ni100 -60°C 180°C 50°C RTD excitation current
Ni1000 -60°C 150°C 50°C Typical 0.350 mA
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% Burn-out values
Potentiometer
200 Ω 500 Ω 10% Max. output value about 22.5 mA
(Nominal value)
0.5 KΩ 2 KΩ 10% Min. output value about 3.6 mA
RES. 2,3,4 wires Response time (10÷90% of f.s.) about 400 ms
Low 0Ω 300 Ω 10 Ω (1) referred to input Span (difference between max. and min. values)
High 0Ω 2000 Ω 200 Ω
OUTPUT
Input calibration (1)
Output type Min Max Span min
RTD the higher of ±0.1 % f.s. and ±0.2°C
Direct current 4 mA 20 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω
Reverse current 20 mA 4 mA 4 mA
Res. High the higher of ±0.2 % f.s. and ±1 Ω
Output calibration
mV the higher of ±0.1 % f.s. and ±10 uV
Current ± 7 uA
Input impedance
mV >= 10 MΩ
Linearity (1)
RTD ± 0.1 % f.s
www.datexel.it
INTRINSICALLY SAFE PC CONFIGURABLE TRANSMITTER FOR UNIVERSAL INPUT
DAT 1015 IS
GENERAL DESCRIPTION
DAT 1015 IS/HT The transmitter DAT 1015 IS is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input. Moreover the DAT 1015 IS is able to measure and linearise the standard thermocouples with internal cold junction com-
pensation. The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, mV, TC, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- On-field reconfigurable - Suitable for DIN B in-head mounting
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
Output /supply Input
INPUT INPUT
Input type Min Max Span min Input impedance
25
TC CJC int./ext. TC, mV >= 10 MΩ
J -200°C 1200°C 2 mV Linearity (1)
K -200°C 1370°C 2 mV TC ± 0.2 % f.s.
S -50°C 1760°C 2 mV RTD ± 0.1 % f.s
R -50°C 1760°C 2 mV Line resistance influence
B 400°C 1820°C 2 mV TC, mV <=0.8 uV/Ohm
E -200°C 1000°C 2 mV RTD 3-wires 0.05 %/Ω (50 Ω balanced max.)
T -200°C 400°C 2 mV RTD 4-wires 0.005 %/Ω (100 Ω balanced max.)
N -200°C 1300°C 2 mV RTD excitation current
RTD 2,3,4 wires Typical 0.350 mA
Pt100 -200°C 850°C 50°C CJC comp. ± 0.5 °C
Pt1000 -200°C 200°C 50°C Thermal drift (1)
Ni100 -60°C 180°C 50°C Full scale ± 0.01 % / °C
Ni1000 -60°C 150°C 50°C CJC ± 0.01 % / °C
Voltage Burn-out values
mV -100 mV +700 mV 2 mV Max. output value about 22.5 mA
0Ω 200 Ω 10% Min. output value about 3.6 mA
Potentiometer
200 Ω 500 Ω 10% Response time (10÷90% of f.s.) about 400 ms
(Nominal value)
0.5 KΩ 2 KΩ 10% (1) referred to input Span (difference between max. and min. values)
Resistance
Low 0Ω 300 Ω 10 Ω OUTPUT
High 0Ω 2000 Ω 200 Ω Output type Min Max Span min
Input calibration (1) Direct current 4 mA 20 mA 4 mA
RTD the higher of ±0.1 % f.s. and ±0.2 °C Reverse current 20 mA 4 mA 4 mA
Res. Low the higher of ±0.1 % f.s. and ±0.15 Ω Output calibration
Res. High the higher of ±0.2 % f.s. and ±1 Ω Current ± 7 uA
mV, TC the higher of ±0.1 % f.s. and ±10 uV
www.datexel.it
ISOLATED INTRINSICALLY SAFE PC CONFIGURABLE
TRANSMITTER FOR UNIVERSAL INPUT
DAT 1065 IS GENERAL DESCRIPTION
DAT 1065 IS/HT The isolated transmitter DAT 1065 IS is able to execute many functions such as: measure and linearisation of the temperature cha-
racteristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentio-
meter connected on its input.
Moreover the DAT 1065 IS is able to measure and linearise the standard thermocouples with internal cold junction compensation. The
measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, mV, TC, Resistance and - Applicable in zones with explosion risk (ZONE 0)
Potentiometer - Programming of the unit measure as °C or °F
- High accuracy - EMC compliant – CE mark
- Configurable by Personal Computer - PROTECTION MODE: II 1 G Ex ia IIC certified in
- 4 ÷ 20 mA configurable output on current loop according to the Directive ATEX 94/9/EC
- Galvanic isolation at 2000 Vac - Suitable for DIN B in-head mounting
- On-field reconfigurable
u s tri es E n er g y er treat me m ic a l o f
In d at he f
sh
W
nt
petro
Application areas
ore
POWER SUPPLY TEMPERATURE & HUMIDITY EX DATA
SMART ATEX SERIES
INPUT INPUT
26 Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
sh
W
nt
petro
ore
Application areas
www.datexel.it
4 PDS
• Single and double channel 4÷20 mA two wires transmitters for Pt100 input
without galvanic isolation (DAT2065, DAT2066)
• 4÷20 mA two wires transmitter for Thermocouple input without galvanic
isolation (DAT2045)
• Single and double channel converters for Pt100 input with configurable
output as voltage or current without galvanic isolation (DAT2165, DAT2166)
• Isolated converter for Pt100 input with configurable output as voltage or
current (DAT2061)
• Converter for Thermocouple input with configurable output as voltage or
current without galvanic isolation (DAT2145)
• Isolated signal converters with configurable input and output as voltage or
current (DAT5020. DAT5021, DAT5023I, DAT5023V)
• Isolated signal splitter with configurable input and output as voltage or
current (DAT5022)
• Isolated signal converter for Strain Gauge input with configurable output as
voltage or current (DAT5025)
INDEX
30 • DAT 2065
Dip Switch Configurable transmitter for Pt100
DAT 2066
Double channel Dip Switch Configurable transmitter for Pt100
31 • DAT 2165
Dip Switch Configurable converter for Pt100
DAT 2166
Double Channel Dip Switch Configurable converter for Pt100
32 • DAT 2061
Isolated Dip switch configurable converter for Pt100
DAT 2045
Not linearized Dip Switch configurable transmitter for thermocouple
33 • DAT 2145
Not linearized Dip Switch configurable converter for thermocouple
DAT 5020
Dip Switch configurable 3 ways isolated signal converter
34 • DAT 5021
3 ways isolated Dip Switch configurable signal converter
DAT 5022
4 ways isolated Dip Switch configurable signal converter/signal splitter
36 • DAT 5023/V
Dip Switch configurable converter for AC / DC voltage signal
DAT 5025
Isolated programmable Dip Switch converter for Strain Gauge / Bridge sensors
P.D.S. SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
04
FEATURES
- Configurable Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with
- 4 to 20 mA linearised output on current loop EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
EMC (for industrial environments) Programmable -50 ÷ 50 °C (difference between max. and min.)
DIRECTIVE 2004 / 108 / EC Input Calibration (1) (*) = inclusive of hysteresis, power supply variation
Immunity EN 61000-6-2 the higher of ± 0.1 % f.s. and 0.2 °C and linearisation error.
Emission EN 61000-6-4 RTD sensor excitation current
HOUSING Typ. 0.6 mA
Material Self-extinguishing plastic Thermal drift (1)
Dim. (mm) W x L x H : 90 x 112 x 12.5 Full Scale ± 0.02 % / °C
Weight about 80 g.
30
tional with the temperature characteristics of the Pt100 sensors connected on its inputs.
It is possible to connect on the input both 3 wire Pt100 and 2 wire Pt100.
ss
nt
F
B
Application areas
www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR PT100
FEATURES
- Configurable Input for Pt100 - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with EN-50022
- Linearised voltage or current output and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
P.D.S. SERIES
temperature
Programmable -50 ÷ 50 °C (*) = inclusive of hysteresis, power supply variation
Humidity (not condensed) 0 .. 90 %
Input Calibration (1) and linearisation error.
EMC (for industrial environments)
the higher of ± 0.1 % f.s. and 0.2 °C
DIRECTIVE 2004 / 108 / EC
RTD sensor excitation current
Immunity EN 61000-6-2
Typ. 0.6 mA
Emission EN 61000-6-4
Thermal drift (1)
HOUSING
Full Scale ± 0.02 % / °C
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 90 x 112 x 12.5
Weight about 80 g.
31
DOUBLE CHANNEL DIP SWITCH CONFIGURABLE CONVERTER FOR PT100
DAT 2166
GENERAL DESCRIPTION
The double channel converter DAT 2166 is designed to provide on the output two linearised voltage or current signals proportional
with the temperature characteristics of the Pt100 sensors connected on its inputs. It is possible to connect on the input both 3 wire
and 2 wire Pt100.
oo at
Application areas
ss
nt
F
ne
ss
nt
F
B
Application areas
TEMPERATURE & HUMIDITY Min. input value programmability (difference between max. and min.)
Operative temperature -20°C .. +70°C Programmable -50 ÷ 50 °C (*) = inclusive of hysteresis, power supply variation
Storage and linearisation error.
temperature
-40°C .. +85°C Input Calibration (1)
Humidity (not condensed) 0 .. 90 % the higher of ± 0.1 % f.s. and 0.2 °C
The transmitter DAT 2045 is designed to provide on its output a 4÷20 mA current loop signal linear and proportional with the value
of voltage generated from the thermocouple connected to its input.
The DAT 2045 doesn’t execute the linearisation of the input signal; this feature allows to use the transmitter with acquisition systems
with an internal linearisation software.
FEATURES
- Configurable Input for thermocouples type K, J, R, S and T - Unit of measure configurable in °C or °F
- Good accuracy and performance stability - EMC compliant – CE mark
- Configurable by DIP-switches - DIN rail mounting in compliance with EN-
- 4 to 20 mA “voltage linear” output on current loop 50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
www.datexel.it
NOT LINEARIZED DIP SWITCH CONFIGURABLE CONVERTER FOR THERMOCOUPLE
ne
ss
nt
F
B
Application areas
P.D.S. SERIES
temperature
Humidity (not condensed) 0 .. 90 % Direct current 4 mA 20 mA - (1) = referred to the input Span
EMC (for industrial environments) Direct Voltage 0V 10 V - (difference between max. and min.)
(*) = inclusive of hysteresis, power supply variation
DIRECTIVE 2004 / 108 / EC Min. input value programmability
and linearisation error.
