HVAC Clearance Distances Spacing Rules Between Air Conditioning & Heating System Components and Other Building Features or Mechanicals
HVAC Clearance Distances Spacing Rules Between Air Conditioning & Heating System Components and Other Building Features or Mechanicals
No ChatBot Pledge: The accuracy & trustworthiness of every InspectApedia article or Q&A is researched by human
InspectAPedia
experts.
ASSESSMENT ELECTRICAL ENERGY SAVINGS ENVIRONMENT EXTERIORS FORENSICS HEATING HOME INSPECTION INDOOR AIR IAQ INSULATION INTERIORS
MOLD CONTAMINATION NOISE ODORS PLUMBING ROOFING SEPTIC SYSTEMS SOLAR ENERGY STRUCTURE VENTILATION WATER SUPPLY EXPERTS DIRECTORY ESTIMATING
SPREADSHEET CONTACT US
InspectAPedia tolerates no conflicts of interest. We have no relationship with advertisers, products, or services discussed at this website.
This article describes the recommended minimum (and maximum) distances to separate HVAC components from other building features, such as
the distance required between an air conditioner or heat pump outdoor compressor/condenser or from a heating boiler or furnace to building
walls, wiring, piping, other equipment, fences, shrubs, etc. In our photo at page top these two compressor/condenser units are too close together
as well as too close to the building walls.
We also provide an ARTICLE INDEX for this topic, or you can try the page top or bottom SEARCH BOX as a quick way to find information you
need.
Air Conditioning & Heat Pump Equipment: Minimum Clearance Distances from Building
Walls, Shrubs, Other Equipment
Blocking air flow through the outdoor A/C or heat pump compressor/condenser unit is a really bad idea that
shortens equipment life (as the equipment runs hotter) and increases system operating costs (for the same reason
- hotter operating temperature means lower efficiency during the cooling season).
Air conditioning or heat pump compressor/condenser units mounted too close to a wall, surrounded by shrubs, or
:
multiple units located too closely together will probably not receive enough cool air flow to function properly.
Learn more
And even worse, compressor/condenser units that are too close together not only have to fight for their incoming cooling air, but they may feed
hot exhaust air to one another, increasing their operating temperatures still further.
The final authority on proper HVAC equipment clearance distances is the manufacturer's installation instruction manual. But here are some
general rules of thumb for air conditioner or heat pump clearances that we will cite here.
In our photo at left, the A/C compressor units are too close together and also suffer from airflow blocked by shrubbery.
This collection of air conditioning compressors are too many, too close together - they will be fighting for cooling air around the condenser unit,
increasing operating cost and shortening air conditioner compressor life
A rule of thumb is to maintain at least two-feet (24") between the A./C compressor/condenser unit and any nearby obstruction such as a building
wall, shrub, or fence.
If there are multiple air conditioner or heat pumps installed in the same area, and following the sense of the rule above, I'd keep the units at least
4 ft. apart from one another as well.
:
Freestyle Fun, Games
and Toys
Join us for Freestyle Festival at BOUNCE -
mini-games, prizes & toys your kids will love!
Book Now
In our photo (above) from a home in New York, the compressor/condenser unit is actually leaning against the house wall (its support pad tipped).
About 1/3 of the air flow from this unit is completely blocked by the building wall.
At least the wall kept the unit from tipping over, though.
But, of course, the final authority is the equipment manufacturer. Here is an adapted (reformatted) quote of clearance requirements from a Carrier
24ANA Infinity Series Air Conditioner of 2-5 nominal ton size A/C equipment installation manual and the Lennox Elite® Series XC13 condensing
units and other condenser installation instruction documents that you can read in PDF form atReferences or Citations .
When installing, allow sufficient space for airflow clearance, wiring, refrigerant piping, and service.
A widely-quoted opinion is a typical minimum working distance to the controls is 36" (or 30" in the UMC) on the unit's side where controls
and fittings are located.
Clearance to the service side or end of the compressor / condenser unit
Lennox Elite® IOM (2017) requires 30" service clearance on one of the unit sides adjacent to the control box.
Clearance space above an air conditioner compressor/condenser unit
Some installation instructions for split system compressor/condenser units specify 60" (150cm) above and 24" (40cm) the unit around the
coil on 3 sides for air intake. Clearance between the unit and the structure (presumably a wall) can be 12".
See details
For proper airflow, a 6-in. (152.4 mm) clearance on 1 side of unit and 12 in. (304.8 mm) on all remaining sides must be maintained.
Lennox Elite® IOM (2017) requires 36" (91.4 cm) clearance on one of the unit's other three sides (after excluding the side closest to the
control box)
:
and permits 12" (30.5cm) on one of the remaining two sides
Whirlpool's condenser installation instructions require 24" on the service side, 12" clearance to the building, and 12" clearance on the air
inlet sides of their unit.
Clearance space to the structure, wall, or fence
Allow at least 12" distance to a wall or fence or similar solid obstruction - typical of most installation instructions.
Some instructions permit reduced clearance to a single object with a small surface area such as the end of a wall, an outside corner, a
fence section, or a post. Eg. a 4" fence post could be 4" from the wall-side of the compressor/condenser unit.
See discussion
Large overhanging soffits may cause air recirculation in a corner area even though recommended clearances
are maintained.
As a guide locate the unit far enough out so that half of the discharge grille is out from under the soffit. [Excerpt from a split system
condenser installation instruction page. - Ed.]
Clearance distance between adjacent air conditioner or heat pump compressor/condenser units
Some of the installation/operation manuals provided atReferences or Citations permit a reduced 20" clearance between adjacent units.
Clearance distances for the compressor/condenser from water, ice, snow
Position so water, snow, or ice from roof or eaves cannot fall directly on unit.
Rooftop clearance distances for A/C or heat pump compressor/condenser units
On rooftop applications, locate unit at least 6 in. (152.4 mm) above roof surface. [1]
A/C Compressor / Condenser distance to windows, doors, patios, occupied spaces
See A/C CLEARANCE DISTANCE TO OTHER MECHANICAL EQUIPMENT such as a direct vent heater or gas fireplace outlet or
combustion air intakes
AC Clearance Distance to Property Lines
Varies by local jurisdiction and codes, typically 3ft to 10ft or more. For example, where a local noise ordinance is also enforced, greater
distances to the property line may be required depending on the noise level of the equipment.
Property line distances may also vary by placement of the AC compressor/condenser unit on different sides of the building with respect to
the building's front entrance.
Please contact your dealer to schedule proper inspection and maintenance for your equipment.
Cleaning of the outdoor unit’s coil should be performed by a trained service technician.
Contact your dealer and set up a schedule (preferably twice a year, but at least once a year) to inspect and service your outdoor unit.
:
Make sure no obstructions restrict airflow to the outdoor unit.
Grass clippings, leaves, or shrubs crowding the unit can cause the unit to work harder and use more energy.
Keep shrubbery trimmed away from the unit and periodically check for debris which collects around the unit
- Lennox Corporation, "Installation Instructions, Elite® Series XC13 Units, Condensing Units 506635-01" (09/2011), retrieved 12/2/2014,
original source: https://www.lennox.com/pdfs/installation_maintenance /Lennox_XC13_IOM.pdf
International Residential Code IRC Model Code on Appliance Access Clearance Distance
Appliances shall be accessible for inspection, service, repair and replacement without removing permanent construction, other appliances, or any
other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced.
(762 mm by 762 mm) shall be provided in front of the control side to service an appliance. Installation of room heaters shall be permitted with at
least an 18-inch (457 mm) working space. A platform shall not be required for room heaters.
National Electrical Code (NEC) Model Code on Electrical Equipment Clearance Distances
I. General
110.1 Scope.
This article covers general requirements for the examination and approval, installation and use, access to and spaces about electrical conductors
and equipment; enclosures intended for personnel entry; and tunnel installations.
Sufficient access and working space shall be provided and maintained about all electrical equipment to permit ready and safe operation and
maintenance of such equipment.
Working space for equipment operating at 600 volts, nominal, or less to ground and likely to require examination, adjustment, servicing, or
maintenance while energized shall comply with the dimensions of 110.26(A)(1), (A)(2), and (A)(3) or as required or permitted elsewhere in this
Code.
:
(1) Depth of Working Space.
The depth of the working space in the direction of live parts shall not be less than that specified in Table 110.26(A)(1) unless the requirements of
110.26(A)(1)(a), (A)(1)(b), or(A)(1)(c) are met.
Distances shall be measured from the exposed live parts or from the enclosure or opening if the live parts are enclosed.
Table 110.26(A)
(1) Working Spaces specifies the minimum clearance in front of the equipment to be 36 inches, and the clearance goes up for some conditions
where the voltage to ground is 151-600 volts to ground (not seen in the typical residence).
