08-Instruction Manual Fan Unit
08-Instruction Manual Fan Unit
List of Revisions
Contents
1 General Description...............................................................................................................................................4
2 Marking of Fan Unit..............................................................................................................................................5
3 Relevant Regulations.............................................................................................................................................5
4 Intended Application.............................................................................................................................................6
5 Limits of Application.............................................................................................................................................6
6 Basic Safety Instructions.......................................................................................................................................6
7 Installation..............................................................................................................................................................7
8 Commissioning.......................................................................................................................................................8
9 Switch Off Fan Unit or Smoke Detection System...............................................................................................8
10 Maintenance.........................................................................................................................................................9
11 Repair..................................................................................................................................................................11
11.1 Replacement of sealing between lower and upper part of enclosure ......................................................... 11
11.2 Replacement of Impeller, Motor and Shaft Sealing ................................................................................... 11
11.3 Replacement of Rubber Vibration Dampers .............................................................................................. 11
11.4 Replacement of Capacitor .......................................................................................................................... 12
11.5 Replacement of Circuit Breaker (SDS-M0441 only) ................................................................................ 12
12 List of Spare Parts and Accessories.................................................................................................................12
13 Log Book.............................................................................................................................................................13
14 Appendix.............................................................................................................................................................13
3
Fan Unit SDS-M0440 / SDS-M0441 safetec
1 General Description
1 General Description
The fan units SDS-M0440 and SDS-M0441 are „duplicate sample extraction fans“ for „Sample Extraction Smoke
Detection Systems“ as defined in FSS-Code Chapter 10 and in RESOLUTION MSC.292(87). They are used for
drawing air samples through pipelines from cargo holds to a smoke detection panel and after passing the smoke
detection panel conveying the air samples to free air.
The fan units SDS-M0440 and SDS-M0441 are identical in construction, however SDS-M0440 shall be connected
to 220/230V 50/60Hz supplies and SDS-M0441 shall be connected to 110/115V 60Hz supplies.
The fan units are designed according EN 14986 for drawing air from hazardous areas. However they must be
installed in a safe area. For more details see below.
The fan units are compound of two fans located in a common housing, consisting of one ventilator and one
electric motor each. Only one fan is running at the time. However the fans will be switched over at regular
intervalls controlled by the smoke detection panel. If one fan fails, the smoke detection panel will switch over to
the standby fan automatically. The motors are protected by internal temperature switches, which interrupt the
motor circuits when the motor temperature has reached a certain value.
The air supply and exhaust connections are located on the upper side of the fan unit. An internal flap
automatically connects the exhaust connection to the running fan.
The enclosures of the fan units are compound of an upper and a lower part, between which a profile gasket cares
for the tightness of the enclosure. The construction of the fan units cares for a low-pressure at the profile
gasket and at both motor shaft seals while one fan is running. Thus in case of any leakage the air passes
from the safe side to the hazardous side.
The layout of the fan unit cares for a sufficient gap between rotating parts and the enclosure. If
however the enclosure of the fan unit is damaged in any way, the fan unit bears the risk of
ignition of the potentially hazardous atmosphere inside the fan unit.
If in the following paragraphs the wording „fan unit“ is used, the types SDS-M0440 and SDS-M0441 are meant,
as long as not otherwise stated.
4
Fan Unit SDS-M0440 / SDS-M0441 safetec
2 Marking of Fan Unit
SDS-M0440 SDS-M0441
safetec Brandes und Niehoff GmbH safetec Brandes und Niehoff GmbH
Type: SDS-M0440 Type: SDS-M0441
Serial No.: 2440.xxxx - 201x Serial No.:2441.xxxx - 201x
Power: 230V 50/60Hz 2,3/2,7A Power: 110/115V 60Hz 6A
Temp.: -20°C ... +45°C Temp.: -20°C ... +45°C
www.safetec-online.com www.safetec-online.com
Explanation of Ex-Marking:
3 Relevant Regulations
The fan units are designed in accordance with the following rules:
• FSS-Code Chapter 10 “Sample Extraction Smoke Detection Systems”
• RESOLUTION MSC.292(87)
• DIN EN 13463-1:2009 “Non-electrical equipment for use in potentially explosive atmospheres.