Immunity EN 61000-6-2 Programmable -50 ÷ 50 °C
Emission EN 61000-6-4 Input Calibration (1)
HOUSING the higher of ± 0.1 % f.s. and 0.2 °C
The converter DAT 5020 is designed to provide on its output a voltage or current signal proportional with the value of the normalised signal or
the potentiometer applied on its input. The user can program the input and output ranges by the proper DIP-switches available after opening the
suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the
top of device. The 2000 Vac isolation between input, power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications. On the input side, an auxiliary supply source
isolated from the power supply is provided; this allows to connect on input both active and passive current loops.
ss
nt
F
B
Application areas
ne
ss
nt
F
B
Application areas
ISOLATION 4 mA 20 mA -
Load resistance (Rload)
All the ways 2000 Vac, 50 Hz, 1 min
0V 10 V - Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY 2V 10 V -
Voltage
Current output </= 500 Ω
Operative temperature -20°C .. +60°C
0V 5V - (*) = inclusive of hysteresis and power supply variation.
Storage
-40°C .. +85°C 1V 5V -
temperature
Humidity (not condensed) 0 .. 90 % Input Calibration ± 0.1 % f.s.
EMC (for industrial environments) Linearity (*) ± 0.05 % f.s.
DIRECTIVE 2004 / 108 / EC Thermal drift
Immunity EN 61000-6-2 Full Scale ± 0.02 % / °C
Emission EN 61000-6-4 Response time (from 10 to 90 % of f.s.) < 10 ms
34
4 WAYS ISOLATED DIP SWITCH CONFIGURABLE SIGNAL CONVERTER/SIGNAL SPLITTER
GENERAL DESCRIPTION
DAT 5022
The converter DAT 5022 is designed to provide on its output two voltage or current signals proportional with the value of the normali-
sed signal applied on its input. The user can program the input and outputs ranges by the proper DIP-switches available after opening
the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.
ss
nt
F
B
Application areas
www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR AC CURRENT SIGNAL
GENERAL DESCRIPTION
DAT 5023Iac The converter DAT 5023Iac is designed to detect the TRMS value of the AC current signal from 0÷5 A to 0÷60 A applied on its input providing
a voltage or current output signal. The user can program the input and output ranges by the proper DIP-switches available after opening the
suitable door located on the side of device. The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on
the top of device. The 2000 Vac isolation between power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications.
The measure of the input signal is executed by a cross connector and a Hall effect transducer; this allows to isolate the input side from the
output and power supply.
FEATURES
- Input for AC current signal - Isolated power supply source for passive loads on output
- Build-in cross connector (8mm diameter) - Independent zero and full scale regulations
- Measure by Hall effect transducer - EMC compliant – CE mark
- True Root Mean Square (TRMS) measure - DIN rail mounting in compliance with
- Galvanic isolation at 2000 Vac EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
P.D.S. SERIES
DAT5023Iac/B 0÷20 A 0÷30 A -
All the ways
2000 Vac, Load resistance (Rload)
50 Hz, 1 min DAT5023Iac/D 0÷40 A 0÷60 A -
Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY Bandwidth (-3dB)
Current output </= 500 Ω
Operative temperature -20°C .. +60°C 40 Hz ÷ 1KHz
Storage Response time (10÷90% of f.s.) About 400 ms
-40°C .. +85°C Input Calibration ± 0.1 % f.s.
temperature (*) = inclusive of hysteresis and power supply variation.
Linearity (*) ±1 % f.s.
Humidity (not condensed) 0 .. 90 %
Thermal drift
EMC (for industrial environments)
Full Scale ± 0.02 % / °C
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2
Emission EN 61000-6-4
35
ISOLATED CONVERTER FOR DC CURRENT SIGNAL
WITH FIXED INPUT AND DIP SWITCH CONFIGURABLE OUTPUT
GENERAL DESCRIPTION
DAT 5023Idc
The converter DAT 5023Idc is designed to convert the DC current signal from 0÷5 A to 0÷60 A applied on its input in a voltage or current
output signal. The device is available in three versions (A, B and D) in function of the input current value.
The user can program the output ranges by the proper DIP-switches available after opening the suitable door located on the side
of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.
ss
nt
F
B
Application areas
www.datexel.it
DIP SWITCH CONFIGURABLE CONVERTER FOR AC / DC VOLTAGE SIGNAL
GENERAL DESCRIPTION
DAT 5023/V The converter DAT 5023/V is designed to detect the TRMS value of the AC voltage signal or to convert the DC voltage signal
applied on its input in a voltage or current output signal. The user can program the input type and output ranges by the proper
DIP-switches available after opening the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.
The 1500 Vac isolation between input, power supply and output eliminates the effects of all ground loops eventually existing and
allows the use of the converter in heavy environmental conditions found in industrial applications.
ne
ss
nt
F
B
Application areas
ISOLATION 1V 5V -
Voltage (Vdc) 0÷36 Vdc 0÷550 Vdc -
All the ways
1500 Vac, Load resistance (Rload)
50 Hz, 1 min Bandwidth (-3dB)
Voltage output >/= 5 KΩ
TEMPERATURE & HUMIDITY 40 Hz ÷ 1KHz
Current output </= 500 Ω
Operative temperature -20°C .. +60°C Input Calibration ± 0.1 % f.s.
(AC) 250 ms
Storage Linearity (*) Response time (10÷90% of f.s.)
-40°C .. +85°C
temperature (DC) 20 ms
(AC) ±1 % f.s. (DC) ± 0.1 % f.s.
Humidity (not condensed) 0 .. 90 %
Thermal drift (1) = To choose the input range refer to the technical
EMC (for industrial environments) data sheet.
Full Scale ± 0.02 % / °C
DIRECTIVE 2004 / 108 / EC (*) = Inclusive of hysteresis and power supply variation.
Immunity EN 61000-6-2
Emission EN 61000-6-4
36
ISOLATED PROGRAMMABLE DIP SWITCH CONVERTER
FOR STRAIN GAUGE / BRIDGE SENSORS
GENERAL DESCRIPTION
DAT 5025
The converter DAT 5025 is designed to provide on its output a voltage or current signal linear and proportional with the output
voltage coming from the output of a bridge transducer applied on its input.
The user can program the bridge excitation voltage value, the input and the output ranges by the proper DIP-switches available
after opening the suitable door located on the side of device.
The regulation of Zero and Span values is made by the ZERO and SPAN potentiometers located on the top of device.
FEATURES
- Input for Strain-Gauge - Isolated power supply source for passive loads on output
- Input range configurable from 0÷10 mV up to 0÷200 - Independent zero and full scale regulations
mV or from ± 5 mV up to ± 200 mV - EMC compliant – CE mark
- Current limiter on the input side - Din rail mounting in compliance with EN-50022
- Galvanic isolation at 2000 Vac on the 3 ways and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
P.D.S. SERIES
P.D.S. series temperature and signal transmitters
www.datexel.it
ss
nt
F
B
Application areas
www.datexel.it
05 Trip amplifiers
DAT5028-DAT5024 SERIES:
Trip amplifiers for DIN rail mounting
The devices of the “DAT5028 - DAT5024” series can accept on input several
types of sensor coming from the field.
INDEX
40 • DAT 5028
Trip amplifier with display for universal analog input
41 • DAT 5024
Trip amplifier with dedicated analog input
42 • DAT 5024E
Economic, isolated trip amplifier configurable by Dip-Switches
TRIP AMPLIFIERS
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
05
FEATURES
- Universal Analog Input : Voltage, Current, TC, RTD, Resistance - 1500 Vac galvanic isolation on all ways
- 2 SPDT + 2 SPST Relay Outputs (Version with 4 trips) - High Accuracy
- 2 SPDT Relay Outputs (Version with 2 trips) - EMC compliance – CE Mark
- 1 V/mA Analog Output for signal transmission - DIN rail suitable mounting (EN-50022)
ne
ss
nt
F
B
Application areas
Current Consumption 120 mA @24Vdc (300mA max) Storage temperature -40°C ÷ +85°C
ISOLATION HOUSING
Isolation voltage 1500 Vac (on all ways) Material Self-extinguishing plastic
EMC (for industrial environments) Mounting DIN Rail
DIRECTIVE 2004/108/EC
Dimensions (mm) W x L x H : 90 x 112 x 22.5
Immunity EN 61000-6-2
Emission EN 61000-6-4 Weight about 150 g.
Tc R -50 / +1760 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Voltage Max. 250Vac (50 / 60 Hz) ,110Vdc
www.datexel.it
TRIP AMPLIFIER WITH DEDICATED ANALOG INPUT
DAT 5024 GENERAL DESCRIPTION
The trip amplifier DAT 5024 is able to accept on its input a wide range of normalised voltage signals, normalised current signals
coming from both active and passive current loop, signals coming from RTDs, Thermocouples and resistance sensors. The input type
and the input range are fixed: refer to the section “Technical Specifications”, table “ Input type ” to order the device. The Threshold 1
is programmed as high alarm, while, by dip-switches, it is possible to set the Threshold 2 either as high or low alarm. The trip level of
each threshold can be adjusted by the potentiometers and checked by the test-points located on the front of the device. It is possible
to adjust by potentiometers also the values of the hysteresis level and delay time. The isolation between input and power supply is
2000 Vac. The isolation between input and contacts of relays is 2000 Vac.The isolation between power supply and contacts of relays
is 1500 Vac. The isolations eliminate the effects of all ground loops eventually existing and allows the use of the converter in heavy
environmental conditions found in industrial applications.
ne
ss
nt
F
B
Application areas
TRIP AMPLIFIERS
AUXILIARY SUPPLY
(only for mA input) > 18 V @ 20 mA Emission EN 61000-6-4 Humidity (not condensed) 0 ÷ 90 %
ISOLATION HOUSING
Input – power supply 2000 Vac 50 Hz, 1 min Material Self-extinguishing plastic
Input – contact of relays 2000 Vac 50 Hz, 1 min Dimensions (mm) W x L x H : 90 x 112 x 22.5
Power supply – contact of relays 1500 Vac 50 Hz, 1 min. Weight about 90 g.
1V 0 mV +1 V V > 100 KΩ
10 V 0 mV +10 V mA < 50 Ω
www.datexel.it
ECONOMIC, ISOLATED TRIP AMPLIFIER CONFIGURABLE BY DIP-SWITCHES
DAT 5024E GENERAL DESCRIPTION
The DAT 5024E is an economic trip amplifier able to accept on its input normalised voltage and current signals coming from both active
and passive current loops. Both the trips can be configured as high or low alarm, the adjustment of the trip values is performed by the
potentiometers THR1 and THR2 located on the front side of the device.
