SG 40mbaa 01
SG 40mbaa 01
Service Manual
TABLE OF CONTENTS These words are used with the safety-alert symbol. DANGER
identifies the most serious of hazards which will result in severe
PAGE personal injury or death. WARNING signifies hazards which could
SAFETY CONSIDERATIONS ....................................................... 1 result in personal injury or death. CAUTION is used to identify
INTRODUCTION............................................................................ 1 unsafe practices which may result in minor personal injury or product
MODEL NUMBER NOMENCLATURE ....................................... 2 and property damage. NOTE is used to highlight suggestions which
SPECIFICATIONS .......................................................................... 3 will result in enhanced installation, reliability, or operation.
DIMENSIONS ................................................................................. 4
PART NAMES................................................................................. 5
CONNECTORS ............................................................................... 6
CLEARANCES................................................................................ 9
WARNING
ELECTRICAL DATA ..................................................................... 10
ELECTRICAL SHOCK HAZARD
WIRING ........................................................................................... 10
CONNECTION DIAGRAMS ......................................................... 11 Failure to follow this warning could result in personal injury or
death.
WIRING DIAGRAMS..................................................................... 12 Before installing, modifying, or servicing the unit, the main
FAN AND MOTOR SPECIFICATIONS ........................................ 15 electrical disconnect switch must be in the OFF position. There
REFRIGERATION CYCLE DIAGRAM........................................ 16 may be more than 1 disconnect switch. Lock out and tag switch
REFRIGERANT LINES .................................................................. 17 with a suitable warning label.
TROUBLESHOOTING................................................................... 18
DIAGNOSIS AND SOLUTION...................................................... 23
APPENDICES.................................................................................. 50
DISASSEMBLY INSTRUCTIONS ................................................ 52
WARNING
EXPLOSION HAZARD
SAFETY CONSIDERATIONS Failure to follow this warning could
result in death, serious personal
Installing, starting up, and servicing air-conditioning equipment can injury, and/or property damage.
be hazardous due to unit pressures, electrical components, and
Never use air or gases containing
equipment location (roofs, elevated structures, etc.). oxygen for leak testing or operating
Only trained, qualified installers and service mechanics should install, refrigerant compressors. Pressurized
start-up, and service this equipment. mixtures of air or gases containing
oxygen can lead to an explosion.
Untrained personnel can perform basic maintenance functions such as
coil cleaning. All other operations should be performed by trained
service personnel only.
When working on the equipment, observe the precautions in the
CAUTION
literature and on tags, stickers, and labels attached to the equipment.
EQUIPMENT DAMAGE HAZARD
Follow all safety codes. Wear safety glasses and work gloves. Keep a Failure to follow this caution may result in equipment damage
quenching cloth and fire extinguisher nearby when brazing. Use care or improper operation.
in handling, rigging, and setting bulky equipment. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
Read this manual thoroughly and follow all the warnings or cautions ground. If any section of pipe is buried, there must be a 6 in. (152
included in the literature and attached to the unit. Consult local mm) vertical rise to the valve connections on the outdoor units. If
building codes and the National Electrical Code (NEC) for special more than the recommended length is buried, refrigerant may
requirements. migrate to the cooler buried section during the extended periods
of unit shutdown. This causes refrigerant slugging and could
Recognize safety information. This is the safety-alert symbol .
possibly damage the compressor at start-up.
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION.
INTRODUCTION
This service manual provides the necessary information to service,
repair, and maintain the indoor units. This manual contains
“APPENDICES” on page 50 with data required to troubleshoot. Use the
“TABLE OF CONTENTS” on page 1 to locate a desired topic.
MODEL NUMBER NOMENCLATURE
Table 1 — Unit Sizes
KBTUH V-PH-HZ ID MODEL NO.
24 40MBAAQ24XA3
36 208/230-1-60 40MBAAQ36XA3
48 40MBAAQ48XA3
INDOOR UNIT
40 MB A A Q 24 X A 3
VOLTAGE
MB = MODEL
3 = 208/230-1-60
UNIT TYPE
C = COOLING ONLY
Q = Heat Pump
21 20 V 10001
*To be used only to set airflow in accordance with the installation manual.
