0% found this document useful (0 votes)
57 views94 pages

SG 40mbaa 01

Uploaded by

hpinet
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
57 views94 pages

SG 40mbaa 01

Uploaded by

hpinet
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 94

40MBAA

Air Handler Unit Ductless System


Sizes 24 to 48

Service Manual
TABLE OF CONTENTS These words are used with the safety-alert symbol. DANGER
identifies the most serious of hazards which will result in severe
PAGE personal injury or death. WARNING signifies hazards which could
SAFETY CONSIDERATIONS ....................................................... 1 result in personal injury or death. CAUTION is used to identify
INTRODUCTION............................................................................ 1 unsafe practices which may result in minor personal injury or product
MODEL NUMBER NOMENCLATURE ....................................... 2 and property damage. NOTE is used to highlight suggestions which
SPECIFICATIONS .......................................................................... 3 will result in enhanced installation, reliability, or operation.
DIMENSIONS ................................................................................. 4
PART NAMES................................................................................. 5
CONNECTORS ............................................................................... 6
CLEARANCES................................................................................ 9
WARNING
ELECTRICAL DATA ..................................................................... 10
ELECTRICAL SHOCK HAZARD
WIRING ........................................................................................... 10
CONNECTION DIAGRAMS ......................................................... 11 Failure to follow this warning could result in personal injury or
death.
WIRING DIAGRAMS..................................................................... 12 Before installing, modifying, or servicing the unit, the main
FAN AND MOTOR SPECIFICATIONS ........................................ 15 electrical disconnect switch must be in the OFF position. There
REFRIGERATION CYCLE DIAGRAM........................................ 16 may be more than 1 disconnect switch. Lock out and tag switch
REFRIGERANT LINES .................................................................. 17 with a suitable warning label.
TROUBLESHOOTING................................................................... 18
DIAGNOSIS AND SOLUTION...................................................... 23
APPENDICES.................................................................................. 50
DISASSEMBLY INSTRUCTIONS ................................................ 52
WARNING
EXPLOSION HAZARD
SAFETY CONSIDERATIONS Failure to follow this warning could
result in death, serious personal
Installing, starting up, and servicing air-conditioning equipment can injury, and/or property damage.
be hazardous due to unit pressures, electrical components, and
Never use air or gases containing
equipment location (roofs, elevated structures, etc.). oxygen for leak testing or operating
Only trained, qualified installers and service mechanics should install, refrigerant compressors. Pressurized
start-up, and service this equipment. mixtures of air or gases containing
oxygen can lead to an explosion.
Untrained personnel can perform basic maintenance functions such as
coil cleaning. All other operations should be performed by trained
service personnel only.
When working on the equipment, observe the precautions in the
CAUTION
literature and on tags, stickers, and labels attached to the equipment.
EQUIPMENT DAMAGE HAZARD
Follow all safety codes. Wear safety glasses and work gloves. Keep a Failure to follow this caution may result in equipment damage
quenching cloth and fire extinguisher nearby when brazing. Use care or improper operation.
in handling, rigging, and setting bulky equipment. Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
Read this manual thoroughly and follow all the warnings or cautions ground. If any section of pipe is buried, there must be a 6 in. (152
included in the literature and attached to the unit. Consult local mm) vertical rise to the valve connections on the outdoor units. If
building codes and the National Electrical Code (NEC) for special more than the recommended length is buried, refrigerant may
requirements. migrate to the cooler buried section during the extended periods
of unit shutdown. This causes refrigerant slugging and could
Recognize safety information. This is the safety-alert symbol .
possibly damage the compressor at start-up.
When you see this symbol on the unit and in instructions or manuals,
be alert to the potential for personal injury. Understand these signal
words: DANGER, WARNING, and CAUTION.
INTRODUCTION
This service manual provides the necessary information to service,
repair, and maintain the indoor units. This manual contains
“APPENDICES” on page 50 with data required to troubleshoot. Use the
“TABLE OF CONTENTS” on page 1 to locate a desired topic.
MODEL NUMBER NOMENCLATURE
Table 1 — Unit Sizes
KBTUH V-PH-HZ ID MODEL NO.
24 40MBAAQ24XA3
36 208/230-1-60 40MBAAQ36XA3
48 40MBAAQ48XA3

INDOOR UNIT
40 MB A A Q 24 X A 3

40 = INDOOR DUCTLESS UNIT

VOLTAGE
MB = MODEL
3 = 208/230-1-60

INDOOR FAN COIL UNIT TYPE


A = AIR HANDLER

MAJOR SERIES A = STANDARD

UNIT TYPE
C = COOLING ONLY
Q = Heat Pump

NOMINAL CAPACITY MAXIMUM NUMBER OF FAN COIL UNITS


24 - 2 TON CONNECTED TO THE OUTDOOR UNIT
36 - 3 TON A=1:1
48 - 4 TONS

21 20 V 10001

Week of Manufacture Sequential Serial Number

Year of Manufacture V = ALL MODELS

Use of the AHRI Certified


TM Mark indicates a
manufacturer’s
participation in the
program For verification
of certification for individual
products, go to
www.ahridirectory.org.

2 Specifications subject to change without notice. SG-40MBAA-01


SPECIFICATIONS
Table 2 — Specifications
SIZE 24K 36K 48K
SYSTEM
Indoor Model 40MBAAQ24XA3 40MBAAQ36XA3 40MBAAQ48XA3
Voltage, Phase, Cycle V/Ph/Hz 208/230-1-60
Power Supply Indoor unit powered from outdoor unit
Electrical
MCA A. 6.0 6.0 6.0
MOCP 15.0 15.0 15.0
Controls* Wireless Remote Control (°F/°C Convertible) Standard Standard Standard
Operating Range Cooling Indoor DB Min - Max °F (°C) 62~90 (17~32) 62~90 (17~32) 62~90 (17~32)
Pipe Connection Size - Liquid in (mm) 3/8” (9.52) 3/8” (9.52) 3/8” (9.52)
Piping
Pipe Connection Size - Suction in (mm) 5/8” (16) 5/8” (16) 5/8” (16)
Face Area (sq. ft.) Sq. Ft. 1.69 1.69 1.69
Indoor Coil No. Rows 2 4 4
Circuits 4 8 8
Unit Width in (mm) 51.18 (1,300) 51.18 (1,300) 51.18 (1,300)
Unit Height in (mm) 24.61 (625) 24.61 (625) 24.61 (625)
Unit Depth in (mm) 22.44 (570) 22.44 (570) 22.44 (570)
Net Weight lbs (kg) 141.09 (64) 144.84 (65.7) 144.84 (65.7)
Indoor Fan speed number 3 3 3
Airflow (lowest to highest) CFM 588/765/882 824/1000/1176 1176/1294/1412
Sound Pressure (lowest to highest) dB(A) 43/40.4/37.2 46.5/43/37.9 53.9/51.9/50
Moisture removal Pint/h (L/h) 3.16pint/hour 7.67pint/hour 11.98 pint/hour
Field Drain Pipe Size O.D. in (mm) 3/4 inch 3/4 inch 3/4 inch
Performance may vary based on the compatible outdoor units. See the respective pages on the outdoor unit's product data for performance data.

*To be used only to set airflow in accordance with the installation manual.

SG-40MBAA-01 Specifications subject to change without notice. 3


DIMENSIONS
Table 3 — Dimensions
UNIT SIZE 24K 36K 48K
Height in (mm) 48.82 (1,240) 48.82 (1,240) 48.82 (1,240)
Width in (mm) 19.61 (498) 19.61 (498) 19.61 (498)
Depth in (mm) 20.98 (533) 20.98 (533) 20.98 (533)
Operating Weight lbs (kg) 141.09 (64) 144.84 (65.7) 144.84 (65.7)
Shipping Weight lbs (kg) 156.09 (70.8) 160.27 (72.7) 159.83(72.5)
Shipping Height in (mm) 24.61 (625) 24.61 (625) 24.61 (625)
Shipping Width in (mm) 51.18 (1,300) 51.18 (1,300) 51.18 (1,300)
Shipping Depth in (mm) 22.44 (570) 22.44 (570) 22.44 (570)

Top View
D DUCT 18.2 [462]
E DUCT 10.3 [262]

2.2 [57]
21]
Ø0.8 [Ø
.3 [Ø 34]
Ø1
[Ø43]
Ø1.7
4.8 [121]
6.7 [171]
2.4 [61]

2.5 [64]
4.9 [124]
6.8 [174]
Rear Side View Front View Right Side View
D 18.2 [462] E 10.3 [262]
Air Outlet

Ø1
.
Ø1 7 [Ø
1.7 [44] Ø .3 [Ø 43]
0.
8 34]

21
]
A HEIGHT 48.1 [1222]
G
as
Li
ne

Liq
Ø

uid
5/
8

Lin Blower


16

3/8
]


9.5
]
13.3 [339]

11.8 [299]

L1 Coil L2

Filter
Air Inlet
3.3 [84]

3.0 [75] B DEPTH 21.1 [535]


1.2 [30]
2.3 [59]

2.2 [55]
"

C WIDTH 19.7 [501]


0.5 [13]

Bottom View
Nominal Filter Size
20 x 16 x 1 inches
(515 x 442 x 25 mm)
19.7 [500]

0.6 [16] 18.4 [466]


0.8 [21]

Fig. 1 — Dimensions

4 Specifications subject to change without notice. SG-40MBAA-01


PART NAMES

Coil Compartment
(Access Panel Removed)
Upflow Drain Pan

Horizontal Drain Pan


Fig. 2 —Part Names

MINIMUM CLEARANCE
OF 1in (25.4mm) ALL SIDES

3.2ft/1M
FLEXIBLE
DUCT COLLAR
Fig. 3 — Service Section

SG-40MBAA-01 Specifications subject to change without notice. 5


CONNECTORS

Fig. 4 — Connectors

For the new motor terminal port (also for the Anion generator) CN43:
1. When the indoor blower is running, CN 43 will be powered on with line voltage (208 or 230). Use this connection to power a relay for controlling
a separate circuit for outdoor air fan or other peripheral.
2. When the unit enters force cooling mode or capacity testing mode, CN43 powers off.

6 Specifications subject to change without notice. SG-40MBAA-01


CONNECTORS (CONT.)

Fig. 5 — Connectors
For ALARM terminal port CN33:
• When there is an alarm on the unit, the CN33 dry contacts close. May be used to control a pilot relay for an external alarm device.

SG-40MBAA-01 Specifications subject to change without notice. 7


CONNECTORS (CONT.)

Fig. 6 — Connectors

For remote control (ON-OFF) terminal port CN23 and short connector of J7
1. Remove the J7 short connector when using the ON-OFF function;
2. When the remote switch is off (OPEN); the system is off and the display displays “CP”;
3. When the remote switch is on (CLOSE); the system is on;
4. When the remote switch is closed or opened, the system responds to the command within 2 seconds.

8 Specifications subject to change without notice. SG-40MBAA-01


CLEARANCES

Allow a minimum of 24in (60.9 cm) clearance from the access panels.