The adjustment of the hysteresis and delay value can be performed by the potentiometers accessible opening the suitable door loca-
ted on the side of the device.
On the devices are foreseen the following isolation power supply/input: 1500 Vac; contact of relays/output-input: 1000 Vac.
FEATURES
- Input for Voltage and Current - Delay time adjustable by potentiometer from 1 up to 6 sec.
- Two independent thresholds - Two relays SPDT (Form C)
- Type of alarm programmable by dip-switch as high - Good accuracy and linearity
or low - EMC compliant – CE mark
- Galvanic isolated among the ways - Suitable for DIN rail mounting in compliance with EN-50022
- Trip level and hysteresis adjustable by potentiometers and EN-50035
ne
ss
nt
F
B
Application areas
Rever. polarity protection 60 Vdc max Immunity EN 61000-6-2 Storage temperature -40°C ÷ +85°C
AUXILIARY SUPPLY
Emission EN 61000-6-4 Humidity (not condensed) 0 ÷ 90 %
(only for mA input) > 18 V @ 20 mA
ISOLATION HOUSING
Input – Power Supply 1500 Vac 50 Hz, 1 min Material Self-extinguishing plastic
Input – contact of relays 1000 Vac 50 Hz, 1 min Dimensions (mm) W x L x H : 90 x 112 x 12.5
Power Supply – Contact of relays 1000 Vac 50 Hz, 1 min. Weight about 90 g.
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
TRIP AMPLIFIERS
“DAT5028 / DAT5024 series”
www.datexel.it
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
INDEX
46 • DAT 205 2W
Fixed range Transmitter for potentiometer
DAT 205 3W
Fixed range Converter for potentiometer
47 • DAT 207 2W
Fixed range transmitter for mV,V and mA signals
DAT 207 3W
Converter for mV,V and mA signals
48 • DAT 511
Self-powered current loop isolator
DAT 511/H
Self-powered current loop isolator HART compatible
DAT200/500 SERIES
06
ne
ss
nt
F
B
Application areas
Storage temperature -40°C .. +85°C Potentiometer ± 0.1 % f.s. Response time (10÷90%) about 500 ms
Linearity
Humidity (not condensed) 0 .. 90 %
± 0.1 % f.s.
EMC (for industrial environments)
Thermal drift
DIRECTIVE 2004/108/EC
Full scale ± 0.02 % / °C
Immunity EN 61000-6-2
Emission EN 61000-6-4
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.
46
FIXED RANGE CONVERTER FOR POTENTIOMETER
GENERAL DESCRIPTION
DAT 205 3W
The converter DAT 205 3W is designed to provide on output a linearised voltage or current signal proportional with the variation of
resistance introduced from the potentiometer connected to its input; to make the measure, a 1 Vdc voltage reference is provided at
the ends of the potentiometer. The regulations of the zero and full-scale value are made using the ZERO and SPAN potentiometers;
there is not influence between the regulations.
ss
nt
F
B
Application areas
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.
www.datexel.it
FIXED RANGE TRANSMITTER FOR mV,V AND mA SIGNALS
DAT 207 2W GENERAL DESCRIPTION
The transmitter DAT 207 2W is designed to provide on output a 4÷20 mA current loop signal proportional with the variation
of the normalised current or voltage signal applied to its input.
ne
ss
nt
F
B
Application areas
The converter DAT 207 3W is designed to provide on output a 4÷20 mA current loop signal proportional with the variation of
the normalised current or voltage signal applied to its input.
ss
nt
F
B
Application areas
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight about 50 g.
www.datexel.it
SELF-POWERED CURRENT LOOP ISOLATOR
GENERAL DESCRIPTION
DAT 511 The transmitter DAT 511 is a passive 0÷20 mA current loop isolator.
The input current, variable from 0 up to 20 mA, is converted in an output current of the same value but keeping a galvanic isolation
from the input circuit.
The converter is a passive isolator: this means that the device employs the measurement signal to power it self, so it does not require
any external power supply.
ne
ss
nt
F
B
Application areas
HOUSING
Material Self-extinguishing plastic
Dim. (mm) W x L x H : 62 x 64 x 17
Weight About 60 g.
48
SELF-POWERED CURRENT LOOP ISOLATOR HART COMPATIBLE
GENERAL DESCRIPTION
DAT 511/H
The transmitter DAT 511/H is a passive 0÷20 mA current loop isolator. The input current, variable from 0 up to 20 mA, is converted
in an output current of the same value but keeping a galvanic isolation from the input circuit. The device allows the bidirectional
communication of signals HART protocol compatible. The converter is a passive isolator: this means that the device employs the
measurement signal to power itself, so it does not require any external power supply.
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
galvanic isolators 49
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
INDEX
52 • DAT 3580
Isolated converter RS232 RS485 / 422
DAT 3580-USB
Isolated converter USB RS485 / 422
53 • DAT 3580-MBTCP
Isolated Ethernet Gateway Modbus TCP Modbus RTU
DAT 3590
Repeater/ Isolator RS485 / 422
54 • DAT 3130
Distributed I/O Module 4 digital inputs + 4 relay outputs on RS-485 network
DAT 3140
Distributed I/O Module 4 digital inputs + 8 NPN outputs on RS-485 network
55 • DAT 3148/8
Distributed I/O Module 8 digital inputs on RS-485 network
DAT 3148/12
Distributed I/O Module 12 digital inputs on RS-485 network
56 • DAT 3188/4
Distributed I/O Module 4 digital inputs + 8 PNP outputs on RS-485 network
DAT 3188/8
Distributed I/O Module 8 digital inputs + 8 PNP outputs on RS-485 network
57 • DAT 3011
Universal Remote I/O module on RS-485 network
58 • DAT 3014
Remote I/O module 4 channels RTD input on RS-485 network
DAT 3015-I
Remote I/O module 4 channels +/-20mA input on RS-485 network
59 • DAT 3015-V
Remote I/O module 4 channels +/-10V input on RS-485 network
DAT 3016
Remote I/O module 4 channels mV / TC input on RS-485 network
60 • DAT 3017-I
Remote I/O module 8 channels ±20mA input on RS-485 network
DAT 3017-V
Remote I/O module 8 channels ±10V input on RS-485 network
61 • DAT 3018
Remote I/O module 8 channels mV / TC input on RS-485 network
DAT 3019
Remote I/O module 8 channels RTD input on RS-485 network
62 • DAT 3022
Remote I/O module 2 channels V / mA output on RS-485 network
DAT 3024
Remote I/O module 4 channels V / mA output on RS-485 network
63 • DAT 3028
Remote I/O module 8 channels Voltage output on RS-485 network
DAT3000 SERIES
07
ne
ss
nt
F
B
Application areas
2 Km @ 19200 bps
35 mA typ. @ 24Vdc HOUSING 3 Km @ 9600 bps
Max. distance / baud-rate
ISOLATIONS Material Self-extinguishing plastic ratio (recommended) (1) 4 Km @ 4800 bps
Power Supply/ RS232 Mounting DIN rail
5 Km @ 2400 bps
2000 Vac, 50 Hz, Dim. (mm) W x L x H : 120 x 100 x 22.5
Power Supply/ RS485-422
1 min. 7 Km @ 1200 bps
Weight About 150 g.
RS232 / RS485-422 Number of modules in multipoint 32 max.
CONNECTION
TEMPERATURE & HUMIDITY RS-232 DB9 and removable screw terminals Switching time TX/RX (RS485) 150 us.
Operative temperature -20°C ÷ +60°C RS-485/422 removable screw terminals Internal terminator resistance (optional) 120 Ohm (optional)
Storage temperature -40°C ÷ +85°C (1) = The maximum distance depends of: number of
devices connected, type of cabling, noises, etc...
Humidity (not condensed) 0 ÷ 90 %
52
The device DAT3580-USB is an isolated interface converter between USB port and asynchronous serial lines RS485 or RS422 that
guarantees a full isolation between power supply, USB and serial line RS-485 or 422 removes eventual ground-loop effects, allowing
the use of the device even in the heavy environmental conditions.
It is designed to operate either on serial interface RS-422 full-duplex 4 wires or RS485 half-duplex 2 wires, with a baud-rate transmis-
sion up to 115.2 Kbps. The transmission is asynchronous without settings of protocol, data format and baud rate.
ss
nt
F
B
Application areas
www.datexel.it
ETHERNET ISOLATED GATEWAY MODBUS TCP MODBUS RTU
DAT 3580-MBTCP GENERAL DESCRIPTION
The gateway DAT3580-MBTCP allows to connect the Modbus RTU devices of a RS-485 network to the Ethernet network throu-
gh the Modbus TCP protocol.
By means of the Telnet interface it is possible to configure all the Modbus TCP side options (IP address, subnet mask, etc..) and
the Modbus RTU side options (baud rate, etc...).
The device guarantees a full isolation between lines, allowing the use even in the heavy environmental conditions.
FEATURES
- Network interface - Distance up to 1200 m, up to 32 devices in multipoint
- Ethernet 10/100Base-T, Modbus TCP - Removable screw-terminal connection
- Telnet configuration - LED signalling for Link/Act Ethernet, serial RX-TX, power supply
- RJ45 connection - Galvanic Isolation on all ways
- RS-485 Serial interface - EMC compliance – CE mark
- Modbus RTU Master - Ethernet IEEE 802.3 and RS485 compliant
- Baud rate up to 115.2 Kbps - Suitable for DIN rail mounting in compliance with EN-50022
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
POWER SUPPLY EMC (for industrial environments) Network interface Ethernet 10/100 Base-T
18 ÷ 30 Vdc DIRECTIVE 2004 / 108 / EC Protocol Modbus TCP
CURRENT CONSUMPTION Immunity EN 61000-6-2 Connection RJ-45
45 mA typ. @ 24Vdc (sleep mode) Emission EN 61000-6-4 Baud-rate (RS-485) up to 115.2 Kbps
DAT3000 SERIES
80 mA max HOUSING 1.2 Km @ 38400 bps
ISOLATIONS Material Self-extinguishing plastic 2 Km @ 19200 bps
Power Supply/ Ethernet 1500 Vac, 50 Hz, 1 min. Mounting DIN rail Max. distance / baud-rate 3 Km @ 9600 bps
Power Supply/ RS485 2000 Vac, 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 22.5 ratio (recommended) (1) 4 Km @ 4800 bps
Ethernet / RS485 2000 Vac, 50 Hz, 1 min. Weight About 150 g. 5 Km @ 2400 bps
Storage temperature -40°C ÷ +85°C RS-485 removable screw terminals Switching time TX/RX (RS485) 150 us.
