Delivery-Smart PV ESS LUNA2000 Technical Training-20221027
Delivery-Smart PV ESS LUNA2000 Technical Training-20221027
WLAN/Ethernet/4G/3G/2G
FusionSolar Smart PV
Without Optimizers Backup Box Management System
Residential
(≤ 10 kW) DI
RS485
Smart Solar Smart Power Sensor Grid
Inverter
Full Configuration of
Optimizers
Battery Important Load Load
Smart Solar Inverter Smart Solar Inverter Residential Battery Backup Box
SUN2000-3/5KTL-L1 SUN2000-5/10KTL-M1 LUNA2000-(5-30)-S0 Backup Box-B0 (single-phase)
Backup Box-B1 (three-phase)
Single-phase Three-phase
4 Huawei Confidential
Janitza UMG 96RM
5 Huawei Confidential
1.2 Battery
Battery Appearance
Indicator
Battery LUNA2000-5KW-C0
LUNA2000-(5-30)-S0
Capacity: 5 kWh for a single module, supporting
the cascading of two batteries with a maximum
of 30 kWh capacity Battery
DC/DC output power: 5 kW expansion
DC/DC peak output power: 7 kW, 10s modules
5 kWh battery expansion module power: 2.5 LUNA2000-5-E0
kW
Cell type: LiFePO4
Supported inverter: SUN2000-(2KTL-6KTL)-
L1/SUN2000-(3KTL-12KTL)-M1 (The 12KTL
Floor-mounted
model is sold only in China.) base
Hybrid use of old and new batteries: supported
Installation mode: floor- and support-mounted
installation
6 Huawei Confidential
1.3 Backup Box
Backup Box-B0 Backup Box-B1
(single-phase Backup Box) (three-phase Backup Box)
8 Huawei Confidential
1.5 Smart Dongle
Smart Dongle-WLAN-FE
⚫ Supports a maximum of 10 inverters,but
only 3 inverters can be cascaded when
configured with LUNA2000
⚫ Provides a plug & play USB interface for
connecting to inverters and management
systems over WLAN or FE
⚫ Local Firmware Upgrade: Supported when
the APP connect to Dongle WLAN
9 Huawei Confidential
1.7 FusionSolar App, Management System
10 Huawei Confidential
1.4.1 Optimizer Compatibility
11 Huawei Confidential
Downloading the FusionSolar App
Method 1: Search for FusionSolar in Huawei AppGallery to download and install the app.
Method 2: Access https://solar.huawei.com using the mobile phone browser and download the latest
installation package. https://intl.fusionsolar.huawei.com
QR code link:
https://intl.fusionsolar.huaw
ei.com/pvmswebsite/nologin
/assets/build/index.html#/ju
FusionSolar APP mppage
12 Huawei Confidential
1.9 Grid-tied ESS Networking 1
Number of
Compatible Smart Power Backup Management
Inverter Battery Cascaded Communication
Optimizer Sensor Box System
Inverters
SUN2000- ⚫ DDSU666-H ⚫ Local commissioning: built-in WLAN of the inverter
3/5KTL-L1
SUN2000- (single-phase) • HUAWEI ⚫ (Standard configuration) WLAN communication: built-in WLAN of the
or
450/600W-P ⚫ DTSU666-H 250 LUNA2000-(5- N/A No inverter FusionSolar
SUN2000
(Optional) A/100 A (three- 30)-S0 ⚫ (Optional) Ethernet communication: Smart Dongle-WLAN-FE
5/10KTL-M1
phase) ⚫ (Optional) 4G communication: Smart Dongle-4G
Optimizer (optional):
The optimizer for the SUN2000-450W-P is installed at the rear of PV modules.
Commissioning:
⚫ Local commissioning: The inverter communicates with the FusionSolar app over the built-in
WLAN.
⚫ Remote management:
﹣ Built-in WLAN of the inverter (standard configuration)
﹣ Smart Dongle-WLAN-FE (optional)
﹣ Smart Dongle-4G (optional)
Communicates with the FusionSolar smart PV management system to register and manage PV
plants.
Supported inverter:
SUN2000-(2KTL-6KTL)-L1 or SUN2000-(3KTL-10KTL)-M1
Smart Power Sensor (optional):
• DDSU666-H (single-phase)
• DTSU666-H 250 A/50 mA (three-phase)
Connects to inverters over RS485 for output power management and export limitation.