Equipment. A general term, including material, fittings, devices, appliances, luminaires, apparatus, machinery, and the like used as a part of, or in
connection with, an electrical installation.
Really? Legal experts, whose opinions we've come across online, claim that HVAC equipment will be turned "off" prior to servicing, so the NEC's
equipment clearance distances that apply to "energized equipment" would not apply to an air conditioner or heat pump compressor/condenser
unit.
This is not quite correct. For example, during charging and during some equipment tests, the HVAC equipment, such as the
compressor/condenser, will indeed be powered on and actually running while test leads, temperature monitors, or a pressure gauge set will be
attached to or used on the equipment.
Air Conditioner / Heat Pump Compressor Unit Clearance Distances to Building Windows
& Doors
Question: aircon unit on our verandah blows into our door and kills our plants and makes the space not-usable
Can someone please help? The area below in the picture is the only entrance doors into the
rental units, a aircon unit has been placed in our outdoor verandah area authorized by Prd
Real estate Kyogle.
The hot air from the exhaust fan is not only killing the pot plants, it blows really hot air straight
through my front door heating my unit and it is noisy.
We cannot sit out on the verandah anymore as it way to hot and it is advertised by the
realestate as a outdoor alfressco shared space!
Surely the placement of this is against the law, could someone with knowledge of this problem please help. - Stuart Such 2020/12/19
Moderator reply:
Stuart:
Unfortunately, the typical codes and standards for installation of air conditioners and heat pumps, like the split system ducted or ductless systems
in your photograph, describe the minimum clearance or working distances necessary for proper installation and maintenance of the equipment,
and do not describe the clearance distances recommended to avoid noise or draft or nuisance complaints such as the issue you raise.
You'll see in the article above that a general rule of thumb for such equipment is a 24" or two foot clearance to obstructions, walls, etc.
It is possible, though I can't be sure from your photos, that the Kaden split system unit in your photos is not properly installed in that it may not
have the clearance distances specified by the manufacturer.
In particular it looks to me as if the units are installed rather close to the building walls. Insufficient clearance to the walls behind each unit means
increased operating cost, lower efficiency, and shorter equipment life. But I acknowledge that's not the concern that you raised.
:
Typical HVAC compressor/condenser unit manufacturers and installers discussion of
clearance distances of the equipment to a nearby window or door state that those distances
don't create working or maintenance issues for the equipment itself, but might state:
"It’s fine, as long as the exhaust air, being vented out by the outdoor unit, does not enter the
room. Long continuous hours of operation can cause the exhaust air to affect the indoor
temperature of the room." [- source kandsac.com/spacing-rules-to-follow-when-installing-an-
ac-outdoor-unit-air-conditioner-installation-in-irving-tx/ ]
They are not addressing noise and comfort nor usability concerns for the space immediately
around the outdoor unit.
When the outdoor compressor condenser unit is installed in an occupied space like a patio or
deck, an experienced installer with an ounce of sense would not place the unit where it makes
the space no longer usable - not, at least, without a careful discussion with the building owners, as otherwise the installer can expect a deluge of
complaints and unhappy customers.
The installer may also have read in the installation instructions these points that do offer, among the comments in step 1, that the installation
location should not annoy neighbours.
If your units are the Kaden Kd-24, then the clearance distance MINIMUMS are given in the sketch here, taken from the
Remarkably it seems almost impossible to contact he company directly with technical questions - their website www.kadenair.com.au does not
provide a CONTACT link that I could find. Instead they want to refer you to their local installers.
Step 1: Select installation location [for the Kaden KD24 AC Outdoor Unit]
The unit should be installed in a location that meets the following requirements:
✓ The air inlet and outlet must not be obstructed or exposed to strong wind.
✓ Ensure the location of the unit will not be subject to snowdrifts, accumulation of leaves or other seasonal debris. If possible, provide an awning
for the unit. Ensure the awning does not obstruct airflow.
✓ There must be enough room to install the connecting pipes and cables and to access them for maintenance.
✓ The pipe length between the outdoor and indoor unit may not exceed the maximum allowable pipe length.
✓ If possible, make sure the unit is located far away from your neighbours’ property so that the noise from the unit will not disturb
them.
✓ If the location is exposed to strong winds (for example: near a seaside), the unit must be placed against the wall to shelter it from the wind. If
necessary, use an awning.
✓ Install the indoor and outdoor units, cables and wires at least 1 meter from televisions or radios to prevent static or image distortion. Depending
on the radio waves, a 1 metre distance may not be enough to eliminate all interference.
Are there any clearance requirements for condensing units and entrances?
Reply:
:
Chuck,
You mean beyond what's in the article above and specific to building entries?
I haven't seen that explicit spec. beyond what's mentioned in the article above or a generic 3-foot rule to give good air circulation. Perhaps in the
unit's installation guide you'll see some schematic on clearances that's different. Is this a noise complaint or an air flow concern?
In my opinion and probably the opinion of your local fire or building code compliance officials, the compressor/condenser should not be located
where it forms an obstruction or hazard around building entrances.
Since an exit stair or door wants at least a 3-foot landing or clearance in the direction of travel it seems to me that'd be a bare minimum and 48"
or more makes more sense; imagine trying to bring a couch into a building having to lift it over the AC unit.
Clearance space above an air conditioner compressor/condenser unit Allow at least 48 in. (1219.2mm) above the compressor/condenser unit.
My question: what about the distance from the wall stretching out above the unit and to the sides? Any recommendation on the length? My e-mail
is [email protected]
Reply:
If you're talking about privacy walls or screens at patios or decks, say at a condo, the A/C compressor condenser side-clearance distances
specified by the manufacturer (and cited above) need to be respected.
On 2020-06-29 - by (mod) - rule prohibiting me from placing the condenser unit under the window
Mike,
Your condenser location 3 ft out from the wall and presumably not blocked for working space nor air movement can be acceptable, for condenser
unit operation and maintenance,
but in my opinion, if the unit is right below an operable window you won't like the noise nor the blast of hot air out of the condenser unit top,
especially if the window is open.
Also, we don't have the option of an air nor noise barrier roof unless we can give at least 48" free space above the top of the condenser.
On 2020-06-29 by Mike
Hi,
Great article. I need to relocate my AC condenser unit. The location I'm thinking of is right outside of the furnace. However, the side of the house
is several windows. Is there any rule prohibiting me from placing the condenser unit under the window, even if I can make it 3 ft from the wall?
Thanks!
Can a condenser for a 12000 BTU ductless mini split system be installed adjacent to a double-hung window? I am building a new ADU in
Inglewood California and want to make sure there isn't some minimum distance required between the condensor and window.
What’s the AC condenser Unit Clearance space to the property line? - Eric, 2022/04/24
Moderator reply: less than 3' to 10' to 22', depending on where you live, local codes, equipment noise, other factors
Bottom line: Required distance from A/C condenser unit to property line is typically 3' to 10' depending on where you live, and is not specified at
all in some jurisdictions. The clearance distance should also respect all of the working distances and clearances given in the rest of this article.
Code Citations for A/C or Heat Pump Compressor/Condenser Distance to Property Lines
In neither the mechanical codes nor installation instructions, do we find a code-specified distance between the A/C condenser unit and the
nearest property line per-se.
:
That is, ... as my buddy Mark Cramer says, ... it depends. I'm wary of answering a trick question when we don't have enough information. Below
are some examples:
If at the property line there is a solid obstruction such as a building wall or an enclosing fence, like a stockade fence, then the condenser unit
needs to meet the clearance distances above that are given from solid obstructions that could prevent either working space or air space.
If at or near the property line there is another building with air intakes such a window or air exhaust such as a dryer exhaust vent, then, similarly,
the AC condenser unit would need to respect those clearance distances.
If the condenser unit produces condensate discharge, that discharge, in many jurisdictions, can not be sent across a public walkway where it may
cause a nuisance or fall hazard.
Noise nuisance restrictions may increase A/C Compressor or Fan Distance to Property Line
In some jurisdictions, the required air conditioner or heat pump compressor/condenser distance to property line depends on the noise rating, in
decibels, of the equipment. For example, in Los Altos, California, if your condenser unit has a sound rating, measured at the equipment, of 74db it
must be located no less than 22 ft. from the nearest property line.
That noise rating over-rides Los Altos' minimum distance of 5 ft. between property line and the compressor/condenser unit.
So your best bet is to review the known condenser unit clearances given above on this page and then to see if any of those pertain to your
installation, including the property line.
In addition, depending on the country and city where your AC condenser unit is being installed, there may be local regulations specifying a
required distance between the A/C condenser and neighbours.
