1. The document outlines specifications for indoor lighting and fan works including supply, installation, testing and commissioning of various light fittings such as LED trunking systems, battens, recessed fixtures, downlighters, flood lights, and highbay fittings. 2. Minimum specifications for luminaires include operating within a voltage fluctuation range, using FR rated components, heat resisting internal wiring, and complying with various industry standards. 3. Electronic ballasts must meet efficiency, power factor, electromagnetic compatibility, and thermal performance standards, and be capable of starting lamps at low temperatures with high frequency and constant light output regulation.

Uploaded by

ANKIT KUMAR RAJ
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views

Lighting System

1. The document outlines specifications for indoor lighting and fan works including supply, installation, testing and commissioning of various light fittings such as LED trunking systems, battens, recessed fixtures, downlighters, flood lights, and highbay fittings. 2. Minimum specifications for luminaires include operating within a voltage fluctuation range, using FR rated components, heat resisting internal wiring, and complying with various industry standards. 3. Electronic ballasts must meet efficiency, power factor, electromagnetic compatibility, and thermal performance standards, and be capable of starting lamps at low temperatures with high frequency and constant light output regulation.

Uploaded by

ANKIT KUMAR RAJ
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 8

Schedule D: E&M Works

S.No. Description

PART-A ELECTRICAL WORKS


E.05 INDOOR LIGHTING AND FANS
Technical Specification E05 shall be followed
1.0 Supply, installation, testing & commissioning of light fittings including all accessories e.g. ballast, HPF condensors,
lamps, holders, surface/recess mounting arrangement etc. including necessary supports, accessories and
hardware as per specifications & as required at site and as below:

A Luminaire minimum specifications and requirements


a) Luminaires should operate at +/- 6% voltage fluctuation for continuous use to
comply to IEC. PF >0.90 for the electronic drivers
b) All the components including the internal wiring of the luminaries to be used shall be manufactured of material, which are
of FR type. All luminaires shall be manufactured to relevant sections of IEC60598 or other approved
international standards and the type tests for all luminaries shall be provided.

c) All internal wiring within the lighting fixtures shall be heat-resisting cables.
B Electronic Ballast for LEDs lamps and luminaires
a) All equipment shall confirm with the objective of the European Directives on
EMC (89/336/EEC) and where appropriate shall be fixed with CE mark
b) The radio frequency interference (RFI) levels generated by the electronic ballasts and control gear shall be in
accordance with the requirements of standard CISPR15 or other international standrads as stated in specifications.

c) It shall comply with following :


Electromagnetic Compatibility Emission
IEC 60555 & EN55015 & IEC 61000
d) Ballasts for LED lamps/luminaires : power factor shall be according to manufacturers recommendation and type of
luminaire. Input volt shall be
240V, 50Hz. Voltage tolerance: 140 - 270V
With Tolerance Of Performance: +6% to 8% --- 202 to 254 V
With Tolerance Of Safety: +/-10% --- 198 to 264 V
e) All ballast shall be capable of starting lamps at ambient temperature of 0 °C
and above.
f) Ballast shall be electronic driver type , operating lamps at a frequency of 20
kHz or higher with no detectable flicker.
g) Light output regulation: ballast shall maintain constant light output of all LED Luminieries over operating ranges of
170Volts to 265 Volts. Luminous flux
should not change more than +/-2%.
h) Relative Light Output: (percentage of light emitted compared with reference tube and ballast) shall not be less than 95%
and more than 100%.
i) Input total harmonic content shall not exceed 10%. Driver shall withstand line transients as per IEC 61547. Driver case
temperature shall not exceed 25 35 degree rise over 43 degree ambient. Ballast power factor shall be 0.90 or
above.

