ABB ME ASURE ME NT & AN AL YT ICS | D AT A SHE ET

ProcessMaster FEP630
Electromagnetic flowmeter
2 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Measurement made easy
The first choice for all industrial applications

EtherNet/IP, PROFINET®
• Minimize commissioning and Start-up
• Configure the Device remotely
• Take advantage of the in-built device driver
(EDS for EtherNet/IP™, GSDML for PROFINET®) reducing integration cost
• Monitor your Process and the Flowmeter Status
• Diagnose your Process and the Flowmeter Status
• Verify the Flowmeter remotely


Diagnostics for real-life situations
• To keep your process up and running
• Gas bubble, partial filling or empty pipe detection, electrode impedance,
conductivity and sensor temperature monitoring
• Clear text messages for simplified troubleshooting


On board health check
• Flowmeter sensor and transmitter integrity check utilizing fingerprint
technology


Noise / Grounding check
• Verify the installation is correct from day one


Service interval monitoring
• Receive timed notifications


Backwards compatibility
• Protect your investment in ABB flowmetering
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 3


ProcessMaster series
ProcessMaster is available in two series – ProcessMaster 610 the good fit for everyday applications and ProcessMaster 630 the
first choice for all process industry applications delivering best in class functionality and options.

Applicability FEP610 series FEP630 series


Good fit for everyday applications The first choice for all industrial applications
Chemical Industry  
Corrosive liquids, acids, bases
Power  
Coal slurry, Lime slurry, Cooling
Mining  
Abrasive slurries, hydraulic transport
Pulp & Paper Up to 2 % Stock Up to 4 % Stock
Stock Flows, Latex, Clay, Liquor, Chemicals
Oil & Gas  
High pressure applications
Food & Beverage  
Hygienic applications
Measuring medium minimum conductivity 20 μS/cm 5 μS/cm

Measuring medium temperature Up to 130 °C (266 °F) Up to 180 °C (356 °F)

Pressure ≤ PN 40 / Cl 300 ≤ PN 40 / Cl 300, option for high pressure

Hazardous area — Yes

Features FEP610 series FEP630 series


Accuracy 0.5 % 0.4 %, Option up to 0.2 %

Nominal diameter DN 3 to 2000 (1/8 to 80″) DN 3 to 2000 (1/8 to 80″)

Liner material PTFE, Rubber, PFA, ETFE PTFE, Rubber, PFA, ETFE, Ceramic Carbide, Linatex

I/O’s 1 x analog, 2 x digital 1 x analog, 2 x digital, option for add-in modules

Communication High Speed Infrared Port HART®, PROFIBUS DP®, PROFIBUS PA®,
Communication based on HART DTM Modbus RTU®, Modbus TCP®, Ethernet IP®,
PROFINET®
Process diagnostics Empty pipe Empty pipe, Partially filling, Gas bubbles, Electrode
Impedance, Conductivity, Sensor temperature
Backwards compatibility — Yes
4 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… ProcessMaster series
Features and Functions
On-board Health Check Diagnostics for real-life situations
ProcessMaster's in-built fingerprint technology helps to Detecting critical process conditions at an early stage helps
ensure Sensor and Transmitter Integrity without the need to reducing unscheduled downtime and maintenance. Clear text
remove the flowmeter from the process. The Check provides messages simplify troubleshooting.
a pass / failed result based on a comparison of the current Device diagnostic information can be accessed without any
flowmeter status to a set of reference data. intervention – either through the HMI or bus communication.

Benefits: Benefits:
• Easy to operate • Peace-of-mind that flowmeter is operating within its
• No additional equipment required specification
• No training necessary • Prioritized alarms to correct most important alarm first
• Quick check of flowmeter integrity • Through-the-glass operation without the need to open
the housing

Backwards Compatibility saves your Investment in ABB


Flowmetering
Take advantage of new features and improved performance. Verify the Installation is correct - from day one
Switch to the new product at your own timeline. Minimize the Improving quality and reducing cost can be a challenge if the
cost of change in stock keeping, documentation and change flow measurement is unstable. A proper grounding is
of internal processes. fundamental to an accurate electromagnetic flow
measurement. ProcessMaster's in-built noise / grounding
Benefits: check helps getting the wiring / grounding right from day
• Drop in replacement one without the need for further Tools.
• Same terminal designation I/O’s, sensor connections
• No need to change wiring documentation
• Sensor cable stays unchanged
• Identical operating philosophy:
Easy Set-up and Sensor Set-up
• Common user experience, less training
• Less inventory, less cost
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 5

Standard functionality Detection of partial filling


Flowmeter sensor coil inductance A partially filled sensor affects the flowmeter reading and the
A measurement of the flowmeter sensor coil inductance can measuring accuracy.
be triggered. This enables to check for the flowmeter sensor If the flowmeter sensor is ordered with a full pipe detection
coil integrity. electrode, which is located at the Top of the sensor, the
transmitter’s ‘...Diagnosis Tfe’ function enables for an alarm
Noise check / Grounding check in case the sensor tube starts to become partially filled.
This function allows checking for noise and proper electrical
Pre-requisites using the functionality:
grounding of the device. While the check is in progress, no
• Nominal diameter: > DN 50 (> 2″)
flow measurement can take place.
• Flowmeter sensor design level A
• Conductivity of the measuring medium:
Pre-requisites using the functionality:
20 to 20000 μS/cm
• Flowmeter sensor must be completely filled
• No flow must occur in the flowmeter sensor
Installation conditions:
• The flowmeter sensor must be installed horizontally
Fingerprint
with the terminal box pointing upward.
The "fingerprint" database integrated in the transmitter
allows for comparison of the values at the time of factory
Verification
calibration or commissioning with the currently recorded
There is an Option for an in-depth verification of the device
values.
using an external Tool from ABB.
A quick "on-board health check" resulting in a pass / fail
This Tool provides a brief documentation of the Verification
information can be performed.
results allowing for a print out.
For an in-depth verification, an external tool is available from
ABB (in preparation).
6 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… ProcessMaster series
… Features and Functions
Optional diagnostic functions
The extended diagnostics functionality package contains the Electrode impedance
following functions. An Impedance measurement between the electrode and
ground can be triggered.
Gasbubble detection This enables to check for the electrode integrity.
Gas bubbles in the measuring medium effect the flowmeter
reading and the accuracy. Flowmeter sensor temperature
Enhanced diagnostics feature the option for gas bubble A flowmeter sensor temperature measurement can be
detection to make the flow measurement most reliable. triggered.
There is the option for a gas bubble alarm triggered once the This enables to check for the flowmeter sensor temperature.
actual gas bubble value exceeds the threshold configured. With flowmeter sensor temperature out of spec, the digital
This alarm is shown in the HMI. The digital output flags an output flags an alarm if configured accordingly.
alarm if configured accordingly.
Transmitter in-house temperature
Pre-requisites using the functionality: Monitoring the temperature of the electronic unit in the
• Nominal diameter: DN 10 to DN 300 (⅜ to 12 in). transmitter triggers an alarm via the digital output, if
• Conductivity of the measuring medium: configured.
20 to 20000 μS/cm. In the ‘...Diagnosis Values’, the current temperature as well as
the smallest and largest previously measured temperature is
Installation conditions: displayed.
• The flowmeter sensor can be installed either
horizontally or vertically. Vertical installation is
preferable.

Conductivity monitoring
The conductivity of the fluid can be monitored by setting
minimum / maximum alarm thresholds.
Once alarm limits are exceeded, the digital output flags an
alarm if configured accordingly.
The conductivity is available as 4 to 20 mA output (option
card).

Pre-requisites using the functionality:


• Conductivity of the measuring medium:
20 to 20000 μS/cm.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 7

Filling function
The optional filling function allows filling with filling times> 3
seconds.

Filling quantity is configurable and the filling process can be


started via the digital input (plug-in card).
As soon as the filling quantity has been reached, the valve can
be closed via the digital output.
Filling quantity correction is calculated by measuring the
overrun quantity.
Additionally, the low flow cut-off can be configured if
required.

1 Supply tank VO Valve open


(filling started)
2 Sensor
VC Valve closed
3 Start / stop fill operation (fill quantity reached)
(digital input through plug-in
t1 Valve closing time
card)
t2 Overrun time
4 Fill valve
5 Filling tank

Figure 1: FillMass fill function


8 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Overview – models without hazardous area approval
Sensor
Integral mount design Remote mount design

1 Single-compartment transmitter housing 3 Flowmeter sensor, Design Level A (DN 3 to 2000)


2 Dual-compartment transmitter housing

Figure 2: Designs

Flowmeter sensor
Model ProcessMaster FEP631, FEP632, FET632
Housing Integral mount design, remote mount design
Measuring accuracy for liquids 0.4 % of the measured value, option for 0.3 % and 0.2 % of the measured value
Permissible measuring medium Standard: −25 to 130 °C (−13 to 266 °F)
temperature Tmedium Option: −25 to 180 °C (−13 to 356 °F)
Minimum conductivity > 5 µS/cm, (20 µS/cm for demineralized water)
Nominal pressure rating PN 6 to 100; ASME CL 150 to 2500; JIS 5K to 20K, AS flanges, AWWA C207 Class B, D, E
Nominal diameter DN 3 to 2000 (¹⁄₁₀ to 80 in)
Process connection Flange based on DIN, ASME, JIS, AS2129 table D, E, AWWA C207 Class B, D, E
Materials process connection Steel, stainless steel
Lining material Hard rubber (DN 25 to 2000), soft rubber (DN 50 to 2000), PTFE (DN 10 to 600), PFA (DN 3 to 200),
ETFE (DN 25 to 600), Ceramic Carbide (DN 25 to 1000), Linatex® (DN 50 to 600)
Electrode material Stainless steel, Hastelloy B®, Hastelloy C®, Platinum-iridium, Tantalum, Titanium, Double Layer, Tungsten carbide
IP rating Integral mount design: IP 65 / IP 67, NEMA 4X
Remote mount design: IP 65 / IP 67 / IP 68 (sensor only), NEMA 4X

Approvals
Pressure Equipment Directive Conformity assessment in accordance with category III, fluid group 1
2014/68/EU
CRN (Canadian regulatory On request
number)
Explosion protection ATEX / IECEx / UKEX Zone 1, 2, 21, 22
FM / cFM Cl 1 Div 1 (≤ DN 300), Cl 1 Div 2
Additional approvals At www.abb.com/flow or on request.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 9

Transmitter

1 Dual-compartment transmitter housing 2 Single-compartment transmitter housing

Figure 3: Designs

Transmitter
Model FET632
Housing Integral mount design, remote mount design
IP rating IP 65 / IP 67 / NEMA 4X
Cable length Maximum 200 m (656 ft), remote mount design only
Power supply 100 to 240 V AC (−15 / +10 %) 50 / 60 Hz, 16.8 to 30 V DC
Outputs Current output: 4 to 20 mA active or passive (can be configured on-site)
Digital output 1: passive, configurable as pulse, frequency or switch output
Digital output 2: passive, configurable as pulse or switch output
Additional outputs The transmitter has two slots which can be used to insert plug-in cards to extend the outputs.
The following plug-in cards are available:
• Current output (passive)
• Digital output (passive)
• Digital input (passive):
• 24 V DC power supply for active outputs
Communication Standard: HART® 7.1
Option: PROFIBUS DP®, PROFIBUS PA®, Modbus RTU®, Modbus TCP®, EtherNet/IP®, ProfiNet®

Approvals
Explosion protection None
Additional approvals At www.abb.com/flow or on request.
10 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Overview – models with Ex protection
Overview – The fast track to explosion protection device data
These safety instructions related to explosion protection are valid in conjunction with the following test documentation and
certificates:

Scope Certificate
ATEX Zone 1 / 21 FM17ATEX0016X
ATEX Zone 2 / 22 FM17ATEX 0017X
IEC Ex Zone 1 / 21 IECEx FME 17.0001X
IEC Ex Zone 2 / 22 IECEx FME 17.0001X
FMus Div 1 (USA) FM17US0062X
FMus Div 2 (USA) FM17US0062X
cFM Div 1 (Canada) FM17CA0033X
cFM Div 2 (Canada) FM17CA0033X
NEPSI Zone 1 GYJ18.1487X
NEPSI Zone 2 GYJ18.1487X
UKEX Zone 1 FM21UKEX0033X
UKEX Zone 2 FM21UKEX0032X

Model Operation in zone Electrical connection and explosion protection data from chapter
FEP631-A1 Zone1, 21 Operation in Zone 1, 21 on page 63
FEP631-A2 Zones 2, 22 Operation in Zone 2, 22 on page 68
FEP632-A1 and FET632-A1 Zone1, 21 Operation in Zone 1, 21 on page 63
FEP632-A1 and FET632-Y0 Zone1, 21 Operation in Zone 1, 21 on page 63
FEP632-A2 and FET632-A2 Zones 2, 22 Operation in Zone 2, 22 on page 68
FEP632-A2 and FET632-Y0 Zones 2, 22 Operation in Zone 2, 22 on page 68

Version in integral mount design


The transmitter and the flowmeter sensor form a single mechanical entity.
The transmitter is available in two housing designs:
• Single-compartment housing
This is suited for use in ATEX/IEC Ex Zone 2, 22.
In the single-compartment housing, the electronics chamber and the connection chamber in the transmitter are not
separated from each other.
• Dual- compartment housing:
This is suited for use in ATEX/IEC Ex Zone 2, 22.
In the dual-compartment housing, the electronics chamber and the connection chamber in the transmitter are
separated from each other.

Note
Further information on the Ex Approval of devices can be found in the type examination certificates or the relevant certificates
at www.abb.com/flow.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 11

ATEX / IEC Zone 1, FM Cl1 Div 1 ATEX / IEC Zone 2, FM Cl1 Div 2

Sensor Sensor
ProcessMaster 630 ProcessMaster 630
FEP631-A1 (Zone 1, 21) FEP631-A2 (Zone 2, 22)
FEP631-F1 (Cl1, Div. 1) FEP631-F2 (Cl1, Div. 2)
FEP631-U1 (Zone 1, 21) FEP631-U2 (Zone 2, 22)

ATEX / UKEX ATEX / UKEX


Certificate ATEX: FM17ATEX0016X Certificate ATEX: FM17ATEX0017X
Certificate UKEX: FM21UKEX0033X Certificate UKEX: FM21UKEX0032X
DN 3 to 300: II 3G Ex ec IIC T6…T1 Gc 3)
II 2 (1) G Ex db eb ib mb [ia Ga] IIC T6…T1 Gb II 3D Ex tc IIIC T80°C…Tmedium Dc
II 2 (1) D Ex tb [ia Da] IIIC T80°C…Tmedium Db
DN 350 to 2000:
II 2 (1) G Ex db eb ib [ia Ga] IIC T6…T1 Gb
II 2 (1) D Ex tb [ia Da] IIIC T80°C…Tmedium Db
IEC IEC
Certificate: IECEx FME 17.0001X Certificate: IECEx FME 17.0001X
DN 3 to 300: II 3G Ex ec IIC T6…T1 Gc 3)
II 2 (1) G Ex db eb ib mb [ia Ga] IIC T6…T1 Gb II 3D Ex tc IIIC T80°C…Tmedium Dc
II 2 (1) D Ex tb [ia Da] IIIC T80°C…Tmedium Db
DN 350 to 2000:
II 2 (1) G Ex db eb ib [ia Ga] IIC T6…T1 Gb
II 2 (1) D Ex tb [ia Da] IIIC T80°C…Tmedium Db
USA, FM approval USA, FM approval
Certificate: FM17US0062X Certificate: FM17US0062X
DN 3 to 300: NI: CL I, Div 2, GPS ABCD T6...T1 3)
S-XP-IS: CL I, Div 1, GPS ABCD T6...T1 DIP: CL II,III, Div 2, GPS EFG T6…T3B
DIP: CL II,III, Div 1, GPS EFG T6...T3B CL I, ZN 2, AEx ec IIC T6…T1 3)
CL I, ZN 1, AEx db eb mb [ia Ga] IIB+H2 T6…T1 Gb ZN 21, AEx tb IIIC T80°C...T165°C
ZN 21, AEx tb [ia Da] IIIC T80°C...T165°C Db
Canada, FM approval Canada, FM approval
Certificate: FM17CA0033X Certificate: FM17CA0033X
DN 3 to 300: NI: CL I, Div 2, GPS ABCD T6...T1 3)
S-XP-IS: CL I, Div 1, GPS BCD T6...T1 DIP: CL II,III, Div 2, GPS EFG T6…T3B 3)
DIP: CL II,III, Div 1, GPS EFG T6...T3B CL I, ZN 2, Ex ec IIC T6...T1 Gc 3)
CL I, ZN 1, Ex db eb mb [ia Ga] IIB+H2 T6…T1 Gb Ex tb IIIC T80°C...T165°C Db 4)
Ex tb [ia Da] IIIC T80°C...T165°C Db
1) Single-compartment housing
2) Dual-compartment housing
When Flowmeter is equipped with Ethernet Card (Ethernet Card availabe with Zone 2, Div. 2 only), the following Notes apply:
3) T4 instead of T6
4) T80°C instead of T80°C ...T165°C
12 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Overview – models with Ex protection
Version with remote mount design
The transmitter is mounted in a separate location from the flowmeter sensor. The electrical connection between the
transmitter and flowmeter sensor may only be established using the signal cable supplied. A maximum signal cable length of
200 m (656 ft) is possible.

Note
Further information on the Ex Approval of devices can be found in the type examination certificates or the relevant certificates
at www.abb.com/flow.

ATEX / IEC Zone 1, FM Cl1 Div1


The following table presents the combination of the FEP632 sensor in explosion-proof design with the FET632 transmitter.

Sensor
ProcessMaster 630 ProcessMaster 630
FEP632-A1 (Zone 1, 21) FEP632-F1 (Cl1, Div. 1)
FEP632-U1 (Zone 1, 21)

ATEX / UKEX USA, FM approval


Certificate ATEX: FM17ATEX0016X Certificate: FM17US0062X
Certificate UKEX: FM21UKEX0033X
DN 3 to 300: DN 3 to 300:
II 2 G Ex eb ib mb IIC T6…T1 Gb S-XP: CL I, Div 1, GPS ABCD T6...T1
II 2 D Ex tb IIIC T80°C…Tmedium Db DIP: CL II,III, Div 1, GPS EFG T6…T3B
DN 350 to 2000: CL I, ZN 1, AEx db eb mb IIB+H2 T6…T1 Gb
II 2 G Ex eb ib IIC T6…T1 Gb ZN 21, AEx tb IIIC T80°C...T165°C Db
II 2 D Ex tb IIIC T80°C…Tmedium Db
IEC Canada, FM approval
Certificate: IECEx FME 17.0001X Certificate: FM17CA0033X
DN 3 to 300: DN 3 to 300:
II 2 G Ex eb ib mb IIC T6…T1 Gb S-XP: CL I, Div 1, GPS BCD T6...T1
II 2 D Ex tb IIIC T80°C…Tmedium Db DIP: CL II,III, Div 1, GPS EFG T6…T3B
DN 350 to 2000: CL I, ZN 1, Ex db eb mb IIB+H2 T6…T1 Gb
II 2 G Ex eb ib IIC T6…T1 Gb Ex tb IIIC T80°C...T165°C Db
II 2 D Ex tb IIIC T80°C…Tmedium Db
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 13

Transmitter
FET632-A1 (Zone 1, 21) FET632-A2 (Zone 2, 22) FET632-Y0
FEP632-F1 (Cl1, Div. 1) FEP632-F2 (Cl1, Div. 2) Outside Ex-area
FET632-U1 (Zone 1, 21) FET632-U2 (Zone 2, 22)

ATEX / UKEX ATEX / UKEX —


Certificate ATEX: FM17ATEX0016X Certificate ATEX: FM17ATEX0017X No Ex Approval!
Certificate UKEX: FM21UKEX0033X Certificate UKEX: FM21UKEX0032X
II 2 (1) G Ex db eb mb [ia Ga] IIC T6 Gb II 3G Ex ec IIC T6 Gc 3)
II 2 (1) D Ex tb [ia Da] IIIC T80°C Db II 3D Ex tc IIIC T80°C Dc
IEC IEC —
Certificate: IECEx FME 17.0001X Certificate: IECEx FME 17.0001 X No Ex Approval!
II 2 (1) G Ex db eb mb [ia Ga] IIC T6 Gb II 3G Ex ec IIC T6 Gc 3)
II 2 (1) D Ex tb [ia Da] IIIC T80°C Db II 3D Ex tc IIIC T80°C Dc
USA, FM approval USA, FM approval —
Certificate: FM17US0062X Certificate: FM17US0062X No Ex Approval!
XP-IS: CL I, Div 1, GPS BCD T6 NI: CL I, Div 2, GPS ABCD T6 3)
DIP: CL II,III, Div 1, GPS EFG T6 DIP: CL II,III, Div 2, GPS EFG T6 3)
CL I, ZN 1, AEx db [ia Ga] IIB+H2 T6 Gb CL I, ZN 2, AEx ec IIC T6 3)
ZN 21, AEx tb [ia Da] IIIC T80°C Db ZN 21, AEx tb IIIC T80°C
Canada, FM approval Canada, FM approval —
Certificate: FM17CA0033X Certificate: FM17CA0033X No Ex Approval!
XP-IS: CL I, Div 1, GPS BCD T6 NI: CL I, Div 2, GPS ABCD T6 3)
DIP: CL II,III, Div 1, GPS EFG T6 DIP: CL II,III, Div 2, GPS EFG T6 3)
CL I, ZN 1, Ex db [ia Ga] IIB+H2 T6 Gb Ex ec IIC T6 Gc 3)
Ex tb [ia Da] IIIC T80°C Db Ex tb IIIC T80°C Db
* Single-compartment housing
** Dual-compartment housing
When Flowmeter is equipped with Ethernet Card (Ethernet Card availabe with Zone 2, Div. 2 only), the following Notes apply:
3) T4 instead of T6
14 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Overview – models with Ex protection
… Version with remote mount design
ATEX / IEC Zone 2, FM Cl1 Div2
The following table presents the combination of the FEP632 sensor in explosion-proof design with the FET632 transmitter.