24in(60.9cm)

24in(60.9cm)

Vertical Upflow Installations Horizontal Installations


Fig. 7 — Clearances

SG-40MBAA-01 Specifications subject to change without notice. 9


ELECTRICAL DATA
Table 4 — Electrical Data
HIGH WALL UNIT INDOOR FAN
MAX FUSE CB AMP
SIZE V-PH-HZ FLA HP W
24K 5 0.20 120
Refer to outdoor unit installation instructions –
36K 208/230-1-60 5 0.42 250
Indoor unit powered by the outdoor unit
48K 5 0.65 400
LEGEND
FLA - Full Load Amps

WIRING
All wires must be sized per NEC (National Electrical Code) or CEC
(Canadian Electrical Code) and local codes. Use the Electrical Data
CAUTION
table MCA (minimum circuit amps) and MOCP (maximum over
current protection) to correctly size the wires and the disconnect fuse EQUIPMENT DAMAGE HAZARD
or breakers respectively. Failure to follow this caution may result in equipment damage
or improper operation.
Recommended Connection Method for Power and Wires should be sized based on NEC and local codes.
Communication Wiring:
The main power is supplied to the outdoor unit. The field supplied 14/3
stranded wire, with ground, has a 600 volt insulation rating and the power/
communication wiring from the outdoor unit to indoor unit consists of CAUTION
four (4) wires and provides the power for the indoor unit.
EQUIPMENT DAMAGE HAZARD
Two wires are line voltage AC power, one is communication wiring Failure to follow this caution may result in equipment damage
(S) and the other is a ground wire. Wiring between the indoor and or improper operation.
outdoor unit is polarity sensitive. The use of BX wire is NOT Be sure to comply with local codes while running wire from
recommended. the indoor unit to the outdoor unit.
Every wire must be connected firmly. Loose wiring may
If installed in a high Electromagnetic field (EMF) area and cause the terminal to overheat or result in unit malfunction. A
communication issues exists, a 14/2 stranded shielded wire can be fire hazard may also exist. Ensure all wiring is tightly
used to replace L2 and (S) between the outdoor unit and indoor unit connected. No wire should touch the refrigerant tubing,
landing the shield onto ground in the outdoor unit only. compressor or any moving parts.
Disconnecting means must be provided and shall be located
within sight and readily accessible from the unit. Connecting
cable with conduit shall be routed through the hole in the
conduit panel.

10 Specifications subject to change without notice. SG-40MBAA-01


CONNECTION DIAGRAMS
208-230-1-60
CONNECTING CABLE FIELD POWER SUPPLY
OUTDOOR TO INDOOR

GND

1(L1) 2(L2) 3(S) GND 1(L1) 2(L2) 3(S) L1 L2


Indoor Unit Indoor Indoor
Power to Signal Main
Power Supply Signal Ground
High Indoor Unit High Power Supply
208/230-1-60 Voltage 208/230-1-60 Voltage 208/230-1-60
Fig. 8 — Size 24K Indoor Unit

208-230-1-60
CONNECTING CABLE FIELD POWER SUPPLY
OUTDOOR TO INDOOR
SHIELDED WIRE CONNECTING
OUTDOOR TO INDOOR
GND
L1 L2 P(S1) Q(S2) S1 S2 (1)L1 (2)L2 L1 L2
Indoor Unit Nonpolar RS-485 Nonpolar RS-485 To Indoor Unit Outdoor Unit
Power Supply communication communication Power Supply Power Supply
208-230-1-60 Low voltage Low voltage 208-230-1-60
Fig. 9 — Size 36K- 48K Indoor Unit
NOTES:
1. DO NOT use a thermostat wire for any connection between the indoor and outdoor units.
2. All connections between the indoor and outdoor units must adhere to the connections shown in figures 8 - 9. The connections are polarity
sensitive and improper wiring results in a fault code.

SG-40MBAA-01 Specifications subject to change without notice. 11


12
Size 24K

Display tube Set/outdoor only Unit type Anti-co ld Au x- heat /dry Freque ncy Time Set/indoor o nly Indoor co ntr ol
S W1- 1 SW 1-2 SW 2-1 SW2-2 S W3- 1 SW3-2 SW4-1 SW4-2

   Outdo or Heat Cooling Indoor Fan Fan


Mode OFF ON Set Mode YES NO Mode Aux-hea t Set Mode 3H 1H Mode Se t/out- only Mode High
Mode only Mode pump only door only Middle
Factory Factory Fac to ry Factory Factory Factory Factory Factory
default default defau lt default default default d efault d efault
3 NOTE:
1.The parts with dotted line indicates NOTE: If the SW4-1 is on,the SW4-2 will take
FAN F OR THE
WIRING DIAGRAMS

FR ESH A IR optional features. effect,or the SW1-2 will take effect.


OR ANIO N Alarm Remo te
FAN1 GE NERATOR Ou tp u t Cont ro l 2.Remove the short connector of J7
when you use the "ON-OFF" function.
DC MOTOR
M
DRIVER MODLE
DC FAN CN1 CON 1 24V INTERFAC E MODULE
4 3
Y/G
CN3 4 CN1 5 ALAR M O N/O FF J7
CN2 4
CN43 CN3 3 CN2 3

10 2 CN17
DI SPLAY CN13 M PU MP
BO ARD CN10

Y/G CN1 6
CN18 CN47 T2
INDOOR COIL TEMP. SENSOR

CN46 T1 CN18 CN19


INDOOR UNIT ROOM TEMP. SENSOR CN 22 CN15 G1 G2 G3 Y W G
R C AC:23 0V AC:24V
MAINBOARD CN2 3 CN 21 CN 20
CN2 CN1 CN10
CN5 RED BLUE
CN3 YE LLOW
CN2
BL ACK
C N2 4 CN 1
RE D

CN40 7 C N40 1 24V THERMOSTAT


YE LLO W

Specifications subject to change without notice.


24V ∼ B LUE
Aux-Heat
con trol singn al
RE D
RED

Fig. 10 — Wiring Diagram Size 24K


BLACK Connector Purpose YELLOW
R/C 24VAC Output
NOTE:
Cooling
NOTE: This symbol indicates the element is
Y
W Heating Aux-he at optional. The actual shape prevails.
G Fan-Auto speed
control signal
6 2 4 AUX/DRY Aux-Hea t/Dry

L1 L2 S

TO OUTDOOR UNIT

SG-40MBAA-01
WIRING DIAGRAMS (CONT)
Table 5 — Wiring Diagram Size 24K-48K
CODE INDOOR UNIT MAINBOARD CONNECTION
CN1 input: 230VAC High voltage
CN2 input: 230VAC High voltage
CN3 communication: 230VAC High voltage (24K only)
CN5 output: 0-5VDC water level switch connection
CN10 output: 12VDC display board connection
CN13 output: 220V AC for the pump
CN15 output: 220V AC for the fan
CN16 RS485 Communication to 24 volt interface 0-10VDC 36-48K only
CN18 output: 0V connection to the ground
CN23 output: 12VDC for the remote controller
CN24 output: 12VDC for the heater control board
CN33 output: 0V for the alarm
CN34 output: 15V DC for the driver board (danger)
CN43 output: 220VAC for the fresh air fan
CN46 input: 5V DC for the T1 sensor
CN47 input: 5V DC for the T2 sensor

Table 6 — Wiring Diagram Size 24K-48K


CODE 24 VOLT INTERFACE CONNECTION
CN1 input: 230VAC High voltage
CN2 input: 230VAC High voltage
CN6 output: 0V for the work
CN7 output: 0V for the alarm
CN8 RS485 Communication to Indoor Unit 0 - 10 VDC 36-48K only
CN9-2 RS485 Communication to Outdoor Unit 0-10 VDC 36-48K only
CN10 input: 24V for the 24V interface board
CN14 output: 12VDC for the remote controller
CN15 output: 24VAC for the 24V thermostat
CN16 output: 24VAC for the heater control
CN17 output: 25VAC for the heater control
CN18 input: 24VAC for the fan control
CN19 input: 24VAC for the mode control
CN20 communication: 230VAC High voltage “S” outdoor 24K only
CN21 communication: 230VAC High voltage “S” Indoor 24K only
CN22 input:24VAC for the AUX
CN23 output: 0V connection to the ground
CN24 input: 230VAC High voltage

SG-40MBAA-01 Specifications subject to change without notice. 13


14
Display tube Set/outdoor only Unit typ e Anti-cold Aux-hea t/dry Frequency Time Set/ indoor only
SW1-1 SW1-2 SW2-1 SW2-2 SW3-1 SW3-2 SW4-1

6 2 4    Outdoor Heat Cooling Set/out- Indoor


Mode OFF ON Mode only Set Mode p ump only Mode YES NO Mode Aux-heat Set Mode 3H 1H Mode door only
only
Factory Factory Factory Factory Factory Factory Factory
default default d efault default default default default
3
FAN F OR THE Indoor c ontrol
FR ESH A IR
NOTE: If the SW4-1 is on,the SW4-2 will take
OR ANIO N Alarm Remo te NOTE:
FAN1 GE NERATOR Ou tp u t Cont ro l 1.The parts with dotted line indicates SW4-2 effect,or the SW1-2 will take effect.
M DC MOTOR optional features.
DRIVER MODLE Fan Fan
2.Remove the short connector of J7 Mode High
DC FAN when you use the "ON-OFF" function. Middle
CN1 CON 1
Factory
4 3 default
Y/G
ALARM ON /OFF J7
WIRING DIAGRAMS (CONT)

CN3 4 CN1 5
CN24
CN43 CN33 CN23

10 2 CN17 24V INTERFAC E MODULE


DI SPLAY CN13 M PU MP
BO ARD CN10

Y/G T2
CN16
CN18 CN47
INDOOR COIL TEMP. SENSOR
3
CN46 T1
INDOOR UNIT ROOM TEMP. SENSOR
MAINBOARD CN15 CN18 CN19 AC:230V AC:24 V
CN16 C N 2 2 R C G1 G2 G3 Y W G CN 8
CN23 CN9-2 CN2 CN1 CN10
CN5 (S 1) P Q (S 2) E RE D BLUE

CN2
BL ACK
C N2 4 CN 1
RE D

CN40 7 C N40 1

Specifications subject to change without notice.


YE LLO W
2 4V THERMO STAT
24V ∼ BLUE

A ux-Heat
RED
control sin gnal
BLACK RE D
Connector Purpose
R/C 24VAC Output

Fig. 11 — Wiring Diagram Sizes 36K - 48K


Cooling
NOTE:
Y
W Heating Aux-he at
G Fan-Auto speed
AUX/DRY Aux-Heat/Dry control signal

Y/G
L1 L2

NOTE:
TO OUTDOOR COMM. BUS
This symbol indicates the element is TO OUTDOOR UNIT
optional, the actual shape shall prevail.