j) The following general lamp parameters shall be applicable unless otherwise


specified in specific design data;
Compliences and approvals
RFI <30MHz --- CISPR15
RFI > 30MHz --- CISPR15
Harmonics --- EN 61000-3-2
Immunity --- EN 61547
Safety --- IEC 61347-2-13
Performance --- IEC 62384
Vibration & bump test --- IEC 60598
Quality standard --- ISO 9001
Environment standard --- ISO 14001
Approvals marks --- Safety marks
a) LEDs
Colour Rendering Index Ra: 70
Colour Temperature: 6500K/5700K/4000K
Life: In excess of 50,000 hours
Surge - 2.5kV for Indoor Luminaires /4kV for Outdoor Luminaires
b) Metal Halide
Colour Rendering Index Ra: 80 for 70W & 150W lamps and 65 for 250W &
400W lamps or above
Colour Temperature: 4000K
Note: Lamp should have free replacement for one year from the date of
Installation. The Date of installation shall be from the date of handing over the work to UPMRC.

Note for Light Fixture: IP rating of all indoor luminaire shall be minimum IP44.
1.1 Supply, installation, testing and commissioning of LED trunking system, with a system lumen output of 4000 lumens and a
minimum system efficacy of 125 lumen/watt. The luminaire body shall be atleast 0.5mm thick extruded
Aluminium to ensure deformation free linear installation and light emitted shall have a CRI>80 with rated system
lifetime of 50,000 hours at L70. The extrusion housing shall be available in 4', 8' and 12' sections.It must conform to
Ingress Protection Classification of IP 54This fixture is similar to Philips catalogue no.LL199X led 40 PSE OD WH or
equivalant (for dust and moisture
Protection). (for Staircase and corridor)

1.2 Supply, installation, testing and commissioning of suspended LED Batten, with a system lumen output of 4000 lumens and a
minimum system efficacy of 95 lumen/watt. The luminaire shall have a CRI of greater than 80 with rated system
lifetime of 50,000 hours at L70. The luminaire should be flicker free with ripple <5% and should have Hi-Low
Cutoff(140-270V) with auto restart feature. The luminaire is made of CRCA housing and shall have diffused
optics.Similar to Havells catalogue no.STOUTPLUS1200BS40WLED857SPCWH or equivalant. (for non false ceiling
equipment room)

1.3 Supply, installation, testing and commissioning of LED Linear 1x4 recessed fixture, with a system lumen output of
3000 lumens at a system efficacy of 105 lumen/watt. The luminaire shall have powder coated CRCA housing and light
output is by means of fully difuused luminaire having SDCM<5. Luminaire should have THD<10% with PF>0.95. Similar
to Havells catalogue no
VENUSNEOHE4X1PLR28WLED857MOD or equivalant. (for public area)

1.4 Supply, installation, testing and commissioning of LED 2X2 recess mounted fixture - 40 Watt that delivers 3500 nominal lumens at a system efficacy of
>90lumen/watt for a design ambient temperature of 45 deg C (Similar to Philips Catalogue no. RC380 LED35 6500 PSU – OD WH or equivalent). The
luminaire shall have a CRCA powder coated body and a high efficiency diffuser. The light output shall have a CRI>80 and the luminaire shall be made available
with a CCT 6500K or as required. The electronic driver shall operate a
power factor>0.9 and a THD<10%. (BOH with False Ceiling Area)

1.5 Supply, Installation, Testing & commissioning of highbay. Fitting should have a aluminium pressure die cast housing with tempered glass for high
transmittence. Luminaire should have system wattage of 80W with system efficacy of 130 lumens/W. The luminaire should have SDCM<5 with high voltage
cut off and autostart facility at 320V. It is designed to meet IP66 and IK08 specifications ensuring L70 for 50000 burning hours with a THD<10% and PF of >0.95 with
input voltage of 140-270V. Similar to PHILIPS BY225P
LED100S CW WB PSU FG GR V1. (for Street lighting)

1.6 Supply, installation, testing and commissioning of surface mounted LED Bulkhead with a system lumen output of 400 lumens and a system efficacy of 40
lumen/watt. The luminaire shall be IP65 & IK09 rated and shall have a CRI of 80. The housing of luminaire is made of high pressure die cast aluminium with front cover
made of polycarbonate diffuser. Similar to Havells catalogue no.RUGBYNEONFT10WLED860SSYMTOPC. (For Shaft, Parapet wall)