Sensor Transmitter
ProcessMaster 630 FET632-A2 (Zone 2, 22) FET632-Y0
FEP632-A2 (Zone 2, 22) FEP632-F2 (Cl1, Div. 2) Outside Ex-area
FEP632-F2 (Cl1, Div. 2) FET632-U2 (Zone 2, 22)
FEP632-U2 (Zone 2, 22)

ATEX / UKEX ATEX / UKEX —


Certificate ATEX: FM17ATEX0017X Certificate ATEX: FM17ATEX0017X No Ex Approval!
Certificate UKEX: FM21UKEX0032X Certificate UKEX: FM21UKEX0032X
II 3G Ex ec IIC T6…T1 Gc Ex ec IIC T6 Gc 2)
II 3D Ex tc IIIC T80°C…Tmedium Dc Ex tc IIIC T80°C Dc
IEC IEC —
Certificate: IECEx FME 17.0001X Certificate: IECEx FME 17.0001 X No Ex Approval!
II 3G Ex ec IIC T6…T1 Gc II 3G Ex ec IIC T6 Gc 2)
II 3D Ex tc IIIC T80°C…Tmedium Dc II 3D Ex tc IIIC T80°C Dc
USA, FM approval USA, FM approval —
Certificate: FM17US0062X Certificate: FM17US0062X No Ex Approval!
NI: CL I, Div 2, GPS ABCD T6...T1 NI: CL I, Div 2, GPS ABCD T6 2)
DIP: CL II,III, Div 2, GPS EFG T6…T6…T3B DIP: CL II,III, Div 2, GPS EFG T6 2)
CL I, ZN 2, AEx ec IIC T6…T1 CL I, ZN 2, AEx ec IIC T6 2)
ZN 21, AEx tb IIIC T80°C...T165°C ZN 21, AEx tb IIIC T80°C
Canada, FM approval Canada, FM approval —
Certificate: FM17CA0033X Certificate: FM17CA0033X No Ex Approval!
NI: CL I, Div 2, GPS ABCD T6...T1 NI: CL I, Div 2, GPS ABCD T6 2)
DIP: CL II,III, Div 2, GPS EFG T6…T3B DIP: CL II,III, Div 2, GPS EFG T6 2)
CL I, ZN 2, Ex ec IIC T6...T1 Gc Ex ec IIC T6 Gc 2)
Ex tb IIIC T80°C...T165°C Db Ex tb IIIC T80°C Db
1) Single-compartment housing
When Flowmeter is equipped with Ethernet Card (Ethernet Card availabe with Zone 2, Div. 2 only), the following Notes apply:
2) T4 instead of T6
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 15


Flowmeter sensor
Measuring principle Measuring accuracy
Measurements performed by the electromagnetic flowmeter Reference conditions
are based on Faraday’s law of induction. A voltage is
Based on EN 29104
generated in a conductor when it moves through a magnetic
field. Temperature of medium 20 °C (68 °F) ±2 K
being measured
Ambient temperature 20 °C (68 °F) ±2 K
Power supply Nominal voltage acc. to name plate
U = ±1 %; frequency f = ±1 %
Installation conditions • Upstream: > 10 x DN straight section
• Downstream: > 5 x DN straight section
Warm-up phase 30 minutes

Measurement value deviation and reproducibility


Measuring error

1 Magnet coil 3 Measuring electrode


2 Measuring tube in electrode
plane

Figure 4: Electromagnetic flowmeter diagram

U1 ~ B × D × v D2 ×π U 1 ~ qv
qv = ×v
4 A Accuracy ± of measured value in %
U1 Measuring span v Average flow velocity
B Flow velocity v in m/s, Q / QmaxDN in %
B Magnetic induction qv Volume flow rate
D Electrode spacing Figure 5: Measuring error

With the device-relevant application of this measuring Impulse output


principle, a conductive measuring medium flows through a Standard calibration DN 3 to 2000
tube in which a magnetic field is generated perpendicular to ±0.4 % of measured value, ±0.02 % QmaxDN*
the flow direction (see Figure 4). Optional calibration
The voltage induced in the measuring medium is tapped by DN 3 to 600, 800: ±0.3 % of measured value, ±0.02 % QmaxDN*
two diametrically opposed electrodes. This measurement Or
voltage is proportional to the magnetic induction, the DN 10 to 600, 800: ±0.2 % of measured value, ±0.02 % QmaxDN*
electrode spacing and the average medium velocity v.
Taking into account that the magnetic induction and the
Current output
electrode spacing are constant values results in a proportion
Same as pulse output plus ±0.1 % of measured value ±0.01 mA
between the measurement voltage U1 and the average
* QmaxDN: See table in chapter Measuring range table on page 20.
medium velocity.
From the calculation of the volume flow rate follows that the
Repeatability, response time
measurement voltage is linear and proportional to the
volume flow rate. Repeatability Response time**
≤ 0.11 % of measured As step function 0 ... 99 %
The induced voltage is converted by the transmitter to value, tmeas = 100 s, 5 τ ≥ 200 ms at 25 Hz excitation frequency
standardized, analog and digital signals. v = 0.5 ... 10 m/s 5 τ ≥ 400 ms at 12.5 Hz excitation frequency
5 τ ≥ 500 ms at 6.25 Hz excitation frequency

Table 1 Repeatability, response time


** Of current output with damping of 0.04 seconds.
16 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
Permitted pipe vibration Temperature data
In accordance with EN 60068-2-6 Storage temperature range
Applicable to sensors in remote mount design and sensors in −40 to 70 °C (−40 to 158 °F)
integral mount design.
• Maximum deflection: 0.15 mm (0.006 in) in the frequency The temperature range offered by the device is dependent on
range of 10 to 58 Hz a number of different factors.
• Maximum acceleration: 2 g in the frequency range of These factors include the measuring medium temperature
58 to 150 Hz Tmedium, the ambient temperature Tamb, operating pressure
• Maximum acceleration: 4g (Tested to DNV DNVGL CG Pmedium, liner material and the approval for explosion
0339-2019) for Devices specified with code 'CL5' in protection.
Modelcode. CL5 = DNV approved device.
Maximum permissible cleaning temperature
IP rating
CIP media Liner Cleaning temperature
• IP 65 / IP 67 in accordance with EN 60529 Steam PTFE, PFA 150 °C (302 °F)
• IP 68 in accordance with EN 60529 (for remote mount Cleaning fluid PTFE, PFA 140 °C (284 °F)
design only)
• NEMA 4X • The maximum cleaning temperature specified applies to a
maximum ambient temperature of 25 °C (77 °F).
If the ambient temperature up-scales > 25 °C (> 77 °F),
Signal cables then the temperature difference to the current
For remote mount design only. temperature must be subtracted from the max. cleaning
The maximum signal cable length between flowmeter sensor temperature.
and transmitter is 200 m (656 ft). • The specified cleaning temperature may have an effect for
A 5 m (16.4 ft) cable is included in the scope of delivery. a maximum of 60 minutes.
If more than 5 m (16.4 ft) is required, the cable can be ordered
separately – see Accessories on page 90.

For marine applications, a certified signal cable is available.


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 17

Maximum ambient temperature depending on measuring medium temperature


Note
When using the device in potentially explosive atmospheres, note the additional temperature data in the chapter entitled
Operation in Zone 1, 21 on page 63 and chapter Operation in Zone 2, 22 on page 68.

Integral mount design

Flowmeter sensor in standard version


Lining material Flange material Ambient temperature range (Tamb) Measuring medium temperature (Tmedium)
Minimum Maximum Minimum Maximum
Hard rubber Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 85 °C (185 °F)
−5 °C (23 °F)* 80 °C (176 °F)*
Hard rubber Stainless steel −15 °C (5 °F) 60 °C (140 °F) −15 °C (5 °F) 85 °C (185 °F)
−5 °C (23 °F) * 80 °C (176 °F) *
Soft rubber Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 60 °C (140 °F)
Soft rubber Stainless steel −15 °C (5 °F) 60 °C (140 °F) −15 °C (5 °F) 60 °C (140 °F)
PTFE Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 90 °C (194 °F)
45 °C (113 °F) 130 °C (266 °F)
PTFE Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −25 °C (−13 °F) 90 °C (194 °F)
−40 °C (−40 °F)** 45 °C (113 °F) 130 °C (266 °F)
Thick PTFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 90 °C (194 °F)
45 °C (113 °F) 130 °C (266 °F)
Thick PTFE*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −25 °C (−13 °F) 90 °C (194 °F)
−40 °C (−40 °F)** 45 °C (113 °F) 130 °C (266 °F)
PFA*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 90 °C (194 °F)
45 °C (113 °F) 130 °C (266 °F)
PFA*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −25 °C (−13 °F) 90 °C (194 °F)
−40 °C (−40 °F)** 45 °C (113 °F) 130 °C (266 °F)
ETFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 90 °C (194 °F)
45 °C (113 °F) 130 °C (266 °F)
ETFE*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −25 °C (−13 °F) 90 °C (194 °F)
−40 °C (−40 °F)** 45 °C (113 °F) 130 °C (266 °F)
Linatex* Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 70 °C (158 °F)
Linatex* Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 70 °C (158 °F)
Ceramic carbide Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 80 °C (176 °F)
Ceramic carbide Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 80 °C (176 °F)
* Only for China production site
** For (optional) low−temperature version only
*** Only for design level ‘A’
18 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Temperature data

Flowmeter sensor in high temperature version***


Lining material Flange material Ambient temperature range (Tamb) Measuring medium temperature (Tmedium)
Minimum Maximum Minimum Maximum
Thick PTFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 180 °C (356 °F)
Thick PTFE*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 180 °C (356 °F)
−40 °C (−40 °F)**
PFA*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 180 °C (356 °F)
PFA*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 180 °C (356 °F)
−40 °C (−40 °F)**
ETFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 130 °C (266 °F)
ETFE*** Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 130 °C (266 °F)
−40 °C (−40 °F)**
* Only for China production site
** For (optional) low−temperature version only
*** Only for design level ‘A’
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 19

Note
When using the device in potentially explosive atmospheres, note the additional temperature data in the chapter entitled
Operation in Zone 1, 21 on page 63 and chapter Operation in Zone 2, 22 on page 68.

Remote mount design

Flowmeter sensor in standard version


Lining material Flange material Ambient temperature range (Tamb) Measuring medium temperature (Tmedium)
Minimum Maximum Minimum Maximum
Hard rubber Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 85 °C (185 °F)
−5 °C (23 °F)* 80 °C (176 °F)*
Hard rubber Stainless steel −15 °C (5 °F) 60 °C (140 °F) −15 °C (5 °F) 85 °C (185 °F)
−5 °C (23 °F)* 80 °C (176 °F) *
Soft rubber Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 60 °C (140 °F)
Soft rubber Stainless steel −15 °C (5 °F) 60 °C (140 °F) −15 °C (5 °F) 60 °C (140 °F)
PTFE Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 90 °C (194 °F)
−10 °C (14 °F) 45 °C (113 °F) −10 °C (14 °F) 130 °C (266 °F)
PTFE Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 130 °C (266 °F)
−40 °C (−40 °F)**
Thick PTFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 130 °C (266 °F)
Thick PTFE*** Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 130 °C (266 °F)
−40 °C (−40 °F)**
PFA*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 130 °C (266 °F)
PFA*** Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 130 °C (266 °F)
−40 °C (−40 °F)**
ETFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 130 °C (266 °F)
ETFE*** Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 130 °C (266 °F)
Linatex* Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 70 °C (158 °F)
Linatex* Stainless steel −20 °C (−4 °F) 60 °C (140 °F) −20 °C (−4 °F) 70 °C (158 °F)
Ceramic carbide Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 80 °C (176 °F)
Ceramic carbide Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −20 °C (−4 °F) 80 °C (176 °F)

Flowmeter sensor in high temperature version***


Lining material Flange material Ambient temperature range (Tamb.) Measuring medium temperature (Tmedium)
Minimum Maximum Minimum Maximum
Thick PTFE*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 180 °C (356 °F)
Thick PTFE*** Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 180 °C (356 °F)
−40 °C (−40 °F)**
PFA*** Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 180 °C (356 °F)
PFA*** Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 180 °C (356 °F)
−40 °C (−40 °F)**
ETFE Steel −10 °C (14 °F) 60 °C (140 °F) −10 °C (14 °F) 130 °C (266 °F)
ETFE Stainless steel −25 °C (−13 °F) 60 °C (140 °F) −25 °C (−13 °F) 130 °C (266 °F)
−40 °C (−40 °F)**
* Only for China production site
** For (optional) low−temperature version only
*** Only for design level ‘A’
20 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
Measuring range table
The full-scale value can be set between 0.02 x QmaxDN and 2 x QmaxDN.

Nominal diameter Lower range value QmaxDN Upper range value


DN in 0.02 x QmaxDN (≈ 0.2 m/s) 0 to ≈ 10 m/s 2 x QmaxDN (≈ 20 m/s)
3 ¹⁄₁₀ 0.08 l/min (0.02 US gal/min) 4 l/min (1.06 US gal/min) 8 l/min (2.11 US gal/min)
4 ⁵⁄₃₂ 0.16 l/min (0.04 US gal/min) 8 l/min (2.11 US gal/min) 16 l/min (4.23 US gal/min)
6 ¼ 0.4 l/min (0.11 US gal/min) 20 l/min (5.28 US gal/min) 40 l/min (10.57 US gal/min)
8 ⁵⁄₁₆ 0.6 l/min (0.16 US gal/min) 30 l/min (7.93 US gal/min) 60 l/min (15.85 US gal/min)
10 ⅜ 0.9 l/min (0.24 US gal/min) 45 l/min (11.9 US gal/min) 90 l/min (23.78 US gal/min)
15 ½ 2 l/min (0.53 US gal/min) 100 l/min (26.4 US gal/min) 200 l/min (52.8 US gal/min)
20 ¾ 3 l/min (0.79 US gal/min) 150 l/min (39.6 US gal/min) 300 l/min (79.3 US gal/min)
25 1 4 l/min (1.06 US gal/min) 200 l/min (52.8 US gal/min) 400 l/min (106 US gal/min)
32 1¼ 8 l/min (2.11 US gal/min) 400 l/min (106 US gal/min) 800 l/min (211 US gal/min)
40 1½ 12 l/min (3.17 US gal/min) 600 l/min (159 US gal/min) 1200 l/min (317 US gal/min)
50 2 1.2 m3/h (5.28 US gal/min) 60 m3/h (264 US gal/min) 120 m3/h (528 US gal/min)
65 2½ 2.4 m3/h (10.57 US gal/min) 120 m3/h (528 US gal/min) 240 m3/h (1057 US gal/min)
80 3 3.6 m3/h (15.9 US gal/min) 180 m3/h (793 US gal/min) 360 m3/h (1585 US gal/min)
100 4 4.8 m3/h (21.1 US gal/min) 240 m3/h (1057 US gal/min) 480 m3/h (2113 US gal/min)
125 5 8.4 m3/h (37 US gal/min) 420 m3/h (1849 US gal/min) 840 m3/h (3698 US gal/min)
150 6 12 m3/h (52.8 US gal/min) 600 m3/h (2642 US gal/min) 1200 m3/h (5283 US gal/min)
200 8 21.6 m3/h (95.1 US gal/min) 1080 m3/h (4755 US gal/min) 2160 m3/h (9510 US gal/min)
250 10 36 m3/h (159 US gal/min) 1800 m3/h (7925 US gal/min) 3600 m3/h (15850 US gal/min)
300 12 48 m3/h (211 US gal/min) 2400 m3/h (10567 US gal/min) 4800 m3/h (21134 US gal/min)
350 14 66 m3/h (291 US gal/min) 3300 m3/h (14529 US gal/min) 6600 m3/h (29059 US gal/min)
400 16 90 m3/h (396 US gal/min) 4500 m3/h (19813 US gal/min) 9000 m3/h (39626 US gal/min)
450 18 120 m3/h (528 US gal/min) 6000 m3/h (26417 US gal/min) 12000 m3/h (52834 US gal/min)
500 20 132 m3/h (581 US gal/min) 6600 m3/h (29059 US gal/min) 13200 m3/h (58117 US gal/min)
600 24 192 m3/h (845 US gal/min) 9600 m3/h (42268 US gal/min) 19200 m3/h (84535 US gal/min)
700 28 264 m3/h (1162 US gal/min) 13200 m3/h (58118 US gal/min) 26400 m3/h (116236 US gal/min)
760 30 312 m3/h (1374 US gal/min) 15600 m3/h (68685 US gal/min) 31200 m3/h (137369 US gal/min)
800 32 360 m3/h (1585 US gal/min) 18000 m3/h (79252 US gal/min) 36000 m3/h (158503 US gal/min)
900 36 480 m3/h (2113 US gal/min) 24000 m3/h (105669 US gal/min) 48000 m3/h (211337 US gal/min)
1000 40 540 m3/h (2378 US gal/min) 27000 m3/h (118877 US gal/min) 54000 m3/h (237754 US gal/min)
1050 42 616 m3/h (2712 US gal/min) 30800 m3/h (135608 US gal/min) 61600 m3/h (271217 US gal/min)
1100 44 660 m3/h (3038 US gal/min) 33000 m3/h (151899 US gal/min) 66000 m3/h (290589 US gal/min)
1200 48 840 m3/h (3698 US gal/min) 42000 m3/h (184920 US gal/min) 84000 m3/h (369841 US gal/min)
1400 54 1080 m3/h (4755 US gal/min) 54000 m3/h (237755 US gal/min) 108000 m3/h (475510 US gal/min)
1500 60 1260 m3/h (5548 US gal/min) 63000 m3/h (277381 US gal/min) 126000 m3/h (554761 US gal/min)
1600 66 1440 m3/h (6340 US gal/min) 72000 m3/h (317006 US gal/min) 144000 m3/h (634013 US gal/min)
1800 72 1800 m3/h (7925 US gal/min) 90000 m3/h (396258 US gal/min) 180000 m3/h (792516 US gal/min)
2000 80 2280 m3/h (10039 US gal/min) 114000 m3/h (501927 US gal/min) 228000 m3/h (1003853 US gal/min)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 21

Process connections
For an overview of available process connection versions, see
Sensor housing, Design level ‘A’
Overview – models without hazardous area approval on
page 8.

Installation length
Part / DN Material
The sensor installation length is based on ISO 13359. Housing
For further details, refer to chapter Dimensions on page 29. DN 3 to 400 Cast aluminum (painted)
(1/10 to 16″) Paint coat: ≥ 80 µm thick, RAL 9002
DN 450 to 2000 Welded steel design (painted)
Materials (18 to 80″) Paint coat: ≥ 80 µm thick, RAL 9002
Meter tube Stainless steel 1)
Wetted parts
Terminal box Aluminum alloy, painted, ≥ 80 μm thick, light
Part Standard Option
gray, RAL 9002
Liner material PTFE, PFA, ETFE, hard Ceramic Carbide,
Option: Plastic, gray white, RAL 9002
rubber, soft rubber Linatex
Option: Stainless Steel
Measurement and grounding electrode for liner material
Cable gland 2) Polyamide, stainless Steel 3)
• Hard rubber SST 1.4571 (AISI 316Ti) Hastelloy B-3 (2.4600),
The meter tube is made of one of the materials listed below:
• Soft rubber Hastelloy C-4 (2.4610),
1) 1.4301, 1.4307, 1.4404, 1.4435, 1.4541, 1.4571
titanium, Tantalum,
ASTM materials:
Platinum-iridium,
Grade TP304, TP304L, TP316L, TP321, TP316Ti, TP317L, 0Cr18Ni9,
SST 1.4539 (AISI 904L)
00Cr18Ni10, 0CR17Ni14Mo2, 0Cr27Ni12Mo3, 0Cr18Ni10Ti
• PTFE, PFA, ETFE SST 1.4539 (AISI 904L) SST 1.4571 (AISI 316Ti),
2) Cable gland with M 20 x 1.5 or NPT thread, to be selected via the order
Hastelloy B-3 (2.4600),
number.
Hastelloy C-4 (2.4610),
3) In the case of explosion-proof design or for ambient temperature
Titanium, Tantalum,
of -40 °C (40 °F).
Platinum-iridium
Grounding ring Stainless steel On request
Protection plate Stainless steel On request

Non-wetted parts (process connection), Design level ‘A’

DN Standard Option
DN 3 to 15 Stainless steel 1) –
(1/10 to 1/2″)
DN 20 to 400 Steel (galvanized) 2) Stainless steel1)
(3/4 to 16″)
DN 450 to 2000 Steel (painted) 2) –
(18 to 80″)
The process connections are made of one of the materials listed below:
1) 1.4301 (AISI 304), 1.4307, 1.4404 (AISI 316L) 1.4435 (AISI 316L),
1.4541 (AISI 321) 1.4571 (AISI 316Ti)
2) 1.0038, 1.0460, 1.0570, 1.0432, ASTM A105, Q255A, 20#, 16Mn
22 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
Material load for process fittings
The limits of the permissible measuring medium temperature Material load
(Tmedium) and permissible pressure (Pmedium) are calculated Flowmeter sensor Design Level ‘A’
on the basis of the liner and flange material used in the
device (see device name plate).

Minimum permissible operating pressure


The following tables show the permissible minimum
operating pressure (Pmedium) as a function of the measuring
medium temperature (Tmedium) and the liner material.