Humidity (not condensed) 0 ÷ 90 % Internal terminator resistance (optional) 120 Ohm (optional)
The device DAT 3590 is an isolated repeater between asynchronous serials lines RS485 or RS422 that guarantees a full isolation
between power supply and serial line removing eventual ground-loop effects, allowing the use of the device even in the heavy
environmental conditions. It is designed to operate either on serial interface RS-422 full-duplex 4 wires or RS485 half-duplex 2
wires, with a baud-rate transmission up to 115.2 Kbps.
The transmission is asynchronous without settings of protocol, data format and baud rate.
ss
nt
F
B
Application areas
RS485-422 / RS485-422 2000 Vac, 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 22.5 Number of modules in multipoint 32 max.
Weight About 150 g. Switching time TX/RX (RS485) 150 us.
TEMPERATURE & HUMIDITY
CONNECTION Internal terminator resistance (optional) 120 Ohm
Operative temperature -20°C ÷ +60°C
RS485/422 removable screw terminals (1) = The maximum distance depends of: number of
Storage temperature -40°C ÷ +85°C devices connected, type of cabling, noises, etc...
Humidity (not condensed) 0 ÷ 90 %
www.datexel.it
DISTRIBUTED I/O MODULE 4 DIGITAL INPUTS + 4 RELAY OUTPUTS ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3130 The device DAT 3130 is able to acquire up to 4 digital inputs and to drive up to 4 relay outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. The 1500 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial
line cancels any ground-loop effect noise, allowing the use of the device in worst ambient conditions.
ne
ss
nt
F
B
Application areas
Inputs – RS485
1500 Vac 50 Hz, 1 DIGITAL INPUTS Switching power (max.)
Inputs – Supply
min. Input channels 4 2 A @ 250 Vac (resistive load) per contact
RS-485 – Supply
Input voltage (bipolar) 2 A @ 30 Vdc (resistive load) per contact
TEMPERATURE & HUMIDITY
OFF State 0÷3V
Operating Temperature -10°C .. +60°C Minimum load 5Vdc , 10mA
ON State 10 ÷ 30 V
Storage Temperature -40°C .. +85°C Max. Voltage 250Vac (50 / 60 Hz), 110Vdc
Humidity (not condensed) 0 .. 90 %
Impedance 4.7 KΩ
Data Transmission (asynchronous serial)
EMC (for industrial environments)
Baud rate up to 38.4 Kbps
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Max. Distance 1.2 Km - 4000ft
Emission EN 61000-6-4 Sample time 5 ms max
The device DAT 3140 is able to acquire up to 4 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. The galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels
any ground-loop effect noise, allowing the use of the device in worst ambient conditions.
ss
nt
F
B
Application areas
www.datexel.it
DISTRIBUTED I/O MODULE 8 DIGITAL INPUTS ON RS-485 NETWORK
FEATURES
- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Four ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 8 digital inputs - EMC compliance – CE Mark
- Watch-Dog alarm - In compliance to EN-50022 DIN rail mounting
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT3000 SERIES
Input 0÷7 1500 Vac 50 Hz, 1 min. Material Self-extinguishing plastic
Data Transmission (asynchronous serial)
Inputs – RS485 2000 Vac 50 Hz, 1 min. Mounting DIN rail Baud rate 38.4 Kbps
Inputs – Supply 2000 Vac 50 Hz, 1 min. Dim. (mm) W x L x H : 120 x 100 x 17.5 Max. Distance 1.2 Km - 4000ft
RS-485 – Supply 2000 Vac 50 Hz, 1 min. Weight About 210 g. Sample time 5 ms max
TEMPERATURE & HUMIDITY
Operating Temperature -10°C .. +60°C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 %
GENERAL DESCRIPTION
The device DAT 3148/12 is able to acquire up to 12 digital inputs. The data are transmitted with MODBUS RTU/ASCII on RS-485 network.
To assure safe operation of the system, the device is equipped with two Watch-Dog timers.
The 2000 Vac galvanic isolation between inputs, power supply and RS-485 serial line cancels any ground-loop effect noise, allowing
the use of the device in worst ambient conditions.
FEATURES
- Field Bus data acquisition - Configurable from a remote terminal
- Master/Slave communication on RS-485 network - Four ways galvanic isolation 2000 Vac
- MODBUS RTU/ASCII protocol - High accuracy
- 12 digital inputs - EMC compliance – CE Mark
- Watch-Dog alarm - In compliance to EN-50022 DIN rail mounting
ss
nt
F
B
Application areas
www.datexel.it
DISTRIBUTED I/O MODULE 4 DIGITAL INPUTS + 8 PNP OUTPUTS ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3188/4 The device DAT 3188/4 is able to acquire up to 4 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network (is available the RS-232 interface model).
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. Also, the outputs are protected against over currents and over temperature.
The 2000 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels any ground-loop effect noise,
allowing the use of the device in worst ambient conditions.
ne
ss
nt
F
B
Application areas
56
The device DAT 3188/8 is able to acquire up to 8 digital inputs and to drive up to 8 transistor outputs. The data are transmitted with
MODBUS RTU/ASCII protocol on RS-485 network (is available the RS-232 interface model).
To assure safe operation of the system, the device is equipped with two Watch-Dog timers: in case of alarm, the outputs are forced
automatically on the safe configuration. Also, the outputs are protected against over currents and over temperature.
The 2000 Vac galvanic isolation between inputs, outputs, power supply and RS-485 serial line cancels any ground-loop effect noise,
allowing the use of the device in worst ambient conditions.
ss
nt
F
B
Application areas
www.datexel.it
UNIVERSAL REMOTE I/O MODULE ON RS-485 NETWORK
DAT 3011 GENERAL DESCRIPTION
The device DAT 3011 is able to acquire RTD or Tc sensors, mV, V or mA input signals connected to the universal analog input. Moreo-
ver a second V/mA analog input is available. The device is able to acquire up to 3 digital inputs and to drive one solid-state relay and
two SPST relays. Data values are transmitted with MODBUS RTU protocol on the RS-485 network.
By means of a 16 bit converter, the device guarantee a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 1500 Vac isolation on all ways (Power Supply / RS485 / Universal input / V-mA input / Digital inputs / Relay outputs) removes
eventual ground-loop effects, allowing the use of the device even in the heavy environmental conditions.
FEATURES
- Field-Bus remote data acquisition - 1 SSR Digital Output + 2 Relay Outputs
- RS-485 Modbus RTU (Slave) communication - Watch-Dog Alarm
- 1 Universal Analog Input - 1500 Vac galvanic isolation on all ways
- 1 V/mA Analog Input - High Accuracy
- 2 0-20mA Analog Outputs - EMC compliance – CE Mark
- 3 Digital Inputs - DIN rail suitable mounting (EN-50022)
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT3000 SERIES
Current consumption 30 mA (100mA max) Protocol Modbus RTU (Slave) Storage Temperature -40°C .. +85°C
Rever. Polarity protection 60 Vdc max Baud Rate up to 38400 bps Humidity (not condensed) 0 .. 90 %
www.datexel.it
REMOTE I/O MODULE 4 CHANNELS RTD INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3014 The DAT 3014 device is able to acquire up to 4 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect RTD , Potentiometers or Resistance signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.
ne
ss
nt
F
B
Application areas
The device DAT 3015I is able to acquire on input up to 4 analog current signals. Data values are transmitted with MODBUS RTU/ASCII
protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 20mA current signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.
ss
nt
F
B
Application areas
www.datexel.it
REMOTE I/O MODULE 4 CHANNELS +/-10V INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3015-V The device DAT 3015V is able to acquire on input up to 4 analog voltage signals. Data values are transmitted with MODBUS RTU/
ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 10V voltage signals.
By means of a 16 bit converter, the device guarantees high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.
ne
ss
nt
F
B
Application areas
DAT3000 SERIES
Inputs – RS485
2000 Vac 50 Hz, (1) Referred to input Span (difference between max. and min. values)
Power Supply– Input INPUT
1 min.
Power Supply– RS-485 Type input Min Max
TEMPERATURE & HUMIDITY Voltage
Operating Temperature -10°C .. +60°C
10 V -10 V +10 V
Storage Temperature -40°C .. +85°C
Input Calibration (1) ± 10 mV
Humidity (not condensed) 0 .. 90 %
Linearity (1) ± 0.1% f.s.
EMC (for industrial environments)
Input Impedance > 100 KΩ
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift (1)
Emission EN 61000-6-4 Full scale ± 0.005 % / °C
The DAT 3016 device is able to acquire up to 4 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol on
the RS-485 network (RS-232 interface is available). It is possible to connect Thermocouples or up to +/- 1V voltage signals.
The Cold Junction compensation for thermocouples is performed internally. By means of a 16 bit converter, the device guarantees high
accuracy and a stable measure versus time and temperature. To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the device
even in the heavy environmental conditions. The DAT 3016 is in compliance with the Directive 2004/108/EC on the electromagnetic
compatibility. The device is housed in a rough self-extinguishing plastic container which, thanks to its thin profile of 17.5mm only, allows
a high density mounting on EN-50022 standard DIN rail.
FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 4 channel input - High Accuracy
- Up to +/- 1V and TC configurable input - EMC compliance – CE mark
Type J,K,R,S,B,E,T,N - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
ne
ss
nt
F
B
Application areas
60
REMOTE I/O MODULE 8 CHANNELS ±10V INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3017-V
The devices DAT 3017V is able to acquire on input up to 8 analog voltage signals. Data values are transmitted with MODBUS RTU/
ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to connect up to ± 10V voltage signals.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.
ss
nt
F
B
Application areas
www.datexel.it
REMOTE I/O MODULE 8 CHANNELS mV / TC INPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3018 The device DAT 3018 is able to acquire up to 8 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect Thermocouples or up to +/- 1V voltage signals. The Cold Junction compensation for thermocouples is
performed internally. By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and
temperature. To ensure the plant safety, two Watch-Dog timer alarms are provided. The 2000 Vac isolation between input, power
supply and serial line RS-485 (or RS-232) removes eventual ground-loop effects, allowing the use of the device even in the heavy
environmental conditions.
FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 8 channel input - High Accuracy
- Up to +/- 1V and TC configurable input ± 1V and - EMC compliance – CE mark
TC Type J,K, R,S,B,E,T,N - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT3000 SERIES
Inputs – RS485
2000 Vac 50 Hz, 250 mV -250 mV +250 mV mV, TC >/=1 MΩ
Power Supply– Input
1 min. 1000 mV -1000 mV +1000 mV Thermal drift (1)
Power Supply– RS-485
Thermocouple Full scale ± 0.005 % / °C
TEMPERATURE & HUMIDITY
J -210 °C +1200 °C Thermal drift CJC
Operating Temperature -10°C .. +60°C
K -210 °C +1372 °C Full scale ± 0.02 % / °C
Storage Temperature -40°C .. +85°C
Humidity (not condensed) 0 .. 90 % R -50 °C +1767 °C Lead wire res. influence (1)
S -50 °C +1767 °C mV, TC < 0.8 uV/Ohm
EMC (for industrial environments)
DIRECTIVE 2004 / 108 / EC B +400 °C +1825 °C Sample time 0.5 ÷ 2 sec.
Immunity EN 61000-6-2 E -210 °C +1000 °C Data Transmission (asynchronous serial)
Emission EN 61000-6-4 T -210 °C +400 °C Baud rate 38.4 Kbps
HOUSING N -210 °C +1300 °C Max. Distance 1.2 Km - 4000ft
Material Self-extinguishing plastic Input Calibration (1) Warm-up time 3 min
Mounting DIN rail
61
The higher of ± 0.05% or 5 uV (1) (1) Referred to input Span (difference between max. and min. values)
Dim. (mm) W x L x H : 120 x 100 x 17.5
Weight About 150 g.
The device DAT 3019 is able to acquire up to 8 analog input signals. Data values are transmitted with MODBUS RTU/ASCII protocol
on the RS-485 network (RS-232 interface is available).
It is possible to connect 2-wires RTD sensors or up to 2 KΩ resistance signals.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the
device even in the heavy environmental conditions.
FEATURES
- Field-Bus remote data acquisition - Watch-Dog Alarm
- RS-485 Master/Slave communication type - Configurable from a remote terminal
- MODBUS RTU/ASCII protocol - 2000 Vac 3-way Galvanic Isolation
- 8 channel 2 wires input - High Accuracy
- Pt100, Pt1K, Ni100, Ni1K and resistance up to 2 KΩ - EMC compliance – CE mark
configurable input - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
ne
ss
nt
F
B
Application areas
Current consumption
typ. 35 mA @ 24 Mounting DIN rail Auxiliary Voltage > 12V @ 20mA (2 channels)
Vdc 60 mA max
Dim. (mm) W x L x H : 120 x 100 x 17.5 Rise time
Rever. Polarity protection 60 Vdc max
DAT3000 SERIES
The device DAT 3024 generates up to 4 output analog signals from digital commands. Data values are transmitted with MODBUS
RTU/ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to generate voltage signals up to 10V and current signals up to 20mA, both active or passive loops.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line removes eventual ground-loop effects, allowing the use of the
device even in the heavy environmental conditions.
ss
nt
F
B
Application areas
Current consumption
typ. 35 mA @ 24 Mounting DIN rail Auxiliary Voltage > 12V @ 20mA (4 channels)
Vdc 100 mA max
Dim. (mm) W x L x H : 120 x 100 x 17.5 Rise time
Rever. Polarity protection 60 Vdc max
Weight About 150 g. Analog output Slew-rate
ISOLATIONS (independent programmation for each channel)
Output – RS485 OUTPUT
2000 Vac 50 Hz, Output type Min Max Voltage V/s Current mA/s
Power Supply– Output
1 min. Voltage 0.125 0.250
Power Supply– RS-485 0.250 0.500
V 0V +10 V
TEMPERATURE & HUMIDITY Current 0.500 1.000
Operating Temperature -10°C .. +60°C mA 0 mA +20 mA 1.000 2.000
Storage Temperature -40°C .. +85°C Output calibration 2.000 4.000
Humidity (not condensed) 0 .. 90 % Voltage ±10 mV 4.000 8.000
EMC (for industrial environments) Current ±20 mA Immediate Immediate
www.datexel.it
REMOTE I/O MODULE 8 CHANNELS VOLTAGE OUTPUT ON RS-485 NETWORK
GENERAL DESCRIPTION
DAT 3028 The device DAT 3028 generates up to 8 output analog signals from digital commands. Data values are transmitted with MODBUS
RTU/ASCII protocol on the RS-485 network (RS-232 interface is available).
It is possible to generate voltage signals up to 10V.
By means of a 16 bit converter, the device guarantees a high accuracy and a stable measure versus time and temperature.
To ensure the plant safety, two Watch-Dog timer alarms are provided.
The 2000 Vac isolation between input, power supply and serial line RS-485 (o RS-232) removes eventual ground-loop effects, al-
lowing the use of the device even in the heavy environmental conditions.r
FEATURES
Field-Bus remote data acquisition - Configurable from a remote terminal
- RS-485 Master/Slave communication type - 2000 Vac 3-way Galvanic Isolation
- MODBUS RTU/ASCII protocol - High Accuracy
- 8 channel 0-10 V output - EMC compliance – CE mark
- Watch-Dog Alarm - DIN rail suitable mounting - EN-50022 compliance
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT3000 SERIES
ISOLATIONS
0.125
Output – RS485
2000 Vac 50 Hz, 0.250
Power Supply– Output
1 min. 0.500
Power Supply– RS-485
OUTPUT 1.000
TEMPERATURE & HUMIDITY Output type Min Max 2.000
Operating Temperature -10°C .. +60°C
Voltage 4.000
Storage Temperature -40°C .. +85°C
V 0V +10 V Immediate
Humidity (not condensed) 0 .. 90 %
Output calibration ±10 mV
EMC (for industrial environments)
Load Resistance > 5 KΩ Data Transmission (asynchronous serial)
DIRECTIVE 2004 / 108 / EC
Immunity EN 61000-6-2 Thermal drift Baud rate 115.2 Kbps
Emission EN 61000-6-4 Full scale 100 ppm /°C Max. Distance 1.2 Km - 4000ft
63
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
The DAT9000 units read and write the parameters of the field
devices to which they are connected, processing functions of the
logical/mathematical type, including complex ones, such as
for example: alarms, linearization, means, square roots, etc..
INDEX
66 • DAT 9000
Intelligent unit with Ethernet interface
DAT 9000-DL
Intelligent unit with Data-logger and Ethernet interface
67 • DAT 9000IO
Intelligent unit with Ethernet Interface and digital I/O
68 • DAT 9000-DL-IO
Intelligent unit with Data-logger, Ethernet interface and digital I/O
69 • DAT 9011
Intelligent unit with Ethernet Interface and digital and analogue I/O
70 • DAT 9011-DL
Intelligent unit with Data-Logger function, Ethernet Interface and digital and analogue I/O
DAT9000 SERIES
08
DAT9000 Intelligent
SERIES units
INTELLIGENT UNIT WITH ETHERNET INTERFACE
GENERAL DESCRIPTION
DAT 9000 The device DAT9000 is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for
the system working. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real
time, the internal registers value.
Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to:
- Programming of the Control Logic
- Monitor, request of data, programming in real time the Intelligent Unit
- Direct programming and request of data from the Slave devices connected on the RS-485 Master.
ne
ss
nt
F
B
Application areas
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals RS-485 Interface
80 mA max EMC (for industrial environments) Baud-rate up to 38.4 Kbps
ISOLATIONS DIRECTIVE 2004 / 108 / EC Max. distance (1) 1.2 Km @ 38.4 Kbps
Power supply / Ethernet Immunity EN 61000-6-2 Number of modules
1500 Vac, 50 Hz, up to 32
Power supply / RS485 Emission EN 61000-6-4 in multipoint
1 min.
Internal termination
Ethernet / RS485 HOUSING 120 Ohm (optional)
resistance
TEMPERATURE & HUMIDITY Material Self-extinguishing plastic
(1) = The maximum distance depends of: number of devices con-
Operative temperature -20°C ÷ +60°C Mounting DIN rail nected, type of cabling, noises, etc...
Storage temperature -40°C ÷ +85°C Dim. (mm) W x L x H : 120 x 100 x 22.5
Relative humidity (not cond.) 0 ÷ 90 % Weight About 160 g.
The device DAT9000 DL is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing
- the logical and mathematical functions necessary for
the system working, managing up to 8 task of recording memorized on files saved on the microSD card. By means of the Ethernet
interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal registers value. By Ethernet it
is possible to get access to the files saved on the microSD card when the Data-Logger function is active.
Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to: Programming of the Control
Logic; Monitor, request of data, programming in real time the Intelligent Unit; Direct programming and request of data from the Slave
devices connected on the RS-485 Master.
ss
nt
F
B
Application areas
CURRENT CONSUMPTION RS-232D RJ-45 (on front side) Protocol Modbus TCP
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals RS-485 Interface
Baud-rate up to 38.4 Kbps
100 mA max EMC (for industrial environments)
Max. distance (1) 1.2 Km @ 38.4 Kbps
ISOLATIONS DIRECTIVE 2004 / 108 / EC Number of modules
up to 32
Power supply / Ethernet Immunity EN 61000-6-2 in multipoint
1500 Vac, 50 Hz, Internal termination
Power supply / RS485 Emission EN 61000-6-4 120 Ohm (optional)
1 min. resistance
Ethernet / RS485 HOUSING Compatible SD card
TEMPERATURE & HUMIDITY Material Self-extinguishing plastic Type microSD
Operative temperature -20°C ÷ +60°C Mounting DIN rail Memory size Up to 8 GB
Storage temperature -40°C ÷ +85°C Dim. (mm) W x L x H : 120 x 100 x 22.5 Format FAT16 or FAT32
Relative humidity (not cond.) 0 ÷ 90 % Weight About 160 g. (1) = The maximum distance depends of: number of devices con-
nected, type of cabling, noises, etc...
www.datexel.it
INTELLIGENT UNIT WITH ETHERNET INTERFACE AND DIGITAL I/O
DAT 9000IO GENERAL DESCRIPTION
The device DAT9000IO is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working. Moreover, the device is equipped with 4 digital inputs channels and 2 relay outputs. On digital inputs are available
32-bit counters and the measure of the frequency up to 300Hz.
By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to:
- Programming of the Control Logic
- Monitor, request of data, programming in real time the Intelligent Unit.
