Manual de La Unidad de Acoplamiento E-TERRAGRIDCOM LMU
Manual de La Unidad de Acoplamiento E-TERRAGRIDCOM LMU
USER’S MANUAL
LMU/EN U/F
GRID
User Manual LMU/EN U/F
CONTENTS
1. INTRODUCTION 6
1.1 GENERAL 6
1.2 ARCHITECTURE 7
2. BLOCKS DESCRIPTION 8
4. INSTALLATION 15
4.1 SHIPMENT 15
4.2 MATERIAL LIST 15
4.3 INSTALLING AND FIXING 15
4.4 CONNECTIONS 17
4.4.1 EARTHING 18
4.4.2 TO COUPLING CAPACITOR 19
4.4.3 PLC EQUIPMENT OR MAIN-AUXILIARY CONNECTION 21
4.4.4 COUPLING UNIT INSTALLATION 22
LMU/EN U/F User Manual
5. COMMISSIONING 24
5.1 SETTINGS 25
5.1.1 BALANCED – UNBALANCED MODE 25
5.1.2 COUPLING MODE 25
5.2 MATCHING & TUNING 25
5.2.1 MATCHING 25
5.2.2 TUNING 26
9. APPENDIX D : CHARACTERISTICS 42
BLANK PAGE
LMU/EN U/F User Manual
MODIFICATIONS PAGE
VERSION DATE COMMENTS
A11 27/09/2013 ORIGINAL ISSUE
A 14/10/2013 Minor layout modifications after first review
B 28/03/2014 Change of the plastic cover
C 11/07/2014 Minor layout changes
D 20/12/2016 Correction of figure page 14
E 05/04/2017 Add text page 20 (reassembling the plastic cover)
F 09/06/2017 Correction in table of chapter 5.1.1 page 25
User Manual LMU/EN U/F
BLANK PAGE
LMU/EN U/F User Manual
1. INTRODUCTION
1.1 GENERAL
The power line carrier technique, using the power line as the transmission medium, requires
particular interfacing functions between the telecommunications equipment (power line carrier
equipment) and the high-voltage components such as the line, the line trap circuits and the
coupling capacitors.
The e-terragridcom LMU coupling devices, which are designed specifically for this application,
guarantee the necessary qualities in terms of reliability and safety.
The principle of modularity adopted for the design of this equipment allows the different
coupling configurations encountered in the power line technique (phase-earth coupling,
phase-phase coupling, inter-circuit coupling) :
The pictures below show the usual arrangement for e-terragridcom LMU (coupling to the H.V
Line) by the single phase or multi-phases methods.
Coupling Coupling
Line Trap Line Trap
capacitor capacitor
PLC PLC
system system
Inter-Circuits Coupling
Line to Line
Coupling
Line 1
Line 2
LMU LMU
PLC
system
User Manual LMU/EN U/F
1.2 Architecture
The e-terragridcom LMU is designed with an architecture using three basic blocks:
2. BLOCKS DESCRIPTION
2.1 Protection Unit
The following devices form this unit:
3 2
Protection Unit
To Tuning To Coupling
Unit Capacitor
External
Tuning Unit
To Matching To Protection
unit Unit
Ground
reference
Several taps perform the tuning (with the coupling capacitor) within the R.F frequency range.
Matching Unit
K To Tuning Unit
Ground reference
Winding taps carries out the primary impedance (Line) matching to the secondary one (PLC
side), basically,
1. Primary winding taps for varied line impedance range.
2. Secondary winding taps to set the impedance on the PLC side.
LMU/EN U/F User Manual
• e-terragridcom LMU-2: The Auxiliary. It is used in conjunction with the Master (e-
terragridcom LMU-1) only when the Phase-to-Phase or Inter-circuits coupling mode is
required. This Auxiliary is connected to the Master by means of a coaxial cable.
Hybrid Device
1/√2 To local
LMU
R = Ze/2
To PLC
To Other LMU
(other phase
coupling)
Ground
reference
The differential transformer is with 1/√2 turn-ratio between the primary and secondary
windings. The resistor in the middle of the secondary winding is provided to dissipate the R.F
power generated by a phase to phase imbalance.
• The resistor is sized for a complete imbalance (i.e. when one of the phases is failed).
• The value of the resistor corresponds to the half value of the equipment impedance.
User Manual LMU/EN U/F
6 dB attenuation Device
To Matching
Ze Ze unit
Ground
reference
The attenuation device is placed between the equipment (PLC) and the matching unit.
The impedance corresponds therefore to the equipment nominal impedance.
LMU/EN U/F User Manual
attenuator
if option OK
this strap has to
be removed
e-terragridcom LMU
Secondary
Tuning Unit
arrester L1
Matching Unit TP3
S27
T2 S13
C1 S26 T1
TP1
S12 S3
Rh Protection Unit
TP2 S20 S19
To PLC
S23 S100
S28
S21
capacitor
S22
S1 TP4 S2
Ground reference
S18 TP5
To Coupling
TP4 S2
Ground reference
S29 S30
e-terragridcom LMU
User Manual LMU/EN U/F
4. INSTALLATION
4.1 Shipment
In order to protect the e-terragridcom LMU from mechanical and environmental damages,
each e-terragridcom LMU is individually packed in a cardboard box.