Design Level ‘A’

Lining material Nominal diameter Pmedium Tmedium*


[mbar abs]
Hard rubber DN 25 to DN 2000 0 < 85 °C (185 °F)
(1 to 80″) < 80 °C (176 °F)**
Soft rubber DN 50 to DN 2000 0 < 60 °C (140 °F)
(2 to 80″)
PTFE DN 10 to DN 600 270 < 20 °C (68 °F)
Figure 6: DIN-flange, stainless steel, to DN 600 (24″); Design Level ‘A’
(⅜ to 24″) 400 < 100 °C (212 °F)
500 < 130 °C (266 °F)
Thick PTFE DN 25 to DN 80 0 < 180 °C (356 °F)
(1 to 3″)
DN 100 to DN 250 67 < 180 °C (356 °F)
(4 to 10″)
DN 300 (12″) 27 < 180 °C (356 °F)
PFA DN 3 to DN 200 0 < 180 °C (356 °F)
(¹⁄₁₀ to 8″)
ETFE DN 25 to DN 600 100 < 130 °C (266 °F)
(1 to 24″)
Ceramic carbide DN 25 to DN 1000 0 < 80 °C (176 °F)
(1 to 40″)
Linatex** DN 50 to DN 600 0 < 70 °C (158 °F)
(6 to 24″)
* For CIP/SIP cleaning, higher temperatures are permitted for limited
Figure 7: ASME-flange, stainless steel, to DN 400 (16″) (CL150/300) to DN 1000
time periods; refer to Maximum permissible cleaning temperature on (40″) (CL150); Design Level ‘A’
page 16.
** Only for China production site
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 23

Figure 8: DIN flange, steel up to DN 600 (24″); Design Level ‘A’


A DN 1000, PN 10 D DN 900, DN 800, PN 16
B DN 700, DN800, DN900, PN 10 E DN 700, PN 16
C DN 1000, PN 16

Figure 10: DIN-flange, stainless steel, up to DN 700 (28″) to DN 1000 (40″); Design
Level ‘A’

Figure 9: ASME-flange, steel up to DN 400 (16″) (CL150/300) to DN 1000 (40″)


(CL150); Design Level ‘A’

JIS 10K-B2210 flange


DN Material PN Tmedium Pmedium
DN 32 to 400 Stainless steel 10 −25 to 180 °C 10 bar (290
(1 ¼ to 16″) (−13 to 356 °F) psi)
A DN 1000, PN 10 D DN 900, DN 800, PN 16
(145 psi)
B DN 700, DN800, DN900, PN 10 E DN 700, PN 16
DN 32 to 400 Steel 10 −10 to 180 °C 10 bar (290
(1 ¼ to 16″) (14 to 356 °F): psi) C DN 1000, PN 16

(145 psi) Figure 11: DIN-flange, steel, up to DN 700 (28″) to DN 1000 (40″); Design Level ‘A’
24 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Material load for process fittings Installation conditions
General
The following points must be observed during installation:
• The flow direction must correspond to the marking, if
present
• The maximum torque for all flange screws must be
complied with
• Secure flange screws and nuts against pipe vibration.
• The devices must be installed without mechanical
tension (torsion, bending)
• Install flange devices / wafer-type devices with plane
parallel counterflanges and use appropriate gaskets
only
• Use gaskets made from a material that is compatible
with the measuring medium and measuring medium
temperature.
Figure 12: ASME flange, steel, DN 25 to 400 (1 to 24″); Design Level ‘A’ • Gaskets must not extend into the flow area, since
possible turbulence could influence the accuracy of
the device
• The piping may not exert any inadmissible forces or
torques on the device.
• Make sure that the temperature limits are not up-
scaled during operation of the device.
• Vacuum shocks in the piping should be avoided to
prevent damage to the liners (PTFE liner). Vacuum
shocks can destroy the device.
• Do not remove the sealing plugs in the cable glands
until you are ready to install the electrical cable
• Make sure the gaskets for the housing cover are
seated correctly. Carefully seal the cover. Tighten the
cover fittings
• The transmitter with a remote mount design must be
Figure 13: ASME flange, stainless steel, DN 25 to 400 (1 to 24″); Design Level ‘A’
installed at a largely vibration-free location
• Do not expose the transmitter and sensor to direct
sunlight. Provide appropriate sun protection as
necessary If necessary, provide a suited means of sun
protection.
• When installing the transmitter in a control cabinet,
make sure adequate cooling is provided

Devices with extended diagnostic functions


For devices with extended diagnostic functions different
installation conditions may be valid.
For additional information, see Optional diagnostic
functions on page 6.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 25

Brackets Flow direction

NOTE
Potential damage to device!
Improperly placed support structures can result in a
deformed housing and damage to the inner solenoids.
Place the support structures at the edge of the transmitter
housing (see arrows in Figure 14).

Figure 15: Flow direction

The device measures the flow rate in both flow directions.


Forward flow is the factory setting, as shown in Figure 15.

Electrode axis

Figure 14: Support for nominal diameters greater than DN 400

Devices with nominal diameters larger than DN 400 must be


mounted on a sufficiently strong foundation with support.

Figure 16: Orientation of the electrode axis


Gaskets
The following points must be observed when installing
The electrode axis 1 should be horizontal if at all possible or
gaskets:
no more than 45° from horizontal.
• To achieve the best results, make sure that the
gaskets and meter tube fit concentrically.
• To make sure that the flow profile is not distorted, the
gaskets may not intrude in the piping cross-section.
• The use of graphite with the flange or process
connection gaskets is prohibited. This is because, in
some instances, an electrically conductive coating may
form on the inside of the meter tube.
• For Non RTJ flange type sensors used in high pressure
installations (PN63, CL600 and up), ensure using an
appropriate gasket.
26 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Installation conditions
Mounting position Inlet and outlet sections

B 3 x DN 2 x DN

Figure 17: Mounting position

A Vertical installation for measuring abrasive materials, G12008

preferably with flow in upward direction. 1 Double elbow 2 Turn-off device


B For a horizontal installation, the meter tube must always
Figure 19: Inlet and outlet section, turn-off devices
be completely filled with the measuring medium.
Provide for a slight incline of the connection for The measuring principle is independent of the flow profile as
degassing. long as standing eddies do not extend into the measured
value formation, such as may for example occur after double
Minimum spacing of the devices elbows, in the event of tangential inflow, or where half-open
gate valves are located upstream of the sensor. In such cases,
measures must be put in place to normalize the flow profile.

A Do not install fittings, manifolds, valves, etc., right before


the flowmeter sensor.
B Inlet / outlet sections: length of the straight piping
upstream and downstream on the sensor.
Experience has shown that, in most installations, straight
inlet sections 3 × DN long and straight outlet sections
2 × DN long are sufficient (DN = nominal diameter of the
Spacing D: ≥ 1.0 m (3.3 ft) for Design Level ‘A’ flowmeter sensor).
Figure 18: Minimum spacing of the devices
For test stands, the reference conditions of 10 × DN
straight inlet and 5 × DN straight outlet must be provided,
in accordance with EN 29104 / ISO 9104.
• In order to prevent the devices from interfering with each
Valves or other turn-off devices should be installed in the
other, a minimum distance as presented in Figure 18
outlet section.
must be maintained between the devices.
Valve flaps must be installed so that the valve damper
• The sensor must not be operated in the vicinity of
plate does not extend into the flowmeter sensor.
powerful electromagnetic fields, e.g., motors, pumps,
transformers, etc. A minimum spacing of approx.
1 m (3.28 ft) must be maintained.
• For installation on or to steel parts (e.g. steel brackets), a
minimum spacing of 100 mm (3.94 in) must be
maintained (based on IEC801-2 and IECTC77B).
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 27

Free inlet or outlet

Figure 22: Insulation of the flowmeter sensor

The high temperature design allows for complete thermal


insulation of the flowmeter sensor. The pipeline and sensor
Figure 20: Free inflow and outflow
must be insulated 1 after installing the unit according to
the illustration.
A For a free outflow, do not install flowmeter at the highest
Grounding
point of the piping or on its outflow side, since the
The flowmeter sensor must be connected to ground
measuring tube may run empty, creating air bubbles.
potential. For technical reasons, this potential must be
B For free inflow/outflow, provide an invert to make sure
identical to the potential of the measuring medium.
that the piping is always full
For plastic or insulated lined pipelines, the measuring
medium is grounded by installing grounding rings.
Mounting with heavily contaminated measuring media
When there are stray potentials present in the pipeline, a
grounding ring is recommended on both ends of the
flowmeter sensor.

Figure 21: Bypass line

For strongly contaminated measuring media, a bypass line in


accordance with the figure is recommended so that
operation of the system can continue to run without
interruption during mechanical cleaning.
28 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Installation conditions
Mounting with pipe vibration Installation in piping with larger nominal diameter

1 Reducer

Figure 24: Using reducers

Determine the resulting pressure loss when using reducers:


1. Determine diameter ratios d/D.
2. Determine the flow velocity based on the flow rate
nomogram (Figure 25).
3. Read the pressure loss on the Y-axis in Figure 25.

1 Pump 3 Shut-off device


2 Damping device

Figure 23: Vibration damping

Strong vibrations in the pipeline must be damped using


flexible damping devices.

The damping devices must be installed beyond the supported


flowmeter section and outside of the section between the
shut-off devices.

Do not connect flexible damping devices directly to the


flowmeter sensor.

Figure 25: Flow rate nomogram for flange transition piece at α/2 = 8°

High pressure sensors (PN63, Cl600 and up)


With sensors, designed for higher pressure rating, the inner
diameter of the sensor might be different from the attached
pipe – see dimensions table.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 29

Dimensions
Flange DN 3 to 100 (¹⁄₁₀ to 4″), aluminum sensor housing (shell housing) — Design level ‘A’
All specified dimensions and weights are in mm (inch) or kg (lb). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the
PG cable inlet.
Figure 26: Integral mount design (top), remote mount design (bottom)
30 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions

Dimensions - Flange device DN 3 to 40, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D B L2), 3) C F7), 8) F17), 8) F27), 8) Weight
diameter
DN 3 ... 84) EN 1092-16), 90 (3.54) 19 (0.75) 200 (7.84) 82 (3.23) 255 (10.04) 269 (10.6) 191 (7.52) 5.5 (12)
(1/8 ... 5/16″5)) PN 10 to 401)
DN 10 ASME B16.5, CL 150 90 (3.54) 14.2 (0.56)
(3/8″5)) ASME B16.5, CL 300 95 (3.74) 17.3 (0.68)
JIS 10K 90 (3.54) 15 (0.59)
DN 15 (1/2″) EN 1092-16), 95 (3.74) 19 (0.75) 200 (7.84) 82 (3.23) 255 (10.04) 269 (10.6) 191 (7.52) 5.5 (12)
PN 10 to 401)
ASME B16.5, CL 150 90 (3.54) 14.2 (0.56)
ASME B16.5, CL 300 95.2 (3.75) 17.3 (0.68)
JIS 10K 95 (3.74) 15 (0.59)
DN 20 (3/4″) EN 1092-16), 105 (4.13) 21 (0.83) 200 (7.84) 82 (3.23) 255 (10.04) 269 (10.6) 191 (7.52) 6.5 (14)
PN 10 to 401)
ASME B16.5, CL 150 98.6 (3.88) 15.7 (0.62)
ASME B16.5, CL 300 117.3 (4.62) 18.7 (0.74)
JIS 10K 100 (3.94) 17 (0.67)
DN 25 (1″) EN 1092-16), 115 (4.53) 21 (0.83) 200 (7.84) 82 (3.23) 255 (10.04) 269 (10.6) 191 (7.52) 7.5 (16.5)
PN 10 to 401)
ASME B16.5, CL 150 108 (4.25) 17.2 (0.68)
ASME B16.5, CL 300 124 (4.88) 20.5 (0.81)
JIS 10K 125 (4.92) 17 (0.67)
DN 32 (1 1/4″) EN 1092-16), 140 (5.51) 21 (0.83) 200 (7.84) 92 (3.62) 262 (10.3) 276 (10.87) 198 (7.80) 8.5 (18.5)
PN 10 to 401)
ASME B16.5, CL 150 117.3 (4.62) 18.7 (0.74)
ASME B16.5, CL 300 133.4 (5.25) 22.1 (0.87)
JIS 10K 135 (5.31) 19 (0.75)
DN 40 (1 1/2″) EN 1092-16), 150 (5.91) 21 (0.83) 200 (7.84) 92 (3.62) 262 (10.3) 276 (10.87) 198 (7.80) 9.5 (21)
PN 10 to 401)
ASME B16.5, CL 150 127 (5.00) 20.5 (0.81)
ASME B16.5, CL 300 155.4 (6.12) 23.6 (0.93)
JIS 10K 140 (5.51) 19 (0.75)

Tolerance for L: +0 / -3 mm (+0 / -0.018 in.)


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 31

Dimensions - Flange device DN 50 to 100, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D B L2), 3) C F7), 8) F17), 8) F27), 8) Weight
diameter
DN 50 (2″) EN 1092-16), 165 (6.50) 23 (0.91) 200 (7.87) 97.5 (3.84) 268 (10.55) 282 (11.1) 204 (8.0) 11 (24)
PN 10 to 401)
ASME B16.5, CL 150 152.4 (6.00) 22.1 (0.87)
ASME B16.5, CL 300 165.1 (6.50) 25.4 (1.0)
JIS 10K 155 (6.10) 19 (0.75)
AS2129 table D, E 150 (5.91) – 8.5 (18.5)
DN 65 (2 1/2″) EN 1092-16), PN 161) 185 (7.28) 22 (0.87) 200 (7.87) 108.5 (4.25) 279 (10.98) 293 (11.54) 215 (8.46) 11.5 (25)
EN 1092-16), PN 401) 185 (7.28) 26 (1.02) 13.5 (30)
ASME B16.5, CL 150 177.8 (7.00) 25.4 (1.0) 11.5 (25)
ASME B16.5, CL 300 190.5 (7.50) 28.4 (1.12) 13.5 (30)
JIS 10K 175 (6.89) 21 (0.83) 13.5 (30)
AS2129 table D, E 165 (6.50) – –
DN 80 (3″) EN 1092-16), N 10 … 401) 200 (7.87) 28 (1.10) 200 (7.87) 108.5 (4.27) 279 (10.98) 293 (11.54) 215 (8.46) 15.5 (34)
ASME B16.5, CL 150 190.5 (7.50) 26.9 (1.06) 15.5 (34)
ASME B16.5, CL 300 210 (8.27) 31.4 (1.24) 17.5 (38.5)
JIS 10K 185 (7.28) 21 (0.83) 17.5 (38.5)
AS2129 table D, E 185 (7.28) – –
DN 100 (4″) EN 1092-16) PN 161) 220 (8.66) 24 (0.94) 250 (9.84) 122.5 (4.82) 301 (11.85) 315 (12.4) 237 (9.33) 17.5 (38.5)
EN 1092-16) PN 25 … 401) 235 (9.25) 28 (1.10) 21.5 (47)
ASME B16.5 CL 150 228.6 (9.00) 27.4 (1.08) 19.5 (43)
ASME B16.5 CL 300 254 (10.0) 35.8 (1.41) 28.5 (63)
JIS 10K 210 (8.72) 21 (0.83) 17.5 (38.5)
AS2129 table D, E 215 (8.46) – –

Tolerance for L: +0 / -3 mm (+0 / -0,018 in.)

1) Other pressure ratings on request.


2) If a grounding ring is fitted (attached to one side of the flange), dimension L increases as follows: by 3 mm (0.118 inch) for DN 3 ... 100, and by
5 mm (0.197 inch) for DN 125.
3) If protection plates are fitted (attached to both sides of the flange), dimension L increases as follows: by 6 mm (0.236 inch) for DN 3 ... 100, and by
10 mm (0.394 inch) for DN 125.
4) Connection flange DN 10.
5) Connection flange 1/2″.
6) Connecting dimensions in accordance with EN 1092-1. For DN 65, PN 16 in accordance with EN 1092-1, please order PN 40.
7) For devices in high-temperature design, dimension F, F1, F2 increases by +127 mm (+5.0 inch).
8) Depending on the device design, the dimensions change according to the following table:

Device design Dimension F, F1 Dimension F2


Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
32 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions
Flange DN 125 to 400 (6 to 16″), aluminum sensor housing (shell housing) — Design level ‘A’
All specified dimensions and weights are in mm (in) or kg (lb).). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the PG cable inlet.

Figure 27: Integral mount design (top), remote mount design (bottom)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 33

Dimensions - Flange device DN 125 to 300, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D B L2), 3) C F4), 5) F14), 5) F24), 5) Weight
diameter
DN 125 (5″) EN 1092-16) PN 161) 250 (9,84) 25 (0,98) 250 (9,84) 130 (5,12) 311 (12,24) 325 (12,80) 247 (9,72) 20,5 (45)
EN 1092-16) PN 25 … 401) 270 (10,63) 29 (1,14) 27,5 (60,5)
ASME B16.5 CL 150 254 (10,0) 27,9 (1,10) 20,5 (45)
ASME B16.5 CL 300 279,4 (11,0) 39,1 (1,54) 450 (17,72) 33,5 (74)
JIS 10K 250 (9,84) 27 (1,06) 250 (9,84) 20,5 (45)
AS2129 table D, E 255 (10,04) – –
DN 150 (6″) EN 1092-1 PN 161) 285 (11,22) 25 (0,98) 300 (11,81) 146 (5,75) 358 (14,09) 372 (14,65) 294 (11,57) 31,5 (69,5)
EN 1092-1 PN 25 … 401) 300 (11,81) 31 (1,22) 37,5 (82,5)
ASME B16.5 CL 150 279,4 (11,0) 29,4 (1,16) 31,5 (69,5)
ASME B16.5 CL 300 317,5 (12,5) 40,5 (1,59) 45,5 (100)
JIS 10K 280 (11,02) 28 (1,10) 31,5 (69,5)
AS2129 table D, E 280 (11,02) – 31,5 (69,5)
DN 200 (8″) EN 1092-1, PN 10 … 161) 340 (13,39) 28 (1,10) 350 (13,78) 170,5 (6,71) 399 (15,71) 413 (16,26) 334 (13,15) 41,5 (90,5)
EN 1092-1, PN 251) 360 (14,17) 34 (1,34) 53,5 (118)
EN 1092-1, PN 401) 375 (14,76) 38 (1,50) 63,5 (151)
ASME B16.5, CL 150 345 (13,58) 33,6 (1,32) 48,5 (107)
ASME B16.5, CL 300 380 (14,96) 46,1 (1,81) 70,5 (155,5)
JIS 10K 330 (12,99) 33 (1,30) 41,5 (90,5)
AS2129 table D, E 335 (13,19) – 48,5 (107)
DN 250 (10″) EN 1092-1, PN 101) 395 (15,55) 30 (1,18) 450 (17,72) 198 (7,80) 413 (16,26) 427 (16,81) 349 (13,74) 59,5 (131)
EN 1092-1, PN 161) 405 (15,94) 30 (1,18) 63,5 (140)
EN 1092-1, PN 251) 425 (16,73) 36 (1,42) 82,5 (182)
EN 1092-1, PN 401) 450 (17,72) 42 (1,65) 93,5 (206)
ASME B16.5, CL 150 405 (15,94) 35,2 (1,39) 68,5 (151)
ASME B16.5, CL 300 445 (17,52) 52,8 (2,08) 103,5 (228)
JIS 10K 400 (15,75) 37 (1,46) 63,5 (140)
AS2129 table D, E 405 (15,94) – 68,5 (151)
DN 300 (12″) EN 1092-1, PN 101) 445 (17,52) 31 (1,22) 500 (19,68) 228 (8,98) 436 (17,17) 450 (17,72) 372 (14,62) 72,5 (160)
EN 1092-1, PN 161) 460 (18,11) 33 (1,30) 78,5 (173)
EN 1092-1, PN 251) 485 (19,09) 39 (1,54) 98,5 (217)
EN 1092-1, PN 401) 515 (20,28) 47 (1,85) 600 (23,62) 138,5 (305)
ASME B16.5, CL 150 485 (19,09) 36,8 (1,45) 500 (19,68) 103,5 (228)
ASME B16.5, CL 300 520 (20,47) 55,8 (2,20) 148,5 (327)
JIS 10K 450 (17,72) 40 (1,57) 78,5 (173)
AS2129 table D, E 455 (17,19) – 103,5 (228)

Tolerance for L: +0 / -3 mm (+0 / -0,018 in.)


34 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions

Dimensions - Flange device DN 350 to 400, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D B L2), 3) C F4), 5) F14), 5) F24), 5) Weight
diameter
DN 350 (14″) EN 1092-1, PN 101) 505 (19,88) 31 (1,22) 550 (21,65) 267 (10,51) 451 (17,76) 465 (18,31) 416 (16,38) 93,5 (206)
EN 1092-1, PN 161) 520 (20,47) 35 (1,38) 108,5 (239)
EN 1092-1, PN 251) 555 (21,85) 43 (1,69) 143,5 (316)
ASME B16.5, CL 150 535 (21,06) 40,1 (1,58) 128,5 (283)
ASME B16.5, CL 300 585 (23,03) 58,8 (2,31) 196,5 (433)
JIS 10K 490 (19,29) – 108,5 (239)
AS2129 table D, E 525 (20,67) – 103,5 (228)
DN 400 (16″) EN 1092-1 PN 101) 565 (22,24) 31 (1,22) 600 (23,62) 267 (10,51) 493 (19,41) 507 (19,96) 416 (16,38) 101,5 (224)
EN 1092-1 PN 161) 580 (22,83) 37 (1,46) 124,5 (274)
EN 1092-1 PN 251) 620 (24,41) 45 (1,77) 168,5 (371)
ASME B16.5 CL 150 595 (23,43) 41,6 (1,64) 173,5 (382)
ASME B16.5 CL 300 650 (25,59) 62,2 (2,45) 262,5 (579)
JIS 10K 560 (22,05) – 124,5 (274)
AS2129 table D, E 580 (22,83) – 173,5 (382)

Tolerance for L: DN 150 to 200: +0 / −3 mm (+0 / −0,018 in), DN 250 to 400: +0 / −5 mm (+0 / −0,197 in)

1) Other pressure ratings on request.


2) If a grounding ring is fitted is fitted (attached to one side of the flange) dimension L increases by 5 mm (0.197 in).
3) If protection plates are fitted (attached to both sides of the flange) dimension L increases by 10 mm (0.394 in).
4) For devices in high-temperature design, dimension F, F1, F2 increases by +127 mm (+5.0 in).
5) Depending on the device design, the dimensions change according to the following table:

Device design Dimension F, F1 Dimension F2


Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 35

Flange DN 450 to 2000 (18 to 80″), steel sensor housing - Design level ‘A.
All specified dimensions and weights are in mm (in) or kg (lb). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Transport lugs
2 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the PG cable inlet.

Figure 28: Integral mount design (top), remote mount design (bottom)
36 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions

Dimensions - Flange device, steel sensor housing - Design level ‘A’


Nominal Process connection D B L2) 3) C F4) 5) F14) 5) F24) 5) Weight
diameter
DN 450 (18″) ASME B16.5, CL 150 635 (25.0) 44.6 (1.76) 686 (27.01) 310 (12.20) 501 (19.72) 515 (20.28) 437 (17.20) 258.5 (570)
AS2129 table D, E 640 (25.20) –
DN 500 (20″) EN 1092-1, PN 101) 670 (26.38) 33 (1.30) 650 (25.59) 310 (12.20) 501 (19.72) 515 (20.28) 437 (17.20) 188.5 (416)
EN 1092-1, PN 161) 715 (28.15) 39 (1.54) 238.5 (526)
ASME B16.5, CL 150 698.5 (27.50) 47.9 (1.89) 762 (30.0) 298.5 (658)
AS2129 table D, E 705 (27.76) – 650 (25.59)
DN 600 (24″) EN 1092-1, PN 101) 780 (30.71) 33 (1.30) 780 (30.71) 361 (14.21) 552 (21.73) 566 (22.28) 490 (19.29) 338.5 (746)
EN 1092-1, PN 161) 840 (33.07) 41 (1.61) 316.5 (698)
ASME B16.5, CL 150 812.8 (32.0) 52.8 (2.08) 914 (35.98) 423.5 (934)
AS2129 table D, E 825 (32.48) – 780 (30.71)

Tolerance for L: DN450, DN500 +0 / −5 mm (+0 / −0.197 in) DN 600 +0 / −10 mm (+0 / −0.394 in)
1) Other pressure ratings on request.
2) If a grounding ring is fitted (attached to one side of the flange) dimension L increases by 5 mm (0.197 in).
3) If protection plates are fitted (attached to both sides of the flange) dimension L increases by 10 mm (0.394 in).
4) For devices in high-temperature design, dimension F, F1, F2 increases by +127 mm (+5.0 in).
5) Depending on the device design, the dimensions change according to the following table:

Device design Dimension F, F1 Dimension F2


Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 37

Flange DN 700 to 2000 (28 to 80″), steel sensor housing Design level ‘A’, ABB Standard Lay Length (1,3xDN)
All specified dimensions and weights are in mm (in) or kg (lb). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Transport lugs
2 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the PG cable inlet.