SG-40MBAA-01
FAN AND MOTOR SPECIFICATIONS

Table 7 — Fan and Motor Specifications


DUCTED SIZE 24K 36K 48K
(208/230 V) (208/230 V) (208/230 V)
Material Metal Metal Metal
INDOOR Type LX-282*245*12.7-49J-B LX-282*245*12.7-49J-B LX-282*245*12.7-49J-B
FAN Diameter inch 11.1 11.1 11.1
Height inch 9.65 9.65 9.65
Model ZKFN-600-10-1 ZKFN-600-10-1 ZKFN-600-10-1
Volts V 208/230 208/230 208/230
Type DC DC DC
Phase 3 3 3
FLA 5 5 5
Insulation class B B B
Safe class IP20 IP20 IP20
Input W 150 320 500
INDOOR Output W 120 250 400
FAN
MOTOR Range of current Amps 1.2±10% 2.4±10% 3.54±10%
Rated current Amps 1.2 2.4 3.54
Capacitor µF NA
Rated HP HP 0.20 0.42 0.65
Rated Power
W 148/107/75 315/191/138 487/394/315
High/Medium/Low
Speed
rev/min 720/640/550 900/800/700 1050/980/910
High/Medium/Low
Rated RPM rev/min 720 900 1050
Max. input W 325 483 610

Airflow Specifications

Table 8 — Airflow Specifications


SYSTEM SIZE 24K 36K 48K
(208/230V) (208/230V) (208/230V)
High 882 1,176 1412,
Indoor (CFM) Medium 765 1,000 1,294
Low 588 824 1,176

SG-40MBAA-01 Specifications subject to change without notice. 15


REFRIGERATION CYCLE DIAGRAM

INDOOR O UT DO O R

EXV
LIQUID SIDE

2- WAY VALVE

HEAT HEAT
EXCHANGE EXCHANGE
(EVAPORATOR) (CONDENSER)
T1 Room temp.
sensor

T2 Evaporator
temp. sensor
GAS SIDE
4- WAY VALVE

3- WAY VALVE

ACCUMULATOR

COOLING
COMPRESSOR
HEATING

Fig. 12 — Heat Pumps

16 Specifications subject to change without notice. SG-40MBAA-01


REFRIGERANT LINES
General refrigerant line sizing
1. The outdoor units are shipped with a full charge of R410A refrigerant. All charges, line sizing, and capacities are based on runs of 25 ft. (7.6 m).
For runs over 25 ft. (7.6 m), consult the product data.
2. Minimum refrigerant line length between the indoor and outdoor units is 10 ft. (3 m).
3. Refrigerant lines should not be buried in the ground. If it is necessary to bury the lines, not more than 36 in. (914 mm) should be buried. Provide
a minimum 6 in. (152 mm) vertical rise to the service valves to prevent refrigerant migration.
4. Both lines must be insulated. Use a minimum of ½ in. (12.7 mm) thick insulation. Closed-cell insulation is recommended in all long-line applica-
tions.
5. Special consideration should be given to isolating interconnecting tubing from the building structure. Isolate the tubing so that vibration or noise
is not transmitted into the structure.
6. For piping runs greater than 25 ft. (7.6 m), add refrigerant up to the allowable length as specified in the product data.

Refrigerant Coil Specifications


Table 9 — Refrigerant Coil Specifications
UNIT SIZE 24 36 48
NUMBER OF ROWS 2 4 4
in 0.83x0.53 0.83x0.53 0.83x0.53
Tube pitch (a) x row pitch (b)
mm 21x13.37 21x13.37 21x13.37
FPI 20 20 20
Fin Spacing
mm 1.3 1.3 1.3
Fin type Louvered Louvered Louvered
Fin Material Hydrophilic Aluminum Hydrophilic Aluminum Hydrophilic Aluminum
inch 0.276 0.276 0.276
Tube outside dia.
mm 7 7 7
Nominal Tube Wall mm (inch) 0.00945 (0.24) 0.00945 (0.24) 0.00945 (0.24)
Tube Enhancement (Yes/ No) Yes Yes Yes
AIR HANDLER Tube Material Copper Copper Copper
INDOOR COIL inch 16.34x14.88x2.10 16.34x14.88x2.10 16.34x14.88x2.10
Coil length x height x width
mm 415x378x53.48 415x378x53.48 415x378x53.48
Face area ft2 1.69 1.69 1.69
Number of circuits 4 8 8
Metering Device EXV in outdoor unit
High Burst Pressure Psi (MPa) 609.2(4.2) 609.2 (4.2) 609.2 (4.2)
Low Burst Pressure Psi (MPa) 217.6 (1.5) 217.6 (1.5) 217.6 (1.5)
Design (high/low) Burst Psi 550/340 550/340 550/340
Pressure
Gas Pipe
In (mm) 5/8” (15.9) 5/8” (15.9) 5/8” (15.9)
(size – connection type)
Liquid Pipe
In (mm) 3/8” (9.52) 3/8” (9.52) 3/8” (9.52)
(size – connection type)

SG-40MBAA-01 Specifications subject to change without notice. 17


TROUBLESHOOTING Test the voltage between P and N on back of the main PCB with a
multimeter. If the voltage is lower than 36V, the capacitors are fully
discharged.
WARNING
Be sure to turn off all power supplies or disconnect all wires to avoid
electric shock.
While checking indoor/outdoor PCB, please equip oneself with anti-
static gloves or wrist strap to avoid damage to the board.

WARNING
Electricity remains in capacitors even when the power supply is off.
Ensure the capacitors are fully discharged before troubleshooting.

Fig. 13 — Voltage P and N


NOTE: Figure 13 is for reference only. The actual appearance
may differ.
Error Display (Indoor Unit)
When the indoor unit encounters a recognized error, the operation lamp flashes in a corresponding series, the timer lamp may turn on or begin
flashing, and an error code appears (see Table 10).

Table 10 — Error Display


OPERATION LAMP TIMER LAMP DISPLAY ERROR INFORMATION SOLUTION
1 time OFF E0 Indoor unit EEPROM parameter error Page 23
2 times OFF E1 Indoor / outdoor unit communication error Page 24
4 times OFF E3 The indoor fan speed is operating outside of the normal range Page 27
5 times OFF E4 Indoor room temperature sensor T1 is in open circuit or has short circuited Page 29
6 times OFF E5 Evaporator coil temperature sensor T2 is in open circuit or has short circuited Page 29
7 times OFF EC Refrigerant Leakage Detection (for some models) Page 31
8 times OFF EE Water-level alarm malfunction Page 30
9 times OFF E8 Communication error between master and slave unit (for twins system) Page 33
10 times OFF E9 Another indoor unit malfunction (for twins system) --
11 times OFF Ed Outdoor unit malfunction Page 32
1 times ON F0 Current overload protection Page 34
2 times ON F1 Outdoor room temperature sensor T4 is in open circuit or has short circuited Page 29
3 times ON F2 Condenser coil temperature sensor T3 is in open circuit or has short circuited Page 29
4 times ON F3 Compressor discharge temperature sensor TP is in open circuit or has short circuited Page 29
5 times ON F4 Outdoor unit EEPROM parameter error Page 23
6 times ON F5 The outdoor fan speed is operating outside of the normal range (for some models) Page 27
7 times ON F6 Evaporator coil outlet temperature sensor T2B is in open circuit or has short circuited Page 29
(for free-match indoor units)
11 times ON fa Communication error between indoor two chips (for some models) Page 35
1 times FLASH P0 IPM malfunction or IGBT over-strong current protection Page 36
2 times FLASH P1 Over voltage or over low voltage protection Page 37
3 times FLASH P2 Top temperature protection of compressor Page 38
5 times FLASH P4 Inverter compressor drive error Page 36
6 times FLASH P5/-- Indoor units mode conflict (match with multi outdoor unit) Page 47
7 times FLASH P6 Low pressure protection (for some models) Page 39
8 times FLASH P7 IGBT temperature sensor TH is in open circuit or has short circuited (for some models) Page 29

For other errors: The display board may display a garbled code or a code undefined by the service manual. Ensure the code is not a
temperature reading.

18 Specifications subject to change without notice. SG-40MBAA-01


Error Display (For Some Outdoor Units)

Table 11 — Error Display


DISPLAY MALFUNCTION OR PROTECTION SOLUTION
E0/F4 Outdoor unit EEPROM parameter error (for some units) Page 23
E1 Indoor / outdoor unit communication error Page 24
XYE For XYE Communication Page 26
E3/F5 The outdoor fan speed is operating outside of the normal range Page 27
E4/E5/F1/F2/F3/ Condenser coil temperature sensor T3 is in an open circuit or has short circuited. Compressor discharge Page 29
F6/P7 temperature sensor TP is in an open circuit or has short circuited.
EE Water-Level Alarm Malfunction Page 30
EC Refrigerant Leakage Detection Page 31
ED Outdoor unit malfunction Page 32
E8 Communication Error Between Master and Slave Unit (for Twins System) Page 33
F0 Overload Current Protection Page 34
FA Communication Error Between Indoor Two Chips Page 35
P0/P4 IPM Malfunction and Inverter Compressor Drive Error Page 36
P1 Over voltage or over low voltage protection Page 37
P2 Top Temperature Protection of Compressor Page 38
P6/J6 Low Pressure Protection Page 39
J0 Evaporator high temperature protection Page 40
J1 Condenser high temperature protection Page 41
J2 High discharge temperature protection Page 42
J3 PFC module protection Page 43
J4 Communication error between outdoor main chip and compressor driven chip Page 44
J5 High pressure protection Page 45
J8 AC power input voltage protection Page 46

SG-40MBAA-01 Specifications subject to change without notice. 19


Outdoor Unit Point Check Function (36 and 48 only)
• A check switch is included on the outdoor PCB.
• Push SW1 to check the unit’s status while running. The digital display shows the codes listed in Table 12 each time SW1 is pressed.
Table 12 — Outdoor Unit Point Check
NUMBER OF PRESSES DISPLAY REMARK
00 Normal display Displays the running frequency, running state, or malfunction code
Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube displays the single digit and tens
01 Indoor unit capacity demand code
digit. (For example, the digital display tube displays “5.0”, which means the capacity demand is 15.
The digital display tube displays “60”, it means the capacity demand is 6.0).
02 Amendatory capacity demand code
The frequency after the capacity
03
requirement transfer
04 The frequency after the frequency limit
05 The frequency of sending to 341 chip
If the temperature is lower than 0 degree, the digital display tube displays “0”. If the temp. is higher
06 Indoor unit evaporator temperature than 70 degrees, the digital display tube displays “70”.
07 Condenser pipe temp.(T3) If the temp. is lower than -9 degrees, the digital display tube displays “-9”. If the temperature is higher
than 70 degrees, the digital display tube displays “70”. If the indoor unit is not connected, the digital
08 Outdoor ambient temp.(T4) display tube displays: “--”
The display value is between 13~129 degrees. If the temperature is lower than 13 degrees, the digital
display tube displays “13”. If the temperature is higher than 99 degrees, the digital display tube
09 Compressor discharge temp. (T5) displays a single digit and tens digit. (For example, the digital display tube displays “0.5”, it means the
compressor discharge temperature. is 105 degrees. The digital display tube displays “1.6”, it means
the compressor discharge temperature. is 116 degrees.
10 AD value of current The display value is a hex number.
11 AD value of voltage For example, the digital display tube displays “Cd”, it means AD value is 205.