Top View
D DUCT 18.2 [462]
E DUCT 10.3 [262]
2.2 [57]
21]
Ø0.8 [Ø
.3 [Ø 34]
Ø1
[Ø43]
Ø1.7
4.8 [121]
6.7 [171]
2.4 [61]
2.5 [64]
4.9 [124]
6.8 [174]
Rear Side View Front View Right Side View
D 18.2 [462] E 10.3 [262]
Air Outlet
Ø1
.
Ø1 7 [Ø
1.7 [44] Ø .3 [Ø 43]
0.
8 34]
[Ø
21
]
A HEIGHT 48.1 [1222]
G
as
Li
ne
Liq
Ø
uid
5/
8
Lin Blower
[Ø
eØ
16
3/8
]
[Ø
9.5
]
13.3 [339]
11.8 [299]
L1 Coil L2
Filter
Air Inlet
3.3 [84]
2.2 [55]
"
Bottom View
Nominal Filter Size
20 x 16 x 1 inches
(515 x 442 x 25 mm)
19.7 [500]
Fig. 1 — Dimensions
Coil Compartment
(Access Panel Removed)
Upflow Drain Pan
MINIMUM CLEARANCE
OF 1in (25.4mm) ALL SIDES
3.2ft/1M
FLEXIBLE
DUCT COLLAR
Fig. 3 — Service Section
Fig. 4 — Connectors
For the new motor terminal port (also for the Anion generator) CN43:
1. When the indoor blower is running, CN 43 will be powered on with line voltage (208 or 230). Use this connection to power a relay for controlling
a separate circuit for outdoor air fan or other peripheral.
2. When the unit enters force cooling mode or capacity testing mode, CN43 powers off.
Fig. 5 — Connectors
For ALARM terminal port CN33:
• When there is an alarm on the unit, the CN33 dry contacts close. May be used to control a pilot relay for an external alarm device.
Fig. 6 — Connectors
For remote control (ON-OFF) terminal port CN23 and short connector of J7
1. Remove the J7 short connector when using the ON-OFF function;
2. When the remote switch is off (OPEN); the system is off and the display displays “CP”;
3. When the remote switch is on (CLOSE); the system is on;
4. When the remote switch is closed or opened, the system responds to the command within 2 seconds.
Allow a minimum of 24in (60.9 cm) clearance from the access panels.
24in(60.9cm)
24in(60.9cm)
WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use the Electrical Data
CAUTION
table MCA (minimum circuit amps) and MOCP (maximum over
current protection) to correctly size the wires and the disconnect fuse EQUIPMENT DAMAGE HAZARD
or breakers respectively. Failure to follow this caution may result in equipment damage
or improper operation.
Recommended Connection Method for Power and Wires should be sized based on NEC and local codes.
Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3
stranded wire, with ground, has a 600 volt insulation rating and the power/
communication wiring from the outdoor unit to indoor unit consists of CAUTION
four (4) wires and provides the power for the indoor unit.
EQUIPMENT DAMAGE HAZARD
Two wires are line voltage AC power, one is communication wiring Failure to follow this caution may result in equipment damage
(S) and the other is a ground wire. Wiring between the indoor and or improper operation.
outdoor unit is polarity sensitive. The use of BX wire is NOT Be sure to comply with local codes while running wire from
recommended. the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may
If installed in a high Electromagnetic field (EMF) area and cause the terminal to overheat or result in unit malfunction. A
communication issues exists, a 14/2 stranded shielded wire can be fire hazard may also exist. Ensure all wiring is tightly
used to replace L2 and (S) between the outdoor unit and indoor unit connected. No wire should touch the refrigerant tubing,
landing the shield onto ground in the outdoor unit only. compressor or any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the unit. Connecting
cable with conduit shall be routed through the hole in the
conduit panel.
GND
208-230-1-60
CONNECTING CABLE FIELD POWER SUPPLY
OUTDOOR TO INDOOR
SHIELDED WIRE CONNECTING
OUTDOOR TO INDOOR
GND
L1 L2 P(S1) Q(S2) S1 S2 (1)L1 (2)L2 L1 L2
Indoor Unit Nonpolar RS-485 Nonpolar RS-485 To Indoor Unit Outdoor Unit
Power Supply communication communication Power Supply Power Supply
208-230-1-60 Low voltage Low voltage 208-230-1-60
Fig. 9 — Size 36K- 48K Indoor Unit
NOTES:
1. DO NOT use a thermostat wire for any connection between the indoor and outdoor units.
2. All connections between the indoor and outdoor units must adhere to the connections shown in figures 8 - 9. The connections are polarity
sensitive and improper wiring results in a fault code.