1.7 Supply, installation, testing and commissioning of LED Downlighter with a system lumen output of 1080 lumens and a minimum system efficacy of 90 lm/W.
The luminaire shall have a CRI greater than 80, SDCM<5 with rated system lifetime of 50,000 hours at L70. The lumaire housing should be of pressure die
cast aluminium with PC diffuser. Height of luminaire shall not be more than 40 mm with THD<10% and PF>0.95.Similar to Havells catalogue no.
ENDURANEODLR12WLED857.(For Toilet)
1.8 Supply, installation, testing and commissioning of surface mounted LED flood light with a system lumen output of 6000 lumens. The luminaire shall have a aluminium
pressure die-cast housing and a minimum system efficacy of 75 lumen/watt. Luminaire should have high voltage cut off (140-270V) and autostart facility at
320V. The luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. Similar to Havells catalogue no.
JETALINEARFL80WLED757LTG and must conform to Ingress Protection
Classification of IP 65. (For Platform staircase)

1.9 Supply, installation, testing and commissioning of SS pole 80mm OD, 6 feet height with suitable base
1.10 Supply, installation, testing and commissioning of led Post Top light fixture 40
Watt ARIAN WW( BGCT W4 LED WW/CDL -BAJAJ or similar make (Corridor, FOB)
1.11 Supply, installation, testing and commissioning of LED Highbay Fixture, with a system lumen output of 9200 lumens and a minimum system efficacy of 115 lumen/watt.
Luminaire housing should be of high pressure die cast aluminium with heat proof silicom rubber gasket and high transmittence tempered glass.The luminaire shall
have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. Lumianire should have operating voltage range of 140 270V with high voltage cut of
@325V. Luminaire should have SDCM<5 with THD<10%. Similar to Havells Catalogue no.
BAYBRITESAUCERHBP80WLED75790DTOLTG and must conform to Ingress Protection Classification of IP 65. (For Platform edge, Lift lobby)

1.12 Supply, installation, testing and commissioning of LED Highbay Fixture, with a system lumen output of 14300 lumens and a minimum system efficacy of 120
lumen/watt. Luminaire housing should be of high pressure die cast aluminium with heat proof silicom rubber gasket and high transmittence tempered glass.The
luminaire shall have a CRI greater than 70 with rated system lifetime of 50,000 hours at L70. Lumianire should have operating voltage range of 140 270V with high
voltage cut of @325V. Luminaire should have SDCM<5 with THD<10%.Similar to Philips Catalogue no.BY415P LED145S CW WB FG PSU GR and must
conform to Ingress Protection Classification of IP 65(For Platform
edge, Lift lobby)

1.13 Supply, installation, testing and commissioning of LED Supply of Surface Mounted 50 Watt Smart Bright LED Flood light similar to Phillips cat. no
B0722RS1XL and operating voltage range from 110 VAC to 270VAC, Fixture to be made of extruded aluminium housing, with Tempered glass cover,
IP65( Waterproof) and including mounting of sutable MS frame with all accessories
or site requirement (For External Art Work)

1.14 Supply, installation, testing and commissioning of LED Supply of Surface Mounted 70 W smart bright LED Flood light simillar to PHILIPS B071VG2PQW or
similar make and operating voltage range from 110 VAC to 270VAC,Fixture to be made of extruded aluminium housing, with Tempered glass cover, IP65( Waterproof),
and including mounting of sutable MS frame with all accessories or site requirement (For External Art Work)