Basic method and requirements“
• DIN EN 13463-5:2003 “Non-electrical equipment for use in potentially explosive atmospheres.
Protection by constructional safety 'c' “
• DIN EN 14986:2007 “Design of fans working in potentially explosive atmospheres”
• TRBS 2153 “Technische Regeln für Betriebssicherheit (TRBS) ”
5
Fan Unit SDS-M0440 / SDS-M0441 safetec
4 Intended Application
4 Intended Application
• The fan units are designed for drawing air samples through pipelines from marine cargo holds to a smoke
detection panel and after passing the smoke detection panel conveying the air samples to free air.
• The fan units are designed for the extraction of air samples from hazardous areas in zone 1 and 2 with
temperatrure class T1 – T5. The fan unit must be installed in a safe area.
5 Limits of Application
• The air samples must not contain dust or solids.
• If dust or solids cannot be excluded, pre-filters must be applied ( Art.No. BG02.861, see accessories list
of safetec).
• The fan unit SDS-M0440 shall be operated with 220/230V 50Hz or 60Hz power supply.
• The fan unit SDS-M0441 shall only be operated with 110V 60Hz power supply.
• The fan unit must not be fed by frequency converters.
To maintain the Ex-protection level of the fan unit, the operator of the fan unit is responsible to check the
following on a regular basis:
• The environment temperature of the installation location must not exceed 45°C.
• The fan unit may not be operated if the enclosure is damaged.
• The fan unit may not be operated if the enclosure or the impeller are corroded.
• If dust in the transported air cannot be excluded, the system must only be operated with pre-filters
(Art.No. BG02.861).
• The running noise of the bearings must be checked regularly for irregular sounds to assure unobstructed
operation. If necessary, the motors must be exchanged. Only original motors shall be used.
• The fan unit must be checked regularly for vibrations. It is recommended to use a vibration severity meter
for this purpose. If vibrations are increased, the fan unit must not be operated until the reason for
increased vibrations has been removed. For more details please refer to ISO 14694.
• Keep off of the fan unit!
6
Fan Unit SDS-M0440 / SDS-M0441 safetec
7 Installation
7 Installation
• The environment temperature of the installation location must not exceed 45°C.
• The typical installation location is the CO2 room.
• If the fan unit shall be installed outside, it must only be mounted in a special housing with natural
ventilation (Art. No. SDS02.445 and SDS02.446). Care must be taken, that the housing is not located in
direct sun light.
• The fan unit must only be installed in horizontal position on its vibration dampers.
• Free airflow around the fan unit and at the cooling fan of the motors must not be constrained.
• The pipes which connect fan unit with smoke detection panel, extension panels and air out must be of
conductive material. The pipes must have conductive connections and must be connected to conductive
earth.
• As protection against foreign material, the connections of the fan unit must have a protection degree of
IP20 acc. EN 60529.
At the “AIR IN” connection of the fan unit, the protection is typically realized by the pipe connection to
the smoke detection panel or extension panel.
At the “AIR OUT” connection of the fan unit, the protection must be realized by other suitable means
(i.e. with a suitable check valve or a separate grid).
• In case of potential dust contamination of sucked air or in case of potential cakings at the impellers,
which result in unbalanced impellers, pre-filters must be mounted (Art.No. BG02.861).
• If dust contamination of sucked air or cakings at the impellers cannot be excluded, for example by means
of pre-filters, hoses and pipes must be of conductive material and must be earthed. Fittings must be of
conductive material and must be earthed, if the internal surface of the fitting exceeds 100cm².
Please observe TRBS 2153 (“Technische Regeln für Betriebssicherheit”) and Technical Report CLC / TR
50404.
• The vibration dampers must not be damaged.
• If pipes, hoses or fittings of non-conductive material are applied, they must only be cleaned with a wet
cloth.
• The electrical connection of the fan unit must comply with the rules and regulations of the responsible
authorities having jurisdiction, such as flag states and classification societies.
• The enclosure of the fan unit must be connected to protective earth at the destined connection bolt.