- Direct programming and request of data from the Slave devices connected on the RS-485 Master.
ne
ss
nt
F
B
Application areas
DAT9000 SERIES
18 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
CURRENT CONSUMPTION RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals
100 mA max Relative humidity (not cond.) 0 .. 90 %
ISOLATIONS
www.datexel.it
INTELLIGENT UNIT WITH DATA-LOGGER, ETHERNET INTERFACE AND DIGITAL I/O
DAT 9000-DL-IO GENERAL DESCRIPTION
The device DAT9000-DL-IO is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-
485 Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for
the system working, managing up to 8 task of recording memorized on files saved on the microSD card. The device is equipped with
4 digital inputs channels and 2 relay outputs. For the digital inputs, are also available 32 bit counters and the measure of the frequency
up to 300 Hz. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the
internal registers value. By Ethernet it is possible to get access to the files saved on the microSD card when the Data-Logger function
is active. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to: Programming of
the Control Logic; Monitor, request of data, programming in real time the Intelligent Unit; Direct programming and request of data
from the Slave devices connected on the RS-485 Master.
ne
ss
nt
F
B
Application areas
18 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
CURRENT CONSUMPTION RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
45 mA typ.@24Vdc (standby) RS-485 Master / Slave Remov. screw terminals
100 mA max ISOLATIONS Relative humidity (not cond.) 0 .. 90 %
Channels 4 Channels 2
Max. distance (1) 1.2 Km @ 38.4 Kbps Dielectric strength between coil and contacts
www.datexel.it
INTELLIGENT UNIT WITH ETHERNET INTERFACE AND DIGITAL AND ANALOGUE I/O
DAT 9011 GENERAL DESCRIPTION
The device DAT9011 is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working. The device is equipped with one universal analogue input channel, one channel for Volt and mA input, two digital
inputs and 2 relay outputs. On input an Auxiliary source is available to supply passive sensors on the field.
By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to program the
Control Logic, to monitor, to request data and programming in real time the Intelligent Unit, to program directly the Slave devices
connected on the RS-485 Master and to request data from them.
FEATURES
- N°1 serial interface RS-485 Modbus RTU Master - Remotely programmable
- N°1 serial interface RS-485/232 Modbus RTU Slave - Connection by removable screw-terminals
- Interface Ethernet 10Base-T, Modbus TCP - LED signallingmfor
u s tri es
Link/ActergEthernet, serial RX-TX,trepower
In d r d a c hi En y d busine er a t m e
- N°1 universal analogue input + N°1 current and voltage supply oa oo at
ne
ss
nt
F
B
analogue input - LED signalling for digital inputs and digital outputs state
- N°2 digital Inputs - Galvanic Isolation on all the ways
- Auxiliary supply to power sensors on field - EMC compliance – CE mark
- N°2 passive 4-20 mA analogue outputs - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- N°2 SPDT Relay Outputs - Suitable for DIN rail mounting in compliance with
- Functional Block programming software EN-50022 standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT9000 SERIES
POWER SUPPLY CONNECTIONS TEMPERATURE & HUMIDITY
Power supply Voltage 9 ÷ 30 Vdc Ethernet RJ-45 (on terminals side) Operative temperature -20°C .. +60°C
Current consumption @ 24 Vdc 60 mA (170 mA max) RS-232D RJ-45 (on front side)
Storage temperature -40°C .. +85°C
Current consumption @ 10 Vdc 147 mA (300 mA max) RS-485
Master / Slave Screw terminals pitch
Reverse polarity protection 60 Vdc max 5.08mm Relative humidity (not cond.) 0 .. 90 %
Outputs Relay
EMC (for industrial environments) Supply/Inputs/ HOUSING
Screw terminals pitch
Analogue Material Self-extinguishing plastic
DIRECTIVE 2004 / 108 / EC 3.81mm
outputs
Mounting DIN rail
Immunity EN 61000-6-2 ISOLATIONS
Dimensions (mm) W x L x H : 120 x 100 x 22.5
Isolations voltage 1500 Vac
Emission EN 61000-6-4 (50 Hz, 1 min.) (on all the ways) Weight About 190 g. 69
ANALOGUE INPUTS Sensor excitation current
Thermal RTD, Res, Pot ~ 400 uA
Type Range Calibration Linearity
Drift CJC comp. ± 1 °C
100 mV -100 ÷ +100 mV ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Sample time 1 sec.
10 V -10 ÷ +10 V ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Warm-up time (TC,RTD) 3 min.
20 mA -20 ÷ +20 mA ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C DIGITAL INPUTS
Pt100 -200 ÷ +850 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Channels 2
Pt1K -200 ÷ +200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C OFF state : 0÷3 V
Input voltage (bipolar)
ON state : 10÷30 V
Ni100 -60 ÷ +180 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Input impedance 4.7 KOhm
Ni1K -60 ÷ +150 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
N°2 Digital counter 32 bit (up to 300 Hz)
Res 0 ÷ 2000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
ANALOGUE OUTPUTS (2 CHANNELS)
Pot 20 ÷ 50000 Ohm ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
Type Range Calibration Linearity Thermal Drift
Tc J -210 ÷ +1200 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
20 mA 4 ÷ +20 mA ±0.05 % f.s. ±0.05 % f.s. 100 ppm/°C
Tc K -210 ÷ +1370 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C
DIGITAL OUTPUTS
Tc R -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C
N.2 SPDT Relays
Tc S -50 ÷ +1760 °C ±0.1 % f.s. ±0.2 % f.s. 100 ppm/°C 2 A @ 250 Vac (per contact)
Switching Power (resistive load)
Tc B +400 ÷ +1825 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C 2 A @ 30 Vdc (per contact)
Tc E -210 ÷ +1000 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Minimum load 5Vdc , 10mA
Tc T -210 ÷ +400 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Max. voltage 250Vac (50 / 60 Hz) ,110Vdc
Tc N -210 ÷ +1300 °C ±0.05 % f.s. ±0.1 % f.s. 100 ppm/°C Dielectric strength between contacts 1000 Vac, 50 Hz, 1 min.
Tc, mV >= 10 MΩ Dielectric strength between 4000 Vac, 50 Hz, 1 min.
coil and contacts
Input impedance Volt >= 1 MΩ
Serial Ports RS-485 (Master & Slave)
Current ~ 22 Ω
Protocol Modbus RTU
Auxiliary voltage >14 V @ 20 mA
Baud Rate up to 115.2 Kbps
Line resistance influence Max. recommended distance (1) 1.2 Km @ 38.4 Kbps
RTD 3 wires 0.05 %/Ω (50 Ω max) Number of modules in multipoint up to 32
mV, Tc < 0.8 uV/Ohm Internal termination resistance 120 Ohm (optional)
(1) = The maximum distance depends of: number of devices connected, type of cabling, noises, etc...
www.datexel.it
INTELLIGENT UNIT WITH DATA-LOGGER FUNCTION, ETHERNET INTERFACE AND DIGITAL AND ANALOGUE I/O
DAT 9011-DL GENERAL DESCRIPTION
The device DAT9011-DL is an Intelligent unit able to control a network of slave Modbus RTU devices connected on serial line RS-485
Master executing the reading and writing of the field values and performing the logical and mathematical functions necessary for the
system working and managing up to 8 tasks of storage data. The data are saved on microSD card; it is possible to get access to the
saved files by means of the Ethernet connection. The device is equipped with one universal analogue input channel, one channel for
Volt and mA input, two digital inputs and 2 relay outputs. On input an Auxiliary source is available to supply passive sensors on the
field. By means of the Ethernet interface or the RS-485 “SLAVE” or RS-232 ports it is possible to read and write, in real time, the internal
registers value. Moreover, by means of the Ethernet interface, or by the RS-485 “SLAVE” or RS-232 ports it is possible to program the
Control Logic,to monitor, to request data and programming in real time the Intelligent Unit,to program directly the Slave devices
connected on the RS-485 Master and to request data from them.
ne
ss
nt
F
B
- N°1 universal analogue input + N°1 current and voltage - LED signalling for digital inputs and digital outputs state
analogue input - Galvanic Isolation on all the ways
- N°2 digital Inputs - EMC compliance – CE mark
- Auxiliary supply to power sensors on field - Ethernet IEEE 802.3 EIA RS485 and RS232 compliance
- N°2 passive 4-20 mA analogue outputs - Suitable for DIN rail mounting in compliance with EN-50022
- N°2 SPDT Relay Outputs standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DAT9000 SERIES
Compatible SD card
Sensor excitation current
Type microSD
RTD, Res, Pot ~ 400 uA
Memory size Up to 8 GB
CJC comp. ± 1 °C
Format FAT16 or FAT32
Sample time 1 sec.
(1) = The maximum distance depends of: number of devices connected, type of
Warm-up time (TC,RTD) 3 min. cabling, noises, etc...
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
DAT9000 SERIES
“DAT9000 SERIES”
www.datexel.it
intelligent units 71
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
By few and simple instructions the PLC is able to acquire more analog
signals on a single digital input. Moreover each module has an Enable
signal, that allows the controller to multiplexing more devices to one
data line and one clock signal.
INDEX
74 • DAT 6011
A/D interface for PLC 2 input channels for mV or Tc
DAT 6012
A/D interface for PLC 2 input channels for RTD, Res
75 • DAT 6013
A/D interface for PLC 2 input channels for V, mA
DAT 6021
A/D interface for PLC 4 input channels for mV, Tc
76 • DAT 6023-I
A/D interface for PLC 4 input channels for +/- 20 mA
DAT 6023-V
A/D interface for PLC 4 input channels for +/- 10V
DAT6000 SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
09
FEATURES
- Acquisition of analogue signals on PLC’s digital I/O - Configurable by DIP-switch
- Analogue input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for voltage up to ± 1V or Tc type with EN-50022 and EN-50035
J,K, R,S,B,E,T,N
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC.
The devices of this series amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high reso-
lution. The digital signal can be connected to any input of the PLC.
FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance with
- Configurable input for Pt100, Pt1000, Ni100, Ni1000, EN-50022 and EN-50035
Resistance and Potentiometers up to 2 Kohm
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
www.datexel.it
A/D INTERFACE FOR PLC 2 INPUT CHANNELS FOR V, mA
GENERAL DESCRIPTION
DAT 6013 The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC. The devices of this series
amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.
FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 2 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 10 V and ± 20 mA with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC. The devices of this series
amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.
