Basics - OpenEnergyMonitor 0.0.1 Documentation
Basics - OpenEnergyMonitor 0.0.1 Documentation
Basics
heat transfer (W) = specific heat (J/kg.K) x flow rate (kg/s) x DT (K)
Where:
Example calculation 1: Heat output of a heat pump from measured flow rate and flow and
return temperature
(e.g heat metering).
The flow rate is 15 Litres/minute, the flow temperature is 35°C and return temperature 30°C.
The system fluid is plain water with a specific heat of 4200 J/kg.K. What is the heat output
from the heat pump?
2. Calculate DT, the difference in temperature between flow and return, 35°C - 30°C = 5
Kelvin (K).
2. Plug the numbers into the mass flow rate heat transfer equation:
heat output (W) = specific heat (J/kg.K) x flow rate (kg/s) x DT (K)
heat output (W) = 4200 J/kg.K x 0.25 kg/s x 5K = 5250 W
The heat output from the heat pump at this particular moment in time is 5.25 kW.
Example calculation 2: Required flow rate for a given heat pump heat output and design DT
We are designing a heat pump system with a maximum output of 8.5 kW, the system fluid is
plain water with a specific heat of 4200 J/kg.K and we are targetting a DT of 5K. What is the
required flow rate to transfer this heat.
Rearranging the mass flow rate heat transfer equation to give flow rate:
flow rate (kg/s) = heat output (W) / (specific heat (J/kg.K) x DT (K))
= 8500 W / (4200 J/kg.K x 5K) = 0.4 kg/s
Multiply by 3600s / 1000 L/m3 to get m3/hr: 0.4 kg/s x 3600s / 1000 kg/m3 = 1.44 m3/hr
Useful links
Results will be more accurate when the heatpump is nearer steady sate conditions as it does
not take into account startup and heatup times of the heatump and dhw system or heatpump
defrost cycles. Other factors are also important such as the heat pump compressors
efficiency curve.
1. Calculate the refrigerant condensing temperature (hot side) as the flow temperature plus
an 2K (approximate difference)
T_condensing = T_flow + 2K
2. Calculate the refrigerant evaporating temperature (cold side) as the external temperature
minus 6K (approximate difference)
T_evaporating = T_ambient - 6K
Practical_COP = 0.5 x Carnot_COP (a real-life heat pump achieves about 50% its 'ideal'
efficiency)
The correction factor of 0.5 will vary from heat pump to heat pump depending on the
efficiency of each thermodynamic process going on inside the heatpump.
Example calculation 1: What COP might we expect from a heat pump during typical UK
January temperatures when the flow temperature is 35°C?
The carnot COP equation suggests with our practical efficiency and offset assumptions that
we might expect a COP of 4.2 from our heat pump.
Example calculation 2: What COP might we expect from a heat pump during typical UK
January temperatures when the flow temperature is 45°C?
We can see that by increasing the flow temperature from 35°C to 45°C we have dropped our
COP from 4.2 to 3.4. If our electricity unit price is 34 p/kWh this makes the difference
between heat delivered at 8.1 p/kWh and 10 p/kWh.
Useful links
The mean water temperature at this rated output is therefore 70°C. (The standard test
procedure for radiators manufactured in Europe is given by the BS EN442 standard. Under this
standard the temperature of the water going to the radiator (the flow temperature) is set to 75C,
the room is set to 20C and then the flow rate is adjusted until the return temperature is 65C)
These temperatures are much higher than those that we would target with a heat pump for
efficient low cost operation and higher than the maximum temperatures that many heat
pumps can achieve.
The carnot COP equation above suggests that a heat pump would only achieve a COP of 2.3
at a flow temperature of 75°C (If this temperature could even be achived).
The heat output of a radiator at different water temperatures can be calculated with the
following equation:
32.5°C . What is the heat output at this MWT from a 1200mm x 600mm K2 radiator which
has a rated heat output of 2112W at DT50?
Our radiator is now only giving 16% of the rated heat output!
Example calculation 2: When we size radiators we need to match the heat output of the
radiator/s with the heat requirement for the room it is heating at a design outside
temperature and room temperature.
Lets say our room requires 1500W at a design outside temperature of -3°C and a room
temperature of 20°C. We set the weather compensation curve for the heat pump to target a
flow temperature of 45°C at this minimum design outside temperature. The return
temperature is 40°C. How many 1200mm x 600mm K2 radiator’s do we need to meet the
heat demand of this room?
Each 1200mm x 600mm K2 radiator would output ~750W at these temperatures, we would
therefore require 2x of these radiators to meet the heat requirement.
The carnot COP equation above would suggest a COP of 2.9 at a flow temperature of 45°C
and outside temperature of -3°C.
Using the carnot COP equation we can work out that our COP would thefore increase to 3.9
at typical January temperatures.
Useful links