Battery working mode:
Supports the maximum self-consumption, time-of-use, and fully fed to the grid modes.
Configure the components in
the dashed-line boxes as
required.
13 Huawei Confidential
1.9 Grid-tied ESS Networking 2
Number of Smart
Compatible Smart Power Management
Inverter Battery Cascaded Backup Communication
Optimizer Sensor System
Inverters Box
SUN2000-3/5KTL-L1
⚫ DDSU666-H ≤ 3 (If the cascading ⚫ Local commissioning: built-in WLAN of the inverter
(single-phase) ⚫ HUAWEI system has batteries or
SUN2000-450W-P or ⚫ (Standard configuration) WLAN communication: built-in WLAN of the inverter
⚫ DTSU666-H 250 LUNA2000-(5- single-phase inverters, No FusionSolar
(Optional) SUN2000 A/100 A (three- 30)-S0 only three inverters can
⚫ (Optional) Ethernet communication: Smart Dongle-WLAN-FE
5/10KTL-M1 ⚫ (Optional) 4G communication: Smart Dongle-4G
phase) be cascaded.)
Optimizer (optional):
The optimizer for the SUN2000-450W-P is installed at the rear of PV modules.
Commissioning:
• Local commissioning: The inverter communicates with the FusionSolar app over the built-in WLAN.
• Remote management:
﹣ Built-in WLAN of the inverter (standard configuration)
﹣ Smart Dongle-WLAN-FE (optional)
﹣ Smart Dongle-4G (optional)
Communicates with the FusionSolar smart PV management system to register and manage PV plants.
Supported inverter:
SUN2000-(2KTL-6KTL)-L1 or SUN2000-(3KTL-10KTL)-M1. Single-phase and three-phase inverters can be
cascaded.
Smart Power Sensor (optional):
• DDSU666-H (single-phase)
• DTSU666-H 250 A/50 mA (three-phase)
Connects to inverters over RS485 for output power management and export limitation.
Battery working mode:
Supports the maximum self-consumption, time-of-use, and fully fed to the grid modes.
When the grid charging function is enabled, the surplus PV power can be converted to AC output through
the inverter and then charged to other batteries in grid reverse charging mode.
Note:
1. The parameters for the battery and Backup Box of each inverter need to be set separately.
2. The battery, power meter, and Smart Dongle must be connected to the same inverter.
14 Huawei Confidential
1.10 Grid-tied and Off-grid ESS Networking 1
Compatible Number of Cascaded Management
Inverter Smart Power Sensor Battery Backup Box Communication
Optimizer Inverters System
SUN2000-3/5KTL- BackupBox-B0 (works with • Local commissioning: built-in WLAN of the inverter
L1 • DDSU666-H (single- ≤ 3 (If the cascading system
• HUAWEI single-phase inverters) • (Standard configuration) WLAN communication: built-in WLAN
SUN2000-450W-P phase) has batteries or single-
or LUNA2000-(5- BackupBox-B1 (works with of the inverter FusionSolar
(Optional) • DTSU666-H 250 A/100
30)-S0
phase inverters, only three
three-phase inverters; off-grid • (Optional) Ethernet communication: Smart Dongle-WLAN-FE
SUN2000 A (three-phase) inverters can be cascaded.)
5/10KTL-M1 output single-phase voltage) • (Optional) 4G communication: Smart Dongle-4G
Applies to areas where the grid is unstable. When the grid fails, batteries Optimizer (optional):
discharge to supply power to primary loads. The optimizer for the SUN2000-450W-P is installed at the rear of PV modules.
Commissioning:
• Local commissioning: The inverter communicates with the FusionSolar app over the built-in WLAN.
• Remote management:
﹣ Built-in WLAN of the inverter (standard configuration)
﹣ Smart Dongle-WLAN-FE (optional)
﹣ Smart Dongle-4G (optional)
Communicates with the FusionSolar smart PV management system to register and manage PV plants.
Supported inverter:
SUN2000-(2KTL-6KTL)-L1 or SUN2000-(3KTL-10KTL)-M1.
Smart Power Sensor (optional):
• DDSU666-H (single-phase)
• DTSU666-H 250 A/50 mA (three-phase)
Connects to inverters over RS485 for output power management and export limitation.
Battery working mode:
Supports the maximum self-consumption, time-of-use, and fully fed to the grid modes.