Codes for A/C Heat Pump Compressor/Condenser Unit Clearance Distance to Property Lines
Distance to
Equipment Location Property
Line
Prohibited in many
Front yard
jurisdictions
General clearance 2 ft
64 6 ft
66 8 ft
68 11 ft
70 14 ft
72 18 ft
74 22 ft
:
Notes to the tables above
1. ANSI/AHRI Standard 275 – 2010, Air Conditioning, Heating and Refrigeration Institute, www.ahrinet.org
2. Los Altos, CA, AIR HANDLING EQUIPMENT/AIR CONDITIONING UNIT SETBACK GUIDELINES [PDF] , City of Los Altos, CA, - retrieved
2022/04/24, original source: https://www.losaltosca.gov/
Excerpts: Air handling equipment, including air conditioning equipment must be located to comply with the City’s Noise Control Ordinance
(Municipal Code Chapter 6.16).
The Planning Division has estimated the following setback guidelines for locating air handling equipment, including air conditioning
equipment in order to meet the Noise Control Ordinance limit of 50 dBA at the property line for most residentially zoned properties. In
addition, if the unit is visible from the street, appropriate screening should be provided.
Regardless of where the air handling unit is located, the provisions of the Noise Control Ordinance (Chapter 6.16) shall apply, and it is the
responsibility of the property owner to mitigate any violations. If baffling and/or repairs do not achieve compliance, it may be necessary to
either relocate or replace the unit.
3. New York City, MECHANICAL CODE, Section MC 301, GENERAL REGULATIONS [PDF] (2014) - retrieved 2022/04/24 original source:
https://www1.nyc.gov/
4. New York State Mechanical Code (2020) retrieved 2022/04/24 original source: https://dos.ny.gov/system/files/documents/2020/09/2020-
mcnys-november-2019.pdf
5. San Mateo, CA, AIR CONDITIONING GUIDE for Residential 1 and 2 Dwelling Units [PDF] (2019), City of San Mateo Building Division, 330
W 20th Ave. , San Mateo, CA 94403 USA Tel: 650-522-7172 Web: www.cityofsanmateo.org - retrieved 2022/04/24 original source:
www.cityofsanmateo.org/DocumentCenter/View/78588/Air-Conditioning-Guide-for-Residential-1-and-2-Dwelling-Units
Excerpt: When the AC condenser installed in a side yard location, it must allow for a clear 3-foot path of travel (between condenser and
property line). -
6. Toronto Ontario, Reduced Side Yard Setback" in residential zones, mounted on the ground. Toronto zoning by-law no. 569-2013, Section
10.5.60.20(10)pursuant to section 34 of the Ontario Planning Act. (2013)
Excerpt:
In the Residential Zone category, for a heating or air-conditioning device that is mounted on the ground may be in a side yard, if it is no
closer to the side lot line than the lesser of 0.9 meters or the minimum side yard setback for the residential building on the lot.
See p. 28, "Determining distance to the property boundary" - factors in sound level in dB, reflection factor and barrier factor.
9. Australia, NSW, Air Conditioning Noise, New South Wales Housing Code, retrieved 2022/04/24 original source:
http://www.jaicrest.com.au/tipsandhints/airconditioning-noise
Excerpt:
Air-conditioning units - residential You don’t need permission from council to install an air-conditioning unit for your home if:
Where the unit is wall mounted, it is not higher than 1.8m above ground level
If your property is a listed heritage item or draft heritage item the unit is to be ground mounted only and cannot be wall mounted
If your property is located within a heritage conservation area or draft heritage conservation area the unit must be in the back yard
...
An offence occurs if the noise continues after a warning has been given by a council or police officer. - retrieved 2/22/04/24 original source:
https://www.environment.nsw.gov.au/questions/noise-from-neighbours-air-conditioner
10. Australia NATIONAL CONSTRUCTION CODE NCC Volume II, AIR CONDITIONING ENCROACHMENT ZONES [PDF] retrieved
2022/04/24 original source: https://ncc.abcb.gov.au/news/2020/allowable-encroachments-how-close-too-close
Zone 1 (3.7.2.7(c)): within 900 mm of the boundary, or 1.8 m of a non-associated building, with only listed encroachments permitted in this
zone.
Zone 2 (3.7.2.7(d)), up to, but not closer than, 450 mm from the boundary, or 900 mm from a non-associated building, with listed
encroachments permitted in this zone.
11. New Zealand, HEAT PUMPS and NEIGHBOURLY INSTALLATION [PDF] - retrived 2022/04/24 original source:
https://www.aucklandcouncil.govt.nz/ building-and-consents /building-renovation-projects/ heat-your-home/Heat pump noise/heat-pumps-
and-neighbourly-installation.pdf
Excerpts:
Noise problems Care must be taken to locate the heat pump so that the noise produced during its operation does not interfere with sensitive
areas – either in the house being heated, or the neighbour’s house. Most noise problems occur between mid-evening and sunrise when
ambient sound levels in the neighbourhood are lower because of cessation of outdoor activity and less traffic sounds. Tonal type sounds are
common from rotating parts in units such as fans and motors and can greatly increase if there is no preventative maintenance to replace
worn bearings or limited-life parts before they fail. Loose screws in a metal casing are a common source of buzzing or rattling noises.
In urban neighbourhoods there is usually insufficient space between residences for exterior heat pump units to be installed without causing
noise problems for the occupants or the neighbours.
Noise is directly propagated to a neighbour’s house wall or indirectly from reflection off the wall of the house being heated, or a combination
of both. Higher frequency sounds are readily attenuated by structure, but lower frequency sounds penetrate structure unless attenuated at
source.
12. Singapore, BE GOOD NEIGHBOURS, A home owner’s guide on good practices to follow when carrying out building works in landed
housing estates, [PDF] (2016) singapore URA, Urban Redevelopment Authority, Building & Construction Authority, 52 Jurong Gateway
Road [Map] #11-01, Singapore 608550 (Above JEM) - BCA Hotline: 1800-3425-222 (1800-DIAL-BCA), (+65) 6534 0219 (for Overseas Call)
- retrieved 2022/04/24 original source: https://www.bca.gov.sg/publications/others/begoodneighbours_July2016.pdf
Excerpt:
Some air-con (AC) condensers generate large amounts of heat and noise, potentially causing nuisance to the neighbours. Air-con
condensers should be located on a roof (ie. attic or flat roof) with proper screening.
Diagram IIc.i illustrated where air-con condensers can be located. Approved air-con ledges should not be converted to any other uses
without planning permission from the URA.
13. Ameristar Heating & Cooling, "INSTALLATION INSTRUCTIONS, 13 SEER Split System Air Conditioner 1.5-5 Tons R410A" [PDF] Ingersoll
Rand (2017), retrieved 2017/07/09., original source: https://d3ciwvs59ifrt8.cloudfront.net/cc0e11ea-02d9-4181-b52b-
d32e607b76de/4f6a2bfd-3d88-45dc-9a47-801c0625c6fb.pdf
14. Lennox Corporation, "ELITE® Series R-410A AIR CONDITIONERS INSTALLATION & OPERATION MANUAL" [PDF] (2017), retrieved
2017/07/09,original source: https://www.lennoxpros.com/docs/Technical/210758.pdf
15. Lennox Corporation, "INSTALLATION INSTRUCTIONS, Elite® Series XC13 Units, Condensing Units 506635-01" [PDF] (09/2011),
extensive 126 page manual, retrieved 12/2/2014, original source: https://www.lennox.com/pdfs/installation_maintenance
/Lennox_XC13_IOM.pdf
16. [1] Carrier Corporation, "24 ANA Infinity™ Series Air Conditioners with Puron® Refrigerant, 2 to 5 Nominal Tons (Sizes 24 to 60),
Installation Instructions", Carrier Corp., 7310 W. Morris St., Indianapolis MN 46231, 2009, for Carrier A/C models 24ANA7 and 24ANA1
units.
17. Whirlpool Home Cooling & Heating "CONDENSING UNIT INSTALLATION INSTRUCTIONS" [PDF] retrieved 2017/07/09, original source:
http://www.whirlpoolcomfort.com/Upload/46897G003.pdf
18. "INSTALLATION INSTRUCTIONS, Split System Performance Line AC & HP Condensers" [PDF] retrieved 2017/07/09, original source:
http://www.utcccs-cdn.com/hvac/docs/1011/Public/01/42101300202_ICP_12631.pdf
At any point of reception in a residential development, no person shall operate an air conditioner that causes a continuous sound
that exceeds the greater of the following sound levels:
Calgary
(a) 70 decibels (dBC) measured over a one-hour period during the day time; or
(b) 60 decibels (dBC) measured over a one-hour period during the night time
Edmonton none
In residential zones, institutional zones, and all other zones that abut a residential zone, heat pumps, air exchangers, air
conditioners, and/or pool mechanical equipment may project 1.5 metres into a required yard, provided the projection is no closer
London than
An air conditioning condenser, heat pump, or similar equipment can project 1.0 metre into a required setback but must be located
Ottowa
0.3 metres from a lot line and cannot be located in a front yard or a side yard on a corner site.