7
Fan Unit SDS-M0440 / SDS-M0441 safetec
8 Commissioning
8 Commissioning
• Check fan unit for any damage, specially transport damage and corrosion. Do not switch on a fan unit
with any deformation of the enclosure or with corroded parts.
• Check tightness of pipe connections between the smoke detection panel / extension panel,
the fan unit and the outlet to free air with leakage detection spray while the fan unit is
running.
Commissioning checklist:
Step No. Description OK
1 Check fan unit for any damage or corrosion. Do not switch on a fan unit with any
deformation of the enclosure and with corroded parts.
2 Check, that the environment temperature of the installation space is limited to 45°C.
4 Check, that the fan unit is securely mounted on its vibration dampers in horizontal
position.
6 Check, that the pipes between fan unit and smoke detection panel, extension panels
and air out are conductive and properly connected to protective earth.
7 Check, that the fan unit is protected against ingress of foreign particles (min. IP20).
8 In case of potential dust contamination of sucked air: check whether pre-filters are
mounted (Art.No. BG02.861).
9 Check tightness of pipe connections between the smoke detection panel / extension
panel, the fan unit and the outlet to free air with leakage detection spray while the
fan unit is running.
10 Check the motor bearings and the complete fan unit for irregular vibrations and
unusual running noise. For more details please refer to ISO 14694:2003.
safetec recommends to measure vibrations on a regular base with a vibration
meter (Art. No. B06.970).
8
Fan Unit SDS-M0440 / SDS-M0441 safetec
10 Maintenance
10 Maintenance
To keep the fan unit in a safe condition during its lifetime, it is of utmost importance to
examine the fan unit in regular intervals. If the fan unit is being operated under critical
conditions (i.e. suction of dust, risque of corrosion), the operator must care for carrying out
the maintenance procedure in appropriate shorter intervals.
• Check fan unit for any damage or corrosion. Stop fan unit operation if fan unit has any deformation of the
enclosure or if parts are corroded.
• If pipes, hoses or fittings of non-conductive material are applied, they must only be cleaned with a wet
cloth.
• If dust or dirt is anticipated in the air samples, the fan unit must be checked regularly for contaminations.
Additional evidence for contamination is given, if the smoke detection panel issues a “dirt” alarm. The
fan unit must be cleaned, if internal and external parts of the fan unit are covered with dirt or dust.
• The sealing between upper and lower part of the enclosure must be checked regularly for damage. If
necessary, the sealings must be exchanged. In case of exchange, only original sealings must be used. The
sealing must be replaced completely. The sealing must not be replaced partially.
• If powder coating is flaked off, repair affected area with paint to avoid corrosion.
• The running noise of the bearings must be checked regularly for irregular sounds to assure unobstructed
operation. If necessary, the motors must be exchanged. Only original motors may be used.
• The motor bearings are calculated for a life cycle of 15 years. Not later than 15 years, the motors must be
replaced. Only original motors may be used.
• Defect or unbalanced impellers must be replaced with original spare parts from the maker of the fan unit.
• Check the condition of the vibration dampers. Exchange the vibration dampers if they are damaged or
worn out.
• Check screwed connections for tightness.
• Check tightness of pipe connections between the smoke detection panel / extension panel, the fan unit and
the outlet to free air with leakage detection spray while the fan unit is running.
Maintenance checklist:
Step No. Description OK
1 Check fan unit for any damage or corrosion. Do not switch on a fan unit with any
deformation of the enclosure and with corroded parts.
4 Wash pre-filter cartridges (if mounted) with warm water. Exchange pre-filter
cartridges if necessary.
5 Check if sealing between upper and lower part of the fan unit is not damaged or
worn out.
9
Fan Unit SDS-M0440 / SDS-M0441 safetec
10 Maintenance
8 Check tightness of pipe connections between the smoke detection panel / extension
panel, the fan unit and the outlet to free air with leakage detection spray while the
fan unit is running.
9 Check the motor bearings and the complete fan unit for irregular vibrations and
unusual running noise. For more details please refer to ISO 14694:2003.
safetec recommends to measure vibrations on a regular base with a vibration
meter (Art. No. B06.970).