Standby:0, Fan only 1,Cooling:2, Heating:3, Forced Cooling:4, Drying:6, Self Clean:8, Forced
12 Indoor unit running mode code Defrosting:10
Standby:0, Fan only 1,Cooling:2, Heating:3, Forced Cooling:4, Drying:6, Self Clean:8, Forced
13 Outdoor unit running mode code Defrosting:10
Actual data/4. If the value is higher than 99, the digital display tube displays a single digit and tens
14 EXV open angle digit. For example, the digital display tube displays “2.0”, it means the EXV open angle is 120x4=480p.
Frequency limit caused by IGBT
Bit7 radiator

Bit6 Frequency limit caused by PFC

Bit5 Frequency limit caused by T4. The display value is a hexadecimal number.
Bit4 Frequency limit caused by T2. For example, the digital display shows 2A, then
15 Frequency limit symbol Bit5=1, Bit3=1, and Bit1=1.
Bit3 Frequency limit caused by T3.
This means that a frequency limit may be caused
Bit2 Frequency limit caused by T5. by T4, T3, or the current.

Bit1 Frequency limit caused by current

Bit0 Frequency limit caused by voltage

16 Outdoor unit fan motor state Off: 0, Turbo:1 High speed:2, Med speed: 3, Low speed: 4, Breeze:5, Super breeze: 6 other speed:7
The display value is between 30~120 degrees. If the temperature is lower than 30 degrees, the digital
display tube displays “30”. If the temperature is higher than 99 degrees, the digital display tube
17 IGBT radiator temperature displays a single digit and a tens digit. (For example, the digital display tube displays “0.5”, it means
the IGBT radiator temperature is 105 degrees. The digital display tube displays “1.6”, it means the
IGBT radiator temperature is 116 degrees.
18 Indoor unit number The indoor unit can communicate with outdoor unit well. General:1, Twins:2
19 Evaporator pipe temp. T2 of 1# indoor unit
If the temperature is lower than 0 degree, the digital display tube displays “0”.
20 Evaporator pipe temp. T2 of 2# indoor unit If the temperature is higher than 70 degrees, the digital display tube displays “70”. If the indoor unit is
not connected, the digital display tube displays: “--”
21 Evaporator pipe temp. T2 of 3# indoor unit
22 1# Indoor unit capacity demand code Actual data*HP*10
If the capacity demand code is higher than 99, the digital display tube displays a single digit and tens
23 2# Indoor unit capacity demand code digit. (For example, the digital display tube displays “5.0”, it means the capacity demand is 15. the
digital display tube show “60”, it means the capacity demand is 6.0). If the indoor unit is not connected,
24 3# Indoor unit capacity demand code the digital display tube displays: “--”
25 Room temp. T1 of 1# indoor unit
26 Room temp. T1 of 2# indoor unit If the temperature is lower than 0 degree, the digital display tube displays “0”. If the temperature is
higher than 70 degree, the digital display tube displays “70”. If the indoor unit is not connected, the
27 Average room temp. T1 digital display tube displays: “--”
28 Reason of stop
29 Evaporator pipe temp. T2B of 1# indoor unit If the temperature is lower than 0 degree, the digital display tube displays “0”.If the temperature is
higher than 70 degree, the digital display tube displays “70”. If the indoor unit is not connected, the
30 Evaporator pipe temp. T2B of 2# indoor unit digital display tube displays: “--”

20 Specifications subject to change without notice. SG-40MBAA-01


Quick Maintenance by Error Code
If you do not have the time to test which specific parts are faulty, you can directly change the required parts according to the error code.
You can locate the parts to replace by error code in Table 13.

Table 13 — Quick Maintenance by Error Code


ERROR CODE
PART REQUIRING PAYMENT
E0 E1 E3 E4 E5 EC EE F0 F1 F2
Indoor PCB        x x x
Outdoor PCB x  x x x x x   
Indoor fan motor x x  x x x x x x x
Outdoor fan motor x x x x x x x  x x
T1 sensor x x x  x x x x x x
T2 Sensor x x x x   x x x x
T3 Sensor x x x x x x x x x 
T4 Sensor x x x x x x x x  x
TP Sensor x x x x x x x x x x
IGBT Sensor x x x x x x x x x x
Additional refrigerant x x x x x  x  x x
Capacitor of compressor x x x x x x x x x x
Compressor x x x x x x x  x x
IPM board x x x x x x x x x x
Capacitor of fan motor x x x x x x x x x x
Outdoor fan x x x x x x x x x x
Display board x x x x x x  x x x
Reactor or inductance x x x x x x x  x x
Bridge rectifier x x x x x x x x x x
Water-level switch x x x x x x  x x x
Water pump x x x x x x  x x x

Table 14 — Quick Maintenance by Error Code


PART REQUIRING ERROR CODE
REPLACEMENT F2 F3 F4 F5 F6 P0/P4 P1 P6/J6 P7
Indoor PCB x x x x x x x x x
Outdoor PCB     x    
Indoor fan motor x x x x x x x x x
Outdoor fan motor x x x  x  x x x
T1 sensor x x x x x x x x x
T2 Sensor x x x x x x x x x
T3 Sensor  x x x x x x x x
T4 Sensor x x x x x x x x x
TP Sensor x  x x x  x x x
IGBT Sensor x x x x x x x x 
Additional refrigerant x x x x x x x x x
Capacitor of compressor x x x x x x x x x
Compressor x x x x x   x x
IPM board x x x x x   x x
Capacitor of fan motor x x x x x x x x x
Outdoor fan x x x x x x x x x
Display board x x x x x x x x x
Reactor or inductance x x x x x   x x
Bridge rectifier x x x x x   x x
Pressure protector x x x x x x x  x
T2B Sensor x x x x  x x x x

SG-40MBAA-01 Specifications subject to change without notice. 21


Table 15 — Quick Maintenance by Error Code

PART REQUIRING ERROR CODE


REPLACEMENT J0 J1 J2 J3 J4 J5 J8 P2
Indoor PCB x x x x x x x x
Outdoor PCB        
Indoor fan motor x x x x x x x x
Outdoor fan motor  x x  x x x x
T1 sensor x x x x x x x x
T2 Sensor  x x x x x x x
T3 Sensor x  x x x x x x
T4 Sensor x x x x x x x x
TP Sensor x x  x x x x x
IGBT Sensor x x x x x x x x
Additional refrigerant x   x x x x x
Capacitor of x x x x x x x x
compressor
Compressor x  x  x x x x
IPM board x  x  x x  x
Fan Motor Capacitor x x x x x x x x
Outdoor fan x x x x x x x x
Display board x x x x x x x x
Reactor or inductance x x x x x x  x
Bridge rectifier x x x x x x  x
Pressure protector x x x x x  x x
Compressor driven x x x x  x x x
chip
Overload protector x x x x x x x 

NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box should be replaced as
a whole.

22 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION
E0 / F4 (EEPROM Parameter Error Diagnosis and Solution)
Description: Indoor or outdoor PCB main chip does not receive feedback from the EEPROM chip.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB

Troubleshooting and repair:

Shut oī the power and turn it on 2


minutes later.

Is it sƟůů
displaying the No The unit is operaƟng normally.
error code?

Yes

The unit is operaƟng normally.

SG-40MBAA-01 Specifications subject to change without notice. 23


DIAGNOSIS AND SOLUTION (CONT.)
E1 (Indoor and Outdoor Unit Communication Error Diagnosis and Solution)
Description: Indoor unit can not communicate with the outdoor unit.
Recommended parts to prepare:
• Indoor PCB
• Outdoor PCB
• Reactor
Troubleshooting and Repair:
For S communication:

Power off. Restart the unit after 2 minutes

Does the error code disappear? No Solved

Yes

Check the wiring


connection between Correct the connection or
indoor and outdoor No
change wires
unit, are they good?

The value is alternative


Yes from negative to positive.

Check the wiring connection


Measure the DC voltage between N/L2 The value is fixed and close from the indoor terminal to Replace indoor PCB
and S (black pin to N/L2, red pin to S). to 0. the indoor PCB. Are they good?

For units
with W wire
Turn on the unit, check if W No
The value is always positive
and 1(L) is connected.

For units without W


wire
For units with a main PCB and IPM board Check the wiring connection
both from the outdoor terminal
to the oudoor PCB and wiring Yes
between the PCBs if there is For units with only one PCB
more than one PCB.

Check the AC voltage of the L, N Replace the Replace the


output to the IPM board. Is it No Yes Check if the power LED is on.
main PCB outdoor PCB
the same as the power input?
Yes
Unplug all the high voltage
components connected to the main Replace short-circuited
PCB such as the 4-way valve, heater, Yes component No
AC fan one by one to check their and the main PCB. PCB
resistance. Is there any component
short circuit?
Yes Unplug all the high voltage
No components connected to the
Replace short-circuited
main PCB such as the 4-way valve,
Check the DC 5V, 12V from component and outdoor Yes
heater, AC fan one by one to check
the IPM board to the main PCB
their resistance. Is there
PCB. Are they normal? No any component short circuit?
No
No
Unplug the electronic expansion
valve. Check if the DC 5V, 12V Replace the electronic Unplug the electronic expansion valve.
Yes Yes
to the main PCB are ok. expansion valve coil. Check if the power LED is on.

No

Replace the IPM board.

NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control
box should be replaced as a whole.

24 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
• Use a multimeter to test the DC voltage between 2 port (or S or L2 port) and 3 port (or N or S port) of the outdoor unit.
• The red pin of the multimeter connects with the 2 port (or S or L2 port) while the black pin is for 3 port (or N or S port).
• When the AC is normal running, the voltage is moving alternately as positive values and negative values.
• If the outdoor unit malfunctions, the voltage has always been the positive value.
• If the indoor unit malfunctions, the voltage maintains a certain value.

Fig. 15 — Multimeter Test

Fig. 14 — Multimeter Test NOTE: The picture and the value are only for reference,
actual condition and specific value may vary.
• Use a multimeter to test the reactor resistance which does not connect
with the capacitor.
• The normal value should be around zero ohm. Otherwise, the reactor
may malfunction.

SG-40MBAA-01 Specifications subject to change without notice. 25


DIAGNOSIS AND SOLUTION (CONT.)
For XYE communication:
Troubleshooting and Repair:

Power off.
Restart the unit 2 minutes later.

Yes

Check for interference (e.g. too Remove the interference or add


many lamps, power transformers. Yes a magnet ring on the power wire.
Or is the signal wire too long?

No

Check whether the signal wire is


Adopt shield cable/shield
a shield cable or whether the No
cable earthing.
shield cable is earthing.

Yes

Check whether the wire is the


correct polarity No Correct the connection.
(P to P, Q to Q, E to E).

Yes

Check whether the signal wire is broken. Yes Replace the signal wire.

No

Check whether the signal wires


No Pull out and insert back.
insert on the PCB as designed.

Yes

Replace the indoor main PCB.


Is the error distinguished?

No

Replace the outdoor main PCB.