1.15 Deleted
1.16 Supply, installation, testing and commissioning of Recessed Light with a nominal system lumen output of 3000 lumens and a minimum system efficacy of 100 lm/W.
The luminaire should have a color temperature of 3000K and CRI>80 with beam angle of 24 deg. The luminaire shall meet IP20 rating with THD<20% and PF > 0.9
and should have tilting angle of +/- 30 deg. The luminaire housing should made of pressure die cast aluminum with a high efficiency diffuser.
Similar to Havells Make " SPARKLEPROADJDLR30W857MOD40D". (For Art work at TOM and as required
)

1.17 Supply, installation, testing and commissioning of LED recessed mounted downlighter luminaire with a system lumen output of 1800 lumens and a minimum
system efficacy of 85 lm/W. The Luminaire shall have a life of 30k hours at L70.Luminaire should have polycarbonate cover with diffused optics. Similar to Havells
catalogue no. ENDURANEODLR21WLED857MOD.(For
Corridor area)

1.18 Supply, installation, testing and commissioning of Endura led well glass light fixture with a system lumen output of 4000 lumens and a minimum system efficacy of 100
lumen/watt.The luminaire shall be IP66 class 1 protection and integrated power supply.The fixture shall have a CRI of 80. Similar to Havells catalogue no.
ENDURAWELGLASSNEOTSWGP40WLED757SPC and must conform to Ingress Protection Classification of IP 66.(Above footpath)

1.19 Supply, installation, testing and commissioning of LED flood lights, 40 w,4000lumen, 6500K, amber color .The luminaire shall be IP66 class 1
protection and integrated power supply.The fixture shall have a CRI of 70. The fixture shall be mounted on suitable frame as per site requirements on bridge
or steel span .

1.20 Supply, installation, testing and commissioning of LED Linear EMERGENCY


Light PEL LED NM 600( IP 20). (Battery Backed Unit complete with all accessories)
1.30 Supply, installation, testing and commissioning of LED Linear EMERGENCY
Light PEL LED NM 1200(IP 20). (Battery Backed Unit complete with all accessories)
1.31 Supply, Installation, testing, Commissioning of Flexible LED Strip with Suitable electronics Driver, with a system wattage of 5W per mtr. The Luminaire shall be
minimum IP-65rated and have a CRI of 80. This shall be powered bt a separate , replaceable, constant voltage electronic driver, output short circuit protection and
other safety test. The housing of luminaire is made of flexible PCB , dual layers, similar to tri-colour, Tiranga LED strip light for decorative
pole Lighting or equivalent.

1.32 Supply Installation, Testing & Commissioning of RGB multi Colour (Minimum 16 colour 4 mode) LED Flood Light of 100W with die cast housing, IC based LED driver
having memory function (i.e when the power is turned ON again, the light should remain at its previous colour setting) with IP65 rating.

Technical & General Specification of the following fixture shall be as per


Chapter E5(1)
DR 1.0 Supply, Installation, Testing & Commissioning of Ambeilla PLUS G4 RECESS or similiar (AT FOYER CEILING) {make Trilux, WIPRO, Philips} For
detailed
description refer Technical Specication item no. DR1.0
LS1.1 Supply, Installation, Testing & Commissioning of BN308 C LED40S or similiar (AT Entrance Staircase) {make WIPRO, Philips, Osram} For detailed description
refer Technical Specication item no. LS1.1

LS2.1 Supply, Installation, Testing & Commissioning of LC52 H OTA or similiar (AT Concourse Ceiling) {make Trilux, LED Linear} For detailed description refer
Technical Specication item no. LS2.1
LS3.5 Supply, Installation, Testing & Commissioning of LCL H 1200 MRO LED or similiar (AT Concourse Level for Art work) {make Trilux, WIPRO, Philips}
For
detailed description refer Technical Specication item no. LS3.5
NH1.1 Supply, Installation, Testing & Commissioning of RFL540-SE LED 111-0929 or similiar (AT Platform Area) {make WE-EF, LIGMAN, BEGA} For detailed
description refer Technical Specication item no. NH1.1

LS4.1 Supply, Installation, Testing & Commissioning of BN308 C LED40S or similiar