10
Fan Unit SDS-M0440 / SDS-M0441 safetec
11 Repair
11 Repair
Check fan unit enclosure for any damage. Damages of the enclosure or internal baffles must only be replaced by
the maker or by trained authorized personel. Use only original spare parts from the maker of the fan unit.
11
Fan Unit SDS-M0440 / SDS-M0441 safetec
11 Repair
12
Fan Unit SDS-M0440 / SDS-M0441 safetec
12 List of Spare Parts and Accessories
13 Log Book
A log book must be kept in order to maintain a record about:
The log must be kept in a safe place and must be available for inspection by any authorized person.
14 Appendix
Document-No. Name Revision
SDS02.010.12 Typical Arrangement: Smoke Detection System SDS-48 Rev.9 13.08.2012
SDS02.440.01 Data Sheet Fan Unit SDS-M0440 Rev.11 14.01.2013
SDS02.441.01 Data Sheet Fan Unit SDS-M0441 Rev.5 20.12.2012
SDS02.441.05 Connection Diagram Fan-Unit SDS-M0441 Rev.3 10.01.2007
BG02.861 Pre-filter for SDS - Smoke Detection System Rev.0 03.02.2003
13
Ausgabe: 20.08.2012
7
8 9
6
5
4 1 3-Wege-Ventil,
(Anschluss an CO2-Sammelrohr
nicht dargestellt)
7 3-Way-Valve,
(Connection to CO2-manifold
not shown)
2 Kabelverschraubung
Cable Gland
3 3 PVC-Schlauch 13/20 mm
PVC-Hose, 13/20mm
Art. Nr. Z02.002
10 4 Rauchmeldezentrale SDS-4
10A Smoke Detection Panel
5 Reduzierungsstück
Reducer
6 Schlauchstück mit Schellen
Hose with Clamps
2 7 Stahlrohr / Steelpipe
8 Erweiterungsgerät SDS-E8
Extension Panel
11 9 Steuerzentrale SDS-R48
Control Panel
10 Schlauchverschraubung
Hose Connection Art.Nr. BG01.930
10A Vorfilter
Prefilter Art.Nr. BG02.861
1 11 Lüftereinheit SDS-M0440 / M0441
Fan-Unit
zu den Laderäumen
to Cargo Holds Pos. 5-7 Größe abhängig von der
Anzahl der Meldelinien
size depends on total
number of detection lines
(siehe Zeichnung BG02.03x /
0 1m see drawing BG02.03x)
359
760
Schwingungsdämpfer, Gewinde M8 x 8mm
Vibration Damper, Thread M8 x 8mm
AIR OUT
75
394
328
AIR IN
75
468 Hi
TW Ha = Main Phase
Hi = Aux. Phase
Ha
826 C TW = Thermal Protector
BN
BK
BL
C = Permanent Capacitor
BK = black
BL = blue
BN = brown
N L1
PE
44 / U1 / C C Z2
43 Z1 U2
Technische Daten
Technical Data L1 N
U1
Maße (HxBxT): 359 x 826 x 394 mm M Z2 Z1
1~
Size (HxBxD) U2
Gewicht: 45 kg
Anschlussplan / Connection Diagram (Siemens)
Weight
Betriebstemperatur: -20°C - 45°C
Operation Temperature
Oberflächenbehandlung und Farbe: tauchgrundiert und pulverbeschichtet RAL 7035
Surface Treatment and Colour: dip primed, powder coated, RAL 7035
Stromversorgung: 220/230V AC 50/60Hz
Power Supply 220V: 495W@50Hz, 611W@60Hz
230V: 510W@50Hz, 630W@60Hz
Schutzart Lüftermotoren: IP54
Degree of Protection Fan Motors
Kabelverschraubungen: 2 x MS20x1,5
Cable Glands:
Kondensator:/ Capacitor: 10 µF 450 V
Nennstrom: / Rated Current: 220V: 2,5A (50Hz) / 3A (60Hz)
230V: 2,3A (50Hz) / 2,7A (60Hz)
Einbaulage: waagerecht auf Schwingungsdämpfern
freier Raum: 300mm über und 50mm seitlich neben Lüfteraggregat
Method of Installation: upright on shock mounts
clearance: 300mm above and 50mm beside fan unit
359
760
Schwingungsdämpfer, Gewinde M8 x 8mm
Vibration Damper, Thread M8 x 8mm
AIR OUT
75
394
328
0 1 0 1
AIR IN
75
413
468
826
Technische Daten
Technical Data
Maße (HxBxT): 359 x 826 x 394 mm
Size (HxBxD)
Gewicht: 45 kg
Weight
Betriebstemperatur: -20°C - 45°C
Operation Temperature
Oberflächenbehandlung und Farbe: tauchgrundiert und pulverbeschichtet RAL 7035
Surface Treatment and Colour: dip primed, powder coated, RAL 7035
Stromversorgung: 110/115V AC 60Hz
Power Supply 630W@60Hz
Schutzart Lüftermotoren: IP54
Degree of Protection Fan Motors
Kabelverschraubungen: 2 x MS20x1,5
Cable Glands:
Kondensator:/ Capacitor: 40 µF 240 V
Nennstrom: / Rated Current: 6,0A
Einbaulage: waagerecht auf Schwingungsdämpfern
freier Raum: 300mm über und 50mm seitlich neben Lüfteraggregat
Method of Installation: upright on shock mounts
clearance: 300mm above and 50mm beside fan unit
Artikelnummer SDS02.441
Article No.