Display tube Set/outdoor only Unit type Anti-co ld Au x- heat /dry Freque ncy Time Set/indoor o nly Indoor co ntr ol
S W1- 1 SW 1-2 SW 2-1 SW2-2 S W3- 1 SW3-2 SW4-1 SW4-2
10 2 CN17
DI SPLAY CN13 M PU MP
BO ARD CN10
Y/G CN1 6
CN18 CN47 T2
INDOOR COIL TEMP. SENSOR
L1 L2 S
TO OUTDOOR UNIT
SG-40MBAA-01
WIRING DIAGRAMS (CONT)
Table 5 — Wiring Diagram Size 24K-48K
CODE INDOOR UNIT MAINBOARD CONNECTION
CN1 input: 230VAC High voltage
CN2 input: 230VAC High voltage
CN3 communication: 230VAC High voltage (24K only)
CN5 output: 0-5VDC water level switch connection
CN10 output: 12VDC display board connection
CN13 output: 220V AC for the pump
CN15 output: 220V AC for the fan
CN16 RS485 Communication to 24 volt interface 0-10VDC 36-48K only
CN18 output: 0V connection to the ground
CN23 output: 12VDC for the remote controller
CN24 output: 12VDC for the heater control board
CN33 output: 0V for the alarm
CN34 output: 15V DC for the driver board (danger)
CN43 output: 220VAC for the fresh air fan
CN46 input: 5V DC for the T1 sensor
CN47 input: 5V DC for the T2 sensor
CN3 4 CN1 5
CN24
CN43 CN33 CN23
Y/G T2
CN16
CN18 CN47
INDOOR COIL TEMP. SENSOR
3
CN46 T1
INDOOR UNIT ROOM TEMP. SENSOR
MAINBOARD CN15 CN18 CN19 AC:230V AC:24 V
CN16 C N 2 2 R C G1 G2 G3 Y W G CN 8
CN23 CN9-2 CN2 CN1 CN10
CN5 (S 1) P Q (S 2) E RE D BLUE
CN2
BL ACK
C N2 4 CN 1
RE D
CN40 7 C N40 1
A ux-Heat
RED
control sin gnal
BLACK RE D
Connector Purpose
R/C 24VAC Output
Y/G
L1 L2
NOTE:
TO OUTDOOR COMM. BUS
This symbol indicates the element is TO OUTDOOR UNIT
optional, the actual shape shall prevail.
SG-40MBAA-01
FAN AND MOTOR SPECIFICATIONS
Airflow Specifications
INDOOR O UT DO O R
EXV
LIQUID SIDE
2- WAY VALVE
HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
T1 Room temp.
sensor
T2 Evaporator
temp. sensor
GAS SIDE
4- WAY VALVE
3- WAY VALVE
ACCUMULATOR
COOLING
COMPRESSOR
HEATING
WARNING
Electricity remains in capacitors even when the power supply is off.
Ensure the capacitors are fully discharged before troubleshooting.
For other errors: The display board may display a garbled code or a code undefined by the service manual. Ensure the code is not a
temperature reading.
Standby:0, Fan only 1,Cooling:2, Heating:3, Forced Cooling:4, Drying:6, Self Clean:8, Forced
12 Indoor unit running mode code Defrosting:10
Standby:0, Fan only 1,Cooling:2, Heating:3, Forced Cooling:4, Drying:6, Self Clean:8, Forced
13 Outdoor unit running mode code Defrosting:10
Actual data/4. If the value is higher than 99, the digital display tube displays a single digit and tens
14 EXV open angle digit. For example, the digital display tube displays “2.0”, it means the EXV open angle is 120x4=480p.
Frequency limit caused by IGBT
Bit7 radiator
Bit5 Frequency limit caused by T4. The display value is a hexadecimal number.
Bit4 Frequency limit caused by T2. For example, the digital display shows 2A, then
15 Frequency limit symbol Bit5=1, Bit3=1, and Bit1=1.
Bit3 Frequency limit caused by T3.
This means that a frequency limit may be caused
Bit2 Frequency limit caused by T5. by T4, T3, or the current.