For the transport between the factory and the site, the boxes making up an order are grouped
in common containers suited to the mode of transport (ship, aircraft and truck transportation).
4.4 Connections
In this chapter, it is assumed that the work environment is electrically safe and secured, and
that all the steps of lockout-tagout procedure have been passed. The HV elements on which
the LMU is to be connected shall be earthed and short circuited.
To make the connections, the plastic cover on the earth switch should be removed. The plastic
cover protects the user against an accidental contact with the hot point when working in or
around the LMU. To remove the plastic cover of the earthing switch, unscrew the two plastic
nuts, and then remove the three black plastic pieces.
LMU/EN U/F User Manual
4.4.1 Earthing
The LMU must be earthed by means of the threaded rod located on the fixed part of the
earthing switch at the bottom left of the case.
The rod is 10 mm in diameter and fitted with a locknut and washers.
This device allows the use of a cable crimp terminal to the physical substation earth.
Earth
Line
Washer ø10mm
Nut ø10mm
Crimp Terminal
User Manual LMU/EN U/F
Crimp Terminal
Washer ø10mm
Nut ø10mm
LMU/EN U/F User Manual
When the connection is done, re-assemble the parts in the following order:
1. Reinstall the central plastic piece
2. Close the earthing switch
3. Reassemble the 2 plastic covers on each side
4. Tighten by hand the white plastic nuts to maintain the cover.
5. Open and close the moving part of the switch to verify the maneuverability
User Manual LMU/EN U/F
• The screw terminal on the right is for the connection towards the PLC equipment.
• The screw terminal on the right is for the connection between main and auxiliary LMU
in phase to phase or Inter-circuits mode.
The following drawings show the connection method for a coaxial cable.
Note that in case a symmetrical cable in balanced mode, the shield of the cable should be
connected to earth outside of the LMU. Generally, to avoid current flowing in the shield, the
earth connection is done on one end of the cable only and generally on PLC side.
LMU/EN U/F User Manual
To PLC
To Earth
To Line Capacitor
Auxiliary
Master Coupling Unit
Coupling Unit
To PLC
To Earth To Earth
5. COMMISSIONING
Before carrying out the tunings of the LMU, it is mandatory to close the earthing switch
in order to protect the operator against any electrical hazard. Once the tunings are
performed, the earthing switch should be open.
Do not remove the earthing switch plastic cover to operate the earthing switch.
It is also mandatory for the operator to wear his Personal Protective Equipment
(insulating electrical gloves, face shield …) and to use an electrical insulating mat
corresponding to the level of the voltage of the line.
The figures below indicate the e-terragridcom LMU layout of the printed circuit and the location
of the commissioning elements (jumpers, straps, measurement points…)
R37B
R37A
TP5
EARTH2
S20
S19
TP4 TP3
S102
S100
S101
S2
TP1 TP2
S21
S27
S29
S30
B1
GY
BR
S28
S22
S1
EARTH1
LINE
User Manual LMU/EN U/F
5.1 Settings
5.1.1 Balanced – Unbalanced Mode
This selection refers to the PLC interface type. It simply consists to connect or not the low
primary point of the Matching transformer to earth.
When PLC Unbalanced mode is used, the shield of the coaxial cable connected to earth.
In this case the matching unit is turned into a self-transformer (not insulated mode).
This selection is carried out by means of the Jumpers S1 & S2.
50 Ω 75 Ω 125 Ω 150 Ω
S23 C
S24 C
S25 C
S26 C
LMU/EN U/F User Manual
Line Impedance
The frequency ranges mentioned in appendix 6 and 7 are not limited to the indicated
values.
The "Return loss meter" RLM5000 allows a fine tuning of the impedance value in any
situation in order to match with lines characteristics and the line capacitor value.
Refer to user process an § 7 Appendix C (Test set-up with return loss meter RLM5000).
Technical bounds :
With line capacitor < 4nF, it is not advised to work at low frequencies because the
bandwidth is too narrow.
With line capacitor > 10nF, the capacitor value has very little effect on the bandwidth.
5.2.2 Tuning
The Tuning is carried out by mean of selected taps S3 to S12.
The nominal bandwidth limits are linked to the line impedance and the Coupling capacitor
value.
The Tuning tables in the next appendix A & B give the tap settings for various Line impedances
and Coupling capacitors.
The resulted bandwidth is given for a composite loss less than 2 dB (IEC 60481 standard) and
a return loss not less than 12dB.
This method could be completed by the impedance measurement (see appendix C).
The response is covered by the composite loss measurement (see appendix D).
User Manual LMU/EN U/F
The method described below makes use of a differential measuring transformer. However,
there are other methods and instruments which lead to the same result.
The test set-up is illustrated on the following scheme.
A A'
C R i2 i1
G Point to be measured
B B'
To LMU/PLC side
Measurement procedure
R and C are varied to obtain a minimum on the selective voltmeter (V) tuned to the frequency
of the generator (G). The minimum is obtained when currents i1 and i2 are balanced, which
occurs when the impedances are equal.