Figure 29: Integral mount design (top), remote mount design (bottom)
38 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions

Dimensions - Flange device, steel sensor housing - Design level ‘A’ ABB standard lay length (1,3xDN)
Nominal Process connection D B L2) 3) C F4) 5) F14) 5) F24) 5) Weight
diameter
DN 700 (28″) EN 1092-1, PN 101) 895 (35.24) 35 (1.38) 910 (35.83) 405 (15.94) 596 (23.46) 610 (24.02) 534 (21.02) 318.5 (702)
EN 1092-1, PN 161) 910 (35.83) 36 (1.42) 438.5 (967)
ASME B16.47, CL 150 836.7 (32.94) 49.5 (1.95) 348.5 (768)
DN 750 (30″) ASME B16.47, CL 150 888 (34.96) 44.5 (1.75) 990 (38.96) 431 (16.97) 606 (23.86) 620 (24.41) 560 (22.05) 474.5 (1046)
AWWA C207 CLASS B 984 (38.74) 990 (38.98) 431 (16.97) 606 (23.86) 620 (24.41) 560 (22.05) 324 (713)
AWWA C207 CLASS D 984 (38.74) 395 (869)
AWWA C207 CLASS E 995 (39.17) 547 (1204)
DN 800 (32″) EN 1092-1, PN 101) 1015 (39.96) 37 (1.46) 1040 (40.94) 455 (17.91) 646 (25.43) 660 (25.98) 584 (22.99) 418.5 (923)
EN 1092-1, PN 161) 1025 (40.35) 43 (1.69) 488.5 (1077)
ASME B16.47, CL 150 942 (37.09) 51 (2.01) 498.5 (1099)
AWWA C207 CLASS B 1060 (41.73) 1040 (40.04) 455 (17.91) 646 (25.43) 660 (25.98) 584 (22.99) 384 (845)
AWWA C207 CLASS D 463 (1019)
AWWA C207 CLASS E 689 (1516)
DN 900 (36″) EN 1092-1, PN 101) 1115 (43.90) 39 (1.54) 1170 (46.06) 505 (19.88) 696 (27.40) 710 (27.95) 635 (25.0) 503.5 (1110)
EN 1092-1, PN 161) 1125 (44.29) 45 (1.77) 588.5 (1297)
ASME B16.47, CL 150 1157.1 (41.62) 57.3 (2.26) 678.5 (1496)
AWWA C207 CLASS B 1068 (45.98) 1170 (46.06) 505 (19.88) 696 (27.40) 710 (27.95) 635 (25.00) 480 (1056)
AWWA C207 CLASS D 556 (1224)
AWWA C207 CLASS E 1175 (46.26) 753 (1657)
DN 1000 (40″) EN 1092-1, PN 101) 1230 (48.43) 39 (1.54) 1300 (51.18) 555 (21.85) 746 (29.37) 760 (29.92) 685 (26.97) 688.5 (1517)
EN 1092-1, PN 161) 1255 (49.41) 47 (1.85) 848.5 (1870)
ASME B16.47, CL 150 1174.8 (46.25) 60.6 (2.39) 878.5 (1937)
AWWA C207 CLASS B 1289 (50.75) 1300 (51.18) 555 (21.85) 746 (29.37) 760 (29.92) 685 (26.97) 578 (1272)
AWWA C207 CLASS D 735 (1617)
AWWA C207 CLASS E 905 (1991)
DN 1050 (42″) ASME B16.47, CL 150 1067 (42.01) 58.7 (2.31) 1365 (53.74) 607 (23.90) 771 (30.35) 785 (30.91) 737 (29.02) 930.5 (2051)
AWWA C207 CLASS B 1346 (52.99) 1365 (53.74) 607 (23.90) 771 (30.35) 785 (30.91) 737 (29.02) 668 (1470)
AWWA C207 CLASS D 772 (1699)
AWWA C207 CLASS E 1246 (2742)
DN 1100 (44″) ASME B16.47, CL 150 1118 (44.02) 60.5 (2.38) 1430 (56.30) 607 (23.90) – – 737 (29.02) 960.5 (2117)
AWWA C207 CLASS B 1403 (55.24) 1430 (56.30) 607 (23.90) – – 737 (29.02) 700 (1540)
AWWA C207 CLASS D 891 (1961)
AWWA C207 CLASS E 1404 (55.26) 1289 (2836)
DN 1200 (48″) EN 1092-1, PN 101) 1455 (57.28) 43 (1.69) 1560 (61.42) 660 (25.98) 856 (33.7) 870 (34.25) 791 (31.14) 928.5 (2047)
EN 1092-1, PN 161) 1485 (58.46) 53 (2.09) 1118.5 (2466)
AWWA C207 CLASS B 1511 (59.49) 1560 (61.42) 660 (25.98) 856 (33.7) 870 (34.25) 791 (31.14) 872 (1919)
AWWA C207 CLASS D 1099 (2418)
AWWA C207 CLASS E 1557 (3426)

Tolerance for L: DN 700 to 2000 +0 / −10 mm (+0 / −0.394 in)


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 39

Dimensions - Flange device, steel sensor housing - Design level ‘A’ ABB standard lay length (1,3xDN)
Nominal Process connection D B L2) 3) C F4) 5) F14) 5) F24) 5) Weight
diameter
DN 1350 (54″) AWWA C207 CLASS B 1638 (66.26) 1755 (69.09) 1119 (2462)
AWWA C207 CLASS D 1350 (2970)
AWWA C207 CLASS E 2079 (4574)
DN 1400 (56″) EN 1092-1 PN 101) 1675 (65.94) 47 (1.85) 1820 (71.65) 755 (29.72) 950 (37.4) 964 (37.95) 885 (34.84) 1208.5 (2664)
EN 1092-1 PN 161) 1685 (66.34) 57 (2.24) 1758.5 (3877)
DN 1500 (60″) ASME B16.47, CL 150 1676 (65.98) 76.2 (3.00) 1950 (76.77) 807 (31.77) 996 (39.21) 1010 (39.76) 937 (36.89) 1950.5 (4300)
AWWA C207 CLASS B 1854 (72.99) 1950 (76.77) 807 (31.77) 996 (39.21) 1010 (39.76) 937 (36.89) 1460 (3212)
AWWA C207 CLASS D 1746 (3842)
AWWA C207 CLASS E 2775 (6105)
DN 1600 (64″) EN 1092-1 PN 101) 1915 (75.39) 51 (2.01) 2080 (81.89) 865 (34.06) 1060 (41.73) 1074 (42.28) 996 (39.21) 1628.5 (3590)
EN 1092-1 PN 161) 1930 (75.98) 63 (2.48) 2148.5 (4737)
DN 1650 (66″) AWWA C207 CLASS B 2032 (80.00) 2145 (84.45) 915 (36.02) 1116 (43.94) 1006 (39.60) 1704 (3749)
AWWA C207 CLASS D 2225 (4895)
DN 1800 (72″) EN 1092-1 PN 101) 2115 (83.27) 55 (2.17) 2340 (92.13) 980 (38.58) 1176 (46.3) 1190 (46.85) 1111 (43.74) 2228.5 (4913)
EN 1092-1 PN 161) 2130 (83.86) 67 (2.64) 2898.5 (6390)
AWWA C207 CLASS B 2197 (86.50) 2340 (92.13) 980 (38.58) 1181 (46.50) 1071 (42.17) 2009 (4420)
AWWA C207 CLASS D 2197 (86.50) 2622 (5769)
DN 2000 (80″) EN 1092-1 PN 101) 2325 (91.54) 59 (2.32) 2600 (102.36) 1090 (42.91) 1286 (50.63) 1300 (51.18) 1221 (48.07) 1878.5 (4141)
EN 1092-1 PN 161) 2345 (92.32) 71 (2.80) 2648.5 (5839)

Tolerance for L: DN 700 to 2000 +0 / −10 mm (+0 / −0.394 in)


1) Other pressure ratings on request.
2) If a grounding ring is fitted (attached to one side of the flange) dimension L increases by 5 mm (0.197 in).
3) If protection plates are fitted (attached to both sides of the flange) dimension L increases by 10 mm (0.394 in).
4) For devices in high-temperature design, dimension F, F1, F2 increases by +127 mm (+5.0 in).
5) Depending on the device design, the dimensions change according to the following table:

Device design Dimension F, F1 Dimension F2


Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
40 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions
Flange DN 700 to 2000 (28 to 80″), steel sensor housing Design level ‘A’, Optional Lay Length (1,0xDN)
All specified dimensions and weights are in mm (in) or kg (lb). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Transport lugs
2 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the PG cable inlet.

Figure 30: Integral mount design (top), remote mount design (bottom)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 41

Dimensions – Flange device, steel sensor housing Design level ‘A’, Optional lay length (1,0xDN)
Nominal diameter Process connection D B L2) 3) C F4),5) F14),5) F24),5) Weight
DN 700 (28″) EN 1092-1, PN 101) 895 (35.24) 35 (1.38) 700 (27.56) 405 (15.94) 596 (23.46) 610 (24.02) 534 (21.02) 318.5 (702)
EN 1092-1, PN 161) 910 (35.83) 36 (1.42) 438.5 (967)
ASME B16.47, CL 150 836.7 (32.94) 49.5 (1.95) 348.5 (768)
JIS 5K 875 (34.45) 31 (1.22) 202 (445)
JIS 10K 905 (35.63) 39 (1.53) 263 (580)
JIS 7.5K 928 (36.53) 36 (1.42) 320 (705)
AS 4087 PN16 910 (35.82) 61 (2.40) 327 (720)
AS2129 TABLE E 910 (35.82) 56 (2.20) 305 (672)
DN 750 (30″) ASME B16.47, CL 150 888 (34.96) 44.5 (1.75) 431 (16.97) 606 (23.86) 620 (24.41) 560 (22.05) 474.5 (1046)
JIS 5K 945 (37.20) 33 (1.30) 762 (30.00) 431 (16.97) 616 (24.25) 630 (24.8) 570 (22.44) 233 (513)
JIS 10K 970 (38.19) 41 (1.61) 762 (30.00) 431 (16.97) 616 (24.25) 630 (24.8) 570 (22.44) 306 (675)
AS 4087 PN16 995 (39.17) 61 (2.40) 762 (30.00) 431 (16.97) 616 (24.25) 630 (24.8) 570 (22.44) 388 (855)
AS2129 TABLE E 995 (39.17) 59 (2.32) 762 (30.00) 431 (16.97) 616 (24.25) 630 (24.8) 570 (22.44) 377 (831)
AWWA C207 CLASS B 984 (38.74) 762 (30.00) 606 (23.86) 431 (16.97) 620 (24.41) 560 (22.05) 268 (590.9)
AWWA C207 CLASS D 984 (38.74) 322 (709.9)
AWWA C207 CLASS E 995 (39.17) 472 (1040.6)
DN 800 (32″) EN 1092-1, PN 101) 1015 (39.96) 37 (1.46) 800 (31.45) 455 (17.91) 646 (25.43) 660 (25.98) 584 (22.99) 373 (822)
EN 1092-1, PN 161) 1025 (40.35) 43 (1.69) 447 (985)
ASME B16.47, CL 150 942 (37.09) 51 (2.01) 498.5 (1099)
JIS 5K 995 (39.17) 33 (1.30) 261 (575)
JIS 10K 1020 (40.16) 41 (1.61) 340 (750)
JIS 7.5K 1034 (40.71) 39 (1.53) 420 (926)
AS 4087 PN16 1060 (41.73) 61 (2.40) 442 (974)
AS2129 TABLE E 1060 (41.73) 59 (2.32) 431 (950)
AWWA C207 CLASS B 1060 (41.73) 800 (31.49) 646 (25.43) 455 (17.91) 660 (25.98) 584 (22.99) 334 (736.4)
AWWA C207 CLASS D 394 (868.7)
AWWA C207 CLASS E 591 (1303)
DN 900 (36″) EN 1092-1, PN 101) 1115 (43.90) 39 (1.54) 900 (35.43) 505 (19.88) 696 (27.40) 710 (27.95) 635 (25.0) 420 (926)
EN 1092-1, PN 161) 1125 (44.29) 45 (1.77) 510 (1124)
ASME B16.47, CL 150 1157.1 (41.62) 57.3 (2.26) 678.5 (1495)
JIS 5K 1095 (43.11) 35 (1.38) 319 (703)
JIS 10K 1120 (44.10) 43 (1.70) 415 (915)
JIS 7.5K 1156 (45.51) 41 (1.61) 520 (1146)
AS 4087 PN16 1175 (46.26) 71 (2.78) 658 (1450)
AS2129 TABLE E 1175 (46.26) 69 (2.71) 645 (1421)
AWWA C207 CLASS B 1068 (45.98) 900 (35.43) 696 (27.40) 505 (19.88) 710 (27.95) 635 (25.00) 397 (875.3)
AWWA C207 CLASS D 436 (961.2)
AWWA C207 CLASS E 1175 (46.26) 744 (1640.3)
DN 1000 (40″) EN 1092-1, PN 101) 1230 (48.43) 39 (1.54) 1000 (39.40) 555 (21.85) 746 (29.37) 760 (29.92) 685 (26.97) 580 (1279)
EN 1092-1, PN 161) 1255 (49.41) 47 (1.85) 780 (1719)
ASME B16.47, CL 150 1174.8 (46.25) 60.6 (2.39) 878.5 (1937)
JIS 5K 1195 (47.04) 37 (1.46) 379 (835)
JIS 10K 1235 (48.62) 45 (1.77) 527 (1162)
JIS 7.5K 1262 (49.68) 43 (1.70) 660 (1455)
AS 4087 PN16 1255 (49.41) 71 (2.80) 696 (1534)
AS2129 TABLE E 1255 (49.41) 72 (2.83) 698 (1539)
AWWA C207 CLASS B 1289 (50.75) 1000 (39.37) 746 (29.37) 555 (21.88) 760 (29.92) 685 (26.97) 474 (1045)
AWWA C207 CLASS D 618 (1362.5)
AWWA C207 CLASS E 922 (2032.7)
Tolerance for L: DN 700 to 2000 +0 / −10 mm (+0 / −0.394 in)
42 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions

Dimensions – Flange device, steel sensor housing Design level ‘A’, Optional lay length (1,0xDN)
Nominal diameter Process connection D B L2) 3) C F4),5) F14),5) F24),5) Weight
DN 1050 (42″) ASME B16.47, CL 150 1067 (42.01) 58.7 (2.31) 1365 (53.74) 607 (23.90) 771 (30.35) 785 (30.91) 737 (29.02) 930.5 (2051)
AWWA C207 CLASS B 1346 (52.99) 1067 (42.01) 771 (30.35) 607 (23.90) 785 (30.91) 737 (29.02) 559 (1232.4)
AWWA C207 CLASS D 614 (1353.7)
AWWA C207 CLASS E 1102 (2429.6)
DN 1100 (44″) ASME B16.47, CL 150 1118 (44.02) 60.5 (2.38) 1430 (56.30) 607 (23.90) – – 737 (29.02) 960.5 (2117)
AWWA C207 CLASS B 1403 (55.24) 1118 (44.02) – 607 (23.90) – 737 (29.02) 605 (1333.8)
AWWA C207 CLASS D 695 (1532.3)
AWWA C207 CLASS E 1404 (55.26) 1132 (2495.7)
DN 1200 (48″) EN 1092-1, PN 101) 1455 (57.28) 43 (1.69) 1560 (61.42) 660 (25.98) 856 (33.7) 870 (34.25) 791 (31.14) 928.5 (2047)
EN 1092-1, PN 161) 1485 (58.46) 53 (2.09) 1118.5 (2466)
AWWA C207 CLASS B 1511 (59.49) 1200 (47.24) 856 (33.70) 660 (25.98) 870 (34.25) 791 (31.14) 746 (1644.7)
AWWA C207 CLASS D 886 (1953.4)
AWWA C207 CLASS E 1389 (3062.3)
DN 1350 (54″) AWWA C207 CLASS B 1683 (66.26) 1350 (53.15) 942 (2076.8)
AWWA C207 CLASS D 1684 (66.30) 1026 (2262)
AWWA C207 CLASS E 1685 (66.34) 1834 (4043.4)
DN 1400 (56″) EN 1092-1 PN 101) 1675 (65.94) 47 (1.85) 1820 (71.65) 755 (29.72) 950 (37.4) 964 (37.95) 885 (34.84) 1208.5 (2664)
EN 1092-1 PN 161) 1685 (66.34) 57 (2.24) 1758.5 (3877)
DN 1500 (60″) ASME B16.47, CL 150 1676 (65.98) 76.2 (3.00) 1950 (76.77) 807 (31.77) 996 (39.21) 1010 (39.76) 937 (36.89) 1950.5 (4300)
AWWA C207 CLASS B 1854 (72.99) 1524 (60.00) 996 (39.21) 807 (31.77) 1010 (39.76) 937 (36.89) 1290 (2844.1)
AWWA C207 CLASS D 1569 (3459.2)
AWWA C207 CLASS E 2497 (5505.1)
DN 1600 (64″) EN 1092-1 PN 101) 1915 (75.39) 51 (2.01) 2080 (81.89) 865 (34.06) 1060 (41.73) 1074 (42.28) 996 (39.21) 1628.5 (3590)
EN 1092-1 PN 161) 1930 (75.98) 63 (2.48) 2148.5 (4737)
DN 1650 (66″) AWWA C207 CLASS B 2032 (80.00) 1650 (64.96) 915 (36.02) 1116 (43.94) 1000 (39.37) 1497 (3300.4)
AWWA C207 CLASS D 2033 (80.04) 1763 (3886.9)
AWWA C207 CLASS E 2032 (80.00) 3044 (6711.1)
DN 1800 (72″) EN 1092-1 PN 101) 2115 (83.27) 55 (2.17) 2340 (92.13) 980 (38.58) 1176 (46.3) 1190 (46.85) 1111 (43.74) 2228.5 (4913)
EN 1092-1 PN 161) 2130 (83.86) 67 (2.64) 2898.5 (6390)
AWWA C207 CLASS B 2197 (86.50) 1800 (70.87) 980 (38.58) 1181 (46.50) 1605 (41.90) 1833 (4041.2)
AWWA C207 CLASS D 2197 (86.50) 2147 (4733.5)
AWWA C207 CLASS E 2197 (86.50) 3842 (8470.5)
DN 2000 (80″) EN 1092-1 PN 101) 2325 (91.54) 59 (2.32) 2600 (102.36) 1090 (42.91) 1286 (50.63) 1300 (51.18) 1221 (48.07) 1878.5 (4141)
EN 1092-1 PN 161) 2345 (92.32) 71 (2.80) 2648.5 (5839)

Tolerance for L: DN 700 to 2000 +0 / −10 mm (+0 / −0.394 in)


1) Other pressure ratings on request.
2) If a grounding ring is fitted (attached to one side of the flange) dimension L increases by 5 mm (0.197 in).
3) If protection plates are fitted (attached to both sides of the flange) dimension L increases by 10 mm (0.394 in).
4) For devices in high-temperature design, dimension F, F1, F2 increases by +127 mm (+5.0 in).
5) Depending on the device design, the dimensions change according to the following table:

Device design Dimension F, F1 Dimension F2


Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 43

Flange DN 25 to 400 (1 to 16″), aluminum sensor housing (shell housing) — Design level ‘A’
All specified dimensions and weights are in mm (in) or kg (lb). The stated weights are approximate; the maximum weight is
always stated.
Integral mount design

Remote mount design


1 Female thread (either 1/2″ NPT or M20 x 1,5) refer to model coding. With 1/2″ NPT there will be a plug instead of the PG cable inlet.