16 Outdoor unit fan motor state Off: 0, Turbo:1 High speed:2, Med speed: 3, Low speed: 4, Breeze:5, Super breeze: 6 other speed:7
The display value is between 30~120 degrees. If the temperature is lower than 30 degrees, the digital
display tube displays “30”. If the temperature is higher than 99 degrees, the digital display tube
17 IGBT radiator temperature displays a single digit and a tens digit. (For example, the digital display tube displays “0.5”, it means
the IGBT radiator temperature is 105 degrees. The digital display tube displays “1.6”, it means the
IGBT radiator temperature is 116 degrees.
18 Indoor unit number The indoor unit can communicate with outdoor unit well. General:1, Twins:2
19 Evaporator pipe temp. T2 of 1# indoor unit
If the temperature is lower than 0 degree, the digital display tube displays “0”.
20 Evaporator pipe temp. T2 of 2# indoor unit If the temperature is higher than 70 degrees, the digital display tube displays “70”. If the indoor unit is
not connected, the digital display tube displays: “--”
21 Evaporator pipe temp. T2 of 3# indoor unit
22 1# Indoor unit capacity demand code Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube displays a single digit and tens
23 2# Indoor unit capacity demand code digit. (For example, the digital display tube displays “5.0”, it means the capacity demand is 15. the
digital display tube show “60”, it means the capacity demand is 6.0). If the indoor unit is not connected,
24 3# Indoor unit capacity demand code the digital display tube displays: “--”
25 Room temp. T1 of 1# indoor unit
26 Room temp. T1 of 2# indoor unit If the temperature is lower than 0 degree, the digital display tube displays “0”. If the temperature is
higher than 70 degree, the digital display tube displays “70”. If the indoor unit is not connected, the
27 Average room temp. T1 digital display tube displays: “--”
28 Reason of stop
29 Evaporator pipe temp. T2B of 1# indoor unit If the temperature is lower than 0 degree, the digital display tube displays “0”.If the temperature is
higher than 70 degree, the digital display tube displays “70”. If the indoor unit is not connected, the
30 Evaporator pipe temp. T2B of 2# indoor unit digital display tube displays: “--”
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box should be replaced as
a whole.
Is it sƟůů
displaying the No The unit is operaƟng normally.
error code?
Yes
Yes
For units
with W wire
Turn on the unit, check if W No
The value is always positive
and 1(L) is connected.
No
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control
box should be replaced as a whole.
Fig. 14 — Multimeter Test NOTE: The picture and the value are only for reference,
actual condition and specific value may vary.
• Use a multimeter to test the reactor resistance which does not connect
with the capacitor.
• The normal value should be around zero ohm. Otherwise, the reactor
may malfunction.
Power off.
Restart the unit 2 minutes later.
Yes
No
Yes
Yes
Check whether the signal wire is broken. Yes Replace the signal wire.
No
Yes
No
YES
Shut off the power supply.
Rotate the fan by hand.
Does it turn easily? NO Find the cause of the problem and resolve it.
YES
YES
YES
YES
Measure the sensor’s
resistance value.
Is it within
acceptable parameters? NO Replace the sensor.
YES
Fig. 17 — Test
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole. Figure 17 and the value are for reference only. The actual appearance and value
may vary.
YES
YES
Is the water-level
NO Replace the water-level switch.
switch broken?
YES
YES
Does the
problem still exist?
YES
NO
NO
Yes
Yes
Yes
Yes
YES
No
YES
YES
YES
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole.
YES
No
Yes
Yes
Is the voltage between L and N normal? No Are L and N wired correctly? Reconnect L and N.
Yes
Yes
Yes
Yes
Is the compressor’s connecting
wire between the main Reconnect the main board Replace the PFC module
board and the IPM board No
and the IPM board. (if this has not been done already).
connected correctly (tight)?
Yes No
Yes
Are the reactor or Replace the reactor
Refer to the “Fan Speed Out of Control” inductance normal? No
or inductance.
Is the outdoor fan running properly? No malfunction solution. Determine the
cause and resolve the problem.
Yes
No
No
Is the compress
running normally? No Replace
Replace the
the compressor
compressor
Yes
Voltage protection
Yes
Measure whether the outdoor Are the power wires Reconnect the
No No
terminal voltage is normal. well connected? wires well.
Yes
Yes
Measure whether the input voltage Is the bridge rectifier Reconnect the
No
of the bridge rectifier is normal. wiring well connected? wires well.
Yes
Check whether
Measure whether the voltage between No the bridge rectifier is No Replace the bridge rectifier.