Several adjustments will be required to R and C in order to get to an absolute minimum. The
adjustment is considered to be correct when a small variation of R (i.e.1 Ohm) and or C (i.e.
100 pF) results in loss of this balance.
NOTE: If C=0 is found and the measurement is still not optimized, move the
capacitance decade box to A' and B', to get a balance.
LMU/EN U/F User Manual
Adjustment
Depending on the values obtained for C and R in the preceding paragraph, the settings are
then carried out for the Matching unit (Transformers T1 & T2) and the Tuning unit (Inductance
L1).
As a first step, the Tuning unit is adjusted to balance out the imaginary part of the impedance
(C value as less as possible):
• To reduce C, the value of the tuning unit (number of turns of the Inductance) should be
increased.
• If the measurement has been carried out with C connected to A' and B'(inductive
impedance), then the value of the tuning unit must be reduced. In this case, the value
of the inductance can be reduced to zero.
As soon as C has been balanced out, the Matching unit is adjusted to bring the value of the
resistance as close as possible to the characteristic impedance of the carrier equipment:
• To reduce R, the line impedance selection should be increased. To increase R, the line
impedance selection should be reduced.
In some case, it could be necessary to change the PLC impedance setting (5.2.1 jumpers S23 to
S26), in order to get better results.
User Manual LMU/EN U/F
Substation A Substation B
Coupling Coupling
capacitor capacitor
PLC PLC
Cx Zn Z'n Cx
R.F
R.F G LMU LMU V
Zi Zi Selective
Generator
Voltmeter
Zi=Zn Z'i=Z'n
R.F Response
One R.F generator and one R.F selective voltmeter are connected at each end of the line to
be tested.
These test equipment are connected at the PLC access of the LMU and should have the same
impedance.
Measurement procedure
Set the generator (G) to a notable level (a level of 0dBm is recommended *).
Sweep (by steps) the frequency and record the level value at the voltmeter (V) side for each
frequency.
It is strongly recommended to extend the spectrum beyond the user band in order to detect
any disturbance around (i.e. to anticipate future network extension) or to check the line traps
efficiency.
It is recommended to select 1 kHz steps within the PLC bandwidth and 10 kHz steps out of
the PLC bandwidth.
* Using this value (and dBm unit), the level read on the voltmeter directly shows the composite
loss.
LMU/EN U/F User Manual
9. APPENDIX D : CHARACTERISTICS
General characteristics
Frequency range 25 kHz - 750 kHz
Nominal P.E.P (Peak Envelope Power) 1000W
Coupling mode Phase to Ground
Phase to Phase (or Inter-circuit)
Coupling capacitor 2000 pF to 13000 pF (see note)
Standard reference IEC 60481
Nominal Impedance
Line side
Impedance 50 Ω to 800 Ω
mode Unbalanced Phase to earth
PLC Side
Impedance 50, 75, 125, 150 Ω
mode Balanced-Unbalanced
Hybrid option
Transformer Composite loss ≤ 0.5 dB
Hybrid Composite loss (when mismatching) ≤ 3.5 dB
Dissymmetry attenuation ≤ 20 dB
Available Impedance 50, 75, 125 or150 Ω
Attenuator option
Attenuation 6 dB
Impedance 50, 75, 125 or150 Ω
Power PEP 200 W
Note: These value are not limitative, an adjustment to other value of coupling capacitor could
be done using differential transformer or RLM5000, refer to Appendix C : impedance
measurement.
User Manual LMU/EN U/F
Climatic characteristics
Protection index (EN 60529) IP55 or IP66
Operational range Temperature -45 °C / +70°C
Relative humidity 95 % at 23 °C
Storage Temperature -45 °C < T < +70°C
Relative humidity 100 %
Earthing switch
Short-circuit Current 200 A / permanent
Primary Arrester
D.C. Spark-over voltage 750 V
Impulse Spark-over voltage (1.2/50 µs) 1600 V
A.C. discharge current (50 Hz, 1s, 10 times) 100 A
Impulse discharge current (8/20 µs) 150 kA
Nominal current after striking 30 A / 1s
100 A / 200ms
Insulation resistance ≥ 1010 Ω at 100 V
Secondary Arrester
D.C. Spark-over voltage. 350 V
Impulse Spark-over voltage (1.2/50 µs) < 0,8 kV
A.C. discharge current (50 Hz, 1s, 10 times) < 100 A
Impulse discharge current (8/20 µs) < 25 kA
Cables range
Coaxial (PLC side) From 8 mm to 18 mm
Coupling Capacitor
Type of connection Bolt and metric threading (M10)
Type of cable Insulated Cable or copper bar.
Section of cable 16 mm2 to 25 mm2
Grounding Bolt for Copper cable up to 75 mm2
Type of connection Bolt and metric threading (M10)
Type of cable Copper naked cable
Section of cable 50 mm2 to 95 mm2
Physical
Box Material Painted Steel
Stainless steel optional
Box size Height x Width x Depth (mm) 500 x 360 x 120
Weight (Master coupling unit) 7.6 kg
Weight (Auxiliary coupling unit) 7.0 kg
9.4 MTBF