26 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
E3 / F5 (Fan speed is Operating Outside of Normal Range Diagnosis and Solution)
Description: When the indoor /outdoor fan speed keeps too low or too high for a certain time, the unit stops and the LED
displays the failure.
Recommended parts to repair:
• Connection wires
• Fan assembly
• Fan motor
• PCB
Troubleshooting and Repair:

Power off. Restart the unit after 2 minutes.

Does a problem remain? NO The unit is operating normally.

YES
Shut off the power supply.
Rotate the fan by hand.

Does it turn easily? NO Find the cause of the problem and resolve it.

YES

Check the fan motor wiring.

Is it improperly wired? Ensure the proper connections.

YES

Measure the voltage for


the fan motor from the PCB.

Is it within normal parameters? NO Replace the main PCB.

YES

Replace the fan motor.

SG-40MBAA-01 Specifications subject to change without notice. 27


Index:
7. Indoor DC Fan Motor (control chip is on PCB)
Release the UVW connector. Measure the resistance of U-V, U-W, V-W. If the resistance is not equal to each other, the fan motor must be
faulty and needs to be replaced. Otherwise the PCB is faulty and needs to be replaced.

Fig. 16 — UVW Connector

28 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
E4/E5/F1/F2/F3/F6/P7 (Open Circuit or Short Circuit of Temperature Sensor Diagnosis and Solution)
Description: If the sampling voltage is lower than 0.06V or higher than 4.94V, the LED displays the failure.
Recommended parts to prepare:
• Connection wires
• Sensors
• PCB
Troubleshooting and Repair:

Check the connection between the


temperature sensor and the PCB.

Is it properly wired? NO Ensure the proper connections.

YES
Measure the sensor’s
resistance value.

Is it within
acceptable parameters? NO Replace the sensor.

YES

Replace the indoor PCB ((E4/E5)


or the outdoor PCB (F1/F2/F3))

Fig. 17 — Test
NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole. Figure 17 and the value are for reference only. The actual appearance and value
may vary.

SG-40MBAA-01 Specifications subject to change without notice. 29


DIAGNOSIS AND SOLUTION (CONT.)
EE (Water-Level Alarm Malfunction Diagnosis and Solution)
Description: If the sampling voltage is not 5V, the LED displays the failure code.
Recommended parts to prepare:
• Connection wires
• Water-level switch
• Water pump
• Indoor PCB
Troubleshooting and Repair:

Shut off the power supply. Wait 2


minutes then turn it back on.

Does the problem NO The


The unit
unit isis operating
operating normally
normally ..
still exist?

YES

Is the water-level Insert


Insert the
the water
water-level
-level
switch broken? NO
switch
switch properly
properly

YES

Is the water-level
NO Replace the water-level switch.
switch broken?

YES

Replace the water pump.

Does the problem


NO The unit is operating normally.
still exist?

YES

Replace the indoor main PCB.

30 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
EC (Refrigerant Leakage Detection Diagnosis and Solution)
Description: Ensure the compressor’s evaporator coil temperature (T2) starts running as Tcool. Initially 5 minutes after
the compressor starts up, if T2 < Tcool 1.8°F (-1°C) does not stabilize for 4 seconds and the compressor running frequency
exceeds 50Hz however it does not maintain for 3 minutes, and this occurs 3 times, the display area displays “EC” and the
AC turns off.
Recommended parts to prepare:
• T2 sensor
• Indoor PCB
• Additional refrigerant
Troubleshooting and Repair:

Power off the unit. Wait 2 minutes then restart it.

Does the
problem still exist?

YES

Place your hands in front of the


indoor air outlet.

Is there cool air


blowing out from the YES Check the T2 sensor.
indoor air outlet?

NO Is it securely Replace the


YES
attached? indoor PCB.
Check the system for leaks.

NO

Repair the leak and


Are any leaks present? YES
recharge the refrigerant.

NO

Check the system for blockages.


If found, clear the blockages.

SG-40MBAA-01 Specifications subject to change without notice. 31


DIAGNOSIS AND SOLUTION (CONT.)
ED (Outdoor unit malfunction Diagnosis and Solution)
Description: The indoor unit detects that the outdoor unit has failed.
Recommended parts to prepare:
• Outdoor unit
Troubleshooting and Repair:

Power off the ,unit. Wait 2 minutes then


Is the main board displaying restart the unit. Does the outdoor main
No board display an error code after a few
an error?
minutes?

Yes
Yes

Refer to the prescribed steps


for resolving the issue?

32 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
E8 (Communication Error Between Master and Slave Unit (for Twins System) Diagnosis and Solution)
Description: When set in twins system, master unit and slave unit cannot be recognized normally.
Recommended parts to prepare:
• Connection wires
• Indoor PCB

Check the master unit’s


and slave unit’s dial switch No Correct the settings.
settings. Are they correct?

Yes

Check the PQE


communication wires
No Correct the wire connections.
connection. Is it wired
correctly?

Yes

One of the 2 indoor PCBs is defective.


Connect only one indoor unit to the
outdoor unit separately. The one that
displays an E1 error code is defective.

SG-40MBAA-01 Specifications subject to change without notice. 33


DIAGNOSIS AND SOLUTION (CONT.)
F0 (Overload Current Protection Diagnosis and Solution)
Description: An abnormal current rise is detected by checking the specified current detection circuit.
Recommended parts to prepare:
• Outdoor PCB
• Connection wires
• Compressor
• Reactor
Troubleshooting and repair:

Check the power supply.

Is it in working order? NO Stop the unit.

YES

Check the system for blockages.

Do any exist? Yes Clear the blockage.

No

Check the compressor resistance values.

Are they within acceptable NO Replace the compressor.


parameters?

YES

Check the connections and the wires.

Ensure proper connections of


Are they properly connected? NO
replace the wires.

YES

Check the reactor.

Is it in working order? NO Replace outdoor PCB.

YES

Replace the outdoor unit.

NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole.

34 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
FA (Communication Error Between Indoor Two Chips Diagnosis and Solution)
Description: The indoor PCB main chip does not receive feedback from another chip.
Recommended parts to prepare:
• Indoor PCB
Troubleshooting and Repair:

Shut off the power supply.


Wait 2 minutes then turn it back on.

Is the unit still


displaying an NO The unit is operating normally.
error code?

YES

Replace the indoor main PCB.

SG-40MBAA-01 Specifications subject to change without notice. 35


DIAGNOSIS AND SOLUTION (CONT.)
P0/P4 (IPM Malfunction) and (Inverter Compressor Drive Error Diagnosis and Solution)
Description: P0:When the IPM sends an abnormal voltage signal to the compressor drive chip, the LED displays the
failure code and the AC turns off.
P4: The driven chip cannot detect the compressor’s right rotor position.
Recommended parts to prepare:
• Connection wires
• IPM module board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
Troubleshooting and Repair:
Test the resistance between every two ports of U, V, W of IPM and P, N. If any test 0 or close, the IPM is defective. Otherwise, follow the flowchart.

IPM module protection

No

Restart the unit when the power supply


Is the power voltage normal? No returns to normal.

Yes

Are the power wires Reconnect the


Is the outdoor terminal voltage normal? No
connected properly? power wires.

Yes

Is the voltage between L and N normal? No Are L and N wired correctly? Reconnect L and N.

Yes

Is the bridge rectifier Is the bridge rectifier Reconnect the


input voltage normal? No properly wired?
˛ bridge rectifier.

Yes

Is the voltage between P and N Is the rectifier


properly wired? No No Replace the bridge rectifier.
operating normally?

Yes
Yes
Is the compressor’s connecting
wire between the main Reconnect the main board Replace the PFC module
board and the IPM board No
and the IPM board. (if this has not been done already).
connected correctly (tight)?

Yes No

Is the compressor’s connecting Reconnect the connecting


No Are the reactor
wire connected correctly (tight? compressor wire.
or the inductance No Reconnect the wiring.
wired properly?
Yes

Is the outdoor unit ventiliation Ensure the outdoor unit


No is ventilating properly. Yes
in working order?

Yes
Are the reactor or Replace the reactor
Refer to the “Fan Speed Out of Control” inductance normal? No
or inductance.
Is the outdoor fan running properly? No malfunction solution. Determine the
cause and resolve the problem.

Yes

Replace the IPM board.


Yes
Is the problem resolved?

No

Replace the outdoor main PCB.


Is the problem resolved?

No

Is the compress
running normally? No Replace
Replace the
the compressor
compressor

Yes

Check whether the refrigerant system


is in working order.

36 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
P1 (Over Voltage or Too Low Voltage Protection Diagnosis and Solution)
Description: Abnormal increases or decreases in voltage are detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
• Power supply wires
• IPM module board
• Outdoor PCB
• Bridge rectifier
• PFC circuit or reactor
Troubleshooting and Repair:

Voltage protection

Check whether the power Restart the unit when the


No
voltage is normal. power supply returns to normal.

Yes

Measure whether the outdoor Are the power wires Reconnect the
No No
terminal voltage is normal. well connected? wires well.

Yes

Measure whether the voltage Is the L and N wiring Reconnect the


No No
between L and N is normal. well connected? wires well.

Yes

Measure whether the input voltage Is the bridge rectifier Reconnect the
No
of the bridge rectifier is normal. wiring well connected? wires well.

Yes

Check whether
Measure whether the voltage between No the bridge rectifier is No Replace the bridge rectifier.
P and N is normal. well connected?

Yes

Replace the PFC module.

No

Yes
Check the reactor
or inductance wiring. No Reconnect the wiring.

Yes

Replace the IPM board. If the IPM board Check whether the
Replace the reactor
and the main board is in a board, Yes reactor or inductance is No
or inductance.
replace the outdoor main PCB. normal.

NOTE: For certain models, the outdoor PCB could not be removed separately. In this case, the outdoor electric control
box should be replaced as a whole.

SG-40MBAA-01 Specifications subject to change without notice. 37


DIAGNOSIS AND SOLUTION (CONT.)
P2 (Top Temperature Protection of Compressor Diagnosis and Solution)
Description: If the sampling voltage is not 5V, the LED displays the failure.
Recommended parts to prepare:
• Connection wires
• Overload protector
• Outdoor PCB
Troubleshooting and Repair:

Check if the air flow system


Clear the air inlet and outlet or the indoor
of the indoor and outdoor units Yes
and outdoor unit’s heat exchanger.
is obstructed.

No

Turn off the power supply.


Wait 10 minutes and turn back on.

Yes

Check if all the connection, especially the


Check if the compressor top No connection of OLP (Over Load Protector) No Correct the connection.
temperature is higher sensor is good.
than 194°F(90°C).
Yes
Yes
Measure the resistance
between the two ports of No Replace the OLP.
Check if the refrigerant system
the OLP. Is it zero?
is normal.
No
Yes Yes Replace the outdoor control PCB.

Repair the
Replace the outdoor control PCB.
refrigerant system.

NOTE: For certain models, the outdoor PCB can not be removed separately. In this case, the outdoor electric control box
should be replaced as a whole.