The air conditioning/heat exchanging unit cannot be located in a front yard and must be at least 3.0 metres from an openable door
Regina
or window of a dwelling on an adjacent lot.
Wall-mounted equipment may encroach to a maximum of 0.9 metres into a rear yard setback, and to a maximum of 0.9 metres
Toronto
into the side yard setback, if it is not located above the first story.
Air conditioning units, heat exchangers, swimming pool filters, pumps and heaters, and related equipment may be located:
in a required front yard, provided a minimum separation distance of 15.0 metres, measured laterally to an opposite window of a
habitable room on an adjoining lot, is provided. The unit must be completely screened and maintained with a compact hedge,
shrubs, or other landscaping.
Winnipeg
in a required side yard, provided a minimum separation distance of 4.57 metres (15 feet), measured laterally to an opposite
window of a habitable room on an adjoining lot, is provided.
A minimum setback of 0.6090 metres (2 feet) to any side lot line must be provided.
Saskatoon, Canada, REGULATIONS on PLACEMENT of NEW AIR CONDITIONING UNITS, CANADIAN CITIES [PDF] (2016) - retrieved
2022/04/24 original source: https://pub-saskatoon.escribemeetings.com/filestream.ashx?DocumentId=47178 includes a table giving
placement & noise regulations for air conditioning units for Canadian cities
Oakville, Ontario, RESIDENTIAL ZONING CODE, Part II [PDF] (2013) - retrieved 2022/04/24 original source:
https://www.oakville.ca/assets/2011%20planning/sczbl-aug13-Part2.pdf
Excerpt:
No person shall, in any residential zone, locate any external heating or air conditioning equipment, swimming pool pumps, and filters in any
side yard or rear yard closer than 0.6m to the side lot line, flankage side yard or rear lot line or in any front yard further than 1.5m from the
front wall of the building.
AIR CONDITION GUIDE FOR RESIDENTIAL 1-2 UNITS [PDF] (2019), source: City of San Mateo, CA, City of San Mateo Building Division,
330 W 20th Ave. , San Mateo, CA 94403 USA Tel: 650-522-7172 Web: www.cityofsanmateo.org - retrieved 2022/04/24 original source:
https://www.cityofsanmateo.org/DocumentCenter/View/78588/Air-Conditioning-Guide-for-Residential-1-and-2-Dwelling-Units
AIR HANDLING EQUIPMENT/AIR CONDITIONING UNIT SETBACK GUIDELINES [PDF] , City of Los Altos, CA, - retrieved 2022/04/24,
original source: https://www.losaltosca.gov/
Other building mechanical systems that could interfere with the heat pump or air
conditioner compressor-condenser unit
:
In our photo above, from a Minneapolis MN home, these two compressor/condenser units are just about three feet apart - a little close, and that
right-most larger compressor/condenser unit is too close to building walls, a clothes dryer vent, and shrubbery.
keep 4 to 8 ft. distance beween the outdoor compressor-condenser unit and other mechanical systems such as a kitchen exhaust fan vent outlet,
clothes drywer outlet, or direct-vent heating equipment or fireplace outlet (and air intake).
We also see that the direct-vented heating appliance's white PVC piping is blowing exhaust close to these units. The installation is nice looking
and neat though.
Do not locate a compressor/condenser unit where the clothes dryer vent will blow onto or close to the unit. Lint-clogging of the
compressor/condenser's condensing coils is likely to be a problem and the extra warm air won't help the cooling cycle efficiency or
equipment life. Move the equipment or move the dryer vent.
see CLOTHES DRYER VENTING for more about safe clothes dryer installation.
Heating appliance direct vent outlet:
Do not locate the outdoor HVAC compressor/condenser unit where exhaust from a direct-vented heating appliance will blow onto the unit.
These four air conditioner compressors were found jammed into a wall niche along a street in Queretaro, Mexico.
Where there simply is not adequate space to provide proper air circulation around an air conditioning compressor or multiple compressors, it may
be a good idea to let the building owner know that the units won't have a long life.
Reply:
OPINION: While we can't anticipate every crazy installation of stuff on or around buildings (people are very creative), there are possible hazards
that I can imagine, so I'd like to see 48", principally because I don't want kitchen grease accumulating on the top of the condenser;
Watch out: there could be a more subtle hazard, even a fire hazard: if the compressor/condenser unit's exhaust is upwards out of the top of the
:
unit (as is often the case) and if it blows up into the air intake of the kitchen exhaust fan while that fan is "on" (such that that fan's outlet baffle is
normally blown-open by the kitchen fan) the strong blast of upwards air out of the A/C condenser unit may either close off the kitchen exhaust fan
outlet baffle or it might even blow backwards back into the kitchen, risking grease accumulation in the kitchen exhaust, backdrafts, odors, even a
fire.
Reader Question: minimum required distance between a home A/C condenser unit and a fill valve for a home
heating oil tank
Reply:
Fair question, Tom but I don't know. I've not seen a specific standard for that distance and doubt one exists. In general the condenser ought to be
far enough away from the fill and vent valves that there is
- good working space around the condenser unit for maintenance and repair as well as adequate distance from the house wall so as not to
obstruct air flow (shown in the article above)
All of that is subjective, but giving the delivery person several feet (3+) ought to be enough in my opinion.
- easy access for your oil delivery driver so she doesn't have to squeeze in between the condenser unit and the wall to reach the fill pipe or listen
at the vent pipe; giving plenty of room here for a person to walk and drag a hose also reduces the chance of a splash of waste oil from the nozzle
onto the AC unit.
Reader Question: impact of the A/C compressor unit on nearby indoor rooms
is it possible that having 2 heat pumps next to the house could cause a room to be too cold or too hot? The room next to the two units is always
too cold in winter or too warm in summer compared to the other rooms in the house.
We were wondering if the air coming off the heat pumps against the side of the house would cause this. The heat pumps blow air up and we can
see that the air hits the windows on that side of the house.
Reply:
David,
I don't think so. It's true that blocking air flow across a heat pump will limit its effectiveness, but I'd be surprised if that showed up as a difference
between rooms in the home.
Your question is a good one but I'd be surprised if we could see an indoor effect from air exiting the heat pump.
Use the CONTACT link to send us photos of the installation and I may be able to comment further.
Rule of Thumb Vertical A/C / Heat Pump clearance distances: 4 ft. overhead free space
In our sketch above, you can see typical air flow patterns from an outdoor central AC compressor/condenser unit. Air enters at the sides and exits
at the top of this unit.
So obstructing airflow out at the unit top will also reduce air flow across the condensing coils, shortening equipment life and cutting its efficiency.
A rule of thumb is to assure that there is at least 4 ft. above the A./C compressor/condenser unit.
:
For example, installing an A/C or heat pump compressor under an outdoor deck might block its airflow (not to mention the noise aggravation).
In fact, typical A/C or heat pump installation instructions recommend that you locate the unit away from windows, patios, decks, etc., where unit
operation sound may disturb the customer.
Should you try shading the compressor/condenser with a roof or lattice overhead? Generally no.
Reader Question: deck interferes with air circulation around the compressor unit
Reply:
Maybe not, Steve. The manufacturer probably specifies a minimum number of feet of clear space above the compressor/condenser unit to avoid
restricting its intake or more often outflow.
For example, Lennox air conditioner installation instructions for the compressor/condenser unit typically require 48" of clear space above the unit.
Not to mention people on the deck may be affected by the noise or exhaust air coming from below them.
The most important clearance distances to respect around an outdoor air conditioner or heat pump compressor/condenser unit are with respect to
those sides of the equipment through which air is intended to flow - either "in" to the unit our "out" of the unit.
Some outdoor units use a top mounted fan that blows "up" out of the unit, drawing cooling air through the condensing coils at one or more sides
of the equipment. For these units, both side clearance and top clearance must be respected.
But often the condensing coil does not extend through all four sides of the unit. If this is the case, the distance clearance from the side of a unit
through which no air is expected to flow is probably less critical - though you should still be careful that multiple units placed too close together
are not competing for the same air.
In our photo above, air moves into this compressor/condenser through three of its sides, but its "back side" (facing the building wall) is not one
through which air moves.