P and N is normal. well connected?
Yes
No
Yes
Check the reactor
or inductance wiring. No Reconnect the wiring.
Yes
Replace the IPM board. If the IPM board Check whether the
Replace the reactor
and the main board is in a board, Yes reactor or inductance is No
or inductance.
replace the outdoor main PCB. normal.
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control
box should be replaced as a whole.
No
Yes
Repair the
Replace the outdoor control PCB.
refrigerant system.
NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole.
NO
YES
NO
YES
YES
NO
YES
Refer to the
“Fan Speed Out ofControl”
Is it running normally? NO solution. Determine the cause
and resolve the problem.
YES
Check the heat
exchanger
and filter.
NO
YES
Correct the
Check the outdoor ambient temperature. Is it in working order? NO
connection.
Is it higher than
YES Stop the unit. YES
122°F(50°C)?
YES
NO
Replace the outdoor main board. YES
NO
Check if the refrigerant level is sufficient.
If not, add more refrigerant.
YES
Check whether the refrigerant
system is functioning normally.
Temperature protection of
compressor discharge
Is the
compressor
discharge temperature Is refrigerant Stop the leak and add
YES YES
higher than 239°F (115°C)? leaking? refrigerant.
NO
NO
YES
YES
YES
NO
Measure the voltage
between P and N.
NO
Check the PFC module inductance.
If the inductance is good, the resistance
of the two ports is 0.
YES
NO
Is is connected YES
properly?
NO
YES
Reconnect and retry?
NO
NO
Replace the
compressor driven chip.
Is the system
running normally? YES
NO
Is the system
running normally? YES
NO
Are
the high
pressure switch and main Connect the high pressure switch
control board wired and main control board.
correctly?
YES
Is it higher than
YES Stop the unit.
122°F (50°C)?
NO
Check if the outdoor unit
ventilation is good
Ensure that the outdoor
Is it good? NO unit ventilation functions
properly.
YES
Check the outdoor fan.
NO
Replace the outdoor main board.
NO
Check whether the refrigerant
system is functioning properly.
YES
Measure the outdoor terminal voltage.
YES
Determine whether the voltage
between P and N is normal.
Refer to Appendix 3.
Check whether
Is it normal? NO the bridge rectifier Replace the bridge rectifier.
is normal.
YES
Replace the PFC module (if equipped)
NO
YES
Check the reactor
or inductance wiring. Reconnect the wiring.
YES
NOTE:
No: No mode conflict
Yes: Mode conflict
WARNING
Turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in
case of injury.
Table 16 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (°C--K)
°C °F K OHM °C °F K OHM °C °F K OHM °C °F K OHM
-20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231
1. Remove the upside board screws (6) and then remove the
upside plate.
2. Remove the electrical control box cover screws (4) and then
remove the cover.
3. Release the nuts (3) securing the fan motor and then remove
the fan.
4. Remove the nut (1) securing the fan and then remove the fan.
2. Remove the pipe clamp board screw (1) and the rear support
board screws (3).
Big Handle
Top Cover
PROCEDURES ILLUSTRATION
4. Remove the front panel screws (7) and then remove the front
panel.
Front Panel
PROCEDURES ILLUSTRATION
6. Remove the rear net screws (2) and then remove the rear net.
7. Remove the right panel screws and then remove the right
panel.
Right Panel
PROCEDURES ILLUSTRATION
Big Handle
Top Cover
3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located underneath the big
handle.
PROCEDURES ILLUSTRATION
4. Remove the front panel screws (8) and then remove the front
panel.
Front Panel
5. Remove the screw (1) from the water collecting cover then
remove the water collecting cover.
PROCEDURES ILLUSTRATION
6. Remove the rear net screws (2) and then remove the rear net.
7. Remove the right panel screws (5) and then remove the right
panel.
Right Panel
PROCEDURES ILLUSTRATION
Big Handle
Top Cover
3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located under the big handle.
PROCEDURES ILLUSTRATION
4. Remove the front panel screws (7) and then remove the front
panel.
Front Panel
PROCEDURES ILLUSTRATION
6. Remove the rear net screws (2) and then remove the rear net.
7. Remove the right panel screws (7) and then remove the right
panel.
Right Panel
PROCEDURES ILLUSTRATION
Big Handle
Top Cover
3. Remove the top cover screws (4) and then remove the top
cover. Two of the screws are located under the big handle.