38 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
P6/J6 (Low Pressure Protection)
Description: If the sampling voltage is not 5V, the LED displays a failure code.
Recommended parts to prepare:
• Wiring mistake
• Overload protector
• System blockages
• Outdoor PCB
Troubleshooting and Repair:

Low pressure protection

Are the low pressure


protector and the main control Reconnect the low pressure protector
NO
board wired properly? and the main control board.

NO

Check the low pressure protector.


Method: Disconnect the plug.
Measure the resistance of the low pressure protector.
If the protector is normal, the value is 0.

Is the low pressure


NO Replace the low pressure protector.
protector normal?

YES

Check the outdoor ambient temperature.

Is it too low? YES Stop the unit.

NO

Check the valve core of


the high pressure valve.

Open the valve core of the


Is it fully opened? NO
high pressure valve.

YES

Replace the outdoor main board.

Does a problem still exist? NO The problem is solved.

YES

Check if the refrigerant level is sufficient.


If not, add more refrigerant.

Does the system function properly?

NO

Check whether the refrigerant system


is functioning properly.

SG-40MBAA-01 Specifications subject to change without notice. 39


DIAGNOSIS AND SOLUTION (CONT.)
J0 (Evaporator High Temperature Protection)
Description: When the evaporator coil temperature is higher than 140°F 60°C, the unit stops. It starts again only when the
evaporator coil temperature is less than a certain value.
Recommended parts to prepare:
• Wiring mistakes
• Overload protector
• System blockages
• Outdoor PCB
Troubleshooting and Repair:

Evaporator high temperature protection

Check the connection


Is the compressor operating? NO
between T2 and the PCB.

YES

Check the outdoor ambient temperature. Correct the


Is it in working order? NO
connection?
Is it higher than
YES Stop the unit. YES
86°F(30°C)?

NO Check the resistance of T2


according to Appendix 1.
Check if the air-outlet is blocked.

Is it blocked? YES Clean the air-outlet. Replace the


Is it normal ? NO
temperature sensor
NO

Check the indoor fan.

Refer to the
“Fan Speed Out ofControl”
Is it running normally? NO solution. Determine the cause
and resolve the problem.
YES
Check the heat
exchanger
and filter.

Are they Clean the heat


YES exchanger and filter.
dirty?

NO

Replace the indoor main PCB. YES

40 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
J1 (Condenser High Temperature Protection)
Description: When the outdoor pipe temperature is more than TP3+5°C, the unit stops. It starts again only when the
outdoor pipe temperature is less than TP3-3°C.
Recommended parts to prepare:
• Condenser temperature sensor
• System leak or blockages
Troubleshooting and Repair:

Condenser high temperature protection

Is the condenser temperature Check the connection between


NO
higher than 149°F (65°C)? T3 and the PCB.

YES
Correct the
Check the outdoor ambient temperature. Is it in working order? NO
connection.

Is it higher than
YES Stop the unit. YES
122°F(50°C)?

NO Check the resistance of T3


Check the outdoor unit according to Appendix 1.
ventilation.

Ensure the outdoor unit’s Replace the


Is it functioning properly? NO Is it normal? NO temperature sensor.
ventilation is functioning properly.

YES

Check the outdoor fan.

Refer to the “Fan Speed Out of Control”


Is it running properly? NO malfunction solution. Find the problem
and resolve the problem.
YES
Check the heat exchanger.

Is it dirty? YES Clean the heat exchanger.

NO
Replace the outdoor main board. YES

Has the problem


been resolved?

NO
Check if the refrigerant level is sufficient.
If not, add more refrigerant.
YES
Check whether the refrigerant
system is functioning normally.

SG-40MBAA-01 Specifications subject to change without notice. 41


DIAGNOSIS AND SOLUTION (CONT.)
J2 (High Discharge Temperature Protection)
Description: When the compressor discharge temperature (T5) is more than 239°F (115°C) for 10 seconds, the compressor
stops and does not restart until T5 is lower than 194°F (90°C).
Recommended parts to prepare:
• Refrigerant
• Wiring
• Discharge temperature sensor
• Outdoor PCB
Troubleshooting and Repair:

Temperature protection of
compressor discharge

Is the
compressor
discharge temperature Is refrigerant Stop the leak and add
YES YES
higher than 239°F (115°C)? leaking? refrigerant.

NO
NO

Check the connection between the


compressor discharge temperature sensor
and PCB according to the wiring diagrams.

Are they connected Correct the wiring


NO
properly? connection.

YES

Measure the compressor discharge’s


temperature sensor resistance value
according to Appendix 2.

Is it normal? NO Replace the compressor discharge


temperature sensor.
YES

Replace the outdoor main PCB.

Does a problem still exist?

YES

Replace the high pressure


valve assembly.

42 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
J3 (Module Protection)
Description: When the voltage signal that the IPM sends to the compressor drive chip is abnormal, the LED displays “J3”
and AC turns off.
Recommended parts to prepare:
• Wiring
• IPM board
• Outdoor fan assembly
• Compressor
• Outdoor PCB
Troubleshooting and Repair:

PFC module protection

Check whether the connecting Connect it tight.


line between the main board and the NO Ensure the unit functions
PFC module is connected normally.
lightly.

YES
NO
Measure the voltage
between P and N.

Is it normal? YES Replace the outdoor main board.

NO
Check the PFC module inductance.
If the inductance is good, the resistance
of the two ports is 0.

Is it good? NO Replace the inductance.

YES

Replace the PFC module. Problem solved.

SG-40MBAA-01 Specifications subject to change without notice. 43


DIAGNOSIS AND SOLUTION (CONT.)
J4 (Communication Error Between Outdoor Main Chip and Compressor Driven Chip)
Description: The main PCB has not received feedback from the driven chip for 1 minute or the feedback data is wrong.
The driven chip has not received feedback from the main PCB for 1 minute or the feedback data is wrong. The failure
code disappears after the compressor stops or the communication runs efficiently.
Recommended parts to prepare:
• Outdoor PCB
• Compressor driven chip
• Signal wire
Troubleshooting and Repair:

Communication error between the outdoor


main chip and the compressor driven chip

Is there at least one


LED in the compressor driven
chip light?

NO

Check the signal wire between the


compressor chip and the main board.

Is is connected YES
properly?

NO
YES
Reconnect and retry?

Does the error


still appear?

NO
NO
Replace the
compressor driven chip.

Is the system
running normally? YES

NO

Replace the outdoor main board.

Is the system
running normally? YES

NO

Replace the electric control box. Problem is resolved.

44 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
J5 (High Pressure Protection)
Description: If the sampling voltage is not 5V, the LED displays a failure code.
Recommended parts to prepare:
• Wiring
• Overload protector
• Outdoor PCB
Troubleshooting and Repair:

High pressure protection

Are
the high
pressure switch and main Connect the high pressure switch
control board wired and main control board.
correctly?

Check the high pressure protector. Method: Disconnect the plug.


Measure the high pressure protector resistance level.
If the protector normal is normal, the value is 0.

Does a problem still exist? NO Replace high pressure protector.

YES

Check the outdoor ambient temperature.

Is it higher than
YES Stop the unit.
122°F (50°C)?

NO
Check if the outdoor unit
ventilation is good
Ensure that the outdoor
Is it good? NO unit ventilation functions
properly.
YES
Check the outdoor fan.

Please refer to the Fan Speed Out of Control


Is it running properly? NO malfunction solution.
Determine the cause and resolve it.
YES

Check the heat exchanger.

Is it dirty? YES Clean the heat exchanger.

NO
Replace the outdoor main board.

Is the problem solved?

NO
Check whether the refrigerant
system is functioning properly.

SG-40MBAA-01 Specifications subject to change without notice. 45


DIAGNOSIS AND SOLUTION (CONT.)
J8 (AC Power Input Voltage Protection)
Description: An abnormal voltage rise or drop is detected by checking the specified voltage detection circuit.
Recommended parts to prepare:
• Wiring
• Bridge rectifier
• IPM board
Troubleshooting and Repair

AC power input voltage protection

Check whether Restart the unit when the power


NO
the power voltage supply is normal.
is normal.

YES
Measure the outdoor terminal voltage.

Is the wiring of the power wires


Is it normal? NO Reconnect the wires well.
connect well?
YES
Measure the bridge rectifier’s
input voltage.

Check if the L and N wires are


Is it normal? NO Reconnect the wires well.
connected well.
YES
Measure the input voltage of
bridge rectifier.

Is the bridge rectifier


Is it normal? NO wiring well connected? Reconnect the wire well.

YES
Determine whether the voltage
between P and N is normal.
Refer to Appendix 3.

Check whether
Is it normal? NO the bridge rectifier Replace the bridge rectifier.
is normal.

YES
Replace the PFC module (if equipped)

NO

YES
Check the reactor
or inductance wiring. Reconnect the wiring.

YES

Replace the IPM board. If the IPM Check whether the


reactor inductance Replace the reactor
board and main board is in a board, YES NO
is normal. of inductance.
replace the outdoor main PCB.

46 Specifications subject to change without notice. SG-40MBAA-01


DIAGNOSIS AND SOLUTION (CONT.)
P5 (Indoor Units Mode Conflict (Match with a Multi Outdoor Unit)
Description: The indoor units cannot work in the COOLING and HEATING modes at the same time. The HEATING
mode has the priority.
Suppose indoor unit (A) is working in the COOLING mode or the FAN mode and the indoor unit (B) is set to the HEATING mode. The indoor
unit (A) turns off and indoor unit (B) keeps running in the HEATING mode.
Suppose indoor unit (A) is working in the HEATING mode, and indoor unit (B) is set to COOLING mode or the FAN mode, then indoor unit
(B) changes to STANDBY and indoor unit (A) remains in the current mode.

COOLING MODE HEATING MODE FAN OFF


COOLING MODE No Yes No No
HEATING MODE Yes No Yes No
FAN No Yes No No
OFF No No No No

NOTE:
No: No mode conflict
Yes: Mode conflict

SG-40MBAA-01 Specifications subject to change without notice. 47


DIAGNOSIS AND SOLUTION (CONT.)
Temperature Sensor Check

WARNING
Turn off all power supplies or disconnect all wires to avoid electric shock.
Operate after compressor and coil have returned to normal temperature in
case of injury.

1. Disconnect the temperature sensor from the PCB.


2. Measure the sensor’s resistance value using a multi-meter.
3. Check the corresponding temperature sensor resistance value.

Fig. 18 — Temperature Sensor Check


NOTE: Figure 18 is for reference only. The actual condition and specific value may vary according to temperature.

48 Specifications subject to change without notice. SG-40MBAA-01


Compressor Check
1. Disconnect the compressor power cord from the outdoor PCB.
2. Measure the resistance value of each winding using a multi-meter.
3. Check the resistance value of each winding using Table 19.