(AT Internal Stairside Wall) {make WIPRO, Philips, Hevels} For detailed description refer Technical Specication item no. LS4.1

LI1.1 Supply, Installation, Testing & Commissioning of VAYA FREE FORM or similiar (AT Façade Horizontal Linear Element) {make Philips, LEDC4, DEBBAS} For
detailed description refer Technical Specication item no. LI1.1

US1.7 Supply, Installation, Testing & Commissioning of Quantum QA-50015-RGBW or similiar (AT Platform Area) {make Philips, WE-EF, LIGMAN} For detailed
description refer Technical Specication item no. US1.7

AP1.7 Supply, Installation, Testing & Commissioning of Quantum QA-50011-Flood


Light or similiar (AT Platform Area) {make Trilux, WIPRO, Philips} For detailed description refer Technical Specication item no. US3.0

US2.5 Supply, Installation, Testing & Commissioning of GI-31631 GINO WALL UP


DOWN or similiar (AT Façade Louvers) {make Trilux, WIPRO, Philips}
US3.0 Supply, Installation, Testing & Commissioning of RBL Wall Bracket or similiar (AT Entrance Gate Side Wall) {make K-LITE, RayBright, WIPRO} For detailed
description refer Technical Specication item no. US3.0

AP2.8 Supply, Installation, Testing & Commissioning of ROMA MIDI or similiar (External Roadside Street Lights) {make Keslec, Philips, WIPRO} For detailed
description refer Technical Specication item no. AP2.8

LS5.1 Supply, Installation, Testing & Commissioning of BN100C LED40S or similiar (FOR BACK UP HOUSE AREA) {make Philips, WIPRO, OSRAM} For
detailed
description refer Technical Specication item no. LS 5.1
DR2.0 Supply, Installation, Testing & Commissioning of Back of House Area Light or similiar (As per Ceiling Type) {make Trilux, WIPRO, Philips} For detailed
description refer Technical Specication item no. DR2.0

LMS Supply Installation, testing & Commissioning of Lighting Management System For Day ligt Linking, Energy Management & Maintenance Support using Software &
Dali {make LUTRON, Philips, Legrand) For detailed description
refer Technical Specication item no. LMS
2 Bracket Fans
2.1 Supply and installations of 240 V, 1-phase, 1440 RPM, sweep of appx. 400mm
Bracket fan including mounting bracket, blades, starters & other standard accessories complete as required.
3 Supplying and installations of 240 V single phase, 1400 mm sweep ceiling fans with electronic regulators including all standard accessories complete, mounting of
regulator on grid plate & MS BOX etc. and suitable length down rod, duly painted, not exceeding minimum fan height of 2.4 m from floor as
required and as below.

4 Supply, installation, testing and commissioning of exhaust fan with fan guards on both sides, double ball bearings, class-E insulation, capacitor (pf 0.90 or better),
complete with all other accessories as per IS 2312 and as required, of
following sizes:
4.1 size 450mm dia, 1400 rpm
4.2 size 300mm dia, 1400 rpm
5 Supply, installation, testing and commissioning of Air Circulation fan of size 600 mm including maitaining brackets blades & other accessories complete as
required.

TOTAL FOR E.05


Unit Quantity Rate Amount
without
GST
No. 950 0

No. 510 0

No. 200 0

No. 50 0

No. 300 0

No. 30 0

No. 200 0
No. 100 0

No. 100 0
No. 3 0
No. 43 0

No. 3 0

No. 7 0

No. 125 0

0
No. 150 0

No. 125 0

No. 11 0

No. 3 0

No. 1 0
No. 1 0
mtr. 400 0

Nos. 120 0

0
No. 25 0

No. 25 0

No. 750 0
No. 25 0

No. 0 0

No. 25 0

No. 25 0

No. 25 0

No. 25 0

No. 0 0
No. 25 0

No. 25 0

NO. 25 0

No. 5 0

No 5 0

0
No. 30 0
No. 15 0

No. 15 0
No. 15 0
No. 10 0

31,120,614