Reader Question: safe clearance distance between a gas fireplace direct vent outlet and the air conditioner or heat
pump compressor/condenser unit
2016/04/06 AJ said:
My Carrier compressor/condensing unit is installed about 2.5 feet from the wall however there is a gas fireplace exhaust pointed right at the unit.
To be more specific, the exhaust would vent to the sides because of it's design. Still, I had a building inspector tell me that's not up to installation
code. I'd attach a picture if I could. What do you think?
Reply: separation distance between a gas appliance terminal vent and an A/C or heat pump compressor/condenser unit may depend
:
on the situation
You wrote by email that the gas fireplace direct-vent is 16" from the unit. The A/C or heat pump unit itself is 23" from the wall. That 23" is already
an inch closer to the wall than recommended - no big deal, but I do have some worries about the close-by gas fireplace vent.
You should find the installation instructions for your specific brand and model gas fireplace and therein you should find the specific clearance
distances given by the manufacturer. But most likely you won't find an explicit clearance distance from the gas fireplace heater vent cap to an air
conditioning compressor.
As neither codes nor manufacturers can anticipate and explicitly prohibit every creative snafu that an installer may invent, a manufacturer whose
instructions we reviewed also states:
The location of the horizontal vent termination on an exterior wall must meet all local and national building codes, and must not be blocked
or obstructed.
Also
see DIRECT VENTS / SIDE WALL VENTS
Reviewing a manufacturer's installation instructions for a direct-vented gas fireplace, you'll see that the manufacturer starts with the Canadian or
U.S. gas codes and then may offer adjustments if the manufacturer offers special chimney or vent terminating options or caps.
You'll see in both our article cited just above and in the manufacturer's instructions for a gas fireplace, that typical gas fireplace vent instructions
specify that the termination cap on the outside wall must be
At least 26" to 30" above ground, depending on the vent type or model. Lower installations can be made, down to 12" above ground but
these require installation of a snorkel to raise the outdoor vent termination opening.
36" from the gas regulator vent
12" (Canada) or 9" (U.S.) to non-mechanical air supply inlet to building or the combustion air inlet to any other appliance
72" (Canada) or 36" (U.S.) to a mechanical air supply inlet, & 3' (91cm) above if within 10' (3m) horizontally.
The sources for that data do not explicitly specify a clearance from a gas appliance direct vent terminal cap to an A/C compressor/condenser.
(particularly if both the gas heater and the compressor unit operate at the same time). The effect of blowing hot exhaust from a gas
appliance onto a nearby condensing coil's air intake grille might heating the condensing coil thus interfere with the coil's ability to cool the
hot refrigerant gas back down to a refrigerant liquid.
There might also be a corrosive effect on the condensing coil, though I've not found reference to that problem.
2. Possible safety issues
that are exacerbated if a passive or atmospheric gas fireplace heater vent exhaust is actually affected by air flows created by the
compressor/condenser unit.
Watch out: Drawing air through the heater due to an outside vacuum source OR blowing air into the heater as backpressure from an
outside condenser unit air output source would both be unsafe, risking potentially fatal carbon monoxide poisoning, a risk increased should
other safety controls be absent or broken.
Your building inspector may be considering the general rule of 24" free space around the condenser unit OR she may be considering this guide
that keeps space between adjoining condenser units:
Clearance distance between adjacent air conditioner or heat pump compressor/condenser units
That's to avoid the heat or the air demand from one unit from impacting the other's operating efficiency and life expectancy.
OR
Your inspector may be considering this more general gas heater direct vent clearance guide:
Distance to a mechanical [systems] air supply inlet: 3 feet above if within 10 feet horizontally
But I think that text refers to a mechanical system air supply inlet for combustion air or for air that will be blown into the building interior (such as
an air ventilation system).
For the installation I see in your photos, the possible effects are not from CO in the exhaust since the compressor/condenser does not involve
drawing in combustion air. It does draw in air to cool the condensing coil.
:
In sum, I agree that there is a potential impact between the gas vent and the condenser unit, particularly if they can run simultaneously, such as if
the condenser unit is for a heat pump and the gas vent is for a space heater.
Watch out: There could be dangerous conditions if the air intake vacuum created by the A/C compressor / condenser unit actually draws air or
gases out from the nearby direct vent gas heater or from a passive-vented (atmospheric vented) gas fireplace appliance, that increased draft may
impact the safe operation of the gas burner, risking dangerous or even fatal carbon monoxide hazards.
Watch out: Separately, if a different compressor unit design caused the unit's exhaust to blow into the gas heater exhaust vent, that could
prevent safe venting of exhaust gases. Where either these conditions are possible, I'd increase the clearance distance to 10 feet or 3 meters.
Air Conditioning & Heat Pump Equipment Maximum Distances From a Building
Moving an air conditioner compressor to a distance of about 40 feet from a building won't prevent it from working, but the installer might need to
adjust the diameter of the refrigerant lines to be sure that the equipment is working at 100% of its capacity.
It's not that the air conditioner won't work at all if the compressor/condenser is located at an unusual distance from the air handler/evaporator coil,
it's more that it may lose some capacity and have to work harder - meaning higher electrical bills and in extreme cases, shorter equipment life.
Some air conditioner manufacturers such as McQuay provide a refrigeration piping guide that gives complete, detailed guidance and charts on
refrigerant line sizing (diameter) as a function of length of run.
Details about refrigerant piping diameters, distances, and effects on equipment operation are
The bare minimum free working area around a residential heating boiler is given in the model codes such as the International Mechanical Code
(IMC) and, of course, may be modified by your state or provincial building authorities and codes.
Passageways around all sides of boilers shall have an unobstructed width of not less than 18 inches (457 mm), unless otherwise approved.
Different clearance spaces may be given in the installation and operating manual for your specific heating equipment.
NCAC, Section 13.0413 CLEARANCES at BOILERS & PRESSURE VESSELS [PDF] (2018) North Carolina Office of Administrative
Hearings, 1711 New Hope Church Road,
Raleigh NC, 27609 USA, 984-236-1850 Web: https://www.oah.nc.gov/, retrieved 2021/06/12 original source:
http://reports.oah.state.nc.us/ncac/title 13 - labor/chapter 13 - boiler and pressure vessel/13 ncac 13 .0413.pdf
Excerpt:
(a) All boilers and pressure vessels shall be located so that adequate space is provided for proper operation, including visibility of all
gauges, for the inspection of all surfaces, tubes, waterwalls, economizers, piping, valves and other equipment, and for maintenance and
repair, including replacement of tubes.
Boiler clearances shall remain free of all items, including temporarily stored items, other than boiler piping and trim. Boiler piping and trim
shall not impede access to the boiler.
(b) Adequate clearance for boilers and pressure vessels installed prior to January 1, 2009 shall not be less than the following:
(1) Three feet of clearance shall be provided between the boiler or pressure vessel on all service sides, and clearances as recommended
by the manufacturer on all other sides.
Service side shall be interpreted as any side, including the top, of a boiler or pressure vessel on which clearance is necessary to access
operating controls, safety devices, drain and blowoff valves, or inspection openings.
On 2023-09-04 by InspectApedia Publisher (mod) - cleareance disteances around MrCool split system outdoor unit & its service switch
:
@LYNND,
Below we include a copy of the clearance distances for the Mr. Cool Mini Split outdoor
condenser unit that I think is the one you are installing.
In reviewing codes and standards for the outdoor condenser unit service switch you'll see that
distance details are not usually given but the switch must be readily accessible and within
sight of the unit - you certainly meet those requirements.
You might also want to check CIRCUIT BREAKER SIZE for A/C or HEAT PUMP
If you don't already have it, the Mr. Cool INSTALLATION MANUAL for the DIY MINI SPLIT SERIES AC units [PDF] can be downloaded here a
Watch out: MrCool warns on the opening pages of any of their DIY installation manuals that "Electrical work must be completed by a qualified
electricial technician."
Whether or not you can legally do your own electrical work depends of course on the codes where you live.
Thank you for the helpful photo and question - that will help other MrCool DIY installers.
On 2023-09-03 by LYNND
Spouse is working this Labor Day weekend to replace an in-wall A/C unit mounted to the side
of our attached garage with a mini split (Mr. Cool 12K/110V 4th Gen DIY series). Installed the
air handler and the condenser first and is now prepping the electrical connections.
It will be on a dedicated 25amp circuit located on the main panel inside the garage. (For this
model we found instances of people using both 30 amp and 20 amp breakers on the Home
Depot and Amazon Q&As for this model, hence a 25 at the panel because the installation
manual doesn't spell it out.)