Fig. 19 — Input Terminal (typical)

SG-40MBAA-01 Specifications subject to change without notice. 49


APPENDICES
Appendix 1

Table 16 — Temperature Sensor Resistance Value Table for T1, T2, T3, T4 (°C--K)
°C °F K OHM °C °F K OHM °C °F K OHM °C °F K OHM
-20 -4 115.266 20 68 12.6431 60 140 2.35774 100 212 0.62973
-19 -2 108.146 21 70 12.0561 61 142 2.27249 101 214 0.61148
-18 0 101.517 22 72 11.5 62 144 2.19073 102 216 0.59386
-17 1 96.3423 23 73 10.9731 63 145 2.11241 103 217 0.57683
-16 3 89.5865 24 75 10.4736 64 147 2.03732 104 219 0.56038
-15 5 84.219 25 77 10 65 149 1.96532 105 221 0.54448
-14 7 79.311 26 79 9.55074 66 151 1.89627 106 223 0.52912
-13 9 74.536 27 81 9.12445 67 153 1.83003 107 225 0.51426
-12 10 70.1698 28 82 8.71983 68 154 1.76647 108 226 0.49989
-11 12 66.0898 29 84 8.33566 69 156 1.70547 109 228 0.486
-10 14 62.2756 30 86 7.97078 70 158 1.64691 110 230 0.47256
-9 16 58.7079 31 88 7.62411 71 160 1.59068 111 232 0.45957
-8 18 56.3694 32 90 7.29464 72 162 1.53668 112 234 0.44699
-7 19 52.2438 33 91 6.98142 73 163 1.48481 113 235 0.43482
-6 21 49.3161 34 93 6.68355 74 165 1.43498 114 237 0.42304
-5 23 46.5725 35 95 6.40021 75 167 1.38703 115 239 0.41164
-4 25 44 36 97 6.13059 76 169 1.34105 116 241 0.4006
-3 27 41.5878 37 99 5.87359 77 171 1.29078 117 243 0.38991
-2 28 39.8239 38 100 5.62961 78 172 1.25423 118 244 0.37956
-1 30 37.1988 39 102 5.39689 79 174 1.2133 119 246 0.36954
0 32 35.2024 40 104 5.17519 80 176 1.17393 120 248 0.35982
1 34 33.3269 41 106 4.96392 81 178 1.13604 121 250 0.35042
2 36 31.5635 42 108 4.76253 82 180 1.09958 122 252 0.3413
3 37 29.9058 43 109 4.5705 83 181 1.06448 123 253 0.33246
4 39 28.3459 44 111 4.38736 84 183 1.03069 124 255 0.3239
5 41 26.8778 45 113 4.21263 85 185 0.99815 125 257 0.31559
6 43 25.4954 46 115 4.04589 86 187 0.96681 126 259 0.30754
7 45 24.1932 47 117 3.88673 87 189 0.93662 127 261 0.29974
8 46 22.5662 48 118 3.73476 88 190 0.90753 128 262 0.29216
9 48 21.8094 49 120 3.58962 89 192 0.8795 129 264 0.28482
10 50 20.7184 50 122 3.45097 90 194 0.85248 130 266 0.2777
11 52 19.6891 51 124 3.31847 91 196 0.82643 131 268 0.27078
12 54 18.7177 52 126 3.19183 92 198 0.80132 132 270 0.26408
13 55 17.8005 53 127 3.07075 93 199 0.77709 133 271 0.25757
14 57 16.9341 54 129 2.95896 94 201 0.75373 134 273 0.25125
15 59 16.1156 55 131 2.84421 95 203 0.73119 135 275 0.24512
16 61 15.3418 56 133 2.73823 96 205 0.70944 136 277 0.23916
17 63 14.6181 57 135 2.63682 97 207 0.68844 137 279 0.23338
18 64 13.918 58 136 2.53973 98 208 0.66818 138 280 0.22776
19 66 13.2631 59 138 2.44677 99 210 0.64862 139 282 0.22231

50 Specifications subject to change without notice. SG-40MBAA-01


Appendix 2
Table 17 — Temperature Sensor Resistance Value Table for T5 (TP) (°C--K)
°C °F K OHM °C °F K OHM °C °F K OHM °C °F K OHM
-20 -4 542.7 20 68 68.66 60 140 13.59 100 212 3.702
-19 -2 511.9 21 70 65.62 61 142 13.11 101 214 3.595
-18 0 483 22 72 62.73 62 144 12.65 102 216 3.492
-17 1 455.9 23 73 59.98 63 145 12.21 103 217 3.392
-16 3 430.5 24 75 57.37 64 147 11.79 104 219 3.296
-15 5 406.7 25 77 54.89 65 149 11.38 105 221 3.203
-14 7 384.3 26 79 52.53 66 151 10.99 106 223 3.113
-13 9 363.3 27 81 50.28 67 153 10.61 107 225 3.025
-12 10 343.6 28 82 48.14 68 154 10.25 108 226 2.941
-11 12 325.1 29 84 46.11 69 156 9.902 109 228 2.86
-10 14 307.7 30 86 44.17 70 158 9.569 110 230 2.781
-9 16 291.3 31 88 42.33 71 160 9.248 111 232 2.704
-8 18 275.9 32 90 40.57 72 162 8.94 112 234 2.63
-7 19 261.4 33 91 38.89 73 163 8.643 113 235 2.559
-6 21 247.8 34 93 37.3 74 165 8.358 114 237 2.489
-5 23 234.9 35 95 35.78 75 167 8.084 115 239 2.422
-4 25 222.8 36 97 34.32 76 169 7.82 116 241 2.357
-3 27 211.4 37 99 32.94 77 171 7.566 117 243 2.294
-2 28 200.7 38 100 31.62 78 172 7.321 118 244 2.233
-1 30 190.5 39 102 30.36 79 174 7.086 119 246 2.174
0 32 180.9 40 104 29.15 80 176 6.859 120 248 2.117
1 34 171.9 41 106 28 81 178 6.641 121 250 2.061
2 36 163.3 42 108 26.9 82 180 6.43 122 252 2.007
3 37 155.2 43 109 25.86 83 181 6.228 123 253 1.955
4 39 147.6 44 111 24.85 84 183 6.033 124 255 1.905
5 41 140.4 45 113 23.89 85 185 5.844 125 257 1.856
6 43 133.5 46 115 22.89 86 187 5.663 126 259 1.808
7 45 127.1 47 117 22.1 87 189 5.488 127 261 1.762
8 46 121 48 118 21.26 88 190 5.32 128 262 1.717
9 48 115.2 49 120 20.46 89 192 5.157 129 264 1.674
10 50 109.8 50 122 19.69 90 194 5 130 266 1.632
11 52 104.6 51 124 18.96 91 196 4.849
12 54 99.69 52 126 18.26 92 198 4.703
13 55 95.05 53 127 17.58 93 199 4.562
14 57 90.66 54 129 16.94 94 201 4.426
15 59 86.49 55 131 16.32 95 203 4.294
16 61 82.54 56 133 15.73 96 205 4.167
17 63 78.79 57 135 15.16 97 207 4.045
18 64 75.24 58 136 14.62 98 208 3.927
19 66 71.86 59 138 14.09 99 210 3.812

SG-40MBAA-01 Specifications subject to change without notice. 51


DISASSEMBLY INSTRUCTIONS
Electrical Parts (Anti-static gloves must be worn)
PROCEDURES ILLUSTRATION

1. Remove the upside board screws (6) and then remove the
upside plate.

2. Remove the electrical control box cover screws (4) and then
remove the cover.

52 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Electrical Parts
PROCEDURES ILLUSTRATION

Data transfer module control board Display board

3. Unfasten the main control board hooks (2) to remove it.


4. Release the data transfer module control board hooks (4) to
remove it.
5. Unfasten the auxiliary electric heater control board hooks (4)
to remove it.
6. Release the screws (2) and remove the transformer.

Auxiliary electric heater control board Transformer Main control board

SG-40MBAA-01 Specifications subject to change without notice. 53


DISASSEMBLY INSTRUCTIONS (CONT.)
Filter
PROCEDURES ILLUSTRATION

1. Remove the supporting bar’s screws (2).

2. Remove the filter.

54 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Fan Motor and Fan
PROCEDURES ILLUSTRATION

1. Remove the fan assembly’s screws (2).

2. Remove the fan assembly.

SG-40MBAA-01 Specifications subject to change without notice. 55


DISASSEMBLY INSTRUCTIONS (CONT.)
Fan Motor and Fan
PROCEDURES ILLUSTRATION

3. Release the nuts (3) securing the fan motor and then remove
the fan.

4. Remove the nut (1) securing the fan and then remove the fan.

56 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Evaporator
PROCEDURES ILLUSTRATION

1. Remove the side plate screws (7).

2. Remove the pipe clamp board screw (1) and the rear support
board screws (3).

SG-40MBAA-01 Specifications subject to change without notice. 57


DISASSEMBLY INSTRUCTIONS (CONT.)
Evaporator
PROCEDURES ILLUSTRATION

3. Take out the evaporator (with the water collector assembly).

4. Remove the water collector assembly screws (4).

5. Release the evaporator and the water collector assembly.

58 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate
PROCEDURES ILLUSTRATION

Big Handle

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screws and then remove the big
handle.
3. Remove the top cover screws and then remove the top cover.

Top Cover

SG-40MBAA-01 Specifications subject to change without notice. 59


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

4. Remove the front panel screws (7) and then remove the front
panel.

Front Panel

Water Collecting Cover

5. Remove the water collecting cover screw (1).

60 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

6. Remove the rear net screws (2) and then remove the rear net.

7. Remove the right panel screws and then remove the right
panel.

Right Panel

SG-40MBAA-01 Specifications subject to change without notice. 61


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

Big Handle

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screws and then remove the big
handle.

Top Cover

3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located underneath the big
handle.

62 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

4. Remove the front panel screws (8) and then remove the front
panel.

Front Panel

Water Collecting Cover

5. Remove the screw (1) from the water collecting cover then
remove the water collecting cover.

SG-40MBAA-01 Specifications subject to change without notice. 63


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

6. Remove the rear net screws (2) and then remove the rear net.

7. Remove the right panel screws (5) and then remove the right
panel.

Right Panel

64 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

Big Handle

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screws and then remove the big
handle.

Top Cover

3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located under the big handle.

SG-40MBAA-01 Specifications subject to change without notice. 65


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

4. Remove the front panel screws (7) and then remove the front
panel.

Front Panel

Water Collecting Cover

5. Remove the water collecting cover screw (1) and then


remove the water collecting cover.

66 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate (Cont.)

PROCEDURES ILLUSTRATION

6. Remove the rear net screws (2) and then remove the rear net.

7. Remove the right panel screws (7) and then remove the right
panel.

Right Panel

SG-40MBAA-01 Specifications subject to change without notice. 67


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

Big Handle

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screws (2) and then remove the big
handle.

Top Cover

3. Remove the top cover screws (4) and then remove the top
cover. Two of the screws are located under the big handle.

68 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

4. Remove the front panel screws (2) and then remove the front
right panel screws.

Front Right Panel

5. Remove the front panel screws (9) and then remove the front
panel.

Front Panel

SG-40MBAA-01 Specifications subject to change without notice. 69


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

6. Remove the water collecting cover screws (2) and then


remove the water collecting cover

Water Collecting Cover

7. Remove the rear net screws (2) and then remove the rear net.

8. Remove the right panel screws (8) and then remove the right
panel.

Right Panel

70 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screw and then remove the big
handle.