Figure 31: Integral mount design (top), remote mount design (bottom)
44 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions
Dimensions - Flange device DN 25 to 50, high pressure design, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D di Shedule L1), 2) A C F3) F13) F23) Weight
diameter Integral / remote
DN 25 EN1092-1 PN63 140 22 — 270 12 10
(1″) EN1092-1 PN100 (5.51) (0.87) (10.63) (27) (22)
ASME B16.5, CL 600 124 22 40 270 12 10
(4.88) (0.87) (1.57) (10.63) 113 82 255 269 191 (27) (22)
ASME B 16.5 CL900/1500 149 19 80 300 (4.45) (3.23) (10.04) (10.6) (7.52) 15 13
(5.87) (0.75) (3.15) (11.81) (33) (29)
ASME B16.5, CL 2500 158 15 160 350 18 16
(6.22) (0.60) (6.30) (13.78) (40) (35)
DN 40 EN1092-1 PN63 170 36 — 280 13 / 14 11 / 12
(1½″) EN1092-1 PN100 (6.69) (1.42) (11.02) (29 / 31) (24 / 27)
ASME B16.5, CL 600 156 35 40 280 13 11
(6.14) (1.38) (1.57) (11.02) 113 92 262 276 198 (29) (24)
ASME B 16.5 CL900/1500 177 26 80 350 (4.45) (3.62) (10.31) (10.87) (7.80) 22 20
(6.97) (1.02) (3.15) (13.78) (48.5) (44)
ASME B16.5, CL 2500 203 22 XXS 400 32 32
(7.99) (0.87) (15.75) (70.5) (70.5)
DN 50 (2″) EN1092-1 PN63 180 48 — 280 15 13
(7.09) (1.89) (11.02) (33) (29)
EN1092-1 PN100 195 48 — 280 18 16
(7.68) (1.89) (11.02) (40) (35)
ASME B16.5, CL 600 165 46 40 280 115 97 268 282 204 15 13
(6.50) (1.81) (1.57) (11.02) (4.53) (3.82) (10.55) (11.1) (8.0) (33) (29)
ASME B 16.5 CL900/1500 216 37 160 400 32 30
(8.50) (1.46) (6.30) (15.75) (70.5) (66)
ASME B16.5, CL 2500 235 32 XXS 450 42 40
(9.25) (1.26) (17.72) (92.5) (88)
DN 65 EN1092-1 PN63 205 64 — 330 18 16
(2½″) (8.07) (2.52) (12.99) (40) (35)
EN1092-1 PN100 220 63 — 330 23 21
(8.66) (2.48) (12.99) (51) (46)
ASME B16.5, CL 600 190 60 30 330 104 108 279 293 215 20 18
(7.48) (2.36) (12.99) (4.09) (4.25) (10.98) (11.54) (8.46) (44) (40)
ASME B 16.5 CL900/1500 244 48 160 400 37 35
(9.61) (1.89) (15.75) (81.5) (77)
ASME B16.5, CL 2500 266 39 XXS 450 56 54
(10.47) (1.53) (17.72) (123.5) (119)

Tolerance L: DN 25 to 100 +0 / −5 mm (+0 / −0,197 in), DN 150 … 200 +0 / −5 mm (+0 / −0,197 in), DN 250 to 400 +0 / −8 mm
(+0 / −0,314 in)
Tolerance Di: ETFE Liner: +1/ −5 mm (+1/ −0,197 in) Hardrubber: +1/ −3 mm (+1/ −0.118 in
All pressure ratings (PN63, PN100, Cl600 to CL2500 available with Hardrubber and ETFE only
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 45

Dimensions - Flange device DN 25 to 50, high pressure design, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D di Shedule L1), 2) A C F3) F13) F23) Weight
diameter Integral / remote
80 EN1092-1 PN63 215 76 — 340 22 20
(3″) (8.46) (2.99) (13.39) (49) (44)
EN1092-1 PN100 230 75 — 340 26 24
(9.06) (2.95) (13.39) (57) (53)
ASME B16.5, CL 600 209 72 40 340 25 23
(8.23) (2.83) (13.39) 104 108 279 293 215 (55) (51)
ASME B16.5, CL 900 241 68 80 400 (4.09) (4.25) (10.98) (11.54) (8.46) 38 36
(9.49) (267) (15.75) (84) (80)
ASME B16.5, CL 1500 266 61 160 400 51 49
(10.47) (2.40) (15.75) (112) (108)
ASME B16.5, CL 2500 305 52 XXS 500 84 82
(12.01) (2.05) (19.68) (185) (181)
100 EN1092-1 PN63 250 100 — 400 29 27
(4″) (9.84) (3.94) (15.75) (64) (60)
EN1092-1 PN100 265 98 — 400 38 26
(10.43) (3.85) (15.75) (84) (57)
ASME B16.5, CL 600 273 91 80 400 46 44
(10.75) (3.58) (15.75) 125 122 301 315 237 (101) (97)
ASME B16.5, CL 900 292 86 120 400 (4.92) (4.8) (11.85) (12.4) (9.33) 58 56
(11.50) (3.38) (15.75) (128) (123.5)
ASME B16.5, CL 1500 311 74 XXS 420 75 73
(12.24) (2.91) (16.54) (165) (161)
ASME B16.5, CL 2500 355 68 — 600 128 126
(13.98) (2.67) (23.62) (282) (278)
125 EN1092-1 PN63 295 124 — 450 70 68
(5″) (11.61) (4.88) (17.72) (154) (150)
EN1092-1 PN100 315 121 — 450 70 68
(12.4) (4.76) (17.72) (154) (150)
ASME B16.5, CL 600 330 116 80 400 70 68
(12.99) (4.56) (15.75) 125 130 311 325 247 (154) (150)
ASME B16.5, CL 900 349 110 120 450 (4.92) (5.12) (12.24) (12,80) (9,72) 88 86
(13.74) (4.33) (17.72) (194) (190)
ASME B16.5, CL 1500 374 97 XXS 500 127 125
(14.72) (3.82) (19.68) (280) (275)
ASME B16.5, CL 2500 419 85 — 700 206 204
(16.50) (3.34) (27.56) (454) (450)
150 EN1092-1 PN63 345 151 — 450 94 92
(6“) (13.58) (5.94) (17.72) (207) (203)
EN1092-1 PN100 355 148 — 450 94 92
(13.98) (5.83) (17.72) (207) (203)
ASME B16.5, CL 600 355 140 80 450 94 92
(13.98) (5.51) (17.72) 166 146 358 294 166 (207) (203)
ASME B16.5, CL 900 381 140 80 500 (6.54) (5.75) (14.09) (11,57) (6.54) 120 118
(15.0) (5.51) (19.68) (265) (260)
ASME B16.5, CL 1500 393 118 XXS 600 168 166
(15.47) (4.64) (23.62) (370) (366)
ASME B16.5, CL 2500 482 102 — 800 335 333
(18.98) (4.01) (31.50) (738) (734)

Tolerance L: DN 25 to 100 +0 / −5 mm (+0 / −0,197 in), DN 150 … 200 +0 / −5 mm (+0 / −0,197 in), DN 250 to 400 +0 / −8 mm
(+0 / −0,314 in)
Tolerance Di: ETFE Liner: +1/ −5 mm (+1/ −0,197 in) Hardrubber: +1/ −3 mm (+1/ −0.118 in
All pressure ratings (PN63, PN100, Cl600 to CL2500 available with Hardrubber and ETFE only
46 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Flowmeter sensor
… Dimensions
Dimensions - Flange device DN 25 to 50, high pressure design, aluminum sensor housing (shell housing) — Design level ‘A’
Nominal Process connection D di Shedule L1), 2) A C F3) F13) F23) Weight
diameter Integral / remote
200 EN1092-1 PN63 415 199 — 500 200 170 399 413 334 150 148
(8") (16.34) (7.83) (19.68) (7.87) (6.69) (15.71) (16,26) (13,15) (331) (326)
EN1092-1 PN100 430 193 — 500 150 148
(16.93) (7.60) (19.68) (331) (326)
ASME B16.5, CL 600 419 188 80 500 150 148
(16.50) (7.40) (19.68) (331) (326)
ASME B16.5, CL 900 470 176 120 600 207 205
(18.50) (6.93) (23.62) (456) (452)
ASME B16.5, CL 1500 482 163 — 700 290 288
(18.98) (6.42) (27.56) (639) (635)
ASME B16.5, CL 2500 552 141 — 950 510 508
(21.73) (5.55) (37.40) (1124) (1120)
250 ASME B16.5, CL 600 508 236 80 600
(10“) (20.0) (9.29) (23.62)
ASME B16.5, CL 900 546 224 120 700
(21.5) (8.82) (27.56) 235 198 413 427 349
On request
ASME B16.5, CL 1500 584 203 — 850 (9.25) (7.80) (16.26) (16,81) (13,74)
(22.99) (7.99) (33.46)
ASME B16.5, CL 2500 673 177 — 1200
(26.50) (6.97) (47.24)
300 ASME B16.5, CL 600 559 283 80 750
(12“) (22.01) (11.14) (29.53)
ASME B16.5, CL 900 609 267 120 800
(23.98) (10.51) (31.50) 272 228 436 450 372
On request
ASME B16.5, CL 1500 673 238 — 950 (10.71) (8.98) (17.17) (17,72) (14,62)
(26.50) (9.37) (37.40)
ASME B16.5, CL 2500 762 214 — 1400
(30.00) (8.42) (55.12)
350 ASME B16.5, CL 600 603 311 80 750
(14“) (23.74) (12.24) (29.53)
ASME B16.5, CL 900 641 294 120 850 322 265 451 465 416
On request
(25.24) (11.57) (33.46) (12.68) (10.43) (17.76) (18,31) (16,38)
ASME B16.5, CL 1500 749 269 — 1050
(29.49) (10.59) (41.34)
400 ASME B16.5, CL 600 686 357 80 800
(16“) (27.01) (14.05) (31.50)
ASME B16.5, CL 900 705 338 120 900 322 265 493 507 416
On request
(27.76) (13.31) (35.43) (12.68) (10.43) (19.41) (19,96) (16,38)
ASME B16.5, CL 1500 825 310 — 1100
(32.48) (12.20) (43.31)

Tolerance L: DN 25 to 100 +0 / −5 mm (+0 / −0,197 in), DN 150 … 200 +0 / −5 mm (+0 / −0,197 in), DN 250 to 400 +0 / −8 mm
(+0 / −0,314 in)
Tolerance Di: ETFE Liner: +1/ −5 mm (+1/ −0,197 in) Hardrubber: +1/ −3 mm (+1/ −0.118 in
All pressure ratings (PN63, PN100, Cl600 to CL2500 available with Hardrubber and ETFE only
1) Other pressure ratings on request.
2) If a grounding ring is fitted (attached to one side of the flange), dimension L increases as follows: by 3 mm (0.118 in) for DN 3 to 100, and by
5 mm (0.197 in) for DN 125.
3) Depending on the device design, the dimensions change according to the following table:
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 47

Dimensions - Flange device DN 25 to 50, high pressure design, aluminum sensor housing (shell housing) — Design level ‘A’
Device design Dimension F, F1 Dimension F2
Without explosion protection Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
Explosion protection Zone 1, Div. 1 Standard sensor design +74 mm (+2.91 in) +47 mm (+1.85 in)
High-temperature sensor design +127 mm (+5 in) +174 mm (+6.85 in)
Explosion protection Zone 2, Div. 2 Standard sensor design 0 0
High-temperature sensor design +127 mm (+5 in) +127 mm (+5 in)
48 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Transmitter
Features
• 4 to 20 mA current output Optional plug-in cards
• Current output in the event of an alarm can be configured The transmitter has two slots (OC1, OC2) into which plug-in
to 21 to 22.6 mA (NAMUR NE43) cards can be inserted to provide additional inputs and
• Measuring range: Can be configured between outputs.
0.02 to 2 x QmaxDN The slots are located on the transmitter motherboard and
• Operating mode for flow measurement can be configured can be accessed after removing the front housing cover.
• Programmable digital output. Can be configured as
frequency output, pulse output or binary output.
• Two slots for optional plug-in cards for retrofitting
additional current / digital outputs or a digital input.
• Damping: 0.04 to 100 s configurable (1 τ)
• Low flow cut-off: 0 to 20 % for current and pulse output
• Parameterization by means of HART communication
• Empty pipe detection*
• Simulation of current and binary output (manual process
execution)
* Requirements for Empty Pipe detector function:
The conductivity of the fluid must be ≥ 20 µS/cm
Nominal diameter must be ≥ DN 10

LCD indicator (option)


• High-contrast LCD indicator
• Display of the current flow rate as well as the total flow
rate
• Application-specific visualizations which the user can
select. Two operator pages can be configured to display
multiple values in parallel.
• Plain text fault diagnostics
Figure 32: Plug-in cards
• Menu-guided parameterization with four buttons
• ‘Easy Set-up‘ function for fast commissioning
Plug-in card Quantity*
• Parameterization of the device through the front glass
with the housing closed 1 Current output, 4 to 20 mA passive (red) 2
Order no.: 3KQZ400029U0100

Isolation of outputs 2 Passive digital output (green) 1**

The digital output terminals 41 / 42 and 51 / 52 have a Order no.: 3KQZ400030U0100

common ground. 3 Passive digital input (yellow) 1

The current output and the digital outputs are electrically Order no.: 3KQZ400032U0100

isolated from each other. 4 24 V DC voltage supply (blue) 1


Order no.: 3KQZ400031U0100
5 Modbus RTU® RS485 (white) 1
Order no.: 3KQZ400028U0100
6 PROFIBUS DP® (white) 1
Order no.: 3KQZ400027U0100
7 Ethernet (various protocols) 1
Order no.: 3KQZ400037U0100
8 Power over Ethernet (POE) 1
Order no.: 3KQZ400039U0100
9 PROFIBUS PA® (blue) 1
Order no.: 3KQZ400061U0100
* The ‘Number’ column indicates the maximum number of plug-in cards
of the same type that can be used.
** Only one plug-in card of the passive digital output type can be inserted
in Pos. 2.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 49

IP rating Dimensions
In accordance with EN 60529: IP 65 / IP 67, NEMA 4X

Vibration
In accordance with EN 60068-2-6
• In the 10 to 58 Hz range, maximum deflection 0.15 mm
(0.006 in.)*
• In the range from 58 to 150 Hz, maximum acceleration
2 g*
* Peak load

Temperature data

Standard Optional
Ambient temperature −20 to 60 °C −40 to 70 °C
(−4 to 140 °F) (−40 to 158 °F)
Storage temperature −20 to 70 °C —
(−4 to 158 °F)

Note
When operating below −20 °C (−4 °F), the LCD display can no
longer be read. Full functionality is assured at temperatures
above −20 °C (−4 °F).
1 Hole pattern for mounting holes
Integral mount design
2 Female thread (either ½ in NPT or M20 × 1.5), see model coding. In the
Housing Cast aluminum, painted
case of a ½ in NPT, there is a plug instead of a cable gland.
Paint ≥ 80 µm thick, RAL 9002 (gray white)
Figure 33: Mounting dimensions dual-compartment housing
Cable gland* Polyamide, M20 x 1.5 or ½ in. NPT
Stainless steel**, M20 x 1.5 or ½ in. NPT
Remote mount design
Housing Cast aluminum, painted
Paint ≥ 80 µm thick, RAL 9002 (gray white)
Cable gland* Polyamide, M20 x 1.5 or ½ in. NPT
Stainless steel**, M20 x 1.5 or ½ in. NPT
Weight 4.5 kg (9.92 lb)
* Cable gland with M 20 x 1.5 or NPT thread, to be selected via the order
number.
** On explosion-proof design for ambient temperature of –40 °C (–40 °F).
50 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Transmitter
… Dimensions

1 Hole pattern for mounting holes


2 Female thread (either ½ in NPT or M20 × 1.5), see model coding. In the
case of a ½ in NPT, there is a plug instead of a cable gland.

Figure 34: Mounting dimensions single-compartment housing


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 51


Electrical connections
Connection diagram

HART

Oc2 Oc1
1+ 2- 52
L N Uco 32 31 V3 V4 V1 V2 41 42 51 UFE GND A B

≤ 200 m
(≤ 656 ft)

UFE GND A B

G12153-01_FEP

A Connections for power supply and inputs / outputs B Connections for signal cable (remote mount design only)

Figure 35: Electrical connections

Note
For detailed information about grounding the transmitter and the flowmeter sensor, please refer to chapter ‘Grounding’ in the
Commissioning instruction or the operating instruction.

Connections for inputs and outputs


Connections for the power supply
Terminal Function / comments
AC voltage Uco / 32 Current output 4 to 20 mA- / HART® output, active
Terminal Function / comments or
L Phase 31 / 32 Current output 4 to 20 mA- / HART® output, passive
N Neutral conductor 41 / 42 Passive digital output DO1
PE / Protective earth (PE)
Potential equalization 51 / 52 Passive digital output DO2

V1 / V2 Plug-in card, slot OC1


DC voltage
V3 / V4 Plug-in card, slot OC2
Terminal Function / comments
For details, see Optional plug-in cards on page 48.
1+ +
2- -
Connecting the signal cable
PE / Protective earth (PE)
Only for remote mount design.
Potential equalization
The sensor housing and transmitter housing must be
connected to potential equalization.

Terminal Function / comments


UFE Sensor power supply
GND Ground
A Data line
B Data line
Functional earth / Shielding
52 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Electrical connections
Electrical data for inputs and outputs
Power supply Current output Uco / 32, 31 / 32
Can be configured for outputting mass flow and volume flow
AC power supply
via the on-site software.
Terminals L/N
Operating voltage 100 to 240 V AC (−15 % / +10 %), 47 to 64 Hz
Power consumption Smax: < 20 VA
Power-up current 18.4 A, t < 3 ms

DC voltage supply
Terminals 1+ / 2−
Operating voltage 16.8 to 30 V DC
A Current output Uco / 32, active B Current output 31 / 32, passive
Ripple <5%
Power consumption Pmax: < 20 W Figure 36: (I = internal, E = external, RB = load)

Power-up current 21 A, t < 10 ms

HART communication
A HART DTM in accordance with FDT1.2 standards is available.
HART protocol based Integrations in other Tools or systems
(e.g., Emerson AMS/Siemens PCS7) are available on request.
The DTM, the DD and EDD is available for download from
www.abb.com/flow.

HART output
Terminals Active: Uco / 32 Permissible source voltage Uq for passive outputs in relation to load
Passive: 31 / 32 resistance RB where Imax = 22 mA.  = Permissible range

Protocol HART 7.1 Figure 37: Source voltage for passive outputs

Transmission FSK modulation on current output 4 to 20 mA in


accordance with Bell 202 standard Current output Active Passive
Baud rate 1200 baud Terminals Uco / 32 31 / 32
Signal amplitude Maximum 1.2 mAss Output signal 4 to 20 mA or 4 to 20 mA
Current output load Minimum 250 Ω 4 to 12 to 20 mA
Cable 0,25 mm2 (AWG 24), twisted switchable
Maximum cable length 1200 m (3937 ft) Load RB 250 Ω ≤ RB ≤ 300 Ω 250 Ω ≤ RB ≤ 600 Ω
Source voltage Uq* — 13 V ≤ Uq ≤ 30 V
For information on communication via the HART protocol, Measuring error < 0.1 % of measured value
refer to HART® communication in Operating Instruction Resolution 0.4 µA per digit
OI/FEP630/FEH630. Insulation The current output and digital outputs are
electrically isolated.
* Source voltage Uq depends on the load RB and must be within the
permissible range.

For information on communication via the HART protocol,


refer to HART® Communication on page 58.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 53

Digital output 41 / 42, 51 / 52 (basic device) Current output V1 / V2, V3 / V4 (plug-in module)
Can be configured as pulse, frequency or binary output via Up to two additional plug-in modules can be implemented via
on-site software. the ‘Passive current output (red)’ option module.

A Current output V1 / V2, passive B Current output V3 / V4, passive

Figure 39: (I = internal, E = external, RB = load)

The plug-in module can be used in slot OC1 and OC2.

A Digital output 41 / 42, 51 / 52 passive as a pulse or frequency output


B Passive digital output 51 / 52 as binary output

Figure 38: (I = internal, E = external, RB = load)

Pulse / frequency output (passive)


Terminals 41 / 42, 51 / 52
Output ‘closed’ 0 V ≤ UCEL ≤ 3 V
For f < 2.5 kHz: 2 mA < ICEL < 30 mA Permissible source voltage Uq for passive outputs in relation to load
For f > 2.5 kHz: 10 mA < ICEL < 30 mA resistance RB where Imax = 22 mA.  = Permissible range
Output ‘open’ 16 V ≤ UCEH ≤ 30 V DC Figure 40: Source voltage for passive outputs
0 mA ≤ ICEH ≤ 0.2 mA
fmax 10.5 kHz Passive current output
Pulse width 0.05 to 2000 ms Terminals V1 / V2, V3 / V4
Output signal 4 to 20 mA
Binary output (passive) Load RB 250 Ω ≤ RB ≤ 600 Ω
Terminals 41 / 42, 51 / 52 Source voltage Uq* 13 V ≤ Uq ≤ 30 V
Output ‘closed’ 0 V ≤ UCEL ≤ 3 V Measuring error < 0.1 % of measured value
2 mA ≤ ICEL ≤ 30 mA Resolution 0.4 µA per digit
Output ‘open’ 16 V ≤ UCEH ≤ 3 V DC * The source voltage Uq is dependent of the load RB and must be placed
0 mA ≤ ICEH ≤ 0.2 mA in an additional area.
Switching function Can be configured using software.

Note
• Terminals 42 / 52 have common grounding. Digital
outputs 41 / 42 and 51 / 52 are not electrically isolated
from each other. An electrically isolated digital output can
be made using a plug-in module.
• If using a mechanical counter, it is advisable to set a pulse
width of ≥ 30 ms and a maximum frequency of
fmax ≤ 3 kHz.
54 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Electrical connections
… Electrical data for inputs and outputs
Digital output V1 / V2, V3 / V4 (plug-in card) Digital input V1 / V2, V3 / V4 (plug-in card)
The ‘digital output passive (green)’ plug-in card can be used A digital input can be implemented via the ‘Passive digital
to create one additional binary output. input (yellow)’ plug-in card.

Figure 41: Plug-in card as binary output (I = internal, E = external, RB = load) Figure 42: Plug-in card as digital input (I = internal, E = external)

The plug-in module can be used in slot OC1 or OC2. The plug-in card can be used in slot OC1 or OC2.

Binary output (passive) Digital input


Terminals V1 / V2, V3 / V4 Terminals V1 / V2, V3 / V4
Output ‘closed’ 0 V ≤ UCEL ≤ 3 V Input ‘On’ 16 V ≤ UKL ≤ 30 V
2 mA < ICEL < 30 mA Input ‘Off’ 0 V ≤ UKL ≤ 3 V
Output ‘open’ 16 V ≤ UCEH ≤ 30 V DC Internal resistance Ri 6.5 kΩ
0 mA ≤ ICEH ≤ 0.2 mA Function Parameterization possible.
Switching function Parameterization possible.

Note
ICEL < 30 mA; Rb = UCEH / ICEL
• Rb depends in the inner resistance of the DCS Input Card.
Rb must be installed in case the inner resistance of the
DCS Input Card does not limit ICE to max. 30 mA.
• With the NAMUR switch set to ‘On’ Rb is not required.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 55

24 V DC loop power supply (plug-in card) Modbus® / PROFIBUS DP/PA® interface V1 / V2


Use of the ‘loop power supply (blue)’ plug-in card allows a (plug-in card)
passive output on the transmitter to be used as an active A Modbus or PROFIBUS DP/PA interface can be implemented
output. See also Connection examples on page 56. by using the ‘Modbus RTU, RS485 (white)’ or ‘PROFIBUS DP,
RS485 (white)’ or ‘PROFIBUS PA, RS485 (blue) plug-in cards.

Figure 43: (I = Internal, E = External)

The plug-in card can only be used in slot OC1.


Figure 44: Plug-in card as a Modbus / PROFIBUS DP/PA interface (I = internal,
E = external)
Loop power supply 24 V DC
Terminals V1 / V2
The corresponding plug-in card can only be used in slot OC1.
Function For active connection of passive outputs
Output Voltage 24 V DC at 0 mA,
For information on communication through the Modbus or
17 V DC at 25 mA
PROFIBUS DP/PA protocols, refer to chapters Modbus®
Load rating Imax 25 mA, permanently short circuit-proof
communication on page 58 or PROFIBUS DP®
communication on page 59 or Bus topology on page 60.
Note PROFIBUS PA connection via M12-Plug
If the device is used in potentially explosive atmospheres, the Only in non-hazardous areas!
plug-in card for the loop power supply may only be used to
supply a passive output. It is not allowed, to connect it to
multiple passive outputs!