Leistungsschalter
Motor Circuit Breaker
PE L N
bk = schwarz
PE N L1 black
bl = blau
blue
bn = braun
brown
Bemerkung:
1. Der Leistungsschalter ist auf der Lüftereinheit montiert
2. Die gestrichelten Linien sind bereits von safetec verdrahtet
3. Die Drehrichtung des Motors ist im Uhrzeigersinn
4. Die Zeichnung für Lüfter Nr.2 ist identisch
5. Leistungsschalter auf 6A einstellen.
safetec Art.Nr.:
Motor Typ Hanning 277940387: FAN02.131
Leistungsschalter (ohne Gehäuse): F05.015
Remark:
1. The motor circuit breakers are mounted on the fan unit
2. The dotted lines are already wired by manufactorer
3. Motor is rotating clockwise
4. The wiring diagram for fan no. 2 is correspondend
5. Adjust the overcurrent protection to 6A.
safetec Art.Nos.:
Motor type Hanning 277940387: FAN02.131
Motor circuit breaker (without housing): F05.015 Rev. 3 10.01.07 PE Maßstab
Gepr. 10.01.07 PE
Bearb. 14.02.01 kb
1:1
Anschlussplan Lüftereinheit SDS-M0441
safetec Connection Diagram Fan-Unit SDS-M0441 SDS02.441.05.tcd
Vorfilter für SDS - Rauchmeldesystem /
Prefilter for SDS - Smoke Detection System
safetec
Brandes und Niehoff GmbH
Prefilter
BG02.861
Filter inset
BG02.862
Arenskule 7- 9 D - 21339 Lüneburg Tel.: 04131 – 7670 200 Fax.: 04131 – 7670 201
E-Mail: [email protected] Internet: www.safetec-online.com
Wir bestätigen hiermit, dass die Lüfteraggregate der EG Richtlinie 94/9/EG (ATEX) entsprechen und
daher im genannten Ex- Bereich eingesetzt werden dürfen. Wir weisen ausdrücklich darauf hin, dass die
in der Betriebsanleitung beschriebenen Einsatzbedingungen zu beachten sind.
Besondere Bedingungen:
Kann eine Verunreinigung der Luftproben nicht ausgeschlossen werden, die zu Anbackungen und einer
Unwucht des Laufrades führen, sind entsprechende Maßnahmen zu ergreifen, wie z.B. Verwendung
We herewith confirm that the fan units are subject of EG directive 94/9/EG (ATEX) and are therefore
suitable for conveying air samples from the mentioned Ex-zone. Application instructions described in
operation manuals must be strictly observed.
Special Provisions:
If a contamination of the air samples cannot be excluded, which leads to agglutination and imbalance at
the fan wheels, suitable measures have to be taken, i.e. Application of pre filters for SDS Smoke
Detection Systems as described in the manual „Installation and Operation Instructions“ (DOK02.055)
Furthermore actions have to be taken, which ensure vibration levels corresponding to ISO 14694.