Max fuse capacity per the Mr. Cool label is 25, so the Fusible Quick Disconnect within view of
the condenser will be equipped with 20 amp fuse.
House is in an unincorporated area of Los Angeles County. Have referred so far to the
Alameda County, CA guidelines because LA County's counterpart to this document didn't pull up on a search.
See: AIR CONDITIONER/DUCTLESS MINI-SPLIT PERMIT REQUIREMENTS [PDF] - retrieved 2023/09/04, original source:
alamedaca.gov/files/assets/public/departments/alameda/building-planning-transportation/building/ac-mini-split.pdf - source of the illustration just
below
To the left of the proposed Quick Disconnect location, there is an unused hose bib emerging from the house about 2’10” away (on a diagonal) and
from that hose bib to the condenser it's 2’6”.
(The unused spigot connects to galvanized water pipe that runs vertically up from a raised crawl space behind the wall.) From the Quick
Disconnect to the condenser, it’s about 4’8” (measured on the diagonal).
2) Before making the final connections, where can we verify against Los Angeles County mini split code requirements? (As mentioned, we
referred to another CA County mini split requirements only because that's what pulled up on a search.)
Thank you for a helpful website. (Have visited it many times in the past!)
On 2023-03-05 by InspectApedia Editor (mod) - Daikin Fit details 4” minimum between side by side installation of units
@Failed Inspection,
But remember that the local building inspector is the final legal authority.
Remember too that the intent is that a. unit be serviceable AND that air flow obstruction
doesn't shorten its life or increase its operating cost.
I would myself be reluctant to install as tight as in your drawings; having serviced such
equipment, in my OPINION you're asking for trouble. Just as one small example, to remove
the cover from the unit there are usually bottom screws at or near the ends.
I cannot imagine how I would reach those screws for a unit installed as you show it.
Daikin Fit details 4” minimum between side by side installation of units, how is this layout
against M1305.1 which states Appliance access for inspection service, repair and
replacement.
Appliances shall be located to allow for access for inspection, service, repair and replacement without removing permanent construction, other
appliances, or any other piping or ducts not connected to the appliance being inspected, serviced, repaired or replaced.
A level working space not less than 30 inches deep and 30 inches wide (762 mm by 762 mm) shall be provided in front of the control side to
service an appliance.
Is the Daikin fit control side from the side panel perspective or looking from back
Of the unit forward or looking forward to back?
My installer followed the mfg instructions and inspection failed is this possible to over turn based on the control side being accessible from the
rear even though access panel mounts off the side?
@Karen Reuter,
Not necessarily but let's first be sure I understand your installation. What copper tube are in the ground? Running from what to what, and how far.
Perhaps you an post a photo.
If replacing my AC and heater must I also put the copper tubes overhead as they have been in the ground for thirty year- thanks
On 2022-08-13 by InspectApedia-911 (mod) - a et back requirements between the AC unit and a 2nd stage LP gas regulator?
:
@Jason McCormick,
Yes
My question is, are there any set back requirements between the AC unit and a 2nd stage LP gas regulator?
[Photo above]
On 2022-07-26 by InspectApedia-911 (mod) - clearance requirements for an outdoor AC unit in Thornton, Colorado
@Susan,
so
The outdoor AC condenser unit clearances given above will apply in Thornton, too, but for an authoritative, un-arguable clearance distance
specification we need to know the AC condenser brand and model number and then to consult the installation manual for that specific equipment.
That's particularly important if a "much bigger" unit than usual has been installed, as it may have different clearance requirements.
You also need to be specific: clearance distance to what, from which side or top of the unit in question. Those distances vary, as you'll read
above.
You can also contact the Thornton CO building department directly to request an appointment. The department notes:
Effective 7/18/2022 the Building Inspection Division counter will be open by appointment only. To request an appointment please contact us at
303-538-7250 or email [email protected].
But I expect that without the specifics that I outlined above, we're flapping in the wind.
On 2022-07-26 by Susan
Where can I find out the clearance requirements for an outdoor AC unit in Thornton, Colorado, specifically? We have a townhome neighbor that
installed a much bigger unit in our allotted space, and we are having difficulties getting our unit replaced because of clearance issues. So we
need to know what the actual code requirements are.
Thank you
On 2022-07-11 InspectApedia-911 (mod) - what is the noise level in decibels if we move 3 fddt. away from the compressor "outflow"
@Harry Keen,
I'm sorry but I don't know what outflow you are referring to.
However if you were saying that you're three feet from the compressor that you can pretty much bet that the decibel level is going to be very
close to the number that was claimed.
If the decibel level of a heat pump compressor is rated at 56 decibels, what might the decibel level be at a distance of 3 feet from the outflow?
On 2022-04-24 by Inspectapedia Com Moderator - what is the clearance distance from AC unit to property line?
@Eric,
Bottom line: Required distance from A/C condenser unit to property line is typically 3' to 10' depending on where you live, and is not specified at
all in some jurisdictions. The clearance distance should also respect all of the working distances and clearances given in the rest of this article.
:
Details:
In neither the mechanical codes nor installation instructions do we find a code-specified distance between the A/C condenser unit and the nearest
property line per-se.
That is, ... as my buddy Mark Cramer says, ... it depends. I'm wary of answering a trick question when we don't have enough information. Below
are some examples:
If at the property line there is a solid obstruction such as a building wall or an enclosing fence, like a stockade fence, then the condenser unit
needs to meet the clearance distances above that are given from solid obstructions that could prevent either working space or air space.
If at or near the property line there is another building with air intakes such a window or air exhaust such as a dryer exhaust vent, then, similarly,
the AC condenser unit would need to respect those clearance distances.
If the condenser unit produces condensate discharge, in many jurisdictions that discharge can not be sent across a public walkway where it may
cause a nuisance or fall hazard.
Noise nuisance restrictions: in some jurisdictions the required air conditioner or heat pump compressor/condenser distance to property line
depends on the noise rating, in decibels, of the equipment. For example, in Los Altos, California, if your condenser unit has a sound rating,
measured at the equipment, of 74db it must be located no less than 22 ft. from the nearest property line.
That noise rating overrides Los Altos' minimum distance of 5 ft. between property line and the compressor/condenser unit.
So your best bet is to review the known condenser unit clearances given above on this page and then to see if any of those pertain to your
installation, including the property line.
In addition, depending on the country and city where your AC condenser unit is being installed, there may be local regulations specifying a
required distance between the A/C condenser and neighbours.
Examples:
When the AC condenser installed in a side yard location, it must allow for a clear 3-foot path of travel (between condenser and property line). -
AIR CONDITION GUIDE FOR RESIDENTIAL 1-2 UNITS [PDF] (2019), source: City of San Mateo, CA, City of San Mateo Building Division, 330
W 20th Ave. , San Mateo, CA 94403 USA Tel: 650-522-7172 Web: www.cityofsanmateo.org - retrieved 2022/04/24 original source:
https://www.cityofsanmateo.org/DocumentCenter/View/78588/Air-Conditioning-Guide-for-Residential-1-and-2-Dwelling-Units
AIR HANDLING EQUIPMENT/AIR CONDITIONING UNIT SETBACK GUIDELINES [PDF] , City of Los Altos, CA, - retrieved 2022/04/24, original
source: https://www.losaltosca.gov/
ANSI/AHRI Standard 275 – 2010, Air Conditioning, Heating and Refrigeration Institute, www.ahrinet.org
Thanks again for a great question - we'll add details in the article above.
On 2022-04-24 by Eric
@Herb Reiter,
Please do take a look at the above article where your clearance question is specifically answered.
On 2021-12-27 by Inspectapedia Com Moderator - manufacturer's clearance directions can be for air flow and maintenance
@Paul, example of a 60" clearance - approaching your 78" - note it is for airflow -for a Rheem Condenser unit.
:
On 2021-12-27 by Paul
The 78-inch front clearance has *nothing* to do with servicing a 16-inch wide condenser that can be hand-lifted into, and out of, place. If you have
no idea of the thermodynamic and/or exhaust hazard considerations, just say so.
You certainly want to follow the manufacturer's clearance distance recommendations. Arguing with them is only going to make trouble and
expense for yourself later when the system needs to be serviced and you find the servicing it is impossible without removing the fence.
On 2021-12-27 by Paul
I only have one possible spot to put the 24K BTU condenser for a split unit. No clearance issues to either side (6 feet+ open on both).
To have the 12-inch clearance between the house side and back of the condenser, I will only have 24 inches from the condenser fan face to a 6-
foot tall privacy fence. The specs say the minimum is 78 inches in front.
So, despite this site being about inspections and building codes, my question is *why* does the condenser need 78 inches? To get that, I will
have to wall mount the unit and have it blow over the fence, against the blank side (no windows or doors) of the neighbor's house.