PROCEDURES ILLUSTRATION
4. Remove the front panel screws (2) and then remove the front
right panel screws.
5. Remove the front panel screws (9) and then remove the front
panel.
Front Panel
PROCEDURES ILLUSTRATION
7. Remove the rear net screws (2) and then remove the rear net.
8. Remove the right panel screws (8) and then remove the right
panel.
Right Panel
PROCEDURES ILLUSTRATION
3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located under the big handle.
PROCEDURES ILLUSTRATION
5. Remove the front panel screws (6) and then remove the front
panel (6 screws - on/off models) (8 screws - inverter
models).
6. Remove the right panel screws (6) and then remove the right
panel.
PROCEDURES ILLUSTRATION
3. Remove the top cover screws (4) and then remove the top
cover. Two of the screws are located underneath the big
handle.
PROCEDURES ILLUSTRATION
5. Remove the front right panel screws (2) and then remove the
front panel.
PROCEDURES ILLUSTRATION
1. Remove the front right panel screws (7) and then remove the
front panel.
2. Remove the right panel screws (10) and remove the right
panel.
PROCEDURES ILLUSTRATION
2. Unfasten the hooks (4) and then open the electronic box
cover.
4-Way Valve
PROCEDURES ILLUSTRATION
1. Unfasten the hooks (4) and then open the electronic control
box cover.
4-Way Valve
Reactor DR
2. Disconnect the fan motor connector from the electronic
control board.
3. Remove the compressor connector.
4. Pull out the two blue wires connected to the four-way valve.
5. Remove the connectors of the condenser coil temperature
sensor (3), outdoor ambient temperature sensor (T4) and the
discharge temperature sensor (TP).
6. Disconnect the electronic expansion valve wire.
7. Remove the electronic control board.
Compressor
T3, T4, TP
PROCEDURES ILLUSTRATION
1. Remove the screws (5) and unfasten the hooks (2) and then
open the electronic box cover.
PROCEDURES ILLUSTRATION
2. Unfasten the hooks (5) and then open the electronic control
box cover.
3. Disconnect the fan motor connector from the IPM board. Compressor
4. Remove the compressor connector.
PROCEDURES ILLUSTRATION
T3/T4
Terminal
Reactor
PROCEDURES ILLUSTRATION
1. Unfasten the hooks (4) and then open the electronic control
box.
PROCEDURES ILLUSTRATION
1. Unfasten the hooks (4) and then open the electronic control
box.
PROCEDURES ILLUSTRATION
1. Unfasten the hooks (4) and then open the electronic control
box cover.
2. Remove the screws (4) from the electronic control board and
then turn over the electronic control board.
PROCEDURES ILLUSTRATION
6. Remove the screws (2) and the connectors (2) and then
remove the inverter control board.
Connect to CN301
Connect to FM1
PROCEDURES ILLUSTRATION
PROCEDURES ILLUSTRATION
PROCEDURES ILLUSTRATION
PROCEDURES ILLUSTRATION
1. Unfasten the hooks (4) and then open the electronic control
box cover.
PROCEDURES ILLUSTRATION
PROCEDURES ILLUSTRATION
PROCEDURES ILLUSTRATION
Sound Blanket(side)
WARNING
EVACUATE THE SYSTEM
Evacuate the system and confirm that there is no refrigerant
remaining in the system before removing the four-way valve and
the compressor.
NOTE: Remove the panel plate and the four-way valve connection before disassembling the sound blanket.
PROCEDURES ILLUSTRATION
1. Heat up the brazed parts and then detach the four-way valve
and the pipe.
2. Remove the four-way valve assembly with pliers.
WARNING
EVACUATE THE SYSTEM
Evacuate the system and confirm that there is no refrigerant
remaining in the system before removing the four-way valve and
the compressor.
NOTE: Remove the panel plate and the compressor connection to the PCB before disassembling the sound blanket.
PROCEDURES ILLUSTRATION
Terminal Cover
1. Remove the terminal cover flange nut and then remove the
terminal cover.
2. Disconnect the connectors.
PROCEDURES ILLUSTRATION
Suction Pipe
Discharge Pipe
4. Heat up the brazed parts and then remove the discharge pipe
and the suction pipe.
5. Lift the compressor from the base pan assembly with pliers.
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: NEW