Note:
1. The power of primary loads does not exceed the maximum off-grid output power of the inverter. The
SUN2000 2-6KTL L1 output capacity does not exceed the rated output power of the inverter
(Maximum 5KVA), and the SUN2000 3-10KTL M1 does not exceed 3.3 KVA for all modules.
Configure the components in 2. The parameters for the battery and Backup Box of each inverter need to be set separately.
the dashed-line boxes as
required.
15 Huawei Confidential
1.11 Grid-tied and Off-grid ESS Networking 2
-2
Smart Power Number of
Inverter Battery Backup Box
Sensor Cascaded Inverters
BackupBox-B0 (works
SUN2000-3/5KTL- with single-phase
• DDSU666-H (single- ≤ 3 (If the cascading
L1 inverters)
phase) • HUAWEI system has batteries or
or BackupBox-B1 (works
• DTSU666-H 250 LUNA2000-(5- single-phase inverters,
SUN2000 with three-phase
A/100 A (three- 30)-S0 only three inverters can
5/10KTL-M1 inverters; off-grid
phase) be cascaded.)
output single-phase
voltage)
-1
Supported inverter:
SUN2000-(2KTL-6KTL)-L1 or SUN2000-(3KTL-10KTL)-M1.
Smart Power Sensor (optional):
• DDSU666-H (single-phase)
• DTSU666-H 250 A/50 mA (three-phase)
Connects to inverters over RS485 for output power management and export limitation.
Battery working mode:
Supports the maximum self-consumption, time-of-use, and fully fed to the grid modes.
Note:
1. When the grid charging function is enabled, the surplus power generated by the inverter without
batteries can be used to charge the inverter connected to the batteries.
2. The power of primary loads does not exceed the maximum off-grid output power of the inverter. The
SUN2000 2-6KTL L1 output capacity does not exceed the rated output power of the inverter
(Maximum 5KVA), and the SUN2000 3-10KTL M1 does not exceed 3.3 KVA for all modules.
3. When inverters are connected in parallel, the phase and frequency of the output voltage of cascaded
inverters are not synchronized in off-grid state. Therefore, the primary load output side of the Backup
Boxes connected to each inverter does not support parallel connection.
Configure the components in
the dashed-line boxes as 4. The parameters for the battery and Backup Box of each inverter need to be set separately.
required.
16 Huawei Confidential
1.12 Pure Off-grid ESS Networking
Compatible Smart Power Number of Cascaded Management
Inverter Battery Backup Box Communication
Optimizer Sensor Inverters System
• Local commissioning: built-in WLAN of the inverter
HUAWEI • (Standard configuration) WLAN communication: built-in WLAN of the
Not Supported SUN2000-3/5KTL-L1 N/A LUNA2000- N/A N/A inverter FusionSolar
(5-30)-S0 • (Optional) Ethernet communication: Smart Dongle-WLAN-FE
• (Optional) 4G communication: Smart Dongle-4G
Supported inverter:
SUN2000-(2KTL-6KTL)-L1. (The SUN2000-(3KTL-10KTL)-M1 does not support the Pure Off-grid mode.)
Black start:
For a pure off-grid system, after the system stops working, the energy storage system (ESS) supports
D.G
black start to resume the power supply. The inverter works in off-grid mode.
ATS and DG (optional):
When the installed PV + battery capacity does not meet the requirements for stable power supply to
loads, a DG is required for auxiliary power supply. When batteries are overdischarged or the system is
faulty, the ATS switches to the DG for power supply. After the system recovers, the ATS switches to the
inverter to supply power to loads and shuts down the DG.
Note:
1. The off-grid function can be enabled only when batteries are configured. If no battery is
configured, the off-grid code cannot be set.
2. In the pure off-grid scenario, the phase and frequency of the output voltages of different inverters
are not synchronized, and inverters cannot be cascaded for output.
3. During site deployment, you need to set the pure off-grid grid code, and off-grid output
voltage/frequency (based on the load working voltage and frequency). You do not need to set the
battery working mode.
4. The batteries shut down after discharging to the end-of-discharge SOC. When there is sunlight the
next day, the batteries are charged to a certain amount of power and then start to supply power
to loads.
5. In the off-grid scenario, it's not supported to configure optimizers. When LUNA2000 discharge
Configure the components in finished and switched off, there is no power to activate optimizers, and the inverter can't be power
the dashed-line boxes as on automatically.
required.
17 Huawei Confidential