FEATURES
- Acquisition of analogue signals on PLC’s digital I/O - Galvanic isolation at 2000 Vac on three ways
- Analogue input to any PLC or micro PLC - EMC compliant – CE mark
- Up to 16-bit resolution with Full Scale high accuracy - Suitable for DIN rail mounting in compliance with
- 4 input channels EN-50022 and EN-50035
- Configurable input for ± 1 V or Tc type J,K, R,S,B,E,T,N
- Configurable by DIP-switch
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ss
nt
F
ne
B
Application areas
FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 4 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 20 mA with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
The devices of the DAT6000 series are an evolution in the techniques of connection of analog signals to PLC.
The devices of this series amplify, linearise, isolate, filter and convert the analog signals coming from various sensors in a high resolution.
The digital signal can be connected to any input of the PLC.
FEATURES
- Acquisition of analog signals on PLC’s digital I/O - Configurable by DIP-switch
- Analog input to any PLC or micro PLC - Galvanic isolation at 2000 Vac on three ways
- Up to 16-bit resolution with Full Scale high accuracy - EMC compliant – CE mark
- 4 input channels - Suitable for DIN rail mounting in compliance
- Configurable input for ± 10 V with EN-50022 and EN-50035
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
ss
nt
F
B
Application areas
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
INDEX
80 • DAT 1010
Two wire transmitter for RTD programmable by PC
81 • DAT 1015
Two wire universal transmitter programmable by PC
82 • DAT 1061
Isolated two wire Transmitter for RTD programmable by PC
83 • DAT 1066
Isolated two wire universal transmitter programmable by PC
DAT1000 SERIES
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
10
ne
ss
nt
F
B
Application areas
INPUT INPUT
Input type Min Max Span min Line resistance influence(1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
80
Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100mV +700mV 2 mV Burn-out values
Potentiometer Max. value output about 21.6 mA
0Ω 200 Ω 10% Min. value output about 3.5 mA
Nominal value 200 Ω 500 Ω 10% Response time (10÷90% of f.s.) about 400 ms
0.5 KΩ 2 KΩ 10% (1) referred to input Span (difference between max. and min. values)
www.datexel.it
TWO WIRE UNIVERSAL TRANSMITTER PROGRAMMABLE BY PC
DAT 1015 GENERAL DESCRIPTION
The transmitter DAT 1015 is able to execute many functions such as: measure and linearisation of the temperature characteristic of
RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer connected
on its input.
Moreover the DAT 1015 is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
ne
ss
nt
F
B
Application areas
DAT1000 SERIES
Reverse polarity protection 60 Vdc max
Humidity (not condensed) 0 .. 90 %
INPUT INPUT
Input type Min Max Span min Input impedance
TC CJC int./ext. TC, mV >= 10 MΩ
Linearity (1) 81
J -200°C 1200°C 2 mV
TC ± 0.2 % f.s.
K -200°C 1370°C 2 mV
RTD ± 0.1 % f.s
S -50°C 1760°C 2 mV
Line resistance influence(1)
R -50°C 1760°C 2 mV
TC, mV <=0.8 uV/Ohm
B 400°C 1820°C 2 mV RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
E -200°C 1000°C 2 mV RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
T -200°C 400°C 2 mV RTD excitation current
N -200°C 1300°C 2 mV Typical 0.350 mA
RTD 2,3,4 wires CJC comp. ± 0.5°C
www.datexel.it
ISOLATED TWO WIRE TRANSMITTER FOR RTD PROGRAMMABLE BY PC
DAT 1061 GENERAL DESCRIPTION
The isolated transmitter DAT 1061 is able to execute many functions such as : measure and linearisation of the temperature characte-
ristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer
connected on its input. The measured values are converted in a 4÷20 mA current signal. The device guarantees high accuracy and
performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, mV, Resistance and - On-field reconfigurable
Potentiometer - Programming of the unit measure as °C or °F
- Galvanic isolation at 1500 Vac - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“DIN RAIL” Option)
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
ISOLATION VOLTAGE
Input- output/Power supply 1500 Vac, 50 Hz,1 min. Humidity (not condensed) 0 .. 90 %
Input Input
Input type Min Max Span min Line resistance influence(1)
RTD 2,3,4 wires mV <=0.8 uV/Ohm
82
Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
Thermal drift (1)
Voltage Full scale ± 0.01 % / °C
mV -100mV +700mV 2 mV Burn-out values
Potentiometer Max. value output about 20.5 mA
0Ω 200 Ω 10% Min. value output about 3.8 mA
Nominal value 200 Ω 500 Ω 10% Value max. fault about 21.6 mA
www.datexel.it
ISOLATED TWO WIRE UNIVERSAL TRANSMITTER PROGRAMMABLE BY PC
DAT 1066 GENERAL DESCRIPTION
The isolated transmitter DAT 1066 is able to execute many functions such as : measure and linearisation of the temperature characte-
ristic of RTDs sensors, conversion of a linear resistance variation, conversion of a voltage signal even coming from a potentiometer
connected on its input.
Moreover the DAT 1066 is able to measure and linearise the standard thermocouples with internal cold junction compensation.
The measured values are converted in a 4÷20 mA current signal.
The device guarantees high accuracy and performances stability both in time and in temperature.
FEATURES
- Configurable input for RTD, TC, mV, Resistance and - On-field reconfigurable
Potentiometer - Programming of the unit measure as °C or °F
- Galvanic isolation at 1500 Vac - EMC compliant – CE mark
- 4 ÷ 20 mA configurable output on current loop - Suitable for DIN B in-head mounting
- Configurable by Personal Computer - Option for DIN rail mounting in compliance with
- High accuracy EN-50022 (“KITDIN RAIL” Option)
ne
ss
nt
F
B
Application areas
DAT1000 SERIES
Input- output/Power supply 1500 Vac, 50 Hz,1 min. Humidity (not condensed) 0 .. 90 %
Input Input
Input type Min Max Span min Input calibration(1)
TC CJC int./ext. RTD the higher of ±0.1 % f.s. or ±0.2 °C
Res. Low the higher of ±0.1 % f.s. or ±0.15 Ω 83
J -200°C 1200°C 2 mV
Res. High the higher of ±0.2 % f.s. or ±1 Ω
K -200°C 1370°C 2 mV
mV, TC the higher of ±0.1 % f.s. or ±10 uV
S -50°C 1760°C 2 mV
Input impedance Application areas
R -50°C 1760°C 2 mV
TC, mV >= 10 MΩ
B 400°C 1820°C 2 mV Linearity (1)
E -200°C 1000°C 2 mV TC ± 0.2 % f.s.
T -200°C 400°C 2 mV RTD ± 0.1 % f.s
N -200°C 1300°C 2 mV Line resistance influence(1)
RTD 2,3,4 wires TC, mV <=0.8 uV/Ohm
Pt100 -200°C 850°C 50°C RTD 3 wires 0.05 %/Ω (50 Ω balanced max.)
RTD 4 wires 0.005 %/Ω (100 Ω balanced max.)
Pt1000 -200°C 200°C 50°C
RTD excitation current
Ni100 -60°C 180°C 50°C
Typical 0.350 mA
Ni1000 -60°C 150°C 50°C
CJC comp. ± 0.5°C
Voltage Thermal drift (1)
mV -100 mV +700 mV 2 mV Full scale ± 0.01 % / °C
0Ω 200 Ω 10% CJC ± 0.01 % / °C
Potentiometer
200 Ω 500 Ω 10% Burn-out values
(Nominal value)
0.5 KΩ 50 KΩ 10% Max. value output about 20.5 mA
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
INDEX
86 • DAT 9550
Remote Graphic Display on RS-485 with Modbus RTU protocol
• DAT 8050
Loop powered 4 digit LED programmable digital indicator
87 • DAT 701
3.5 digit LED digital indicator
• DAT 702
3.5 digit LCD digital indicator
88 • DAT 733
3.5 digit LCD digital indicator
• DAT 734
3.5 digit LCD or LED display digital thermometer for Pt100
89 • DAT 735
3.5 digit LCD or LED display digital thermometer for Thermocouple
DIGITAL INDICATORS
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
11
DAT9550
DAT8050 Digital indicators for
DAT700 SERIES panel mounting
REMOTE GRAPHIC DISPLAY ON RS-485 WITH MODBUS RTU PROTOCOL
GENERAL DESCRIPTION
DAT 9550 The device DAT 9550 is a graphic display designed for panel mounting and communicating with Modbus RTU protocol on RS-485
and RS-232 serial Slave port. Moreover on the device there is a RS-485 Master port by means of which it is possible to communi-
cate with the eventual Modbus Slave devices connected. It can be used as Slave peripheral for the visualization of the data coming
from the Intelligent Units of the DAT9000 series or from a PC, PLC or panel operator.
ne
ss
nt
F
B
Application areas
86
LOOP POWERED 4 DIGIT LED PROGRAMMABLE DIGITAL INDICATOR
GENERAL DESCRIPTION
DAT 8050
The digital panel indicator DAT 8050 accept on the input a 4 - 20 mA current loop signal.
The input current signal is used to supply the device introducing a 5 Vdc voltage drop-out on the current loop, so is not required
any external supply source. The user can program the visualisation of the measure in the range from -1999 up to 9999 points in
order to set the values of the physical or electrical parameter transmitted on the current loop in the desired format.
The programming of the visualization is made by the buttons “SET” and “ENTER” located on the front side of the instrument.
FEATURES
- 4÷20 mA loop powered - Visualization configurable on the front side
- Voltage Drop-out < 5V - Connections on removable screw terminals
- High accuracy and linearity - Compact case size (DIN 48 x 96 mm)
- 0.52” LED display - EMC compliance - CE mark
ss
nt
F
B
Application areas
www.datexel.it
3.5 DIGIT LED DIGITAL INDICATOR
ne
ss
nt
F
B
Application areas
DIGITAL INDICATORS
Input impedance Out of range visualisation High = 1; Low = -1
Humidity (not condensing) 0 .. 90 %
basic scale: 10 MΩ Type of visualization 3.5 digit standard LED display (version S)
EMC (for industrial environments) Voltage Display LED 3.5 digit high efficiency LED display (version H)
attenuated scale: 1 MΩ
DIRECTIVE 2004/108/EC Digit height 0.52 ‘‘
Current From 1 Ω up to 1KΩ
Immunity EN 61000-6-2
Maximum input signal 2.5 full scale
Emission EN 61000-6-4 CHARACTERISTICS AND PERFORMANCES
± 2 V referred to the
Common mode voltage Reading accuracy ± 0.1 % of f.s.
