Polyphase System Lec 5
Polyphase System Lec 5
The three phase system can be used as three single phase line so it can act as
three single phase system.
The three phase generation and single phase generation is same in the
generator except the arrangement of coil in the generator to get 120° phase
difference.
A three-phase system needs three conductors; however, each conductor is only
75% the size of the equivalent kVA rated single-phase conductors.
The instantaneous power in single phase system falls down to zero as in single
phase we can see from the sinusoidal curve but in three phase system the net
power from all the phases gives a continuous power to the load.
Single three phase transformers for the same KVA rating will be smaller,
cheaper and lighter than individual single phase transformers connected
together because copper and iron core are used more effectively
Three phase connection
Where Vp, the phase voltage, is the magnitude of the phasor voltage from the
neutral to any line.
The line-to-line voltages or, simply, line voltages can be calculated using KVL;
for example,
Phasor diagram
All the line voltages together with the phase voltages are shown
Therefor the magnitude of the line voltages as VL, for a balanced system is
Neutral line current
The neutral current In is then
Since there is no current in the neutral, this conductor could contain any impedance or it
could be an open or a short circuit, without changing the results found previously.
As illustrated by the wye–wye connection in previous slide , the current in the line connecting
the source to the load is the same as the phase current flowing through the impedance ZY.
Therefore, in a wye–wye connection,
Although we have a three-phase system composed of three sources and three loads, we can
analyze a single phase and use the phase sequence to obtain the voltages and currents in the
other phases. This is, of course, a direct result of the balanced condition.
We may even have impedances present in the lines; however, as long as the system remains
balanced, we need analyze only one phase. If the line impedances in lines a, b, and c are
equal, the system will be balanced.
In unbalanced system, unbalanced current will flow in the three phase circuit, then neutral
plays a vital role as it will take the unbalanced current through to the ground.
That is why if you lose out the neutral point in a star connection, there will be an overflow of
current through to the loads.
The loads also take in more current, generating much more power and could damage the
appliance you are using)
Example
Example
Delta system voltage and current
relationships.
Power
strands
AAC --- ALL ALUMINIUM CONDUCTOR
AAC conductor is also known as aluminum stranded conductor.
AAC is manufactured from electrolytically refined (E.C.GRADE) Aluminium,
having purity of minimum 99.5% of Aluminium (with minimum conductivity of
61%).
It consists of one or more strands of aluminum wire depending on the end usage.
AAC conductor is used mainly in urban areas because the spacing is short and the
supports are close.
Because of its relatively poor strength to weight ratio, AAC had limited use in
transmission lines and rural distribution because of long spans utilized.
AAC conductors are also used extensively in coastal areas because they have a
very high degree of corrosion resistance.
Why Aluminium is used in overhead power line conductors instead of copper?
Pure copper has good electrical conducting properties as compared to Aluminium
but lower mechanical strength than it.
Alloys of copper, particularly cadmium copper, although have higher mechanical
strength than pure copper but since both pure copper and cadmium copper are
expensive, these have largely been replaced by Aluminium as a conductor
material.
OVERHEAD POWER LINES
ACSR --- ALUMINIUM CONDUCTOR STEEL REINFORCED
Aluminium has low mechanical strength in its pure form.
In order to increase the mechanical strength of pure aluminium, often a central core of steel strands,
surrounded by aluminium strands is employed.
This combination results in ACSR --- Aluminium Conductor, Steel Reinforced.
Underground cables are classified according to the voltage for which these are manufactured
Low tension (L.T) cables for operating voltage up to 1000v
High tension(H.T) cables for operating voltage up to 11kv
Super tension cables for operating voltage from 22kv to 33kv
Super tension (S.T) ---- from 22KV to 33KV
Extra high tension (E.H.T) cables ------- from 33KV to 66KV
Extra super voltage cables ------beyond 132KV
A cable may have one or more than one core depending upon the type of service for
application. It may be,
Single Core
Two Core
Three Core
Four Core
General construction of underground cables
Core : A cable may have one or more than one core depending upon the type of service for which it is
intended
The conductor could be of aluminum or copper and is stranded in order to provide flexibility to the
cable.
Insulation: The core is provided with suitable thickness of insulation, depending upon the voltage to be
withstood by the cable. The commonly used material for insulation are impregnated paper, varnished
cambric or rubber mineral compound
Metallic sheath: A metallic sheath of lead or aluminium is provided over the insulation to protect the
cable from moisture, gases or other damaging liquids
Bedding: Bedding is provided to protect the metallic sheath from corrosion and from mechanical
damage due to armoring. It is a fibrous material like jute or hessian tape.
Armouring: Its purpose is to protect the cable from
mechanical injury while laying it or during the course of
handling. It consists of one or two layers of galvanized
steel wire or steel tape.
Serving: To protect armouring from atmospheric conditions,
a layer of fibrous material is provided
Insulating Materials for Cables
Rubber
It can be obtained from milky sap of tropical trees or from oil products.
It has the dielectric strength of 30 KV/mm & Insulation resistivity
Relative permittivity varying between 2 and 3.
They readily absorbs moisture, soft and liable to damage due to rough handling
and ages when exposed to light.
Maximum safe temperature is very low about 38 C
Vulcanized India Rubber
It can be obtained from mixing pure rubber with mineral compounds i-e zinc
oxide, red lead and sulphur and heated up to 150 C.
It has greater mechanical strength, durability and wear resistant property.
The sulphur reacts quickly with copper so tinned copper conductors are used.
it is suitable for low and moderate voltage cables.
Insulating Materials for Cables
Impregnated Paper
This material has superseded the rubber, consists of chemically pulped paper
impregnated with naphthenic and paraffinic materials.
It has low cost, low capacitance, high dielectric strength and high insulation
resistance.
The only disadvantage is the paper is hygroscopic, for this reason paper insulation
is always provided protective covering.
Varnished Cambric
This is simply the cotton cloth impregnated and coated with varnish.
As the varnish cambric is also hygroscopic so need some protection.
Its dielectric strength is about 4KV / mm and permittivity is 2.5 to 3.8.
Polyvinyl chloride (PVC)
This material has good dielectric strength, high insulation resistance and high
melting temperatures.
These have not so good mechanical properties as those of rubber.
Insulating Materials for Cables