Except for the 78-inch spec, every other consideration has me placing it on grade exactly where I intend it.
Only the elevation (blowing against privacy fence 24 inches away or blowing over the fence) is in doubt. With open air on both sides and above
the fence, I'm having a hard time imagining why that 78 inches would be truly necessary.
@kelly banks,
We haven't found a code citation specifically addressing clothes dryer clearance to AC unit condensers but that topic is discussed in the article
above.
Do not locate a compressor/condenser unit where the clothes dryer vent will blow onto or close to the unit.
Lint-clogging of the compressor/condenser's condensing coils is likely to be a problem and the extra warm air won't help the cooling cycle
efficiency or equipment life. Move the equipment or move the dryer vent.
Find the installation instructions for your specific brand and model heat pump and therein you should find the specific clearance distances given
by the manufacturer. For example, different units have different clearance requirements for air flow and servicing needs.
See the general rules of thumb above on this page, for clearances above and to the sides of the unit.
On 2021-09-23 by inspectapedia.com.moderator - always best to follow manufacturer's installation instructions or life of unit may be
shortened
@qofmiwok,
With the generic ducking and weaving, that it is always best to follow the manufacturer's installation instructions, I will add that your system may
work with less clearance than recommended but it will work harder and may have a shorter life.
On 2021-09-22 by qofmiwok
We're planning out mini-split compressors under a covered storage area due to heavy snow. Imagine 2 side by side with a wall behind (we can
give plenty of clearance to that wall), a roof above (6' above the units), and one side wall. I see the issue about concern with airflow in corners.
Our exact config doesn't show up in the Daikin manual but the closest one looks like they want 40" to the side corner. But that would make our
storage area need to be very deep (40+37+4+37"). Is 40" really necessary to the side in a cold, dry climate, when the roof is way above and we
can leave a lot of clearance in front of and behind the units? Also we have a super efficient house and this is a VRV, so it should be running on
low most of the time.
:
On 2021-09-09 by inspectapedia.com.moderator
@Anonymous,
Please see
On 2021-09-08 by Anonymous
On 2021-08-19 by inspectapedia.com.moderator (mod) - hot air from the top of the condenser blows into the room when the window is
opened
Yes those clearances and code citations and manufacturers instructions are given above
I live on the ground floor of a condominium building and an A/C condenser, serving a third floor unit was install just below one of bedroom
windows
Besides the noise, hot air from the top of the condenser blows into the room when the window is opened and the condenser is running. Is there a
building code specifying the distance a condenser should be installed away from windows , doors or building openings?
@Elizabeth Eagle,
Condenser units are designed to be located outdoors where snow on the unit won't hurt it.
If your roof dumps heavy loads of snow or ice on equipment below, then you need to fix that at the roof with SNOW GUARDS. (Search
InspectApedia using the search box above to find that article)
If you don't already have it, pick up a copy of the installation and operation manual for your AC unit. Look at the installation clearance
requirements given in the manual.
Show that to your installer. Point out that for fire safety, as well as for proper operation of the AC equipment, the dryer vent and AC condenser
unit need to be accessible and properly located.
If your installer won't fix the problem perhaps you'll have to hire someone else and, if it's really worth it, pursue your claim in small claims court.
Safety comes first.
I have a Daikin AC unit. It was installed 8 inches from my substrate, home, & I have a dryer vent behind it that I cant get to for maintenance.
The installer is not taking responsibility for th I s. What do I do? Also, dryer vent is blowing hot air into my Ac unit!
It's right under a soffit for snow debris to fall on it. How am I going to get any help without paying more money to fix this mess?
@sean,
On 2021-05-31 by sean
want to move my AC unit to the far corner of the house. i would like the lines to run as far as possible inside the house and then continue outside
for approx. 15 ft. (dont want the lines to be visible in my finished basement recroom)
the temperature here can reach -30 or more degrees plus windchills. will the lines freeze? even insulated? or is that not long enough for that to
occur?
just to add... this is a central air conditioning unit. not a heat pump. not being used in winter months.
On 2021-05-03 by (mod)
@Ron,
That's a helpful question about outdoor condenser unit clearance under a deck.
:
There are two clearance concerns, working space and air circulation;
My OPINION ('m not an authority) is that your 48" distance to the underside of deck *might* meet the air circulation requirement, though joists do
tend to channel air a bit and won't be without any effect.
Regarding working distance, if to work on the A/C condenser it is necessary to lift its cover straight up to remove it, you'll want to be sure that
removal isn't being blocked by the underside of those deck joists. Most likely, with 48" free space to the decking underside and using a 2x10 joist
as an example, you've got
(48 - 9.5) or about 38.5 inches of free working space above the unit.
So if the unit's enclosure is taller than say 38" your service tech wouldn't be able to remove it.
On 2021-05-03 by Ron
The requirement of 48 inches, if the actual deck boards are 48 inches above the unit but the framing joists are not is that a problem?
On 2020-07-31 by (mod) - Possible solution to AC condenser unit discharge that short-circuits back into its own intake
@Howard:
Keeping at least 24" of clear space around all sides of a condenser unit is a general rule of
thumb, but the actual space required for service access and airflow is given by the installation
manual for your specific condenser unit brand and model.
You are quite right that short-circuiting the condenser unit exhaust air back around to its inlet
sides will
An HVAC engineer, given the actual dimensions of clearance distances, heights, air velocity, etc. could calculate the amount of A/C condensing
unit exhaust that exits from the top of your unit and, as you put it, "short circuits" and flows back down to the inlet sides of the unit because of the
blockage caused by an improper installation of the unit - too close to the house wall, and an improper fence construction - too close to the other
side of the unit.
Without that actual data, we are both doing a bit of arm-chair theorizing and arm-waving.
There will be some restriction of the AC Condenser output airflow caused by the strict vertical sides of your cylinder - shown in green in our
sketch if we've understood your design correctly, but that's probably not a show-stopper.
By discharging the exhaust air higher up above the fence-top, there will be some reduction in short-circuiting of condenser up-flowing exhaust
back around into the inlet sides of the unit - if we presume that in fact the actual air intake velocity is uniform around the full 360° sides of the unit.
However, the air inflow to the condenser unit is still going to be reduced below its design point by the presence of the house, too close on one
side, and the fence, too close on the other side.
In fact, I have seen this condenser clearance distance violation quite a few times - people like to build a fence to hide the unit and perhaps to
block a portion of its sound, and they often put the fence too close to the unit.
At one installation whose owner shall remain nameless as she was a famous actress whose initials were MTM, we learned that a collection of
A/C condenser units was frequently replaced due to short life because they were all jammed together between the house and an aesthetic wall
blocking view of them.
1. The best solution for your air flow short circuiting AC condenser unit installation would be to move the unit away from the house wall and
move the fence away from the unit to give the required air inlet on all sides of the condenser unit.
2. The second-best solution at the condenser unit might be to move just the fence - less expensive as no one has to cut the refrigerant lines to
move the condenser.
3. The ??-best solution is to try what you propose, though it would sure be useful and interesting to make some actual measurements of the
effectiveness of the design change.
I suggest that when you have constructed your AC condenser exhaust deflector cylinder, on a day that's warm enough that the condenser can be
set to run continuously for a time, let it get up to full operating temperature, then measure
Let us know what you find - it may prove very valuable to the many other homeowners whose AC or heat pump compressor is also suffering from
blocked airflow.
On 2020-07-31 by Howard - short circuiting vertical AC unit discharge into its own intake
I have a two ton round condensing unit which does not have near the recommended clearance on two sides (house wall on one side and a fence
consisting of horizontal 1'' x 6" boards with 1" gaps on the opposite side).
The other two sides are wide open and allow maintenance access. Although I have not measured temperatures, it is apparent that this
configuration is causing some significant short circuiting from the vertical discharge from the unit into the condensing coil intake.
I would like to install a removable vertical discharge cylindrical sheet metal duct the same diameter as the unit OD and about 36" long to get the
discharge to just above the top of the fence.
I would leave the fan guard/hanger in place and install a very coarse guard to the discharge of the new duct. The cross - sectional area of the
duct would be the same as the area of the existing factory discharge opening and would be a straight vertical run with no offsets.
The house is two stories so there would be no roof overhang or other obstruction for 10+ feet, and there are no windows on that wall.
Obviously still not an ideal situation, but it seems to me this would be a worthwhile improvement.
On 2020-07-10 - by (mod) -
Setback codes vary by country, city, province, etc. Also by which lot line, side vs front or back: Typically 10 ft
Could you answer a question? my neighbor has placed a huge AC outside package unit right on our line in the back yard of our R1 zoned area.