HOUSING power supply ground
Common mode Thermal drift 0.005 % of f.s./°C
Material Self-extinguishing plastic rejection ratio 86 dB
Reading rate 3 read/second
Mounting Panel mounting Normal mode
rejection ratio 50 dB @ 50 Hz Power supply voltage 5 Vdc ± 5 %
Dim. (mm) W x H x T : 72 x 36 x 15
Decimal point From front side, on Version S: 90 mA
Weight about 50 g. programming Current consumption
three decades Version H: 180 mA
The DAT 702 is a 3.5 digit LCD digital indicator with high accuracy and reliability able to measure the normalised current or voltage
signal applied to its input .
In function of the parameters requested in phase of order, the following versions of the device are available:
- DAT 702 V - A: measure of voltage signal with amplitude from ± 200 mV up to ± 20 V ;
- DAT 702 V - B: measure of voltage signal with amplitude from ± 2 V up to ± 200 V;
- DAT 702 I - A: measure of current signal with amplitude from ± 200 µA up to ± 2 mA;
- DAT 702 I - B: measure of current signal with amplitude from ± 2 mA up to ± 200 mA.
ss
nt
F
B
Application areas
www.datexel.it
3.5 DIGIT LCD DIGITAL INDICATOR
GENERAL DESCRIPTION
DAT 733 The DAT 733 is a current loop, 3.5 digit LCD digital indicator with high accuracy and reliability.
By dip-switches and potentiometers, it is possible to set the visualisation of the input measure in engineering units in a range
included between 100 and 2000 points, to set the zero point between -1999 and 1999 and the position of the decimal point.
FEATURES
- 4 ÷ 20 mA current loop self-powered - EMC compliant – CE mark
- Visualisation configurable in engineering units - DIN 36 x 72 mm housing
- High accuracy and linearity - Mounting on panel in according to DIN 43700
- Measure freezing by command standard
ne
ss
nt
F
B
Application areas
88
3.5 DIGIT LCD OR LED DISPLAY DIGITAL THERMOMETER FOR PT100
GENERAL DESCRIPTION
DAT 734
The DAT 734 is a 3.5 digit LCD or LED display, digital thermometer for Pt100 2 or 3 wires sensor with high accuracy and reliability.
The range of measure must be chosen in phase of order between the two options : -50 ÷ 200 °C or 0 ÷ 600 °C.
ss
nt
F
B
Application areas
www.datexel.it
3.5 DIGIT LCD OR LED DISPLAY DIGITAL THERMOMETER FOR THERMOCOUPLE
FEATURES
- Input for Thermocouple sensors type E, K, J, N, S and T - Low current consumption
- Visualisation on LCD or LED display - EMC compliant – CE mark
- High accuracy - DIN 36 x 72 mm housing
- Measure freezing by command - Mounting on panel in according to DIN-43700
standard
u s tri es r d m a c hi E n er g y d busine er treat me
In d oa oo at
ne
ss
nt
F
B
Application areas
DIGITAL INDICATORS
DIRECTIVE 2004/108/EC Thermocouple type K 0 ÷ 1200 °C Digit height 0.52‘‘
Immunity EN 61000-6-2
Thermocouple type J 0 ÷ 600 °C
Emission EN 61000-6-4 CHARACTERISTICS AND PERFORMANCES
Thermocouple type N 0 ÷ 1200 °C Reading accuracy ±0.25 % of f.s.
HOUSING
Thermocouple type S 0 ÷ 1600 °C Cold Junction Compensation ±0.5 °C
Material Self-extinguishing plastic
Thermocouple type T 0 ÷ 300 °C Thermal drift 0.02 % of f.s./°C
Mounting Panel mounting
Response time 800 ms
Dim. (mm) W x H x T : 72 x 36 x 39 High: 1 (On the left side);
Out of scale visualisation Power supply voltage 5 Vdc ± 5 %
Weight About 100 g. Low -1 (On the left side)
Version D: 180 mA (high efficiency),
Current consumption
90 mA (standard)
89
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
Accessories / Software:
All of the DATEXEL devices configurable by PC need,
for their configuraton, special software combined with communication
interface between device and PC.
The software available to configure the DATEXEL devices are the following:
INDEX
92 • MDR 20-12 / MDR 40-12 / MDR 60-12 / MDR 100-12
Power Supply DIN rail
94 • SOFTWARE
PRODAT USB
Configuration interface for USB port
PROSOFT
Configuration software for SMART series devices
DATESOFT
Configuration software for SLIM series devices
Dev 9K
Configuration software for intelligent units DAT9000 series
ACCESSORIES AND SOFTWARE
in d
u stri ale
rd
o macchi e nergia a li
m e n tari
ta
m e n to a c
qu
bo
na
t
tr a
e
12
MDR-60-12
MDR-20-12
POWER SUPPLY
MDR-40-12
92
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
Other devices are available on request. For more technical information log on to the website: www.meanwell.com
www.datexel.it
DIN RAIL POWER SUPPLY
MDR-60-24
MDR-20-24
85....264 VAC 85....264 VAC
POWER SUPPLY
INPUT INPUT
120....370 VDC 120....370 VDC
OUTPUT 24 VDC @ 2.5 A OUTPUT 24 VDC @ 1 A
MDR-100-24
MDR-40-24
93
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
Other devices are available on request. For more technical information log on to the website: www.meanwell.com
www.datexel.it
CONFIGURATION INTERFACE FOR USB PORT
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
ACCESSORIES / SOFTWARE
GENERAL DESCRIPTION
PROSOFT
PROSOFT is a software developed by Datexel srl, running under the operative system
Windows® and designed to program and visualize the measure of the converters and
transmitters programmable by PC.
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
94
GENERAL DESCRIPTION
DATESOFT
DATESOFT is a software developed by Datexel srl, running under the operative system
Windows® designed to program and visualize the measure of the converters program-
mable by PC.
SYSTEM REQUIREMENTS
Operative System........................Windows® 98 / 2000 / NT / ME / XP / Vista / Win 7
Available Hard Disk space......................2 MB
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
GENERAL DESCRIPTION
Dev 9K
With Dev9K it is possible to set the DAT9000 series devices to execute I/O read and write
operations (DAT3000 series), mathematical and logic operations and timers.
Moreover it is possible to read and write in real time the Internal Registers of the Con-
troller or connect it directly to the slave devices connected to its Modbus Master Port.
SYSTEM REQUIREMENTS
Operative System........................Windows 2000 / NT / ME / XP / Vista / Win 7
Available Hard Disk space......................2 MB
In d
u s tri es r d m a c hi E n er g y d busine er treat me
oa oo at
ne
ss
nt
F
B
Application areas
www.datexel.it
DATEXEL: CONFIGURATION SOFTWARE
ACCESSORIES / SOFTWARE
95
www.datexel.it
GENERAL CONDITIONS OF SALE
General conditions
The sale of the products described, in this catalog, is in compliance with the requirements listed below that are considered
in force after formal order will be accepted only if received by us in writing. These terms and conditions of sale (including
any type of written specification, quotation and / or additional terms and conditions) will determine only the sale of all
goods and services (including, without limitation, hardware, software and accessories in the Catalog and described in the
proper price list). The receipt or acceptance of delivery by the buyer of any product ordered or purchased will constitute
your acceptance of these terms and conditions.
for which the total amount does not exceed the minimum billable (€ 150.00) will be required to pay on delivery or bank
transfer at ready goods.
Payment terms
All payments must be made with a bank document. At the first delivery cash payment or bank transfer is required. Unless
otherwise agreed, payment standards are provided within 30 calendar days from date of invoice. In case of late or missed
payment, the company DATEXEL act in accordance with the provisions of Legislative Decree n. 231 October 9, 2002 as
required by Directive 2000/35/EC.
Prices
All prices quoted in the catalog list are exclusive of VAT Ex-works our factory Work Tradate (VA).
Guarantee
All products are guaranteed against defects and manufacturing faults under current law. We don’t accept returns for re-
pair or replacement under warranty even if not previously authorized. The transportation costs of any product returned for
repair or replacement even if under warranty are responsibility of the buyer. Will not be accepted unless agreed in advan-
ce, collect shipments (if received materials c / repair or replace, under warranty, shipped freight collect, the same will be
rejected). The guarantee of all material we produce is valid for a period of 24 months from date of shipment. All work done
under warranty will be ex works DATEXEL (VA). All repaired or replaced products are covered for the remaining period
by the remaining term of the original warranty. Are not covered, by warranty products or components subject to wear.
Repairs
Unless otherwise specified, the return devices shall be subject to repair. In advance DATEXEL will provide, to the customer,
by fax or e-mail, a document that will be described the type of fault / anomaly. This document, once completed, will be
returned to DATEXEL that examined the content, will grant the authorization to return by providing all necessary informa-
tion regarding the individual appearing on the shipping document and the method of delivery. It will care by DATEXEL,
than, to inform the internal staff responsible for return acceptance. Upon receipt of the goods, authorized personnel will
verify that the same is accompanied by the documents agreed during a return authorization and will repair or replace the
defective product. If the goods were not accompanied by the documents mentioned above can be made to the sender
rejected. Will not be repaired under warranty all products received outside the period of 24 months from the delivery date
and all products that are damaged due to misuse or failure to comply with the conditions of use indicated on identification
labels and related technical data sheets.
Order cancellation
Any cancellation of an order, by the customer, before the shipment must be notified in writing, by fax or e-mail. It will be
discretion of the DATEXEL staff whether to accept or reject such request. DATEXEL also has the right to cancel an order for
right cause at any time upon written notice.
www.datexel.it
GENERAL CONDITIONS OF SALE
Force majeure
DATEXEL will not be responsible for any loss, damage or delays due to causes beyond its reasonable control, including,
without limitation, acts of God, causes or omissions attributable to the buyer, causes of civil or military authority, fires,
strikes, floods, epidemics, quarantine restrictions, wars, riots, acts of terrorism, delays in transportation or transportation
embargoes.
Responsibility
DATEXEL will not be responsible for problems, breakages, accidents due to lack of knowledge or lack of compliance with
the requirements indicated on products for its use or on technical Data Sheets.
DATEXEL is also not responsible for problems caused by not authorized changes made on their products.
DATEXEL reserves the right to make changes to its products without obligation to promptly update their technical docu-
mentation.
Technical data
The technical data in this catalog are provided only as a guideline for compatibility verification with the application of the
product’s user and does not constitute a functional guarantee or performance of any kind.
DATEXEL
Reserves the right to modify or change the content of this publication without notice at any time.
www.datexel.it
ELECTRONIC AND CONTROL PROCESS DEVICES
Powered by:
www.datexel.it