4 3

1 2

G11003-02
Figure 45: Pin assignment* PROFIBUS PA M12-Plug (option)

Pin assignment*
Pin Function
1 PA+
2 Not connected
3 PA−
4 Shield
* Front view showing pin insert and pins
56 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Electrical connections
… Electrical data for inputs and outputs
Connection examples
Input and output functions are configured via the device Digital output 41 / 42, 51 / 52 passive on distributed
software in accordance with the desired application. control system

Digital output 41 / 42, 51 / 52, V3 / V4 active


When the ‘loop power supply 24 V DC (blue)’ plug-in card is
used, the digital outputs on the basic device and on the
option modules can also be wired as active digital outputs.

Note
Each ‘loop power supply (blue)’ plug-in card must only power
one output.
It must not be connected to two outputs (for example digital
A Transmitter Ex. 2 Input 2
output 41 / 42 and 51 / 52)!
B Distributed control system / RX Resistor for current limitation
Memory programmable RI Distributed control system
controller internal resistance
Ex. 1 Input 1

Figure 48: Digital output 41 / 42 on distributed control system (example)

The RX resistors limit the maximum current through the


optoelectronic coupler of the digital outputs in the
transmitter.
The maximum permissible current is 25 mA. An RX value of
A ‘Loop power supply (blue)’ plug-in card in slot 1 1000 Ω / 1 W is recommended at a voltage level of 24 V DC.
B Digital output, digital output 41 / 42
The input on the distributed control system is reduced from
24 V DC to 0 V DC (falling edge) with ‘1’ at the digital output.
Figure 46: Active digital output 41 / 42 (example)

The connection example shows usage for digital output


41 / 42; the same applies to usage for digital output 51 / 52.

A ‘Loop power supply (blue)’ plug-in card in slot 1


B ‘Digital output (green)’ plug-in card in slot 2

Figure 47: Active digital output V3 / V4 (example)


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 57

Current output V3 / V4 active Connection versions digital output 41 / 42, 51 / 52


When the ‘loop power supply 24 V DC, blue’ plug-in card is Depending on the wiring of digital outputs DO 41 / 42 and
used, the current output on the plug-in card can also be wired 51 / 52, they can be used parallel or only individually. The
as the active current output. electrical isolation between the digital outputs also depends
on the wiring.

A ‘Loop power supply (blue)’ plug-in card in slot 1


B ‘Passive current output (red)’ plug-in card in slot 2

Figure 49: Active current output V3 / V4 (example)

Digital input V3 / V4 active


When the ‘loop power supply 24 V DC, blue’ plug-in card is
used, the current output on the plug-in card can also be wired
as the active current output.

A ‘Loop power supply (blue)’ plug-in card in slot 1


B ‘Passive digital input (yellow)’ plug-in card in slot 2

Figure 50: Active digital output V3 / V4 (example)

Figure 51: Connection versions digital output 41 / 42 and 51 / 52

DO 41 / 42 and 51 / 52 DO 41 / 42 and 51 / 52 electrically


can be used parallel isolated
A Yes No
B Yes No
C No, only DO 41 / 42 can be used No
D No, only DO 51 / 52 can be used No
58 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Digital communication
HART® Communication Modbus® communication
Note Note
The HART® protocol is an unsecured protocol, as such the The Modbus® protocol is an unsecured protocol, as such the
intended application should be assessed to ensure that these intended application should be assessed to ensure that these
protocols are suitable before implementation. protocols are suitable before implementation.

In connection with the DTM (Device Type Manager) available Modbus is an open standard owned and administrated by an
to the device, communication (configuration, independent group of device manufacturers styled the
parameterization) can be carried out FDT 0.98 or 1.2. Modbus Organization (www.modbus.org/).
Other tool or system integrations (e.g. Emerson AMS /
Siemens PCS7) on request. Using the Modbus protocol allows devices made by different
manufacturers to exchange information via the same
The necessary DTMs and other files can be downloaded from communication bus, without the need for any special
www.abb.com/flow. interface devices to be used.

Modbus protocol
HART output
Terminals V1 / V2
Terminals Active: Uco / 32
Configuration Via the Modbus interface or via the local
Passive: 31 / 32
operating interface in connection with a
Protocol HART 7.1
corresponding Device Type Manager (DTM)
Transmission FSK modulation on current output 4 to 20 mA in
Transmission Modbus RTU - RS485 serial connection
accordance with the Bell 202 standard
Baud rate 2400, 4800, 9600, 19200, 38400, 56000, 57600,
Baud rate 1200 baud
115200 baud
Signal amplitude Maximum 1.2 mAss
Factory setting: 9600 baud
Parity None, even, odd

Factory setting of the HART process variables Factory setting: odd


Stop bit One, two
HART process variable Process value
Factory setting: One
Primary Value (PV) Volume Flow in %
IEEE format Little endian, big endian
Secondary Value (SV) Massflow in %
Factory setting: Little endian
Tertiary Value (TV) Volumeflow Totalizer Forward
Typical response time < 100 ms
Quaternary Value (QV) Volumeflow Totalizer Reverse
Response delay time 0 to 200 milliseconds
Factory setting: 10 milliseconds
The process values of the HART variables can be set in the
device menu.

1 Modbus master 3 Modbus slave 1


2 Terminating resistor 4 Modbus slave n to 32

Figure 52: Communication with the Modbus protocol


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 59

PROFIBUS DP® communication


Cable specification Note
The maximum permissible length is dependent on the baud The PROFIBUS DP® protocol is an unsecured protocol, as such
rate, the cable (diameter, capacity and surge impedance), the the intended application should be assessed to ensure that
number of loads in the device chain, and the network these protocols are suitable before implementation.
configuration (2-core or 4-core).
PROFIBUS DP interface
• At a baud rate of 9600 and with a conductor cross-section
Terminals V1 / V2
of at least 0.14 mm2 (AWG 26), the maximum length is
Configuration Via the PROFIBUS DP interface or via the local
1000 m (3280 ft).
operating interface in connection with a
• When using a 4-core cable as a 2-wire wiring system, the
corresponding Device Type Manager (DTM)
maximum length must be halved.
Transmission Based on IEC 61158-2
• The spur lines must be short, a maximum of 20 m (66 ft).
• When using a distributor with ‘n’ connections, each Baud rate 9.6 kbps, 19.2 kbps, 45.45 kbps, 93.75 kbps,

branch must have a maximum length of 40 m (131 ft) 187.5 kbps, 500 kbps, 1.5 Mbps

divided by ‘n.’ The baud rate is automatically detected and


does not need to be configured manually

The maximum cable length depends on the type of cable Device profile PA Profile 3.02

used. The following standard values apply: Bus address Address range 0 to 126

• Up to 6 m (20 ft): Factory setting: 126

cable with standard shielding or twisted-pair cable. Number of DP nodes ≤ 32, Node = Devices with / without PROFIBUS
• Up to 300 m (984 ft): address
double twisted-pair cable with overall foil shielding and Bus termination Bus termination required at the beginning and
integrated earth cable. end of each DP segment!
• Up to 1200 m (3937 ft):
double twisted-pair cable with individual foil shielding For commissioning purposes, you will need a device driver in
and integrated earth cables. Example: Belden 9729 or EDD (Electronic Device Description) or DTM (Device Type
equivalent cable. Manager) format plus a GSD file.

A category 5 cable can be used for Modbus RS485 up to a You can download EDD, DTM and GSD from
maximum length of 600 m (1968 ft). For the symmetrical www.abb.com/flow.
pairs in RS485 systems, a surge impedance of more than
100 Ω is preferred, especially at a baud rate of 19200 and The files required for operation can also be downloaded from
above. www.profibus.com.

ABB provides three different GSD files which can be


integrated in the system.

ID number GSD file name


0x9740 PA139740.gsd 1xAI, 1xTOT
0x9700 PA139700.gsd 1AI
0x3432 ABB_3432.gsd 6xAI, 2xTOT, 1xAO,
1xDI, 1xDO

Users decide at system integration whether to install the full


range of functions or only part. Switching is made using the
‘Ident Nr. Selector’ parameter.

See also Parameter description in the operating instruction.


60 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Digital communication
… PROFIBUS DP® communication PROFIBUS PA® communication
General Information Note
The PROFIBUS PA® protocol is an unsecured protocol, as such
the intended application should be assessed to ensure that
LT /m
these protocols are suitable before implementation.
1200
1000 PROFIBUS PA interface
EIA 485 (RS485) Terminals V1 (PA+) / V2 (PA−)
PROFIBUS DP Configuration Via Device HMI or PROFIBUS PA-DTM or FDI

400 package
Transmission Based on IEC 61158-2
200 Device profile The interface conforms to profile 3.02
100 (PROFIBUS standard, EN 50170,
DIN 19245 [PRO 91])

0 PROFIBUS PA ID no 0x3438
Bit/s
G12390 Alternative standard ID no 0x9700 or 0x9740
Figure 53: Bus cable length depends on the transmission rate Bus cable Shielded, twisted cable (acc. to IEC 61158-2,
types A or B are preferred)
Pro PROFIBUS Line
(Line = Starts at DP Master and goes to last DP/PA Slave) Bus topology
• Approximately 4 to 8 DP segments through the repeater • Tree and/or line structure
(see repeater data sheets) • Bus termination: passive at both ends of the main bus line
• Recommended DP transfer rate 500 to 1500 kBit/s (RC element R = 100 Ω, C = 1 μF)
• The slowest DP node determines the transfer rate of the
DP line Voltage / current consumption
• Number of PROFIBUS DP and PA nodes ≤ 126 • Average current consumption: 10 mA
(addresses 0 to 125) • In the event of an error, the integrated FDE function
(=Fault Disconnection Electronic) integrated in the device
Per PROFIBUS DP segment is ensures that the current consumption can rise to a
• Number of DP nodes ≤ 32 maximum of 13 mA.
(Node = Devices with / without PROFIBUS address) • The upper current limit is restricted electronically.
• Bus termination required at the beginning and end of • The voltage on the bus line must be within 9 to 32 V DC
each DP segment!
• Trunk cable length (LT) see diagram (length dependent on Short circuit protection / reverse polarity protection
transfer rate) The Device Terminals V1 and V2, Profibus connects to, are
• Cable length of at least 1 m between two DP nodes at short-circuit protected and have a reverse polarity
≥ 1500 kBit/s! protection.
• Spur cable length (LS), at ≤ 1500 kBit/s: LS ≤ 0.25 m,
System integration
at > 1500 kBit/s: LS = 0.00 m!
ABB provides three different GSD files which can be
• At 1500 kBit/s and ABB DP cable type A:
integrated in the system.
– Sum of all spur cable lengths (LS) ≤ 6.60 m, trunk cable
length (LT) > 6.60 m, total length = LT+ (Σ LS) ≤ 200 m, ID number GSD file name
maximum 22 DP nodes (= 6.60 m / (0.25 m + 0.05 m 0x9700 PA139700.gsd
spare)) 0x9740 PA139740.gsd
0x3438 ABB_3438.gsd

Users decide at system integration whether to install the full


range of functions or only part. Switching is made using the
‘Ident Nr. Selector’ parameter.

See also Parameter description in the operating instruction.

You can download the GSD files from www.abb.com/flow.

For additional information, see separate interface


documentation.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 61

EtherNet/IP™ and PROFINET® communication


Note Two port connection without power over Ethernet
The EtherNet/IP™ and PROFINET® protocols are unsecured
Terminal designation:
protocols (in the sense of IT or cyber security), as such the
Port Pin Function Color coding
intended application should be assessed before
1 Pin 1 RD+ White / Orange
implementation to make sure that this protocol is suited.
Pin 2 RD− Orange
Pin 3 TD+ White / Green
Pin 4 TD− Green
2 Pin 1 RD+ White / Orange
Pin 2 RD− Orange
Pin 3 TD+ White / Green
Pin 4 TD− Green

Ethernet communication
Equipped with an Ethernet Card, the flowmeter provides
2 Ports supporting a Ring, Star and Daisy Chain Network
configuration.
Figure 54: Ethernet communication plug-in card

In addition to the Ethernet Card, a plug-in Card providing


One port connection without power over Ethernet
‚Power over Ethernet‘ is available. This Card allows to power
Terminal designation: the 24 V DC Version of the flowmeter through Ethernet
Port Pin Function Color coding
without the need for additional power supply.
1 Pin 1 RD+ White / Orange
Pin 2 RD− Orange
Pin 3 TD+ White / Green
Pin 4 TD− Green

Standard Ethernet 10/100 BASE-T/TX (IEEE802.3) single port


connection.

One port connection with power over Ethernet


Terminal designation:
Port Pin Function Color coding
1 Pin 1 RD+ White / Orange
Pin 2 RD− Orange
Pin 3 TD+ White / Green
Pin 4 TD− Green
2 Pin 1 PWR+ White / Blue
Pin 2 PWR+ Blue
Pin 3 PWR− White / Brown
Pin 4 PWR− Brown

Standard Ethernet 10/100 BASE-T/TX (IEEE802.3) single port


connection.
62 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Digital communication
… EtherNet/IP™ and PROFINET® communication
EtherNet/IP™ and PROFINET® protocol Further communication protocols
Note Note
The protocol is not secure, as such. The application should be The device supports following security modes:
assessed before Implementation to ensure the protocol is
Secured Protocols Unsecured protocols
suitable.
Webserver https EtherNet/IP, Modbus TCP and
PROFINET
The EtherNet/IP and PROFINET protocol supports cyclic
• Used ports by Webserver: • Used ports by EtherNet/IP:
communication. Process Variables, Diagnostic Data and
TCP 443 TCP 44818, UDP 2222
Device Status Information can be accessed cyclically.
• Security is based on • Used ports by Modbus/TCP:
With PROFINET communication, the DHCP (Dynamic Host
.x509 Certificates TCP 502
Configuration Protocol) function is not supported and
• Used ports by PROFINET:
PROFINET DCP (Discovery and Configuration Protocol) is
UDP 34964, 49152
used instead.

For Device Configuration a Webserver is available providing All protocols can be enabled / disabled in the HMI Menu.
full access to all parameter and diagnostic data.

EtherNet/IP Interface
Configuration Through the Webserver or the local operating
Interface (Display).
EtherNet / IP 5002
ProductCode
EDS file FEW530_FEPFEH630_01_01.eds
Device profile Profile 0x43, Generic Device, (keyable).
Supporte standards Common Industrial Protocol (CIP™) Vol1, Ed 3.25
and protocols EtherNet/IP™ Adaptation of CIP™, Vol2, Ed 1.23

Cable Cat 5

PROFINET Interface
Configuration Through the Webserver or the local operating
Interface (Display).
Device profile PA Profile 4.01 Specification
GSDML File GSDML-V2.42-ABB_001A-
3437_FLOW_EL_MAGNETIC-20220713.xml
GSD File ABB 0x3437 or PNO 0xB332
Supporte standards Common Industrial Protocol (CIP™) Vol1, Ed 3.25
and protocols EtherNet/IP™ Adaptation of CIP™, Vol2, Ed 1.23

PROFINET PNIO_Version V2.42


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 63


Operation in Zone 1, 21
Electrical connections
Sensor FEP632 (Zone 1) Transmitter FET632 (Zone 2) FET632 transmitter outside the hazardous area
Sensor FEH632 (Zone 1)

PA

PA
FEP631 (Zone 1)
FEH631 (Zone 1) A B
HART

Oc2 Oc1
PA 1+ 2- 52
L N Uco 32 31 V3 V4 V1 V2 41 42 51 UFE GND A B

PA /

FEP631 + FET632 (Zone 1) PE


FEH631 + FET632 (Zone 1)

≤ 200 m
(≤ 656 tt)

PA UFE GND A B

B PA /
G12472
A Transmitter B Sensor

Figure 55: Electrical connections

Note Connections for inputs and outputs


For detailed information about grounding the transmitter
Terminal Function / comments
and the flowmeter sensor, please refer to chapter ‘Grounding’
Uco / 32 Current output 4 to 20 mA- / HART output, active
in the Commissioning instruction or the operating
or
instruction.
31 / 32 Current output 4 to 20 mA- / HART output, passive
41 / 42 Passive digital output DO1
Connections for the power supply

AC power supply 51 / 52 Passive digital output DO2


Terminal Function / comments
L Phase V1 / V2 Plug-in card, slot OC1
N Neutral conductor V3 / V4 Plug-in card, slot OC2
PE / Protective earth (PE) Plug-in cards may not be retrofitted in devices with explosion
/ PA Potential equalization protection on-site – loss of Ex Approval.

DC voltage supply
Terminal Function / comments
1+ +
2− −
PE / Protective earth (PE)
/ PA Potential equalization
64 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Operation in Zone 1, 21
… Electrical connections
Optional plug-in cards Special connection conditions
See Optional plug-in cards on page 48. The output circuits are designed so that they can be
connected to both intrinsically-safe and non-intrinsically-safe
Configuring the current output circuits.
Current output terminals 31 / 32 / Uco can be operated on- • Combining intrinsically safe and non-intrinsically safe
site in active or passive mode through appropriate switching. circuits is not permitted.
• On intrinsically safe circuits, potential equalization should
Terminal Uco / 32 Current output 4 to 20 mA- / HART be established along the entire length of the cable used
output, active for the signal outputs.
Terminal 31 / 32 Current output 4 to 20 mA- / HART • The rated voltage of the non-intrinsically safe circuits is
output, passive UM = 30 V.
• Intrinsic safety is preserved If the rated voltage UM = 30 V
Configuring the digital outputs is not up-scaled when connections are established to non-
In the case of the device version suited for operation in Ex intrinsically safe external circuits.
Zone 1 (dual-compartment housing), digital outputs DO1
(41 / 42) and DO2 (51 / 52) can be configured for connection
to a NAMUR switching amplifier.
On leaving the factory, the device is configured with the
standard wiring (non-NAMUR).

Note
The outputs' type of protection remains unaffected by this.
The devices connected to these outputs must conform to the
applicable regulations for explosion protection.

Electric data for operation in Zone 1, 21


Devices with HART protocol
When operating in potentially explosive areas, observe the following electrical data for the signal inputs and outputs of the
transmitter.
Current output terminals 31 / 32 / Uco can be operated on-site in active or passive mode through appropriate switching.

Model: FEP631, FEH631 or FET632 Type of protection


Outputs on basic device ‘e’ / ‘XP’ ‘ia’ / ‘IS’
UM IM UO UI IO II PO PI CO CI COPA CIPA LO LI
[V] [A] [V] [mA] [mA] [mW] [mW] [nF] [nF] [nF] [nF] [mH] [mH]
Current / HART output 31 / UCO, active 30 0.2 30 30 115 115 815 815 10 10 5 5 0.08 0.08
Terminals 31 / UCO
Current / HART output 31 / 32, passive 30 0.2 — 30 — 115 — 815 — 27 — 5 0.08 0.08
Terminals 31 / 32
Digital output 41 / 42, active* 30 0.1 27.8 30 119 30 826 225 20 20 29 29 0.22 0.22
Terminals 41 / 42 and V1 / V2*
Digital output 41 / 42, passive 30 0.1 — 30 — 30 — 225 — 27 — 5 — 0.08
Terminals 41 / 42
Digital output 51 / 52, active* 30 0.1 27.8 30 119 30 826 225 20 20 29 29 0.22 0.22
Terminals 51 / 52 and V1 / V2*
Digital output 51 / 52, passive 30 0.1 — 30 — 30 — 225 — 27 — 5 — 0.08
Terminals 51 / 52

All outputs are electrically isolated from each other and from the power supply.
Digital outputs 41 / 42 and 51 / 52 are not electrically isolated from each other. Terminals 42 / 52 have the same potential.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 65

Model: FEP631, FEH631 or FET632 Type of protection


Inputs and outputs with optional plug-in ‘e’ / ‘XP’ ‘ia’ / ‘IS’
cards UM IM UO UI IO II PO PI CO CI COPA CIPA LO LI
[V] [A] [V] [mA] [mA] [mW] [mW] [nF] [nF] [nF] [nF] [mH] [mH]
Current output V3 / V4, active* 30 0.1 27.8 30 119 30 826 225 29 29 117 117 0.4 0.4
Terminals V3 / V4 and V1 / V2*
Current output V1 / V2, passive** 30 0.1 — 30 — 68 — 510 — 45 — 59 — 0.27
Current output V3 / V4, passive**
Terminals V1 / V2** or V3 / V4**
Digital output V3 / V4, active* 30 0.1 27.8 30 119 68 826 225 17 17 31 31 0.4 0.4
Terminals V3 / V4 and V1 / V2*
Digital output V1 / V2, passive** 30 0.1 — 30 — 30 — 225 — 13 — 16 — 0.27
Digital output V3 / V4, passive**
Terminals V1 / V2** or V3 / V4**
Digital input V3 / V4, active* 30 0.1 27.8 30 119 3.45 826 25.8 17 17 31 31 0.4 0.4
Terminals V3 / V4 and V1 / V2
Digital input V1 / V2, passive* 30 0.1 — 30 — 3.45 — 25.8 — 13 — 16 — 0.27
Digital input V3 / V4, passive*
Terminals V1 / V2** or V3 / V4**
Modbus Card (RTU) 30 0.1 4.2 4.2 150 150 150 150 5300 5300 0.06 0.06 0.09 0.09
Terminals V1 / V2
PROFIBUS DP 30 0.1 4.2 4.2 150 150 150 150 5300 5300 0.06 0.06 0.09 0.09
Terminals V1 / V2
PROFIBUS PA (Non-FISCO) 30 0.38 — 30 — 100 — 815 — 4 — — 0 0.008
Terminals V1 / V2
PROFIBUS PA (FISCO) — — — 17.5 — 380 — 5320 — 4 — — 0 0.008
Terminals V1 / V2
* Only in conjunction with additional ‘24 V DC loop power supply (blue)’ plug-in card in slot OC1.
** The terminal assignment depends on the model number or the slot assignments. For connection examples, refer to Installation in the operating
instruction.

For devices in Zone 1 / Div. 1 the bus termination must conform to the FISCO model or the explosion protection regulations,
respectively.
66 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Operation in Zone 1, 21
Temperature data
Measuring medium temperature (Ex Data) for ProcessMaster Model FEP631
Nominal diameter

Ambient temperature Ambient temperature Ambient temperature


Temperature

(−40 °C)* −20 °C to +40 °C (−40 °C)* −20 °C to +50 °C (−40 °C)* −20 °C to +60 °C
Design

class

thermally uninsulated, thermally uninsulated, thermally uninsulated,


thermally insulated thermally insulated thermally insulated
Gas & dust Gas & dust Gas & dust
NT 130°C 130°C 130°C
T1
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T2
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
DN3 to 2000

T3
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T4
HT 130°C 130°C 130°C
NT 95°C 95°C 95°C
T5
HT 95°C 95°C 95°C
NT 80°C 80°C 80°C
T6
HT 80°C 80°C 80°C
* Low-temperature version (option)

NT standard version, Tmedium maximum 130 °C (266 °F)


HT high-temperature version, Tmedium maximum 180 °C (356 °F)
Thermally uninsulated: the sensor is not enclosed with pipe insulation material.
Thermally insulated: the sensor is enclosed with pipe insulation material.