3. Remove the top cover screws (3) and then remove the top
cover. One of the screws is located under the big handle.

4. Remove the water collecting cover screws (2) and then


remove the water collecting cover.

SG-40MBAA-01 Specifications subject to change without notice. 71


DISASSEMBLY INSTRUCTIONS (CONT.)
Panel Plate

PROCEDURES ILLUSTRATION

5. Remove the front panel screws (6) and then remove the front
panel (6 screws - on/off models) (8 screws - inverter
models).

6. Remove the right panel screws (6) and then remove the right
panel.

72 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
Panel Plate

PROCEDURES ILLUSTRATION

1. Turn off the air conditioner and the power breaker.


2. Remove the big handle screws and then remove the big
handle.

3. Remove the top cover screws (4) and then remove the top
cover. Two of the screws are located underneath the big
handle.

4. Remove the water collecting cover screws (2) and then


remove the water collecting cover.

SG-40MBAA-01 Specifications subject to change without notice. 73


DISASSEMBLY INSTRUCTIONS (CONT)
Panel Plate

PROCEDURES ILLUSTRATION

5. Remove the front right panel screws (2) and then remove the
front panel.

74 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
Panel Plate

PROCEDURES ILLUSTRATION

1. Remove the front right panel screws (7) and then remove the
front panel.

2. Remove the right panel screws (10) and remove the right
panel.

SG-40MBAA-01 Specifications subject to change without notice. 75


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 1

PROCEDURES ILLUSTRATION

1. Remove the top cover screws (2).

2. Unfasten the hooks (4) and then open the electronic box
cover.

4-Way Valve

3. Disconnect the fan motor connector from the electronic


control board.
4. Remove the compressor connector.
5. Remove the two blue wires connected to the four-way valve.
6. Remove the connectors of the condenser coil temperature
sensor (T3), outdoor ambient temperature sensor (T4) and
the discharge temperature sensor (TP).
7. Disconnect the electronic expansion valve wire.
8. Remove the electronic control board.

Compressor T3, T4, TP

Electronic Expansion Valve

76 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 2

PROCEDURES ILLUSTRATION

1. Unfasten the hooks (4) and then open the electronic control
box cover.

4-Way Valve

Reactor DR
2. Disconnect the fan motor connector from the electronic
control board.
3. Remove the compressor connector.
4. Pull out the two blue wires connected to the four-way valve.
5. Remove the connectors of the condenser coil temperature
sensor (3), outdoor ambient temperature sensor (T4) and the
discharge temperature sensor (TP).
6. Disconnect the electronic expansion valve wire.
7. Remove the electronic control board.

Compressor
T3, T4, TP

Electronic Expansion Valve

SG-40MBAA-01 Specifications subject to change without notice. 77


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 3

PROCEDURES ILLUSTRATION

1. Remove the screws (5) and unfasten the hooks (2) and then
open the electronic box cover.

2. Disconnect the fan motor connector from the electronic


control board.
3. Remove the compressor connector.
4. Remove the two blue wires from the four-way valve.
5. Remove the connectors of the condenser coil temperature
sensor (T3), outdoor ambient temperature sensor (T4), and
the discharge temperature sensor (TP).
6. Disconnect the electronic expansion valve wire.
7. Remove the DR connector and the reactor.
8. Remove the electronic control board.

78 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 4

PROCEDURES ILLUSTRATION

1. Remove the top cover screw (1).

2. Unfasten the hooks (5) and then open the electronic control
box cover.

3. Disconnect the fan motor connector from the IPM board. Compressor
4. Remove the compressor connector.

SG-40MBAA-01 Specifications subject to change without notice. 79


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 4 (CONT)

PROCEDURES ILLUSTRATION

T3/T4

5. Remove the wire connected to the terminal.


6. Remove the connectors of the condenser coil temperature TP
sensor (T3), outdoor ambient temperature sensor (T4) and
the discharge temperature sensor (TP).
4-Way Valve
7. Disconnect the electronic expansion valve wire.
8. Remove the four-way valve connector.
9. Remove the reactor connector.
10. Remove the electronic control box.

Terminal

Reactor

80 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 5

PROCEDURES ILLUSTRATION

1. Unfasten the hooks (4) and then open the electronic control
box.

2. Disconnect the outdoor DC fan connector from the


electronic control board.
3. Remove the compressor connector.
4. Remove the two blue wires from the four-way valve.
5. Remove the connectors of the condenser coil temperature
(T3), outdoor ambient temperature sensor (T4) and the
discharge temperature sensor (TP).
6. Disconnect the electronic expansion valve wire.
7. Disconnect the communication wire indoor PCB.
8. Disconnect the PFC inductor.
9. Remove the electronic control box.

SG-40MBAA-01 Specifications subject to change without notice. 81


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 6

PROCEDURES ILLUSTRATION

1. Unfasten the hooks (4) and then open the electronic control
box.

2. Remove the screws (8) on the electronic control board and


then turn over the electronic control board.

3. Remove the two blue wires connected with the four-way


valve. connect to IPM board PFC Inductor
4. Remove the connectors of the condenser coil temperature T3&T4 Compressor
sensor (T3), outdoor ambient temperature sensor (T4) and
the discharge temperature sensor (TP).
5. Disconnect the electronic expansion valve wire.
6. Remove the screws (4) and unfasten the hooks (3). Next,
remove the main control board. DC fan
7. Disconnect the connector for the outdoor DC fan from the
IPM board.
8. Remove the compressor connector.
9. Remove the PFC inductor connector.
10. Remove the connectors (3) between the IPM board and the
main control board.
11. Remove the screws (2) and unfasten the hooks (4) to release Main control board AC fan 4-way valve
the IPM board. IPM board connect to main board

82 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 7

PROCEDURES ILLUSTRATION

1. Unfasten the hooks (4) and then open the electronic control
box cover.

2. Remove the screws (4) from the electronic control board and
then turn over the electronic control board.

SG-40MBAA-01 Specifications subject to change without notice. 83


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 7

PROCEDURES ILLUSTRATION

3. Remove the connectors.


4. Remove the screws (9) and unfasten the hooks (3). Next,
remove the electronic control board.

5. Remove the screws (2) and then remove the electronic


control box subassembly on the partition board assembly.

6. Remove the screws (2) and the connectors (2) and then
remove the inverter control board.

Connect to CN301

Connect to FM1

84 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 8

PROCEDURES ILLUSTRATION

1. Remove the screws (2) to disconnect the supply wires.


2. Remove the screws (3) to disconnect the ground wires.
3. Disconnect the wires connected to the main control board.
4. Disconnect the wires between the main control board and the
IPM module board.
5. Remove the screws (4) and unfasten the hooks (6) and then
remove the main control board.
6. Remove the screw (1) to remove the fan motor capacitor (1
screw for each capacitor).

connect to indoor unit T3&T4 TP AC Fan motors


Fan motor capacitors
connect to IPM
low and high pressure switch

SG-40MBAA-01 Specifications subject to change without notice. 85


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 8 (CONT)

PROCEDURES ILLUSTRATION

7. Remove the screws (2) to disconnect the power supply wires.


8. Remove the screws (3) to disconnect the wires connected to
the compressor.
9. Remove the screws (3) to remove the radiator.
10. Disconnect the wires between the IPM module board and the
main control board.
11. Remove the screws (4) and unfasten the hooks (4) and then
remove the IPM module board.

Compressor DC Fan motors


connect to the main control board

86 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 9

PROCEDURES ILLUSTRATION

1. Remove the screws (3) to disconnect the wires connected to


the compressor.
2. Remove the screws (2) to disconnect the power supply wires.
3. Disconnect the wires connected to the main control board.
4. Remove the screws (4) and unfasten the hooks (6) and then
remove the main control board.
5. Remove the fan capacitor screw and then remove the fan
capacitor (one screw for each capacitor).

Fan motor capacitors

6. Remove the screws (3) to disconnect the power supply wires.


7. Remove the screws (3) to disconnect the ground wires.
8. Disconnect the wires connected to the main control board.
9. Remove the screws (4) and unfasten the hooks (4) to remove
the filter board.
10. Remove the reactor screws (2) and remove it.

11. Disconnect the wires connected to the main control board.


12. Remove the screws (2) and then remove the DC motor driver
board.

(for some models)

SG-40MBAA-01 Specifications subject to change without notice. 87


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 10

PROCEDURES ILLUSTRATION

1. Unfasten the hooks (4) and then open the electronic control
box cover.

2. Remove the screws (6) on the electronic control board and


then turn over the electronic control board.

88 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
PCB Board 10 (CONT)

PROCEDURES ILLUSTRATION

3. Pull out the connectors.


4. Remove the screws (4) and then remove the electronic
control board.

5. Remove the connector. Remove one screw and then remove


the key board assembly on the terminal board.

SG-40MBAA-01 Specifications subject to change without notice. 89


DISASSEMBLY INSTRUCTIONS (CONT)
Fan Assembly

PROCEDURES ILLUSTRATION

1. Remove the nut securing the fan with a spanner.


2. Remove the fan.

3. Remove the screws (4) securing the fan motor.


4. Remove the fan motor.

90 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
Sound Blanket
NOTE: Remove the panel plate before disassembling the sound blanket.

PROCEDURES ILLUSTRATION

1. Remove the sound blanket (side and top). Sound Blanket(top)

Sound Blanket(side)

Four-way Valve (For Heat Pump Models)

WARNING
EVACUATE THE SYSTEM
Evacuate the system and confirm that there is no refrigerant
remaining in the system before removing the four-way valve and
the compressor.

NOTE: Remove the panel plate and the four-way valve connection before disassembling the sound blanket.

PROCEDURES ILLUSTRATION

1. Heat up the brazed parts and then detach the four-way valve
and the pipe.
2. Remove the four-way valve assembly with pliers.

SG-40MBAA-01 Specifications subject to change without notice. 91


DISASSEMBLY INSTRUCTIONS (CONT)
Compressor

WARNING
EVACUATE THE SYSTEM
Evacuate the system and confirm that there is no refrigerant
remaining in the system before removing the four-way valve and
the compressor.

NOTE: Remove the panel plate and the compressor connection to the PCB before disassembling the sound blanket.

PROCEDURES ILLUSTRATION

Terminal Cover

1. Remove the terminal cover flange nut and then remove the
terminal cover.
2. Disconnect the connectors.

92 Specifications subject to change without notice. SG-40MBAA-01


DISASSEMBLY INSTRUCTIONS (CONT)
Compressor

PROCEDURES ILLUSTRATION

3. Remove the hex nuts and washers securing the compressor.

Suction Pipe

Discharge Pipe

4. Heat up the brazed parts and then remove the discharge pipe
and the suction pipe.
5. Lift the compressor from the base pan assembly with pliers.

SG-40MBAA-01 Specifications subject to change without notice. 93


Copyright 2020 CAC/BDP D 3300 Riverwood Parkway Atlanta GA, 30339 Edition Date: 09/20 Catalog No. SG-40MBAA-01

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Replaces: NEW

You might also like