She did this because she has a very small area next to her house. How far must the AC unit be set back from the property line between us?
Tuti
Thanks for the condenser unit clearance distance question; in my opinion, as long as the total
air space provided by the lattice near the condenser/compressor unit gives as much free open
area in sq .in. as the square inches of intake and exhaust venting of the condenser unit itself
you'll be OK.
I can't tell from your photo but if the back side of that condenser unit is expected to take in or
exhaust air it may be blocked by the solid fencing.
Watch out: blocking air flow into the compressor/condenser unit increases its operating cost
and reduces its life.
I found the reference below about a fence clearance, and also the one side of the air conditioner could be at 6in respecting the clearance on the
other 3 sides.
So, I wanted to double-check if a breathable fence material as lattice, which is not a solid obstruction, in fact, has wide gaps for airflow, could be
installed closer to the unit at 4in distance in one of the side of the unit. The fence will be a lifting panel so it can be fully removed for maintenance
access.
Allow at least 12" distance to a wall or fence or similar solid obstruction - typical of most installation instructions.
Some instructions permit reduced clearance to a single object with a small surface area such as the end of a wall, an outside corner, a fence
section, or a post. Eg. a 4" fence post could be 4" from the wall-side of the compressor/condenser unit.
On 2020-04-17 - by (mod) - can I plant a hibiscus tree next to the compressor unit?
Jane:
Beyond that, leaves are going to fall onto the unit and some may be sucked against the air intake areas of the condenser unit even if a tree is
quite distant, if leaves are falling onto the lawn, so you'll want to keep the area clean and to inspect it regularly during leaf-fall season where you
live.
On 2020-04-17 by Jane
If have an outside a/c unit can I plant a hibiucus tree next to it or will the leaves be sucked in
On 2020-04-07 - by (mod) - codes or standards for the foundation for a heat pump?
Bill
Thank you for the great question on whether or not we need an actual Foundation or Frost footing under pads for air conditioners and heat pumps
Outdoors.
General answer is that the best Authority is the manufacturer's installation instructions for your particular heat pump or air conditioner brand and
model.
I will say that from the installation instructions with which I am familiar, the answer is no, a footing is not required underneath the pad for your
condenser compressor unit.
However it's rather likely that the manufacturer's instructions do require that the pad be level and that the condenser unit be installed with
sufficient slack or extra material in wiring and refrigerant piping that should the unit move slightly the wiring and refrigerant piping will not be
disturbed, broken, or made to leak or made unsafe.
On 2020-04-07 by Bill
Are there any codes or standards for the foundation for a heat pump? My contractor said not a big deal if not level and through some pea gravel
underneath unit.
1. adequate working space around the unit for inspection, maintenance and repair -
but the installation and operation manual for your specific HVAC condenser unit brand and model would, of course, be the best authority as their
data could differ.
Blocking air flow means higher operating cost and blocking service access means extra costs to remove the fence when the unit needs work.
On 2019-07-05 by Bruce
We are having a fence installed. What is the minimum/recommended clearances for each side of the condenser?
One side is adjacent to the house, two sides are completely open and the front has 16" of clearance to the fence. Is this adequate? Does this
break and codes or manufacturer specs.
...
Continue reading at COMPRESSOR / CONDENSER INSTALLATION ERRORS or select a topic from the closely-related articles below, or see
the complete ARTICLE INDEX.
Or see CLEARANCE DISTANCE, HVAC FAQs - questions & answers posted originally at this page.
Or see these
Recommended Articles
CLEARANCE DISTANCE, HVAC at InspectApedia.com - online encyclopedia of building & environmental inspection, testing, diagnosis, repair,
& problem prevention advice.
Or see this
INDEX to RELATED ARTICLES: ARTICLE INDEX to AIR CONDITIONING & HEAT PUMPS
Or use the SEARCH BOX found below to Ask a Question or Search InspectApedia
...
Search
Note: appearance of your Comment below may be delayed: if your comment contains an image, photograph, web link, or text that looks to the
software as if it might be a web link, your posting will appear after it has been approved by a moderator. Apologies for the delay.
Only one image can be added per comment but you can post as many comments, and therefore images, as you like.
You will not receive a notification when a response to your question has been posted.
Please bookmark this page to make it easy for you to check back for our response.
Our Comment Box is provided by Countable Web Productions countable.ca
Comments
Name
I'm not sure what we're looking at in these photos. If that air register in your "part 2" photo is simply an HVAC duct outlet, then sure, you can move ductwork,
though I think you may have sticker-shock when you see the cost of rerouting ductwork say to a ceiling or another wall.
The cost will be affected alot by access to the building from below or above to move ductwork.
If what's in that wall extension is something else, such as a convector unit, then moving it is still possible but more costly.
Moving the outside compressor/condenser unit around a corner is of course technically possible, too, as you're simply adding longer refrigerant lines, though the
exact location needs to respect some other building clearance distances such as working space.
Jon
:
Like · Reply · Flag
If the supporting deck joists and rim joist are not passed in front of the condenser unit's air intake then I don't think that the mere edge of deck boards would
create a worrisome block of condenser unit airflow.
But I have some other concerns noted "in passing" (we can't pretend a comprehensive building inspection from a single photo):
- Even if the air intake to the condenser unit isn't blocked by the deck, you need to provide adequate working space in front of the condenser for maintenance
and repair. Building the deck edges close to the unit violate that need.
A common solution and an easy one is to construct the deck such that it includes removable deck sections that can be simply lifted out and set aside when the
condenser unit needs service or repair.
- I notice that the backfill is higher than the foundation waterproofing memberane visible at the left side of your photo. I am guessing that this home has a
basement. If roof drainage spills through a deck and into the area of mu fat blue arrow you may risk basement water entry later in the life of the home.
- I notice what look like a dryer or bath exhaust vent (smaller rectangle) and two larger rectangles that, if they are air intakes for HVAC or other equipment must
not be blocked by the deck framing or rim joist and more, need to remain accessible for cleaning or inspection.
- I notice that your deck is going to block two basement (?) windows - you may live with that but will give up some light; and I'd be sure that that right hand
basement window is not going to receive water from surface runoff or from that downspout that spills quite close to the window.
- I notice a downspout that spills right next to the foundation; often this seems "fine" when a house is new but it can become an ugly source of basement water
entry later in the life of a home. At the very least I'd want that downspout extended 6-10 ft. away from the home and ending where water will continue away from
the building. In my OPINION, relying on basement or foundation waterproofing, membranes, footing drains rather than getting roof drainage away from the
building is, in the longer term, a mistake.
On this page of HVAC clearance distances you'll see that we're addressing clearances from the equipment itself, such as the outdoor compressor/condenser
unit, in order to meet the need for working space and noise restrictions.
LP or natural gas piping and refrigerant piping clearance distances really need only to respect the necessary space for securing and routing of those pipes or
tubing and of course the need not to over-cut building framing.
and at
Dan
House is in an unincorporated area of Los Angeles County. Have referred so far to the Alameda County, CA guidelines because LA County's counterpart to this
document didn't pull up on a search. (See: www.alamedaca.gov/files/assets/public/departments/alameda/building-planning-transportation/building/ac-mini-split.pdf )
1) Are the following clearances adequate? In the attached photo, the proposed Fusible Quick Disconnect location is ~4’7” from the ground,, about 2’ from the
galvanized steel water pipe running up the corner of the garage to the driveway (location of another hose bib on far right of photo). To the left of the proposed Quick
Disconnect location, there is an unused hose bib emerging from the house about 2’10” away (on a diagonal) and from that hose bib to the condenser it's 2’6”. (The
unused spigot connects to galvanized water pipe that runs vertically up from a raised crawl space behind the wall.) From the Quick Disconnect to the condenser, it’s
about 4’8” (measured on the diagonal).
2) Before making the final connections, where can we verify against Los Angeles County mini split code requirements? (As mentioned, we referred to another CA
County mini split requirements only because that's what pulled up on a search.)
Thank you for a helpful website. (Have visited it many times in the past!)
Please find your recently posted questions, comments, and photos along with our reply now at the Reader Q&A section in the article above on this page. You
may need to clear or refresh your browser cache to see the updated page.
Thank you for your suggestion and I'm sorry you had a hard time finding it.
It's not a link but an actual section within the article above on this page. In this instance, it begins close to the middle of the page.
You'll see there that your question and photo and our reply is the first one in that Q&A section.
Like · Reply · Flag
:
Citations & References
In addition to any citations in the article above, a full list is available on request.
HOME ABOUT ASK a QUESTION CONTACT CONTENT USE POLICY DESCRIPTION POLICIES PRINT PRIVACY