Note
Cables for power supply, signal inputs and outputs must meet the following specifications:
• At an ambient temperature ≤ 50 °C the cable must be suited for at least 60 °C
• At an ambient temperature ≤ 60 °C the cable must be suited for at least 70 °C
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 67

Measuring medium temperature (Ex Data) for ProcessMaster Model FEP632


Nominal diameter

Ambient temperature Ambient temperature Ambient temperature


Temperature

(−40 °C)* −20 °C to +40 °C (−40 °C)* −20 °C to +50 °C (−40 °C)* −20 °C to +60 °C
Design

class

thermally uninsulated, thermally uninsulated, thermally uninsulated,


thermally insulated thermally insulated thermally insulated
Gas & dust Gas & dust Gas & dust
NT 130°C 130°C 130°C
T1
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T2
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
DN3 to 2000

T3
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T4
HT 130°C 130°C 130°C
NT 95°C 95°C 95°C
T5
HT 95°C 95°C 95°C
NT 80°C 80°C 80°C
T6
HT 80°C 80°C 80°C
* Low-temperature version (option)

NT standard version, Tmedium maximum 130 °C (266 °F)


HT high-temperature version, Tmedium maximum 180 °C (356 °F)
Thermally uninsulated: the sensor is not enclosed with pipe insulation material.
Thermally insulated: the sensor is enclosed with pipe insulation material.

Note
Cables for power supply, signal inputs and outputs must meet the following specifications:
• At an ambient temperature ≤ 50 °C the cable must be suited for at least 70 °C
• At an ambient temperature ≤ 60 °C the cable must be suited for at least 80 °C
68 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


Operation in Zone 2, 22
Electrical connections
Sensor FEP631, FEH631, FEP632, FEH632 and transmitter FET632 (Zone 2) FET632 transmitter outside the
hazardous area
FEP631 FEH631 FEP632, FEH632 FET632 FET632

PA
PA PA

PA

A B
HART

Oc2 Oc1
1+ 2- 52
L N Uco 32 31 V3 V4 V1 V2 41 42 51 UFE GND A B

PA /

PE

UFE GND A B

B PA /
G12476
A Transmitter B Sensor

Figure 56: Electrical connections

Note Connections for inputs and outputs


For detailed information about grounding the transmitter
Terminal Function / comments
and the flowmeter sensor, please refer to chapter ‘Grounding’
Uco / 32 Current output 4 to 20 mA- / HART output, active
in the Commissioning instruction or the operating
or
instruction.
31 / 32 Current output 4 to 20 mA- / HART output, passive
41 / 42 Passive digital output DO1
Connections for the power supply

AC power supply 51 / 52 Passive digital output DO2


Terminal Function / comments
L Phase V1 / V2 Plug-in card, slot OC1
N Neutral conductor V3 / V4 Plug-in card, slot OC2
PE / Protective earth (PE) Plug-in cards may not be retrofitted in devices with explosion
/ PA Potential equalization protection on-site – loss of Ex Approval.

DC voltage supply Connecting the signal cable


Terminal Function / comments
Only for remote mount design.
The sensor housing and transmitter housing must be
1+ +
connected to potential equalization.
2− −
PE / Protective earth (PE) Terminal Function / comments
/ PA Potential equalization UFE Sensor power supply
GND Ground
A Data line
B Data line
Functional earth / Shielding
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 69

Special connection conditions


Note
The AS plug-in card (24 V DC loop power supply) may only be
used to power the internal inputs and outputs on the device.
It must not be used to power external circuits!

Note
If the protective earth (PE) is connected in the flowmeter's
terminal box, you must ensure that no dangerous potential
difference can arise between the protective earth (PE) and
the potential equalization (PA) in areas with explosion risk.

Note
For devices with a power supply of 16 to 30 V DC, on-site
external overvoltage protection must be provided.
It must be ensured that the overvoltage is limited to 140 % (=
42 V DC) of the maximum operating voltage.
70 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Operation in Zone 2, 22
Electrical data for operation in Zone 2, 22
Devices with HART protocol
When operating in potentially explosive areas, observe the following electrical data for the signal inputs and outputs of the
transmitter.
Current output terminals 31 / 32 / Uco can be operated on-site in active or passive mode through appropriate switching.

Model: FEP631, FEH631 or FET632


Outputs on basic device Operating values (general) Type of protection – ‘nA’ / ‘NI’ / ‘ec’
UN IN UN IN
Current / HART output 31 / UCO, active 30 V 30 mA 30 V 30 mA
Terminals 31 / UCO
Current / HART output 31 / 32, passive 30 V 30 mA 30 V 30 mA
Terminals 31 / 32
Digital output 41 / 42, passive 30 V 25 mA 30 V 25 mA
Terminals 41 / 42
Digital output 51 / 52, passive 30 V 30 mA 30 V 30 mA
Terminals 51 / 52
Digital output 41 / 42, active* 30 V 30 mA 30 V 30 mA
Terminals 41 / 42 and V1 / V2*
Digital output 51 / 52, active* 30 V 30 mA 30 V 30 mA
Terminals 51 / 52 and V1 / V2*
* Only in conjunction with additional ‘24 V DC loop power supply (blue)’ plug-in card in slot OC1.

All outputs are electrically isolated from each other and from the power supply.
Digital outputs 41 / 42 and 51 / 52 are not electrically isolated from each other. Terminals 42 / 52 have the same potential.

Model: FEP631, FEH631 or FET632


Plug-in cards Operating values (general) Type of protection – ‘nA’ / ‘NI’ / ‘ec’
UN IN UN IN
Current output, active* 30 V 30 mA 30 V 30 mA
Terminals V3 / V4 and V1 / V2**
Current output, passive 30 V 30 mA 30 V 30 mA
Terminals V1 / V2 or V3 / V4**
Digital output, active* 30 V 25 mA 30 V 25 mA
Terminals V3 / V4 and V1 / V2**
Digital output, passive 30 V 30 mA 30 V 30 mA
Terminals V1 / V2 or V3 / V4**
Digital input, active* 30 V 3.45 mA 30 V 3.45 mA
Terminals V3 / V4 and V1 / V2**
Digital input, passive 30 V 3.45 mA 30 V 3.45 mA
Terminals V1 / V2 or V3 / V4**
Modbus Card (RTU) 30 V 30 mA 30 V 30 mA
Terminals V1/V2
Profibus DP card 30 V 30 mA 30 V 30 mA
Terminals V1/V2
Profibus PA card 32 V 30 mA 32 V 30 mA
Terminals V1/V2
Ethernet card 57 V 417 mA 57 V 417 mA
Port 1: Pin X1 to X4
Port 2: Pin X5 to X8
Ethernet Card in conjunction with Power over 57 V 417 mA 57 V 417 mA
Ethernet (POE Card)
Port 1: Pin X1 to X4
Port 2: Pin X5 to X8
* Only in conjunction with additional ‘24 V DC loop power supply (blue)’ plug-in card in slot OC1.
** The terminal assignment relates to the Option Card Slot. Slot 1 = Terminals V1/V2. Slot 2 = Terminal V3/V4. For more details, refer to Installation in the
operating instruction.
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 71

Temperature data
Measuring medium temperature (Ex Data) for ProcessMaster Model FEP631
Single-compartment housing Dual- compartment housing

Ambient temperature Ambient temperature Ambient temperature


Temperature

(−40 °C)* −20 °C to +40 °C (−40 °C)* −20 °C to +50 °C (−40 °C)* −20 °C to +60 °C
diameter
Nominal

Design

class

thermally uninsulated, thermally uninsulated, thermally uninsulated,


thermally insulated thermally insulated thermally insulated
Gas & dust Gas & dust Gas & dust
NT 130°C 130°C 130°C
T1
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T2
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T3
HT 180°C 180°C 180°C
DN3 to 2000

NT 130°C 130°C 130°C


T4
HT 130°C 130°C 130°C
Note: The data below does not apply to Flowmeters equipped with the plug-in card for Ethernet communication (model code DR6)!
NT 95°C 95°C 40°C**
T5 —***
HT 95°C 95°C —
NT 80°C — —
T6
HT 80°C — —
* Low-temperature version (option)
** Single-compartment housing
*** Dual-compartment housing

NT standard version, Tmedium maximum 130 °C (266 °F)


HT high-temperature version, Tmedium maximum 180 °C (356 °F)
Thermally uninsulated: the sensor is not enclosed with pipe insulation material.
Thermally insulated: the sensor is enclosed with pipe insulation material.

Note
Cables for power supply, signal inputs and outputs must meet the following specifications:
With single-compartment housing
• At an ambient temperature of 50 °C the cable must be suited for at least 80 °C
• At an ambient temperature of 60 °C the cable must be suited for at least 90 °C
With dual-compartment housing
• At an ambient temperature of 50 °C the cable must be suited for at least 70 °C
• At an ambient temperature of 60 °C the cable must be suited for at least 80 °C
72 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Operation in Zone 2, 22
… Temperature data
Measuring medium temperature (Ex Data) for ProcessMaster Model FEP632

Ambient temperature Ambient temperature Ambient temperature


Temperature

(−40 °C)* −20 °C to +40 °C (−40 °C)* −20 °C to +50 °C (−40 °C)* −20 °C to +60 °C
diameter
Nominal

Design

class

thermally uninsulated, thermally uninsulated, thermally uninsulated,


thermally insulated thermally insulated thermally insulated
Gas & dust Gas & dust Gas & dust
NT 130°C 130°C 130°C
T1
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T2
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
DN3 to 2000

T3
HT 180°C 180°C 180°C
NT 130°C 130°C 130°C
T4
HT 130°C 130°C 130°C
NT 95°C 95°C 95°C
T5
HT 95°C 95°C 95°C
NT 80°C 80°C 40°C
T6
HT 80°C 80°C 20°C
* Low-temperature version (option)

NT standard version, Tmedium maximum 130 °C (266 °F)


HT high-temperature version, Tmedium maximum 180 °C (356 °F)
Thermally uninsulated: the sensor is not enclosed with pipe insulation material.
Thermally insulated: the sensor is enclosed with pipe insulation material.

Note
Cables for power supply, signal inputs and outputs must meet the following specifications:
• At an ambient temperature ≤ 50 °C the cable must be suited for at least 70 °C
• At an ambient temperature ≤ 60 °C the cable must be suited for at least 80 °C

Use in areas exposed to combustible dust


When using the device in areas exposed to combustible dusts (dust ignition), the following points must be observed:
• The maximum surface temperature of the device may not up-scale the following values.
FEP631, FEH631 80 °C (176 °F)
FEP632, FEH632 80 °C (176 °F)
FET632 80 °C (176 °F)
• The process temperature of the attached piping may up-scale 80 °C (176 °F).
• Approved dust-proof cable glands must be used when operating in Zone 21, 22 or in Class II, Class III.
• In potentially explosive atmospheres, the signal cable must measure at least 5 m (16.40 ft).
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 73


Ordering Information
ProcessMaster FEP631
Electromagnetic Flowmeter system, integral mount

ProcessMaster FEP631 7,8 9,10 11,12,13,14 ... 96,97


Explosion Protection Certification
Without, Flowmeter based on CE Standard Y0
Without, Flowmeter based on UKCA Standard Y1
ATEX / IECEx (Zone 1 / 21) A11)
ATEX / IECEx (Zone 2 / 22) A2
cFMus Class 1 Div. 1 (Zone 1 / 21)30) F11), 32)
cFMus Class 1 Div. 2 (Zone 2 / 22) F2
NEPSI (Zone 1) S11)
NEPSI (Zone 2) S2
UKEX Zone 1 U1
UKEX Zone 2 U2
Housing Type / Housing Material / Thread for Cable Glands
Single compartment / Aluminium / M20 x 1.5 S14)
Single compartment / Aluminium / NPT 1/2 in. S24)
Dual compartment / Aluminium / M20 x 1.5 D13)
Dual compartment / Aluminium / NPT 1/2 in. D23)
Meter size
DN 3 (1/10 in.) 0003
DN 4 (5/32 in.) 0004
DN 6 (1/4 in.) 0006
DN 8 (5/16 in.) 0008
DN 10 (3/8 in.) 0010
DN 15 (1/2 in.) 0015
DN 20 (3/4 in.) 0020
DN 25 (1 in.) 0025
DN 32 (1-1/4 in.) 0032
DN 40 (1-1/2 in.) 0040
DN 50 (2 in.) 0050
DN 65 (2-1/2 in.) 0065
DN 80 (3 in.) 0080
DN 100 (4 in.) 0100
DN 125 (5 in.) 0125
DN 150 (6 in.) 0150
DN 200 (8 in.) 0200
DN 250 (10 in.) 0250
DN 300 (12 in.) 0300
DN 350 (14 in.) 0350
DN 400 (16 in.) 0400
DN 450 (18 in.) 0450
DN 500 (20 in.) 0500
DN 600 (24 in.) 0600
DN 700 (28 in.) 0700
DN 750 (30 in.) 0750
DN 800 (32 in.) 0800
DN 900 (36 in.) 0900
DN 1000 (40 in.) 1000
DN 1050 (42 in.) 1050

Continued on next page


74 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP631

ProcessMaster FEP631 7,8 ... 11,12,13,14 15,16 17,18 19 20 ... 96,97


Meter size (continuation)
DN 1100 (44 in.) 1100
DN 1200 (48 in.) 1200
DN 1350 (54 in.) – AWWA flange only 1350
DN 1400 (54 in.) 1400
DN 1500 (60 in.) 1500
DN 1600 (66 in.) 1600
DN 1650 (66 in.) – AWWA flange only 1650
DN 1800 (72 in.) 1800
DN 2000 (80 in.) 2000
Process Connection Type
Flanges DIN PN 6 D07)
Flanges DIN PN 10 D1
Flanges DIN PN 16 D2
Flanges DIN PN 25 D3
Flanges DIN PN 40 D4
Flanges DIN PN 63 D56)
Flanges DIN PN 100 D66)
Flanges ASME CL 150; B16.5 up to DN 600, B16.47 series B > DN 600 A15)
Flanges ASME CL 300; B16.5 up to DN 600, B16.47 series B > DN 600 A35)
Flanges ASME CL 600 RF A66a)
Flanges ASME CL 900 RF A76a)
Flanges ASME CL 1500 RF A86b)
Flanges ASME CL 2500 RF A96b)
Flanges ASME CL 600 RTJ H66b)
Flanges ASME CL 900 RTJ H76b)
Flanges ASME CL 1500 RTJ H86b)
Flanges ASME CL 2500 RTJ H96b)
Flanges JIS 5K J2
Flanges JIS 7,5K J02)
Flanges JIS 10K J1
Flanges JIS 20K J3
AS 4087 PN16 E12)
Flange, AS2129 table E E42)
Flange, AS2129 table E E52)
Flanges AWWA C207 Class B C141)
Flanges AWWA C207 Class C C241)
Flanges AWWA C207 Class E C341)
Liner Material
Hard rubber R211)
Soft rubber R412)
ETFE E19)
PTFE T113)
PFA P110)
Thick PTFE T214)
Ceramic-Carbide C18)
Linatex R62)
Others Z9
Continued on next page
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 75

ProcessMaster FEP631 7,8 … 19 20 21 22 23 24,25 26 27 28,29 30 … 96,97


Process Connection Material
Carbon steel B
Stainless steel C15)
Others Z
Electrode Design
Standard 1
Pointed head 516)
Others 9
Measuring Electrodes Material
Hast. C-4 (2.4610) D
Titanium F
Tantalum G
Hast. B-3 (2.4600) H
Platinum-Iridium J
Stainless steel 316Ti (1.4571) S
Double Layer W16)
Tungsten Carbide, coated T
Others Z
Grounding Electrode / Full Pipe Detection
No grounding electrode / No full pipe detection 0
No grounding electrode / With full pipe detection 117)
Grounding electrode / No full pipe detection 218)
Grounding electrode / With full pipe detection 319)
Others 9
Grounding Accessories
Without A
Grounding ring (1 off), mounted to flange B20)
Grounding ring (2 off), mounted to flange C20)
Others Z
Protection Class Transmitter / Protection Class Sensor
IP 67 / IP 67 70
Power Supply
100 ... 230 V AC, 50 Hz A
24 V DC, 50 Hz D
100 ... 230 V AC, 60 Hz C
24 V DC, 60 Hz E
Display
Without 0
Display with Keypad 2
Outputs
1 Current output (active or passive). 2 Digital Outputs (passive). HART G021)
Current output 1 (active or passive), digital output 1 & 2 (passive). HART. MODBUS RTU M134)
Current output 1 (active or passive). digital output 1 & 2 (passive). HART. PROFIBUS DP D135)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART. 1 port Ethernet E236)
Current output 1 (active or passive), digital output 1 & 2 (passive). HART, 2 port Ethernet E336)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART. 1 port Ethernet + POE E436)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART, PROFIBUS PA P1
Design Level
Specified by ABB A22)
Continued on next page
76 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP631

ProcessMaster FEP631 7,8 … 31,32,33 34,35,36 37,38 39,40 41,42,43 44,45,46 47,48,49 50,51 52,53,54 55,56,57 58,59 … 96,97
Option Card 1
Without DR0
1 x Digital Input DRN
1 x Digital Output DRG
24 V DC transmitter loop power DRT
supply
1 x Analog Output passive (4…20mA) DRA
Modbus RTU DRM
PROFIBUS DP DRD
Card for Ethernet IP, Modbus TCP,
PROFINET DR637)
Option Card 2
Without DS0
1 x Analog Output passive (4…20mA) DSA
1 x Digital Input DSN
1 x Digital Output DSG
Module Power over Ethernet/
Modbus TCP (for Single Comp Hsg) DS838)
Usage Certifications
Without C0
Inspection certificate 3.1 acc. EN C2
10204
Others CZ
SIL Certificate
SIL2 Certificate CS33)
Shipping Register Certificate
Marine approval (DNA) CL533)
Calibration Certifications
ABB Standard CMA
3rd party witnessed calibration CMW
5-point calibration acc. DAKKS CMD23)
Other Usage Certifications
Meter tube with PED certificate CRP
Meter tube without PED certificate CRA2)
Sensor Length
ABB Standard J6
1,0 x DN length (from DN700 and up) JH30)
Potable Water and Food&Beverage Approvals
DVGW; KTW certified liner material CWL
Without CWY
Other Explosion Protection Certifications and other Approvals
Russia metro+EAC ED1
Russia metro+EAC+EX ED2
Other Options
Without K0
With Gore-tex membrane KG

Continued on next page


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 77

ProcessMaster FEP631 7,8 … 60,61 62,63,64 65,66,67 68,69,70 71,72,73 74,75,76 77,78,79 80,81,82 83,84 85,86,87 … 96,97
Documentation Language
German M1
English M5
Language package Western Europe / MW
Scandinavia
Language package Eastern Europe ME
Others MZ
Pressure Bearing Parts Material Source
Standard MS0
Tests and Reports
Without CR0
Pressure test acc. to DIN CPD
Sensorhousing Material
Standard SMA
Configuration Type
Parameters set to factory defaults NC1
Parameters set customer specific NCC
Transmitter Software Function Package
Standard NFS
Enhanced diagnostics NFE
Batch Functionality NFB
Calibration Type
0,4% Factory Calibration RCD25)
0,3% Factory Calibration (Option) RCE26)
0,2% Factory Calibration (Option) RCB27)
Signal Cable
Without SC0
Device Identification Plate
Adhesive label TC
Stainless steel T1
Stainless steel and TAG plate (stainless steel) TS
Others TZ
Temperature Range of Installation /
Ambient Temperature Range
Standard design / -20 ... 60 °C (-4 ... 140 °F) TK127)
Standard design / -40 ... 60 °C (-40 ... 140 °F) TK427)
High temperature design /
-20 ... 60 °C (-4 ... 140 °F) TKH28)
High temperature design /
-40 ... 60 °C (-40 ... 140 °F) TKK28)

Continued on next page


78 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP631

ProcessMaster FEP631 7,8 … 88,89,90 91,92 93,94,95 96,97


Number of Testpoints
2 Points TV2
3 Points TV3
5 Points TV5
Verification Capability
disabled V0
enabled V1
Communication options activated
Ethernet IP GCE
Modbus TCP GCM
Webserver GCW
PROFINET GCP
Connector type
Without U0
1 × M 12 Plug for Ethernet 1 Port (4 signal leads) UE39)
2 × M 12 Plug for Ethernet 2 Port (4 signal leads) UF39)
1 × M 12 Plug for Ethernet 1 Port (8 signal leads) UG39)
1 × RJ45 connector with 5 m (15 ft) cable length fitted (4 signal leads) U539)
2 × RJ45 connector with 5 m (15 ft) cable length fitted (4 signal leads) UB39)
1 × RJ45 connector with 5 m (15 ft) cable lenth fitted (8 signal leads) UC39)
1 × RJ45 connector with 10 m (30 ft) cable length fitted (4 signal leads) U639)
2 × RJ45 connector with 10 m (30 ft) cable length fitted (4 signal leads) UD39)
1 × RJ45 connector with 10 m 30 ft cable lenth fitted (8 signal leads) UH39)
1 × RJ45 connector with 15 m (49 ft) cable length fitted (4 signal leads) U739)
2 × RJ45 connector with 15 m (49 ft) cable length fitted (4 signal leads) UJ39)
1 × RJ45 connector with 15 m 49 ft cable lenth fitted (8 signal leads) UK39)
1 × RJ45 connector with 2O m (66 ft) cable length fitted (4 signal leads) U839)
2 × RJ45 connector with 2O m (66 ft) cable length fitted (4 signal leads) UN39)
1 × RJ45 connector with 2O m (66 ft) cable length fitted (8 signal leads) UP39)
Fieldbus M12x1 (for Profibus PA) UR

Notes for ProcessMaster FEP631


1) Not available with Single Compartment Housing
2) For China production site only.
3) Not available with Div1 in conjunction with -40°C
4) Not available with Zone 1 / Div 1
5) Flange DN 15 … 600 based on ASME B16.5. Flange > DN 600 based on ASME 16.47 Serie B.
6) DN 25 ... DN 200 (1 ... 8 in.) Hard Rubber
6a) Available from DN25 ... 400 with Hardrubber or ETFE
6b) Upon Request
7) Available from DN 1000 (40 in.)
8) Available from DN25-1000. With Tungsten-Carbide electrode only
9) Available from DN25-1000
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 79

Notes for ProcessMaster FEP631


10) Available from DN3-200
11) Available from DN25
12) Available from DN50
13) Available from DN10-600
14) Available from DN25-300
15) Material: Refer to data sheet. Available with Design Level A
16) Available from DN10-400
17) TFE Electrode for detection of partial filling, available from DN 50 (2 in.)
18) Grounding electrodes, material same as measuring electrodes material
19) Grounding electrodes, material same as measuring electrodes material TFE Electrode for detection of partial filling, available from DN 50 (2 in.)
20) Available with sensor size <= DN 600 (24 in.) and PTFE / Thick-PTFE / ETFE / PFA liner material. For material, refer to data sheet
21) Current output (active or passive) can be configured on site
22) Will be specified by ABB
23) Available with 5points Calibration
24) Not available with size DN 3-8 and > DN900. 0,2% calibration assumes 3 calibration points. If more than 3 calibration points are required, specify 5
points under 'Number of test points'.
25) 2 points calibration is Standard. If more than 2 test points are required, please specify 3 or 5 points with option 'Number of Test points'. Accuracy = 0.4
% of rate with size > DN 3
26) 3 or 5 test points to be specified
27) Maximum fluid temperature with standard sensor design:
130 °C (266 °F) with PTFE, PFA, ETFE
80 °C (194 °F / 176 °F) with hard rubber
60 °C (140 °F) with soft rubber
28) Max. fluid temperature with high temperature sensor design:
180 °C (356 °F) with PFA, Thick PTFE.
130 °C (266 °F) with ETFE, PTFE liners.
Thick PTFE available for sensor size DN 25 ... DN 300. PFA available for sensor size DN 10 ... DN 200
29) Not available with calibration acc to ISO17025
30) Available from DN700 and up from China production site
31) Not available with Ex
32) Available up to DN300 (12”)
33) Available with Housing Type Code "D1" or "D2"
34) To be configured in conjunction with Option Card 1 = Mod bus RTU
35) To be configured in conjunction with Option Card 1 = Profibus DP
36) To be configured in conjunction with Option Card 1 = Ethernet IP or Modbus TCP
37) Available with single compartment housing only, Non Ex or Zone 2, Div. 2 only
38) Available with single compartment housing only and with 24 V power supply unit
39) Available with single compartment housing, Ethernet Card, Non-Ex or ATEX Zone 2
40) PROFINET in preparation
41) Available from 30" onwards
80 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
ProcessMaster FEP632
Electromagnetic Flowmeter system, remote mount design

ProcessMaster FEP632 7,8 9,10 11,12,13,14 ... 88,89


Explosion Protection Certification
Without, Flowmeter based on CE Standard Y0
Without, Flowmeter based on UKCA Standard Y1
ATEX / IECEx (Zone 1 / 21) A1
ATEX / IECEx (Zone 2 / 22) A2
cFMus Class 1 Div. 1 (Zone 1 / 21) F132)
cFMus Class 1 Div. 2 (Zone 2 / 22) F2
NEPSI (Zone 1) S1
NEPSI (Zone 2) S2
UKEX Zone 1 U1
UKEX Zone 2 U2
Housing Type / Housing Material / Thread for Cable Glands
Remote / Plastic / M20 x 1.5 P1
Remote / Plastic / NPT 1/2 in. P2
Remote / Aluminum / M20 x 1.5 A1
Remote / Aluminum / NPT 1/2 in. A2
Meter size
DN 3 (1/10 in.) 0003
DN 4 (5/32 in.) 0004
DN 6 (1/4 in.) 0006
DN 8 (5/16 in.) 0008
DN 10 (3/8 in.) 0010
DN 15 (1/2 in.) 0015
DN 20 (3/4 in.) 0020
DN 25 (1 in.) 0025
DN 32 (1-1/4 in.) 0032
DN 40 (1-1/2 in.) 0040
DN 50 (2 in.) 0050
DN 65 (2-1/2 in.) 0065
DN 80 (3 in.) 0080
DN 100 (4 in.) 0100
DN 125 (5 in.) 0125
DN 150 (6 in.) 0150
DN 200 (8 in.) 0200
DN 250 (10 in.) 0250
DN 300 (12 in.) 0300
DN 350 (14 in.) 0350
DN 400 (16 in.) 0400
DN 450 (18 in.) 0450
DN 500 (20 in.) 0500
DN 600 (24 in.) 0600
DN 700 (28 in.) 0700
DN 750 (30 in.) 0750
DN 800 (32 in.) 0800
DN 900 (36 in.) 0900
DN 1000 (40 in.) 1000
DN 1050 (42 in.) 1050
DN 1100 (44 in.) 1100

Continued on next page


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 81

ProcessMaster FEP632 7,8 ... 11,12,13,14 15,16 17,18 19 20 ... 88,89


Meter size (continuation)
DN 1200 (48 in.) 1200
DN 1350 (54 in.) – AWWA flange only 1350
DN 1400 (54 in.) 1400
DN 1500 (60 in.) 1500
DN 1600 (66 in.) 1600
DN 1650 (66 in.) – AWWA flange only 1650
DN 1800 (72 in.) 1800
DN 2000 (80 in.) 2000
Process Connection Type
Flanges DIN PN 6 D04)
Flanges DIN PN 10 D1
Flanges DIN PN 16 D2
Flanges DIN PN 25 D3
Flanges DIN PN 40 D4
Flanges DIN PN 63 D53)
Flanges DIN PN 100 D63)
Flanges ASME CL 150; B16.5 up to DN 600, B16.47 series B > DN 600 A12)
Flanges ASME CL 300; B16.5 up to DN 600, B16.47 series B > DN 600 A32)
Flanges ASME CL 600 RF A66a)
Flanges ASME CL 900 RF A76a)
Flanges ASME CL 1500 RF A86b)
Flanges ASME CL 2500 RF A96b)
Flanges ASME CL 600 RTJ H66b)
Flanges ASME CL 900 RTJ H76b)
Flanges ASME CL 1500 RTJ H86b)
Flanges ASME CL 2500 RTJ H96b)
Flanges JIS 5K J2
Flanges JIS 7,5K J02)
Flanges JIS 10K J1
Flanges JIS 20K J3
AS 4087 PN16 E12)
Flange, AS2129 table E E42)
Flange, AS2129 table E E52)
Flanges AWWA C207 Class B C134)
Flanges AWWA C207 Class C C234)
Flanges AWWA C207 Class E C334)
Liner Material
Hard rubber R28)
Soft rubber R49)
ETFE E16)
PTFE T110)
PFA P17)
Thick PTFE T211)
Ceramic-Carbide C15)
Linatex R61)
Others Z9
Process Connection Material
Carbon steel B
Stainless steel C12)
Others Z
Electrode Design
Standard 1
Pointed head 513)
Others 9
Continued on next page
82 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP632

ProcessMaster FEP632 7,8 … 21 22 23 24,25 26 27 28,29 30 … 88,89


Measuring Electrodes Material
Hast. C-4 (2.4610) D
Titanium F
Tantalum G
Hast. B-3 (2.4600) H
Platinum-Iridium J
Stainless steel 316Ti (1.4571) S
Double Layer W13)
Tungsten Carbide, coated T
Others Z
Grounding Electrode / Full Pipe Detection
No grounding electrode / No full pipe detection 0
No grounding electrode / With full pipe detection 114)
Grounding electrode / No full pipe detection 215)
Grounding electrode / With full pipe detection 316)
Others 9
Grounding Accessories
Without A
Grounding ring (1 off), mounted to flange B17)
Grounding ring (2 off), mounted to flange C17)
Others Z
Protection Class Transmitter / Protection Class Sensor
IP 67 / IP 67 70
IP 67 / IP 68 7618)
IP 67 / IP 68, signal cable fitted and potted 7719)
Power Supply
Without Y
Display
Without 0
Outputs
Without Y0
Design Level
Specified by ABB A20)

Continued on next page


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 83

ProcessMaster FEP632 7,8 … 31,32,33 34,35,36 37,38 39,40,41 42,43,44 45,46 47,48 49,50,51 52,53,54 55,56 57,58 ... 88,89
Option Card 1
Without DR0
Option Card 2
Without DS0
Usage Certifications
Without C0
Inspection certificate 3.1 acc. EN 10204 C2
Others CZ
Calibration Certifications
ABB Standard CMA
3rd party witnessed calibration CMW
5-point calibration acc. DAKKS CMD21)
Other Usage Certifications
Meter tube with PED certificate CRP
Meter tube without PED certificate
(For China and USA production site only) CRA1)
Power Supply Line Frequency
50 Hz F522)
60 Hz F623)
Sensor Length
ABB Standard J6
1,0 x DN length (from DN700 and up) JH30)
Potable Water and Food&Beverage Approvals
DVGW; KTW certified liner material CWL
Without CWY
Other Explosion Protection
Certifications and other Approvals
Russia metro+EAC ED1
Russia metro+EAC+EX ED2
Other Options
Without K0
With Gore-tex membrane KG
Documentation Language
German M1
English M5
Language package Western Europe / Scandinavia MW
Language package Eastern Europe ME
Others MZ

Continued on next page


84 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP632

ProcessMaster FEP632 7,8 … 59,60,61 62,63,64 65,66,67 68,69,70 71,72,73 74,75,76 77,78,79 ... 88,89
Pressure Bearing Parts Material Source
Standard MS0
Tests and Reports
Without CR0
Pressure test acc. to DIN CPD
Sensorhousing Material
Standard SMA
Configuration Type
Parameters set to factory defaults NC1
Parameters set customer specific NCC
Transmitter Software Function Package
Standard NFS
Enhanced diagnostics NFE
Batch Functionality NFB
Calibration Type
0,4% Factory Calibration 25) RCD
0,3% Factory Calibration (Option) 26) RCE
0,2% Factory Calibration (Option) 24) RCB
Signal Cable
Without SC0
5 m (approx. 15 ft) SC1
10 m (approx. 30 ft) SC2
15 m (approx. 49 ft) SC3
20 m (approx. 66 ft) SC4
25 m (approx. 82 ft) SC5
30 m (approx. 98 ft) SC6
35 m (approx. 115 ft) SC7
40 m (approx. 131 ft) SC8
50 m (approx. 164 ft) SCA
60 m (approx. 197 ft) SCB
70 m (approx. 230 ft) SCC
80 m (approx. 262 ft) SCD
100 m (approx. 328 ft) SCE
125 m (approx. 410 ft) SCF
150 m (approx. 492 ft) SCG
175 m (approx. 574 ft) SCH
200 m (approx. 656 ft) SCJ

Continued on next page


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 85

ProcessMaster FEP632 7,8 ... 80,81 82,83,84 85,86,87 88,89


Device Identification Plate
Adhesive label TC
Stainless steel T1
Stainless steel and TAG plate (stainless steel) TS
Others TZ
Temperature Range of Installation / Ambient Temperature Range
Standard design / -20 ... 60 °C (-4 ... 140 °F) 27) TK1
Standard design / -40 ... 60 °C (-40 ... 140 °F) 27) TK4
High temperature design / -20 ... 60 °C (-4 ... 140 °F) 28) TKH
High temperature design / -40 ... 60 °C (-40 ... 140 °F) 28) TKK
Number of Testpoints
2 Points 29) TV2
3 Points 29) TV3
5 Points TV5
Verification Capability
disabled V0
enabled V1

Notes for ProcessMaster FEP632


1) For China production site only.
2) Flange DN 15 … 600 based on ASME B16.5. Flange > DN 600 based on ASME 16.47 Serie B.
3) DN 25 ... DN 200 (1 ... 8 in.) Hard Rubber
4) Available from DN 1000 (40 in.)
5) Available from DN25-1000. With Tungsten-Carbide electrode only
6) Available from DN25-1000
6a) Available from DN25-400 with Hardrubber or ETFE
6b) Upon Request
7) Available from DN3-200
8) Available from DN25
9) Available from DN50
10) Available from DN10-600
11) Available from DN25-300
12) Material: Refer to data sheet. Available with Design Level A
13) Available from DN10-400
14) TFE Electrode for detection of partial filling, available from DN 50 (2 in.)
15) Grounding electrodes, material same as measuring electrodes material
16) Grounding electrodes, material same as measuring electrodes material TFE Electrode for detection of partial filling, available from DN 50 (2 in.)
17) Available with sensor size <= DN 600 (24 in.) and PTFE / Thick-PTFE / ETFE / PFA liner material. For material, refer to data sheet
18) Only available with remote transmitter, sealing compound (optional) D141B038U01
19) Only available with remote transmitter
20) Will be specified by ABB
21) Available with 5 points Calibration
22) 50 Hz (to be specified in case no Tx is ordered)
23) 60 Hz (to be specified in case no Tx is ordered)
86 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… ProcessMaster FEP632
Notes for ProcessMaster FEP632
24) Not available with size DN 3-8 and > DN800. 0,2% calibration assumes 3 calibration points. If more than 3 calibration points are required, specify 5
points under 'Number of test points'.
25) 2 points calibration is Standard. If more than 2 testpoints are required, please specify 3 or 5 points with option 'Number of Testpoints'. Accuracy =
0.4 % of rate with size > DN 3
26) 3 or 5 testpoints to be specified
27) Max. fluid temperature with standard sensor design:
130 °C (266 °F) with PTFE, PFA, ETFE
80 °C (194 °F / 176 °F) with hard rubber
60 °C (140 °F) with soft rubber
28) Max. fluid temperature with high temperature sensor design:
180 °C (356 °F) with PFA, Thick PTFE. Thick PTFE available for sensor size DN 25 ... DN 300. PFA available for sensor size DN 10 ... DN 200
130 °C (266 °F) with ETFE, PTFE liners.
29) Not available with calibration acc to ISO17025
30) Available from DN700 and up from China production site
31) Not available with Ex
32) Available up to DN300 (12”)
33) Not available with EX Zone 1, Div 1
34) Available from 30" onwards
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 87

Remote transmitter FET632


FET632 Electromagnetic Flowmeter, remote transmitter for ProcessMaster FEP630

Remote transmitter FET632 7,8 9,10 11,12 13 14 15,16 17,18,19 ... 51,52
Explosion Protection Certification
Without, Flowmeter based on CE Standard Y0
Without, Flowmeter based on UKCA Standard Y1
ATEX / IECEx (Zone 1 / 21) A1
ATEX / IECEx (Zone 2 / 22) A2
cFMus Class 1 Div. 1 (Zone 1 / 21) F1
cFMus Class 1 Div. 2 (Zone 2 / 22) F2
NEPSI (Zone 1) S1
NEPSI (Zone 2) S2
UKEX Zone 1 U1
UKEX Zone 2 U2
Housing Type / Housing Material / Thread for Cable Glands
Field-mount / Single compartment / Aluminum / 4 x M20 x 1.5 F13)
Field-mount / Single compartment / Aluminum / 4 x NPT 1/2 in. F23)
Wall-mount / Dual compartment / Aluminum / M20 x 1.5 W13a)
Wall-mount / Dual compartment / Aluminum / NPT 1/2 in. W23a)
Protection Class Transmitter / Protection Class Sensor
IP 67 / IP 67 70
Power Supply
100 ... 230 V AC, 50 Hz A
24 V DC, 50 Hz D
100 ... 230 V AC, 60 Hz C
24 V DC, 60 Hz E
Display
Without 0
Display with Keypad 2
Outputs
1 Current output (active or passive). 2 Digital Outputs (passive). HART G04)
Current output 1 (active or passive), digital output 1 & 2 (passive). HART. MODBUS RTU M17)
Current output 1 (active or passive). digital output 1 & 2 (passive). HART. PROFIBUS DP D18)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART. 1 port Ethernet E29)
Current output 1 (active or passive), digital output 1 & 2 (passive). HART, 2 port Ethernet E39)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART. 1 port Ethernet + POE E49)
Current output 1 (active or passive), digital output 1 & 2 (passive), HART, PROFIBUS PA P1
Option Card 1
Without DR0
1 x Digital Input DRN
1 x Digital Output DRG
24 V DC transmitter loop power supply DRT
1 x Analog Output passive (4…20mA) DRA
Modbus RTU DRM
PROFIBUS DP DRD
Card for Ethernet IP, Modbus TCP, PROFINET DR610)

Continued on next page


88 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
… Remote transmitter FET632

Remote transmitter FET632 7,8 ... 20,21,22 23,24 25,26,27 28,29,30 31,32,33 34,35 36,37 38,39 40,41,42 43,44 45,46,47 … 51,52
Option Card 2
Without DS0
1 x Analog Output passive (4…20mA) DSA
1 x Digital Input DSN
1 x Digital Output DSG
Module Power over Ethernet/ Modbus TCP DS811)
(for Single Comp Hsg)
SIL Certificate
SIL Certificate CS
Shipping Register Certificate
Marine approval (DNV) CL5
Potable Water and Food & Beverage Approvals
Without CWY
Other Explosion Protection Certifications and other Approvals
Russia metro+EAC ED1
Russia metro+EAC+EX ED2
Other Options
Without K0
With Gore-tex membrane KG
Documentation Language
German M1
English M5
Language package Western Europe / MW
Scandinavia
Language package Eastern Europe ME
Device Identification Plate
Adhesive label TC
Stainless steel T1
Stainless steel and TAG plate (stainless steel) TS
Others TZ
Temperature Range of Installation / Ambient Temperature Range
Standard design / -20 ... 60 °C (-4 ... 140 °F) TK1
Standard design / -40 ... 60 °C (-40 ... 140 °F) TK4
Remote Transmitter Mounting Kit
Without B0
2" Pipe Mounting Kit for Wall-mount / Dual compartment Housing B1
2" Pipe Mounting Kit for Field-mount / Single compartment Housing B2
Transmitter Software Function Package
Standard NFS

Continued on next page


PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 89

Remote transmitter FET632 7,8 ... 48,49,50 51,52


Communication options activated
Ethernet IP GCE
Modbus TCP GCM
Webserver GCW
PROFINET GCP13)
Connector type
Without U0
1 × M 12 Plug for Ethernet 1 Port (4 signal leads) UE12)
2 × M 12 Plug for Ethernet 2 Port (4 signal leads) UF12)
1 × M 12 Plug for Ethernet 1 Port (8 signal leads) UG12)
1 × RJ45 connector with 5 m (15 ft) cable length fitted (4 signal leads) U512)
2 × RJ45 connector with 5 m (15 ft) cable length fitted (4 signal leads) UB12)
1 × RJ45 connector with 5 m (15 ft) cable lenth fitted (8 signal leads) UC12)
1 × RJ45 connector with 10 m (30 ft) cable length fitted (4 signal leads) U612)
2 × RJ45 connector with 10 m (30 ft) cable length fitted (4 signal leads) UD12)
1 × RJ45 connector with 10 m 30 ft cable lenth fitted (8 signal leads) UH12)
1 × RJ45 connector with 15 m (49 ft) cable length fitted (4 signal leads) U712)
2 × RJ45 connector with 15 m (49 ft) cable length fitted (4 signal leads) UJ12)
1 × RJ45 connector with 15 m 49 ft cable lenth fitted (8 signal leads) UK12)
1 × RJ45 connector with 2O m (66 ft) cable length fitted (4 signal leads) U812)
2 × RJ45 connector with 2O m (66 ft) cable length fitted (4 signal leads) UN12)
1 × RJ45 connector with 2O m (66 ft) cable length fitted (8 signal leads) UP12)
Fieldbus M12x1 (for Profibus PA) UR

Notes for Remote transmitter FET632


1) Not available with Single Compartment Housing 9) To be configured in conjuction with Option Card 1 = Ethernet IP or
2) Not available with -40°C. Not available with Single Compartment Modbus TCP
Housing 10) Available with single compartment housing only, Non Ex or Zone 2, Div.
3) Not available with Zone 1 / Div. 1 2 only
3a) Not available with Zone 2 / Div. 2 11) Available with single compartment housing only and with 24 V power
4) Current output (active or passive) can be configured on site supply unit
5) Not available with Ex 12) Available with single compartment housing, Ethernet Card, Non-Ex or
6) Available with housing Type Code 'W1' or 'W2' ATEX Zone 2
7) To be configured in conIunction with Option Card 1 = Modbus RTU 13) PROFINET in preparation
8) To be configured in conjunction with Option Card 1 = Profibus DP
90 PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I


… Ordering Information
Accessories

Description Order code


Infrared service port adapter FZA100 FZA100

Installation set for NPT 1/2" cable gland 3KXF081300L0001


For sealing the cable conduit during outdoor installation

Adapter M20x1.5 to 1/2"NPT D365B269U01

Data link cable 3KXS360040L0003*

Signal cable
5 m (approx. 15 ft) 3KQZ407123U0500
10 m (approx. 30 ft) 3KQZ407123U1000
15 m (approx. 49 ft) 3KQZ407123U1500
20 m (approx. 66 ft) 3KQZ407123U2000
25 m (approx. 82 ft) 3KQZ407123U2500
30 m (approx. 98 ft) 3KQZ407123U3000
35 m (approx. 115 ft) 3KQZ407123U3500
40 m (approx. 131 ft) 3KQZ407123U4000
50 m (approx. 164 ft) 3KQZ407123U5000
80 m (approx. 262 ft) 3KQZ407123U8000
100 m (approx. 328 ft) 3KQZ407123U1H00
150 m (approx. 492 ft) 3KQZ407123U1F00
200 m (approx. 656 ft) 3KQZ407123U2H00
ABB Ability Verification Tool SRV500*
* Available from ABB Service
"Torque information" in the operating instruction
Parameter description in the operating instruction
PROCESSMASTER FEP630 ELECTROMAGNETIC FLOWMETER | DS/FEP630-EN REV. I 91


Trademarks
FOUNDATION Fieldbus is a registered trademark of FieldComm Group,
Austin, Texas, USA.
HART is a registered trademark of FieldComm Group, Austin, Texas, USA
PROFIBUS and PROFIBUS PA are registered trademarks of PROFIBUS &
PROFINET International (PI)
PROFINET are registered trademarks of PROFIBUS & PROFINET
International (PI)
LINATEX is a registered trademark of Linatex Ltd.
Hastelloy C is a trademark of Haynes International

Sales Service

ABB Measurement & Analytics

For your local ABB contact, visit:


www.abb.com/contacts

For more product information, visit:


www.abb.com/flow


DS/FEP630-EN Rev. I 10.2023

We reserve the right to make technical changes or modify the contents of this document without
prior notice. With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors or possible lack of
information in this document.

We reserve all rights in this document and in the subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or utilization of its contents – in whole or in parts – is
forbidden without prior written consent of ABB.

© ABB 2023 3KXF231601R1001